602.2 Combustibles Within Ducts or Plenums.
California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Materials exposed within ducts or plenums shall be noncombustible or shall have a flame spread index not to exceed 25 and a smoke-developed index not to exceed 50, where tested as a composite product in accordance with ASTM E84 or UL 723. Plastic piping installed in plenums shall be tested in accordance with all requirements of ASTM E84 or UL 723. Mounting methods, supports and sample sizes of materials for testing that are not specified in ASTM E84 or UL 723 shall be prohibited. Exceptions: (1) Return-air and outside-air ducts, plenums, or concealed
spaces that serve a dwelling unit. (2) Air filters in accordance with the requirements of Sec tion 311.2. (3) Water evaporation media in an evaporative cooler. (4) Charcoal filters where protected with an approved fire
suppression system.
« «
2022 CALIFORNIA MECHANICAL CODE 123
Ducts shall be installed in a building with clearances that will retain the full thickness of fireproofing on structural members.
603.3.1 Earthquake Loads. Ducts located in structures that are installed in areas classified as seismic design category C, D, E, or F shall be in accordance with the California Building Code or California Residential Code .
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
▸Chapter 6 — DUCT SYSTEMS
Overview- 602.3 Metallic. Ducts, plenums, or fittings of metal shall com…
- 602.4 Nonmetallic Ducts. Nonmetallic ducts shall comply
- 601.1 Applicability. Ducts and plenums that are portions of
- 601.2 Sizing Requirements. Duct systems shall be sized
- 602.1 General. Materials used for duct systems shall comply wi…
- 602.2 Combustibles Within Ducts or Plenums. Materials exposed …
- 603.4 Flexible Air Ducts. Flexible air ducts shall comply
- 602.5 Vibration Isolators. Vibration isolation connectors
- 602.6 Corridors. Corridors shall not be used to convey air
- 603.1 General. Air ducts shall be installed in accordance
- 603.2 Under Floor or Crawl Space. Air ducts installed
- 603.3 Metal Ducts. Ducts shall be supported at each change
- 603.8 Protection Against Flood Damage. In flood hazard areas, …
- 603.9 Joints and Seams of Ducts. Joints and seams for
- 603.5 Plastic Ducts. Plastic air ducts and fittings shall be
- 603.6 Protection of Ducts. Ducts installed in locations
- 603.7 Support of Ducts. Ducts shall be supported in
- 603.12 Air Dispersion Systems. Where installed, air dispersion…
- 603.13 Clearances. Duct clearances shall be in accordance
- 604.1 Furnace Plenums and Air Ducts. Furnace plenums
- 604.2 Supplied as a Part of Furnace. A furnace plenum
- 604.3 Not Supplied with the Furnace. Where a furnace
- 603.10 Cross Contamination. Exhaust ducts that convey
- 603.11 Underground Installation. Ducts installed underground s…
- 604.4 Return Air. Where a furnace is installed so supply
- 605.1 General. Air ducts conveying air at temperatures
- 605.2 [OSHPD 1, 1R, 2, 3 (Surgical Clinics), 4 & 5] Ther-
- 605.3 [OSHPD 1, 1R, 2, 4 & 5] Thermal or acoustical lining
- 606.1 Smoke Dampers. Smoke dampers shall comply
- 606.2 Fire Dampers. Fire dampers shall comply with UL
- 606.3 Ceiling Radiation Dampers. Ceiling radiation
- 606.4 Multiple Arrangements. Where size requires the
- 606.5 Access and Identification. Fire and smoke
- 608.1 General. An under-floor space shall be permitted to
- 608.2 Dwelling Units. The use of under-floor space shall
- 608.3 Enclosed. Such spaces shall be cleaned of all loose
- 608.4 Flammable Materials. The enclosing material of
- 608.5 Access. Access shall be through an opening in the
- 608.6 Automatic Control. A furnace supplying warm air
- 608.7 Temperature Limit. A furnace supplying warm air to
- 608.8 Noncombustible Receptacle. A noncombustible
- 608.9 Floor Registers. Floor registers shall be designed
- 608.10 Exterior Wall and Interior Stud Partitions.
- 606.6 Freedom from Interference. Dampers shall be
- 606.7 Temperature Classification of Operating Ele-
- 606.8 When the automatic activation of a smoke damper or a
- 607.1 General. Perforated ceilings shall be permitted to be
- 607.2 Requirements. Ventilating ceilings shall comply
- 608.11 Wall Register. Each wall register shall be connected
- 608.12 Distance from Combustible. A duct complying
- 608.13 Vapor Barrier. The entire ground surface of the
- 608.14 Prohibited. Fuel gas lines and plumbing waste
- 609.1 Air-Moving Systems and Smoke Detectors.
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — GEOTHERMAL ENERGY SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE