603.4 Flexible Air Ducts. Flexible air ducts shall comply
California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
with UL 181, and shall be installed in accordance with the manufacturer’s installation instructions and SMACNA HVAC Duct Construction Standards – Metal and Flexible. Flexible air duct installations shall comply with the following: (1) Ducts shall be installed using the minimum required
length to make the connection. (2) Horizontal duct runs shall be supported at not more than
4 feet (1219 mm) intervals. (3) Vertical risers shall be supported at not more than 6 feet
(1829 mm) intervals. (4) Sag between support hangers shall not exceed 1 ⁄ 2 inch
(12.7 mm) per foot (305 mm) of support spacing. (5) Supports shall be rigid and shall be not less than 1 1 ⁄ 2
inches (38 mm) wide at point of contact with the duct surface. (6) Duct bends shall be not less than one duct diameter bend
radius. (7) Screws shall not penetrate the inner liner of non-metal lic flexible ducts unless permitted in accordance with the manufacturer’s installation instructions. (8) Fittings for attaching non-metallic ducts shall be beaded
and have a collar length of not less than 2 inches (51 mm) for attaching the duct. Metal worm-gear clamps shall be used. Exception: Where attaching metallic ducts using screws in accordance with the manufacturer’s installation instructions. (9) Duct inner liner shall be installed at not less than 1 inch
(25.4 mm) on the collar and past the bead prior to the application of the tape and mechanical fastener. Where mastic is used instead of tape, the mastic shall be applied in accordance the mastic manufacturer’s instructions. (10)Duct outer vapor barriers shall be secured using two
wraps of approved tape. A mechanical fastener shall be permitted to be used in place of, or in combination with, the tape. (11)Flexible air ducts shall not penetrate a fire-resistance rated assembly or construction. (12)The temperature of the air to be conveyed in a flexible air
duct shall not exceed 250°F (121°C). (13)Flexible Air ducts shall be sealed in accordance with Sec tion 603.9.
603.4.1 Length Limitation. [Not permitted for OSHPD 1, 1R, 2, 3, 4 & 5] Flexible air ducts shall be not more than 5 feet (1524 mm) in length and shall not be
«
» »
DUCT SYSTEMS
and moisture content shall be controlled so that the material is not adversely affected. All gypsum products shall have a mold or mildew resistant surface. For the purpose of this section, gypsum products shall not be exposed in supply ducts. 602.4.3 Air Dispersion Systems. Air dispersion systems shall be listed and labeled in accordance with UL 2518. 602.4.4 Other Materials. Flexible and rigid ducts, plenums, or fittings for use in heating, ventilation, and air conditioning systems of other nonmetallic materials listed and labeled to UL 181 shall be permitted. Exception: Plastic ducts shall comply with Section 603.5.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
▸Chapter 6 — DUCT SYSTEMS
Overview- 602.3 Metallic. Ducts, plenums, or fittings of metal shall com…
- 602.4 Nonmetallic Ducts. Nonmetallic ducts shall comply
- 601.1 Applicability. Ducts and plenums that are portions of
- 601.2 Sizing Requirements. Duct systems shall be sized
- 602.1 General. Materials used for duct systems shall comply wi…
- 602.2 Combustibles Within Ducts or Plenums. Materials exposed …
- 603.4 Flexible Air Ducts. Flexible air ducts shall comply
- 602.5 Vibration Isolators. Vibration isolation connectors
- 602.6 Corridors. Corridors shall not be used to convey air
- 603.1 General. Air ducts shall be installed in accordance
- 603.2 Under Floor or Crawl Space. Air ducts installed
- 603.3 Metal Ducts. Ducts shall be supported at each change
- 603.8 Protection Against Flood Damage. In flood hazard areas, …
- 603.9 Joints and Seams of Ducts. Joints and seams for
- 603.5 Plastic Ducts. Plastic air ducts and fittings shall be
- 603.6 Protection of Ducts. Ducts installed in locations
- 603.7 Support of Ducts. Ducts shall be supported in
- 603.12 Air Dispersion Systems. Where installed, air dispersion…
- 603.13 Clearances. Duct clearances shall be in accordance
- 604.1 Furnace Plenums and Air Ducts. Furnace plenums
- 604.2 Supplied as a Part of Furnace. A furnace plenum
- 604.3 Not Supplied with the Furnace. Where a furnace
- 603.10 Cross Contamination. Exhaust ducts that convey
- 603.11 Underground Installation. Ducts installed underground s…
- 604.4 Return Air. Where a furnace is installed so supply
- 605.1 General. Air ducts conveying air at temperatures
- 605.2 [OSHPD 1, 1R, 2, 3 (Surgical Clinics), 4 & 5] Ther-
- 605.3 [OSHPD 1, 1R, 2, 4 & 5] Thermal or acoustical lining
- 606.1 Smoke Dampers. Smoke dampers shall comply
- 606.2 Fire Dampers. Fire dampers shall comply with UL
- 606.3 Ceiling Radiation Dampers. Ceiling radiation
- 606.4 Multiple Arrangements. Where size requires the
- 606.5 Access and Identification. Fire and smoke
- 608.1 General. An under-floor space shall be permitted to
- 608.2 Dwelling Units. The use of under-floor space shall
- 608.3 Enclosed. Such spaces shall be cleaned of all loose
- 608.4 Flammable Materials. The enclosing material of
- 608.5 Access. Access shall be through an opening in the
- 608.6 Automatic Control. A furnace supplying warm air
- 608.7 Temperature Limit. A furnace supplying warm air to
- 608.8 Noncombustible Receptacle. A noncombustible
- 608.9 Floor Registers. Floor registers shall be designed
- 608.10 Exterior Wall and Interior Stud Partitions.
- 606.6 Freedom from Interference. Dampers shall be
- 606.7 Temperature Classification of Operating Ele-
- 606.8 When the automatic activation of a smoke damper or a
- 607.1 General. Perforated ceilings shall be permitted to be
- 607.2 Requirements. Ventilating ceilings shall comply
- 608.11 Wall Register. Each wall register shall be connected
- 608.12 Distance from Combustible. A duct complying
- 608.13 Vapor Barrier. The entire ground surface of the
- 608.14 Prohibited. Fuel gas lines and plumbing waste
- 609.1 Air-Moving Systems and Smoke Detectors.
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — GEOTHERMAL ENERGY SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE