Appendix E — SUSTAINABLE PRACTICES

California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

Adopting Agency BSC BSC-
CG
SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
Adopting Agency **BSC ** BSC-
CG
SFM 1 2 1-AC **AC ** SS SS/CC 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
Adopt Entire Chapter
Adopt Entire Chapter as
amended (amended sections
listed below)
Adopt only those sections
that are listed below
Chapter/Section

This state agency does not adopt sections identified with the following symbol: † The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.

2022 CALIFORNIA MECHANICAL CODE 373

374 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

SUSTAINABLE PRACTICES The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.

E 101.0 General. E 101.1 Applicability. The purpose of this appendix is to provide a comprehensive set of technically sound provisions that encourage sustainable practices and works towards enhancing the design and construction of mechanical systems that result in a positive long-term environmental impact. This appendix is not intended to circumvent the health, safety, and general welfare requirements of this code. E 101.2 Definition of Terms. For the purposes of this code, the definitions shall apply to this appendix.

No attempt is made to define ordinary words, which are used in accordance with their established dictionary meanings, except where a word has been used loosely, and it is necessary to define its meaning as used in this appendix to avoid misunderstanding.

The definitions of terms are arranged alphabetically according to the first word of the term.

E 201.0 Definitions. E 201.1 Cycles of Concentration for Cooling Towers. Cycles of concentration equals the specific conductance of the water in the cooling tower basin divided by the combined flow-weighted average specific conductance of the makeup water(s) to the cooling tower. E 201.2 Duct Wall Penetrations. Includes pipe, tubing, rods, and wire. Screws and other fasteners are not considered to be ductwork penetrations. E 201.3 Energy Star. A joint program of the U.S. Environmental Protection Agency and the U.S. Department of Energy. Energy Star is a voluntary program designed to identify and promote energy-efficient products and practices. E 201.4 Geothermal. Renewable energy generated by deep-earth.

pipe, tubing, rods, and wire. Screws and other fasteners are not considered to be ductwork penetrations. E 201.3 Energy Star. A joint program of the U.S. Environmental Protection Agency and the U.S. Department of Energy. Energy Star is a voluntary program designed to identify and promote energy-efficient products and practices. E 201.4 Geothermal. Renewable energy generated by deep-earth.

E 201.5 Heating Seasonal Performance Factor (HSPF). The total heating output of a heat pump during its normal annual usage period for heating in British thermal units (Btu) (kW•h) divided by the total electric energy input during the same period. [ASHRAE 90.1:3.2] E 201.6 Integrated Energy Efficiency Ratio (IEER). A single-number figure of merit expressing cooling part-load EER efficiency for commercial unitary air-conditioning and heat pump equipment on the basis of weighted operation at various load capacities for the equipment. [ASHRAE 90.1:3.2] E 201.7 Integrated Part-Load Value (IPLV). A single-number figure of merit based on part-load EER, COPC, or kW/kW expressing part-load efficiency for air-conditioning and heat pump equipment on the basis of weighted operation at various load capacities for the equipment. [ASHRAE 90.1:3.2]

E 201.8 Joint, Transverse . Connections of two duct sections oriented perpendicular to airflow. E 201.9 Maintenance. The upkeep of property or equipment by the owner of the property in accordance with the requirements of this appendix.

E 201.10 Minimum Efficiency Reporting Value (MERV). Filter minimum efficiency reporting value, in accordance with ASHRAE 52.2. E 201.11 Multi-Occupant Spaces. Indoor spaces used for presentations and training, including classrooms and conference rooms. E 201.12 Recirculation System. A system of hot water supply and return piping with shutoff valves, balancing valves, circulating pumps, and a method of controlling the circulating system. E 201.13 Seam, Longitudinal . Joints oriented in the direction of airflow. E 201.14 Seasonal Energy Efficiency Ratio (SEER). The total cooling output of an air conditioner during its normal annual usage period for cooling in Btu (kW•h) divided by the total electric energy input during the same period in Btu (kW•h). [ASHRAE 90.1:3.2]

E 301.0 General Regulations. E 301.1 Installation. Mechanical systems covered by this appendix shall be installed in accordance with this code, other applicable codes, and the manufacturer’s installation and operating instructions. E 301.2 Qualifications. Where permits are required, the Authority Having Jurisdiction shall have the authority to require contractors, installers, or service technicians to demonstrate competency. Where determined by the Authority Having Jurisdiction, the contractor, installer or service technician shall be licensed to perform such work.

manufacturer’s installation and operating instructions. E 301.2 Qualifications. Where permits are required, the Authority Having Jurisdiction shall have the authority to require contractors, installers, or service technicians to demonstrate competency. Where determined by the Authority Having Jurisdiction, the contractor, installer or service technician shall be licensed to perform such work.

E 302.0 Disposal of Liquid Waste. E 302.1 Disposal. It shall be unlawful for a person to cause, suffer, or permit the disposal of liquid wastes, in a place or manner, except through and by means of an approved drainage system, installed and maintained in accordance with the provisions of the plumbing code. E 302.2 Connections to Plumbing System Required. Equipment and appliances, used to receive or discharge liquid wastes or sewage, shall be connected to the drainage system of the building or premises in accordance with the requirements of the plumbing code and this appendix.

2022 CALIFORNIA MECHANICAL CODE 375

APPENDIX E

E 303.0 Abandonment. E 303.1 General. An abandoned system or part thereof covered under the scope of this appendix shall be disconnected from remaining systems, drained, plugged, and capped in an approved manner.

E 401.0 Water Conservation and Efficiency. E 401.1 General. The provisions of this section establish the means of conserving potable and nonpotable water used in and around a building.

E 402.0 Meters. E 402.1 Required. A water meter shall be required for buildings connected to a public water system, including municipally supplied reclaimed (recycled) water. In other than single-family houses, multi-family structures not exceeding three stories above grade, and modular houses, a separate meter or submeter shall be installed in the following locations: (1) The makeup water supply to cooling towers, evaporative

condensers, and fluid coolers. (2) The makeup water supply to one or more boilers collec tively exceeding 1 000 000 British thermal units per hour (Btu/h) (293 kW). (3) The water supply to a water-using process where the con sumption exceeds 1000 gallons per day (gal/d) (0.0438 L/s), except for manufacturing processes. (4) The makeup water supply to an evaporative cooler hav ing an air flow exceeding 30 000 cubic feet per minute (ft 3 /min) (14.1584 m 3 /s). E 402.2 Consumption Data. A means of communicating water consumption data from submeters to the water consumer shall be provided. E 402.3 Access. Meters and submeters shall be accessible.

/s), except for manufacturing processes. (4) The makeup water supply to an evaporative cooler hav ing an air flow exceeding 30 000 cubic feet per minute (ft 3 /min) (14.1584 m 3 /s). E 402.2 Consumption Data. A means of communicating water consumption data from submeters to the water consumer shall be provided. E 402.3 Access. Meters and submeters shall be accessible.

E 403.0 HVAC Water Use. E 403.1 Once-Through Cooling. Once-through cooling using potable water is prohibited. E 403.2 Cooling Towers and Evaporative Coolers. Cooling towers and evaporative coolers shall be equipped with makeup water and blow down meters, conductivity controllers, and overflow alarms. Cooling towers shall be equipped with efficiency drift eliminators that achieve drift reduction to 0.002 percent of the circulated water volume for counterflow towers and 0.005 percent for cross-flow towers. E 403.3 Cooling Tower Makeup Water. Not less than 5 cycles of concentration is required for air-conditioning cooling tower makeup water having a total hardness of less than 11 grains per gallon (gr/gal) (188 mg/L) expressed as calcium carbonate. Not less than 3.5 cycles of concentration is required for air-conditioning cooling tower makeup water having a total hardness equal to or exceeding 11 gr/gal (188 mg/L) expressed as calcium carbonate.

Exception: Air-conditioning cooling tower makeup water having discharge conductivity range not less than 7 gr/gal (120 mg/L) to 9 gr/gal (154 mg/L) of silica measured as silicon dioxide. E 403.4 Evaporative Cooler Water Use. Evaporative cooling systems shall use 3.5 gallons (13.2 L) or less of water per ton-hour (kW•h) of cooling where system controls are set to maximum water use. Water use expressed in maximum water use per ton-hour (kW•h) of cooling, shall be marked on the device and included in the product user manual, product information literature, and manufacturer’s installation instructions. Water use information shall be readily available at the time of code compliance inspection.

ter per ton-hour (kW•h) of cooling where system controls are set to maximum water use. Water use expressed in maximum water use per ton-hour (kW•h) of cooling, shall be marked on the device and included in the product user manual, product information literature, and manufacturer’s installation instructions. Water use information shall be readily available at the time of code compliance inspection.

E 403.4.1 Overflow Alarm. Cooling systems shall be equipped with an overflow alarm to alert building owners, tenants, or maintenance personnel where the water refill valve continues to allow water to flow into the reservoir where the reservoir is full. The alarm shall have a sound pressure level rating of not less than 85 dBa measured at a distance of 10 feet (3048 mm). E 403.4.2 Automatic Pump Shut-Off. Cooling systems shall automatically cease pumping water to the evaporation pads where airflow across evaporation pads ceases. E 403.4.3 Cooler Reservoir Discharge. A water quality management system (either timer or water quality sensor) shall be provided. Where timers are used, the time interval between discharge of reservoir water shall be set to 6 or more hours of cooler operation. Where water quality sensors are used, the discharge of reservoir water shall be set for 800 ppm or more of total dissolved solids (TDS). Continuous discharge or continuous bleed systems shall not be installed. E 403.4.4 Discharge Water Reuse. Discharge water shall be reused where applications exist on site. Where a nonpotable water source system exists on site, evaporative cooler discharge water shall be collected and discharged to the collection system. Exception: Where the reservoir water affects the quality of the nonpotable water supply making the nonpotable water unusable for its intended purposes. E 403.4.5 Discharge Water to Drain. Where discharge water is not recovered for reuse, the sump overflow line shall not be directly connected to a drain. Where the discharge water is discharged into a sanitary drain, an air gap of not less than 6 inches (152 mm) shall be provided between the termination of the discharge line and the drain opening. The discharge line shall terminate in a location that is visible to the building owner, tenants, or maintenance personnel.

E 403.5 Use of Reclaimed (Recycled) and Onsite Treated Nonpotable Water for Cooling. Where approved for use by the water or wastewater utility and the Authority Having Jurisdiction, reclaimed (recycled), or onsite treated nonpotable water shall be permitted to be used for industrial and commercial cooling or air-conditioning.

376 2022 CALIFORNIA MECHANICAL CODE

E 403.5.1 Drift Eliminator. A drift eliminator shall be utilized in a cooling system, utilizing alternate sources of water, where the aerosolized water is capable of coming in contact with employees or members of the public. E 403.5.2 Disinfection. A biocide shall be used to treat the cooling system recirculation water where the recycled water is capable of coming in contact with employees or members of the public.

or.** A drift eliminator shall be utilized in a cooling system, utilizing alternate sources of water, where the aerosolized water is capable of coming in contact with employees or members of the public. E 403.5.2 Disinfection. A biocide shall be used to treat the cooling system recirculation water where the recycled water is capable of coming in contact with employees or members of the public.

E 501.0 Heating, Ventilation, and Air-Conditioning Sys- tems and Equipment – Energy Efficiency. E 501.1 Scope. The provisions of this section shall establish the means of enhancing energy efficiency associated with mechanical systems in a building.

E 502.0 Heating, Ventilation, and Air-Conditioning Low-Rise Residential Buildings. E 502.1 General. The heating, ventilating, air-conditioning, for single-family houses, multi-family structures not exceeding three stories above grade, and modular houses shall be in accordance with Section E 502.2 through Section E 502.12. The heating, ventilation, and air-conditioning system of other buildings shall be in accordance with Section E 503.0. E 502.2 Heating, Ventilating, and Air-Conditioning Sys- tems and Equipment. This section shall regulate only equipment using single-phase electric power, air conditioners, and heat pumps with rated cooling capacities less than 65 000 British thermal units per hour (Btu/h) (19 kW), warm air furnaces with rated heating capacities less than 225 000 Btu/h (66 kW), boilers less than 300 000 Btu/h (88 kW) input, and heating-only heat pumps with rated heating capacities less than 65 000 Btu/h (19 kW). [ASHRAE 90.2:6.2]

E 502.2.1 Nonresidential Type Systems and Equip- ment. Heating, ventilating, and air-conditioning systems and equipment that do not fall under the requirements of Section E 502.0 shall be in accordance with the applicable requirements of Section E 503.0. E 502.3 Balancing. The air distribution system design, including outlet grilles, shall provide a means for balancing the air distribution system unless the design procedure provides a system intended to operate within plus or minus 10 percent of design air quantities. [ASHRAE 90.2:6.3]

E 502.3.1 Balancing Dampers. Balancing dampers shall be installed in branch ducts, and the axis of the damper shall be installed parallel to the direction of airflow in the main duct. E 502.4 Ducts. Ducts shall be sized, installed, and tested in accordance with Section E 502.4.1 through Section E 502.4.4.

E 502.4.1 Insulation for Ducts. Portions of the air distribution system installed in or on buildings for heating and cooling shall be R-8. Where the mean outdoor dew-point temperature in a month exceeds 60°F (16°C), vapor retarders shall be installed on conditioned-air supply ducts. Vapor retarders shall have a water vapor permeance not exceeding 0.5 perm [2.87 E-11 kg/(Pa•s•m 2 )] where tested in accordance with Procedure A in ASTM E96.

Insulation shall not be required where the ducts are within the conditioned space. [ASHRAE 90.2:6.4]

APPENDIX E

E 502.4.2 Ducts and Register Penetrations. Joints, seams, and penetrations of duct systems shall be made airtight by means of mastics, gasketing, or other means in accordance with this code. Register penetrations shall be sealed to the wall or floor assemblies. Where HVAC duct penetrates a conditioned space, the duct penetration shall be sealed to the wall or floor assembly to prevent leakage into an unconditioned space. E 502.4.3 Duct Leakage Test. For systems with a duct or air handler outside of the conditioned space, a duct leakage test shall be performed in accordance with Section E 502.4.3.1.

E 502.4.3.1 Duct Leakage Verification Test. Ductwork shall be tested to the maximum permitted leakage in 1 cubic foot per minute (ft 3 /min) per 100 square feet [0.0001 (m 3 /s)/m 2 ] of duct surface area in accordance with SMACNA HVAC Air Duct Leakage Test Manual. Register penetrations shall be sealed during the test. The test shall be conducted with a pressure differential of 0.1 inch water gauge (0.02 kPa) across the tested system. E 502.4.4 Duct Sizing. Duct systems shall be sized in accordance with ACCA Manual D or other methods approved by the Authority Having Jurisdiction with the velocity in the main duct not to exceed 1000 feet per minute (ft/min) (5.08 m/s) and the velocity in the secondary branch duct not to exceed 600 ft/min (3.048 m/s). E 502.5 Insulation for Piping. HVAC system piping installed to serve buildings and within buildings shall be thermally insulated in accordance with Table E 502.5. [ASHRAE 90.2:6.5] E 502.6 Ventilation and Combustion Air. The building shall be designed to have the capability to provide the ventilation air specified in Table E 502.6. Mechanical ventilation shall be calculated in accordance with Equation E 502.6.

[ASHRAE 90.2:6.6.1]

(Equation E 502.6) Mechanical Ventilation = [(0.35 – Summer ) × Volume ] / 60

Where: Mechanical Ventilation = required mechanical ventilation

rate to supplement summer infiltration, CFM (m 3 /s) Summer = summer design infiltration rate, ACH Volume = volume of conditioned space, ft 3 (m 3 )

E 502.6.1 Combustion Air. Combustion air for fossil fuel heating equipment shall comply with this code or with one of the following: (1) Natural gas and propane heating equipment, NFPA

54 (2) Oil heating equipment, NFPA 31 (3) Solid fuel burning equipment, NFPA 211

[ASHRAE 90.2:6.6.2]

2022 CALIFORNIA MECHANICAL CODE 377

APPENDIX E

E 502.7 Electric Heating Systems. Electric heating systems shall be installed in accordance with the following requirements. [ASHRAE 90.2:6.7]

E 502.7.1 Wall, Floor, or Ceiling Electric-Resis- tance Heating. Where wall, floor, or ceiling electricresistance heating units are used, the structure shall be zoned and heaters installed in each zone in accordance with the heat loss of that zone. Where living and sleeping zones are separate, the number of zones shall be not less than two. Where two or more heaters are installed in one room, they shall be controlled by one thermostat.

sis-** tance Heating. Where wall, floor, or ceiling electricresistance heating units are used, the structure shall be zoned and heaters installed in each zone in accordance with the heat loss of that zone. Where living and sleeping zones are separate, the number of zones shall be not less than two. Where two or more heaters are installed in one room, they shall be controlled by one thermostat.

[ASHRAE 90.2:6.7.1]

E 502.7.2 Electric Central Warm Air Heating. Where electric central warm air heating is to be installed, an electric heat pump or an off-peak electric heating system with thermal storage shall be used. Exceptions: (1) Electric resistance furnaces where the ducts are

located inside the conditioned space, and not less than two zones are provided where the living and sleeping zones are separate. (2) Packaged air-conditioning units with supplemental

electric heat. [ASHRAE 90.2:6.7.2]

TABLE E 502.5 MINIMUM PIPE INSULATION THICKNESS 1, 5

[ASHRAE 90.2: TABLE 6.5]

INSULATION CONDUCTIVITY NOMINAL PIPE DIAMETER (inches)
FLUID DESIGN
OPERATING
TEMERATURE
RANGE (°F)
Btu•inch/(h•ft2•°F) MEAN RATING
TEMPERATURE (°F)
<1 1 TO 11⁄4 11⁄2 TO 31⁄2 4 TO 6 EQUAL TO OR
GREATER THAN 8
HEATING SYSTEMS (STEAM, STEAM CONDENSATE, AND HOT WATER)2, 3
201–250 0.27–0.30 150 1.5 1.5 2.0 2.0 2.0
141–200 0.25–0.29 125 1.0 1.0 1.0 1.5 1.5
105–140 0.22–0.28 100 0.5 0.5 1.0 1.0 1.0
COOLING SYSTEMS (CHILLED WATER, BRINE, AND REFRIGERANT)4
40–55 0.22–0.28 100 0.5 0.5 1.0 1.0 1.0
Below 40 0.22–0.28 100 0.5 1.0 1.0 1.0 1.5

For SI Units: °C= (°F-32)/1.8, 1 British thermal unit inch per hour square foot degree Fahrenheit = [0.1 W/(m•K)], 1 inch = 25 mm Notes: 1 For insulation outside the stated conductivity range, the minimum thickness ( T ) shall be determined as follows: T = r {(1 + t/r) K/k - 1}

Where: T = minimum insulation thickness (inches). r = actual outside radius of pipe (inches) (mm). t = insulation thickness listed in this table for applicable fluid temperature and pipe size. K = conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature [Btu•in/(h•ft 2 •°F)] [W/(m•K)]. k = the upper value of the conductivity range listed in this table for the applicable fluid temperature. 2 These thicknesses are based on energy efficiency considerations only. Additional insulation is sometimes required relative to safety issues/surface temperature. 3 Piping insulation is not required between the control valve and coil on run-outs where the control valve is located within 4 feet (1219 mm) of the coil and the pipe size is 1 inch (25 mm) or less. 4 These thicknesses are based on energy efficiency considerations only. Issues such as water vapor permeability or surface condensation sometimes require vapor retarders, additional insulation or both. 5 For piping exposed to outdoor air, increase insulation thickness by 1 ⁄ 2 of an inch (12.7 mm). The outdoor air is defined as any portion of insulation that is exposed to outdoor air. For example, attic spaces and crawl spaces are considered exposed to outdoor air.

TABLE E 502.6
VENTILATION AIR
[ASHRAE 90.2: TABLE 6.6.1]
CATEGORY
MINIMUM REQUIREMENT
CONDITIONS
Mechanical ventilation1
50 ft3/min outdoor air
Where summer design infiltration rate calculated in accordance with
reference standard (a) or (b) is less than 0.35 ACH2.
Where summer design infiltration rate calculated in accordance with
reference standard (a) or (b) is less than 0.35 ACH2.
Kitchen exhaust
100 ft3/min intermittent
All conditions
Bath exhaust
intermittent
All conditions
For SI units: 1 cubic foot per minute = 0.00047 m3/s

Notes: 1 Calculate in accordance with Equation E 502.6. 2 Reference standards: (a) ACCA Manual J (b) ASHRAE GRP-158

378 2022 CALIFORNIA MECHANICAL CODE

E 502.8 Bath Ceiling Units. Bath ceiling units providing a combination of heat, light, or ventilation shall be provided with controls permitting separate operation of the heating function. [ASHRAE 90.2:6.8] E 502.9 HVAC Equipment, Rated Combinations. HVAC system equipment and system components shall be furnished with the input(s), the output(s), and the value of the appropriate performance descriptor of HVAC products in accordance with federal law or in accordance with Table E 502.9, as applicable. These shall be based on newly produced equipment or components. Manufacturer’s instructions shall be furnished with and attached to the equipment. The manufacturer of electric-resistance heating equipment shall furnish full-load energy input over the range of voltages at which the equipment is intended to operate. [ASHRAE 90.2:6.9] E 502.10 Controls. Each system or each zone within a system shall be provided with not less than one thermostat capable of being set from 55°F (13°C) to 85°F (29°C) and capable of operating the system’s heating and cooling. The thermostat or control system, or both, shall have an adjustable deadband, the range of which includes a setting of 10°F (6°C) between heating and cooling where automatic changeover is provided. Wall-mounted temperature controls shall be mounted on an inside wall. [ASHRAE 90.2:6.10.1]

E 502.10.1 Initial Control Setting. The control shall initially be set for a maximum heating temperature of 70°F (21°C) and a cooling temperature of not less than 78°F (26°C). E 502.10.2 Ventilation Control. Each mechanical ventilation system (supply, exhaust, or both) shall be equipped with a readily accessible switch or other means for shutoff. Manual or automatic dampers installed for the purpose of isolating outside air intakes and exhausts from the air distribution system shall be designed for tight shutoff.

[ASHRAE 90.2:6.10.2] E 502.10.3 Humidity Control. Where additional energy-consuming equipment is provided for adding moisture to maintain specific selected relative humidities in spaces or zones, a humidistat shall be provided. This device shall be capable of being set to prevent energy

APPENDIX E

from being used to produce relative humidity within the space above 30 percent. [ASHRAE 90.2:6.10.3.1]

E 502.10.3.1 Cooling. Where additional energyconsuming equipment is provided for reducing humidity, it shall be equipped with controls capable of being set to prevent energy from being used to produce a relative humidity within the space below 50 percent during periods of human occupancy and below 60 percent during unoccupied periods.

[ASHRAE 90.2:6.10.3.2] E 502.10.4 Freeze Protection Systems. Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, including self-regulating heat tracing, shall include automatic controls capable of and configured to shut off the systems where outdoor air temperatures are above 40°F (4°C) or where the conditions of the protected fluid will prevent freezing. Snowand ice-melting systems shall include automatic controls capable of and configured to shut off the systems where the pavement temperature is above 50°F (10°C) and no precipitation is falling and an automatic or manual control that will allow shutoff where the outdoor temperature is above 40°F (4°C) so that the potential for snow or ice accumulation is negligible. [ASHRAE 90.1:6.4.3.7] E 502.10.5 Other Controls. Where setback, zoned, humidity and cooling controls and equipment are provided, they shall be designed and installed in accordance with Section E 502.10 through Section E 502.10.3.1.

[ASHRAE 90.2:6.10.3.3] E 502.11 Whole House Fans. Whole house exhaust fans shall have insulated louvers or covers which close where the fan is off. Covers or louvers shall have an insulation value of not less than R-4.2, and shall be installed in accordance with the manufacturer’s installation instructions. The attic openings shall be sufficient to accommodate the ventilation capacity of the whole house fan. The operation of the whole house fan shall be considered in determining the adequacy of providing combustion air in accordance with this code. E 502.12 Dampers. Dampers shall be installed to close off outdoor air inlets and exhaust outlets where the ventilation system is not operating.

TABLE E 502.9 MINIMUM REQUIREMENTS FOR NON-FEDERALLY COVERED HVAC EQUIPMENT

[ASHRAE 90.2: TABLE 6.9]

EQUIPMENT TYPE SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE
Groundwater source heat pump* Cooling Mode 11.0 EER at 70°F Ent. Water ARI 325
Groundwater source heat pump* Cooling Mode 11.5 EER at 50°F Ent. Water 11.5 EER at 50°F Ent. Water
Groundwater source heat pump* Heating Mode 3.4 COP at 70°F Ent. Water 3.4 COP at 70°F Ent. Water
Groundwater source heat pump* Heating Mode 3.0 COP at 50°F Ent. Water 3.0 COP at 50°F Ent. Water
Unitary A/C Water cooled split system 9.3 EER at 85°F Ent. Water ARI 210/240
Unitary A/C Water cooled split system 8.3 IPLV at 75°F Ent. Water 8.3 IPLV at 75°F Ent. Water
Unitary A/C Evaporatively cooled split system 9.3 EER at 95°F Out. Amb. 9.3 EER at 95°F Out. Amb.
Unitary A/C Evaporatively cooled split system 8.5 IPLV at 80°F Out. Amb. 8.5 IPLV at 80°F Out. Amb.

For SI units: °C = (°F-32)/1.8

  • Performance for electrically powered equipment with capacity less than 65 000 Btu/h (19 kW) where rated in accordance with ARI 325.

2022 CALIFORNIA MECHANICAL CODE 379

APPENDIX E

E 503.0 Heating, Ventilation, and Air-Conditioning – Other than Low-Rise Residential Buildings. E 503.1 General. The heating, ventilation, and air-conditioning in buildings, other than single-family houses, multi-family structures of not more than three stories above grade, and modular houses, shall be in accordance with Section E 503.0.

E 503.1.1 New Buildings. Mechanical equipment and systems serving the heating, cooling, ventilating, or refrigeration needs of new buildings shall be in accordance with the requirements of this section as described in Section E 503.2. [ASHRAE 90.1:6.1.1.1] E 503.1.2 Additions to Existing Buildings. Mechanical equipment and systems serving the heating, cooling, ventilating, or refrigeration needs of additions to existing buildings shall be in accordance with the requirements of this section as described in Section E 503.2. Exception: Where HVACR to an addition is provided by existing HVACR systems and equipment, such existing systems and equipment shall not be required to be in accordance with this appendix. A new system or equipment installed shall be in accordance with specific requirements applicable to those systems and equipment.

[ASHRAE 90.1:6.1.1.2] E 503.1.3 Alterations to Heating, Ventilating, Air- Conditioning, and Refrigeration in Existing Buildings. New HVACR equipment as a direct replacement of existing HVACR equipment shall be in accordance with the following sections as applicable for the equipment being replaced: (1) Section E 503.3 (2) Section E 503.4 (3) Section E 503.4.6 (4) Section E 503.4.6.2 (5) Section E 503.4.6.3 (6) Section E 503.4.6.4 (7) Section E 503.4.6.8 (8) Section E 503.4.6.9 (9) Section E 503.4.6.11 (10)Section E 503.5.1 (11)Section E 503.5.3 (12)Section E 503.5.4 (13) Section E 503.5.6.1.2 (14) Section E 503.5.6.2 (15) Section E 503.5.6.5 (16) Section E 503.5.7 (17) Section E 503.5.7.2 (18) Section E 503.5.8.1. [ASHRAE 90.1:6.1.1.3.1]

E 503.1.3.1 New Cooling Systems. New cooling systems installed to serve previously uncooled spaces shall be in accordance with this section as described in Section E 503.2. [ASHRAE 90.1:6.1.1.3.2] E 503.1.3.2 Existing Cooling Systems. Alterations to existing cooling systems shall not decrease economizer capability unless the system is in accor

dance with Section E 503.5 through Section 503.5.4.1.

[ASHRAE 90.1:6.1.1.3.3] E 503.1.3.3 Ductwork. New and replacement ductwork shall comply with Section E 503.4.7.1 through Section E 503.4.7.2.1. [ASHRAE 90.1:6.1.1.3.4] E 503.1.3.4 Piping. New and replacement piping shall comply with Section E 503.4.7.1. Exceptions: (1) For equipment that is being modified or

repaired but not replaced, provided that such modifications or repairs will not result in an increase in the annual energy consumption of the equipment using the same energy type. (2) Where a replacement or alteration of equipment

requires extensive revisions to other systems, equipment, or elements of a building, and such replaced or altered equipment is a like-for-like replacement. (3) For a refrigerant change of existing equipment. (4) For the relocation of existing equipment. (5) For ducts and piping where there is insufficient

space or access to comply with these requirements. [ASHRAE 90.1:6.1.1.3.5] E 503.2 Compliance Path(s). Section E 503.0 shall be achieved in accordance with the requirements of Section E 503.1.1 through Section E 503.1.3.4, Section E 503.6, Section E 503.7, and one of the following: (1) Section E 503.3 and Section E 503.3.1 (2) Section E 503.4 (3) Section E 503.4 and Section E 503.8 [ASHRAE 90.1:6.2.1]

E 503.2.1 Projects Using Energy Cost Budget Method. Projects using the energy cost budget method in accordance with ASHRAE 90.1 shall comply with Section E 503.4, the mandatory provisions of this section, as a portion of that compliance path. [ASHRAE 90.1:6.2.2]

E 503.3 Simplified Approach Option for HVAC Sys- tems. The simplified approach shall be an optional path for compliance where the following conditions are met: (1) The building is not more than two stories in height. (2) Gross floor area is less than 25 000 square feet (2322.6 m 2 ). (3) The HVAC system in the building is in accordance with

the requirements listed in Section E 503.3.1. [ASHRAE 90.1:6.3.1] E 503.3.1 Criteria. The HVAC system shall comply with the following criteria: (1) The system serves a single HVAC zone. (2) The equipment shall comply with the variable flow

requirements of Section E 503.5.6.2. (3) Cooling (where any) shall be provided by a unitary

packaged or split-system air conditioner that is either air-cooled or evaporatively cooled, with efficiency that is in accordance with the requirements shown

380 2022 CALIFORNIA MECHANICAL CODE

in Table E 503.7.1(1), Table E 503.7.1(2), or Table E 503.7.1(4) for the applicable equipment category. (4) The system shall have an air economizer in accor dance with Section E 503.5 and Section E 503.4.6.13. (5) Heating (where any) shall be provided by a unitary

packaged or split-system heat pump that is in accordance with the applicable efficiency requirements shown in Table E 503.7.1(2) or Table E 503.7.1(4), a fuel-fired furnace that is in accordance with the applicable efficiency requirements shown in Table E 503.7.1(5), an electric resistance heater, or a baseboard system connected to a boiler that is in accordance with the applicable efficiency requirements shown in Table E 503.7.1(6). (6) The system shall comply with the exhaust air energy

recovery requirements in accordance with Section E 503.5.10. (7) The system shall be controlled by a manual

changeover or dual setpoint thermostat. (8) Where a heat pump equipped with auxiliary internal

electric resistance heaters is installed, controls shall be provided that prevent supplemental heater operation where the heating load is capable of being met by the heat pump alone during both steady-state operation and setback recovery. Supplemental heater operation shall be permitted during outdoor coil defrost cycles. The heat pump shall be controlled in accordance with one of the following: (a) A digital or electronic thermostat designed for

heat pump use that energizes auxiliary heat where the heat pump has insufficient capacity to maintain setpoint or to warm up the space at a sufficient rate. (b) A multistage space thermostat and an outdoor

air thermostat wired to energize auxiliary heat on the last stage of the space thermostat and where outdoor air temperature is less than 40°F (4°C). Exceptions: Heat pumps that comply with the following: (1) Have a minimum efficiency regulated by

NAECA. (2) In accordance with the requirements shown in

Table E 503.7.1(2). (3) Include all usage of internal electric resistance

heating. (9) The system controls shall not permit reheat or other

form of simultaneous heating and cooling for humidity control. (10)Systems serving spaces other than hotel or motel

guest rooms, and other than those requiring continuous operation, which have both a cooling or heating capacity more than 15 000 Btu/h (4.4 kW) and a supply fan motor power more than 0.75 horsepower (hp) (0.56 kW), shall be provided with a time clock that is in accordance with the following:

APPENDIX E

(a) Can start and stop the system under different

schedules for seven different day-types per week. (b) Is capable of retaining programming and time

setting during a loss of power for a period of not less than 10 hours. (c) Includes an accessible manual override that

allows temporary operation of the system for up to 2 hours. (d) Is capable of and configured with temperature

setback down to 55°F (13°C) during off hours. (e) Is capable of and configured with temperature

setup to 90°F (32°C) during off hours. (11) Systems serving hotel/motel guest rooms shall com ply with Section E 503.4.6.3.5. (12) Except for piping within manufacturer’s units,

HVAC piping shall be insulated in accordance with Table E 503.7.3(1) and Table E 503.7.3(2). Insulation exposed to weather shall be suitable for outdoor service, e.g., protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation. (13) Ductwork and plenums shall be insulated in accor dance with Table E 503.7.2 and shall be sealed in accordance with Section E 503.4.7.2. (14) Construction documents shall require a ducted sys tem to be air balanced in accordance with industryaccepted procedures. (15) Outdoor air intake and exhaust systems shall comply

with Section E 503.4.6.4 through Section E 503.4.6.5. (16) Where separate heating and cooling equipment

serves the same temperature zone, thermostats shall be interlocked to prevent simultaneous heating and cooling. (17) Systems with a design supply air capacity more than

10 000 ft 3 /min (4.7195 m 3 /s) shall have optimum start controls. (18) The system shall comply with the demand control

ventilation requirements of Section E 503.4.6.9 and the ventilation design requirements of Section E 503.5.6.6. (19) The system shall comply with the door switch require ments of Section E 503.5.14. [ASHRAE 90.1:6.3.2] E 503.3.2 Climate Zone Determination. Climate zones identified in this appendix shall be determined in accordance with ASHRAE 90.1. For locations in the United States and its territories, the assigned climate zone and, where required, the assigned climate zone letter shall be in accordance with ASHRAE 169. Exception: Where recorded historical climatic data are available for a construction site, it is permitted to be used to determine compliance where approved by the Authority Having Jurisdiction. [ASHRAE 90.1:5.1.4.1]

2022 CALIFORNIA MECHANICAL CODE 381

APPENDIX E

E 503.4 Mandatory Provisions. Equipment shown in Table E 503.7.1(1) through Table E 503.7.1(16) shall have a minimum performance at the specified rating conditions where tested in accordance with the specified test procedure. Where multiple rating conditions or performance requirements are provided, the equipment shall satisfy the stated requirements unless otherwise exempted by footnotes in the table. Equipment covered under the Federal Energy Policy Act of 1992 (EPACT) shall have no minimum efficiency requirements for operation at minimum capacity or other than standard rating conditions. Equipment used to provide service water-heating functions as part of a combination system shall satisfy the stated requirements for the appropriate space heating or cooling category. Tables are as follows: (1) Table E 503.7.1(1), “Electrically Operated Unitary Air

Conditioners and Condensing Units-Minimum Efficiency Requirements” (2) Table E 503.7.1 (2), “Electrically Operated Unitary and

Applied Heat Pumps-Minimum Efficiency Requirements” (3) Table E 503.7.1 (3), “Water-Chilling Packages-Effi ciency Requirements” (See Section E 503.4.1 for watercooled centrifugal water-chilling packages that are designed to operate at nonstandard conditions.) (4) Table E 503.7.1 (4), “Electrically Operated Packaged

Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air Conditioner Heat Pumps-Minimum Efficiency Requirements” (5) Table E 503.7.1 (5), “Warm-Air Furnaces and Combi nation Warm-Air Furnaces/Air-Conditioning Units, Warm-Air Duct Furnaces, and Unit Heaters-Minimum Efficiency Requirements” (6) Table E 503.7.1 (6), “Gas- and Oil-Fired Boilers-Mini mum Efficiency Requirements” (7) Table E 503.7.1 (7), “Performance Requirements for

onditioners, and Room Air Conditioner Heat Pumps-Minimum Efficiency Requirements” (5) Table E 503.7.1 (5), “Warm-Air Furnaces and Combi nation Warm-Air Furnaces/Air-Conditioning Units, Warm-Air Duct Furnaces, and Unit Heaters-Minimum Efficiency Requirements” (6) Table E 503.7.1 (6), “Gas- and Oil-Fired Boilers-Mini mum Efficiency Requirements” (7) Table E 503.7.1 (7), “Performance Requirements for

Heat-Rejection Equipment” (8) Table E 503.7.1 (8), “Heat Transfer Equipment” (9) Table E 503.7.1 (9), “Electrically Operated Variable Refrigerant-Flow Air Conditioners- Minimum Efficiency Requirements” (10)Table E 503.7.1 (10), “Electrically Operated Variable Refrigerant-Flow and Applied Heat Pumps-Minimum Efficiency Requirements” (11)Table E 503.7.1 (11), “Air Conditioners and Condens ing Units Serving Computer Rooms” (12)Table E 503.7.1 (12), “Commercial Refrigerators and

Freezers-Minimum Efficiency Requirements” (13)Table E 503.7.1 (13), “Commercial Refrigeration-Mini mum Efficiency Requirements” (14)Table E 503.7.1 (14), “Vapor-Compression-Based

Indoor Pool Dehumidifiers-Minimum Efficiency Requirements” (15)Table E 503.7.1 (15), “Electrically Operated DX-DOAS

Units, Single-Package and Remote Condenser, without Energy Recovery-Minimum Efficiency Requirements”

(16)Table E 503.7.1 (16), “Electrically Operated DX-DOAS

Units, Single-Package and Remote Condenser, with Energy Recovery-Minimum Efficiency Requirements” All furnaces with input ratings of 225 000 Btu/h (66 kW) or more, including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75 percent of the input rating. Air conditioners primarily serving computer rooms and covered by ASHRAE 127 shall comply with the requirements in Table E 503.7.1(11). All other air conditioners shall meet the requirements in Table E 503.7.1(1). [ASHRAE 90.1:6.4.1.1]

E 503.4.1 Water-Cooled Centrifugal Chilling Packages. Equipment not designed for operation in accordance with AHRI 550/590 test conditions of 44.00°F (6.67°C) leaving and 54.00°F (12.22°C) entering chilled-fluid temperatures, and with 85.00°F (29.44°C) entering and 94.30°F (34.61°C) leaving condenser-fluid temperatures, shall have maximum full-load kW/ton ( FL ) and part-load rating requirements adjusted in accordance with Equation E 503.4.1(1) through Equation E 503.4.1(3):

FLadj = FL / Kadj [Equation E 503.4.1(1)] PLVadj = IPLV.IP / Kadj [Equation E 503.4.1(2)] Kadj = A x B [Equation E 503.4.1(3)]

Where: FL = full-load kW/ton value from Table E

503.7.1(3) FLadj = maximum full-load kW/ton rating, adjusted

for nonstandard conditions IPLV.IP = IPLV.IP value from Table E 503.7.1(3) PLVadj = maximum NPLV rating, adjusted for non standard conditions A = 0.00000014592 x (LIFT ) 4 - 0.0000346496

x ( LIFT ) 3 + 0.00314196 x ( LIFT ) 2 0.147199 x ( LIFT ) + 3.93073 B = 0.0015 x LvgEvap + 0.934 LIFT = LvgCond - LvgEvap LvgCond = Full-load condenser leaving fluid tempera ture (°F) LvgEvap = Full-load evaporator leaving temperature

(°F)

The FLadj and PLVadj values shall only be applicable for centrifugal chillers meeting all of the following full-load design ranges: (1) 36.00°F (2.22°C) ≤ LvgEvap ≤ 60.00°F (15.56°C) (2) LvgCond ≤ 115.00°F (46.11°C) (3) 20.00°F (-6.67°C) ≤ LIFT ≤ 80.00°F (26.67°C)

Manufacturers shall calculate the FLadj and PLVadj before determining whether to label the chiller in accordance with Section E 503.4.4. Chillers that are in accordance with ASHRAE 90.1 shall be labeled on chillers in accordance with the scope of ASHRAE 90.1.

382 2022 CALIFORNIA MECHANICAL CODE

Centrifugal chillers designed to operate outside of these ranges shall not be covered under this appendix.

Example: Path A, 600 ton (600 000 kg) centrifugal chiller Table E 503.7.1(3) efficiencies. FL = 0.5600 kW/ton IPLV.IP = 0.5000 kW/ton LvgCond = 91.16°F LvgEvap = 42.00°F LIFT = 91.16°F – 42.00°F = 49.16°F A = 0.00000014592 x (49.16) 4 - 0.0000346496

x (49.16) 3 + 0.00314196 x (49.16) 2 0.147199 x (49.16) + 3.93073 = 1.02331 B = 0.0015 x 42.00 + 0.934 = 0.99700 Kadj = A x B FLajd = 0.5600/1.02024 = 0.5489 kW/ton PLVadj = 0.5000/1.02024 = 0.4901 kW/ton

[ASHRAE 90.1:6.4.1.2.1]

For SI units: 1 metric ton = 1000 kg, 1000 British thermal units per hour = 0.293 kW, 1 gallon per minute = 0.06 L/s, °C = (°F-32)/1.8

E 503.4.1.1 Positive Displacement (air- and water-cooled) Chilling Packages. Equipment with an evaporator leaving fluid temperature higher than 32.00°F (0.00°C) and water-cooled positive displacement chilling packages with a condenser leaving fluid temperature below 115.00°F (46.11°C) shall show compliance with Table E 503.7.1(3) when tested or certified with water at standard rating conditions, in accordance with the referenced test procedure. [ASHRAE 90.1:6.4.1.2.2] E 503.4.2 Equipment not Listed. Equipment not listed in the tables referenced in Section E 503.4 and Section E 503.4.1 shall be permitted to be used. [ASHRAE 90.1:6.4.1.3] E 503.4.3 Verification of Equipment Efficiencies. Equipment efficiency information supplied by manufacturers shall be verified in accordance with one of the following: (1) Equipment covered under EPACT shall be in accor dance with U.S. Department of Energy certification requirements. (2) Where a certification program exists for a covered

product, and it includes provisions for verification and challenge of equipment efficiency ratings, then the product shall be listed in the certification program. (3) Where a certification program exists for a covered

product, and it includes provisions for verification and challenge of equipment efficiency ratings, but the product is not listed in the existing certification program, the ratings shall be verified by an independent laboratory test report. (4) Where no certification program exists for a covered

product, the equipment efficiency ratings shall be supported by data furnished by the manufacturer.

APPENDIX E

(5) Where components such as indoor or outdoor coils

from different manufacturers are used, the system designer shall specify component efficiencies whose combined efficiency is in accordance with the minimum equipment efficiency requirements in Section E 503.4 through Section E 503.4.4.1. (6) Requirements for plate-type liquid-to-liquid heat

exchangers are listed in Table E 503.7.1(8).

[ASHRAE 90.1:6.4.1.4] E 503.4.4 Labeling. Mechanical equipment that is not covered by the U.S. National Appliance Energy Conservation Act (NAECA) of 1987 shall carry a permanent label installed by the manufacturer stating that the equipment is in accordance with the requirements of ASHRAE 90.1. [ASHRAE 90.1:6.4.1.5.1] E 503.4.4.1 Packaged Terminal Air Condi- tioners. Nonstandard-size packaged terminal air conditioners and heat pumps with existing sleeves having an external wall opening of less than 16 inches (406 mm) high or less than 42 inches (1067 mm) wide and having a cross-sectional area less than 670 square inches (0.432 m 2 ) shall be factory labeled as follows:

Manufactured for nonstandard-size applications only: Not to be installed in new construction projects. [ASHRAE 90.1:6.4.1.5.2] E 503.4.5 Load Calculations. Heating and cooling system design loads for the purpose of sizing systems and equipment shall be determined in accordance with ASHRAE/ACCA 183. [ASHRAE 90.1:6.4.2.1]

E 503.4.5.1 Pump Head. Pump differential pressure (head) for the purpose of sizing pumps shall be determined in accordance with generally accepted engineering standards and handbooks acceptable to the Authority Having Jurisdiction. The pressure drop through each device and pipe segment in the critical circuit at design conditions shall be calculated.

[ASHRAE 90.1:6.4.2.2] E 503.4.6 Zone Thermostatic Controls. The supply of heating and cooling energy to each zone shall be individually controlled by thermostatic controls responding to temperature within the zone. For the purposes of Section E 503.4.6, a dwelling unit shall be permitted to be considered a single zone. Exceptions: Independent perimeter systems that are designed to offset only building envelope loads shall be permitted to serve one or more zones also served by an interior system, provided that: (1) the perimeter system includes not less than one ther mostatic control zone for each building exposure having walls facing only one orientation for 50 contiguous feet (15 240 mm) or more and (2) the perimeter system heating and cooling supply is

controlled by thermostatic controls located within the zones served by the system. Exterior walls and semiexterior walls are considered to have different orientations where the exposures they

2022 CALIFORNIA MECHANICAL CODE 383

APPENDIX E

face differ by more than 45 degrees (0.79 rad).

[ASHRAE 90.1:6.4.3.1.1]

E 503.4.6.1 Dead Band. Where used to control both heating and cooling, zone thermostatic controls shall be capable of and configured to provide a temperature range or dead band of not less than 5°F (3°C) within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum. Exceptions: (1) Thermostats that require manual changeover

between heating and cooling modes. (2) Special occupancy or special applications

where wide temperature ranges are not acceptable (such as retirement homes, process applications, museums, some areas of hospitals) and are approved by the Authority Having Jurisdiction. [ASHRAE 90.1:6.4.3.1.2] E 503.4.6.2 Setpoint Overlap Restriction. Where heating and cooling to a zone are controlled by separate zone thermostatic controls located within the zone, means (such as limit switches, mechanical stops, or, for DDC systems, software programming) shall be provided to prevent the heating setpoint from exceeding the cooling setpoint minus any applicable proportional band. [ASHRAE 90.1:6.4.3.2] E 503.4.6.3 Off-Hour Controls. HVAC systems shall have the off-hour controls required by Section E 503.4.6.3.1 through Section E 503.4.6.3.4. Exceptions: (1) HVAC systems intended to operate continu ously. (2) HVAC systems having a design heating capac ity and cooling capacity less than 15 000 Btu/h (4.4 kW) that are equipped with readily accessible manual ON/OFF controls. [ASHRAE 90.1:6.4.3.3] E 503.4.6.3.1 Automatic Shutdown. HVAC systems shall be equipped with not less than one of the following: (1) Controls that can start and stop the system

under different time schedules for seven different day-types per week, are capable of retaining programming and time setting during loss of power for a period of not less than 10 hours, and include an accessible manual override, or equivalent function, that allows temporary operation of the system for up to 2 hours. (2) An occupant sensor that is capable of shut ting the system off where no occupant is sensed for a period of up to 30 minutes. (3) A manually operated timer capable of

being adjusted to operate the system for up to 2 hours.

(4) An interlock to a security system that shuts

the system off where the security system is activated. Exception: Residential occupancies shall be permitted to use controls that can start and stop the system under two different time schedules per week. [ASHRAE 90.1:6.4.3.3.1] E 503.4.6.3.2 Setback Controls. Heating systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the system as required to maintain zone temperatures above an adjustable heating setpoint of not less than 10°F (6°C) below the occupied heating setpoint. Cooling systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the mechanical cooling system as required to maintain zone temperatures below an adjustable cooling setpoint of not less than 5°F (3°C) above the occupied cooling setpoint or to prevent high space humidity levels. Exception: Radiant heating systems capable of and configured with a setback heating setpoint at not less than 4°F (2°C) below the occupied heating setpoint. [ASHRAE 90.1:6.4.3.3.2] E 503.4.6.3.3 Optimum Start Controls. Individual heating and cooling systems with setback controls and DDC shall have optimum start controls. The control algorithm shall, as a minimum, be a function of the difference between space temperature and occupied setpoint, the outdoor temperature, and the amount of time prior to scheduled occupancy. Mass radiant floor slab systems shall incorporate floor temperature into the optimum start algorithm. [ASHRAE 90.1:6.4.3.3.3] E 503.4.6.3.4 Zone Isolation. HVAC systems serving zones that are intended to operate or be occupied nonsimultaneously shall be divided into isolation areas. Zones shall be permitted to be grouped into a single isolation area provided it does not exceed 25 000 square feet (2322.6 m 2 ) of conditioned floor area and does not include more than one floor. Each isolation area shall be equipped with isolation devices capable of and configured to automatically shut off the supply of conditioned air and outdoor air to and exhaust air from the area. Each isolation area shall be controlled independently by a device meeting the requirements of Section E 503.4.6.3.1. For central systems and plants, controls and devices shall be provided to allow stable system and equipment operation for any length of time while serving only the smallest isolation area served by the system or plant. Exceptions: Isolation devices and controls are not required for the following:

384 2022 CALIFORNIA MECHANICAL CODE

(1) Exhaust air and outdoor air connections to

isolation zones where the fan system to which they connect is not more than 5000 ft 3 /min (2.3597 m 3 /s). (2) Exhaust airflow from a single isolation zone

of less than 10 percent of the design airflow of the exhaust system to which it connects. (3) Zones intended to operate continuously or

intended to be inoperative only when all other zones are inoperative. [ASHRAE 90.1:6.4.3.3.4] E 503.4.6.3.5 Automatic Control of HVAC in Hotel/Motel Guest Rooms. Hotels and motels with more than 50 guest rooms shall be provided with automatic controls for the HVAC equipment serving each guest room capable of and configured according to the requirements in Section E 503.4.6.3.1. [ASHRAE 90.1:6.4.3.3.5]

E 503.4.6.3.5.1 Guest Room HVAC Set-Point Control. Within 30 minutes of all occupants leaving the guest room, HVAC set points shall be automatically raised by not less than 4°F (2°C) from the occupant set point in the cooling mode and automatically lowered by at least 4°F (2°C) from the occupant set point in the heating mode. When the guest room is unrented and unoccupied, HVAC set points shall be automatically reset to 80°F (27°C) or higher in the cooling mode and to 60°F (16°C) or lower in the heating mode. Unrented and unoccupied guest rooms shall be determined by either of the following: (1) The guest room has been continuously

unoccupied for up to 16 hours. (2) A networked guest room control sys tem indicates the guest room is unrented and the guest room is unoccupied for no more than 30 minutes.

APPENDIX E

Exceptions: (1) A networked guest room control system

shall be permitted to return the thermostat set points to their default occupied set points 60 minutes prior to the time the room is scheduled to be occupied. (2) Cooling for humidity control shall be

permitted during unoccupied periods. E 503.4.6.4 Ventilation System Controls. Stair and elevator shaft vents shall be equipped with motorized dampers that are capable of and configured to automatically close during normal building operation and are interlocked to open as required by fire and smoke detection systems. [ASHRAE 90.1:6.4.3.4.1]

E 503.4.6.4.1 Shutoff Damper Controls. Outdoor air intake and exhaust systems shall be equipped with motorized dampers that will automatically shut when the systems or spaces served are not in use. Ventilation outdoor air and exhaust or relief dampers shall be capable of and configured to automatically shut off during preoccupancy building warm-up, cooldown, and setback, except when ventilation reduces energy costs or when ventilation shall be supplied to comply with the code requirements. Exceptions: (1) Back-draft gravity (nonmotorized) dampers

shall be permitted for exhaust and relief in buildings less than three stories in height and for ventilation air intakes and exhaust and relief dampers in buildings of any height located in Climate Zones 0, 1, 2 and 3. Backdraft dampers for ventilation air intakes shall be protected from direct exposure to wind. (2) Back-draft gravity (nonmotorized) dampers

shall be permitted in systems with a design outdoor air intake or exhaust capacity of 300 ft 3 /min (0.142 m 3 /s) or less.

TABLE E 503.4.6.4.2 MAXIMUM DAMPER LEAKAGE (cubic foot per minute per square foot) at 1.0 in. w.g

[ASHRAE 90.1: TABLE 6.4.3.4.3]

VENTILATION AIR INTAKE EXHAUST/RELIEF
CLIMATE ZONE NONMOTORIZED* MOTORIZED NONMOTORIZED* MOTORIZED
0, 1, 2
any height

20

4

20

4
3
any height

20

10

20

10
4, 5b, 5c
less than 3 stories
3 or more stories

not allowed
not allowed

10
10

20
not allowed

10
10
5a, 6, 7, 8
less than 3 stories
3 or more stories

not allowed
not allowed

4
4

20
not allowed

4
4

For SI units: 1 cubic foot per minute = 0.00047 m 3 /s, 1 square foot = 0.0929 m 2, 1 inch water gauge = 0.249 kPa

  • Dampers smaller than 24 inches (610 mm) in either dimension shall be permitted to have leakage of 40 ft 3 /min per square foot [0.203 (m 3 /s)/m 2 ].

2022 CALIFORNIA MECHANICAL CODE 385

APPENDIX E

(3) Dampers shall not be required in ventila tion or exhaust systems serving unconditioned spaces. (4) Dampers shall not be required in exhaust

systems serving Type 1 kitchen exhaust hoods. [ASHRAE 90.1:6.4.3.4.2] E 503.4.6.4.2 Dampers Leakage. Where outdoor air supply, and exhaust or relief dampers are required in Section E 503.4.6.4, they shall have a maximum leakage rate in accordance with Table E 503.4.6.4.2 where tested in accordance with AMCA 500D. [ASHRAE 90.1:6.4.3.4.3] E 503.4.6.4.3 Ventilation Fan Controls. Fans with motors more than 0.75 hp (0.56 kW) shall have automatic controls in accordance with Section E 503.4.6.3.1 that are capable of and configured to shut off fans when not required. Exception: HVAC systems intended to operate continuously. [ASHRAE 90.1:6.4.3.4.4] E 503.4.6.5 Enclosed Parking Garage Venti- lation. Enclosed parking garage ventilation systems shall automatically detect contaminant levels and stage fans or modulate fan airflow rates to 50 percent or less of design capacity, provided acceptable contaminant levels are maintained. Exceptions: (1) Garages less than 30 000 square feet (2787.09 m 2 )

with ventilation systems that do not utilize mechanical cooling or mechanical heating. (2) Garages that have a garage area to ventilation

system motor nameplate horsepower ratio that exceeds 1500 square feet per horsepower (ft 2 /hp) (186.8 m 2 /kW) and do not utilize mechanical cooling or mechanical heating. (3) Where not permitted by the Authority Having

Jurisdiction. [ASHRAE 90.1:6.4.3.4.5]

E 503.4.6.6 Heat Pump Auxiliary Heat Con- trol. Heat pumps equipped with internal electric resistance heaters shall have controls that prevent supplemental heater operation where the heating load is capable of being met by the heat pump alone during both steady-state operation and setback recovery. Supplemental heater operation shall be permitted during outdoor coil defrost cycles. Exception: Heat pumps whose minimum efficiency is regulated by U.S. National Appliance Energy Conservation Act (NAECA) and whose ratings are in accordance with the requirements shown in Table E 503.7.1(2) and includes the use of an internal electric resistance heating. [ASHRAE 90.1:6.4.3.5] E 503.4.6.7 Humidification and Dehumidifica- tion. Humidity control shall prevent the use of fossil fuel or electricity to produce relative humidity above 30 percent in the warmest zone served by the humidification system and to reduce relative humidity below 60 percent in the coldest zone served by the dehumidification system. Where a zone is served by

a system or systems with both humidification and dehumidification capability, means (such as limit switches, mechanical stops, or, for DDC systems, software programming) shall be provided capable of and configured to prevent simultaneous operation of humidification and dehumidification equipment. Exceptions: (1) Zones served by desiccant systems, used with

direct evaporative cooling in series. (2) Systems serving zones where specific humidity

levels are required, such as museums and hospitals, and approved by the Authority Having Jurisdiction or required by accreditation standards and humidity controls are capable of and configured to maintain a dead band of at least 10 percent relative humidity where no active humidification or dehumidification takes place. (3) Systems serving zones where humidity levels

are required to be maintained with precision of not more than ± 5 percent relative humidity to comply with applicable codes or accreditation standards or as approved by the Authority Having Jurisdiction. [ASHRAE 90.1:6.4.3.6] E 503.4.6.8 Freeze Protection and Snow or Ice Melting Systems. Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, including self-regulating heat tracing, shall include automatic controls capable of and configured to shut off the systems when outdoor air temperatures are more than 40°F (4°C) or when the conditions of the protected fluid will prevent freezing. Snow and ice melting systems shall include automatic controls capable of and configured to shut off the systems when the pavement temperature is more than 50°F (10°C) and no precipitation is falling, and an automatic or manual control that will allow shutoff when the outdoor temperature is more than 40°F (4°C) so that the potential for snow or ice accumulation is negligible. [ASHRAE 90.1:6.4.3.7] E 503.4.6.9 Ventilation Controls for High- Occupancy Areas. Demand control ventilation (DCV) shall be required for spaces that are more than 500 square feet (46.45 m 2 ) and with a design occupancy for ventilation of not less than 25 people per 1000 square feet (92.9 m 2 ) of floor area and served by systems with one or more of the following: (1) Air-economizer. (2) Automatic modulating control of outdoor air

damper. (3) Design outdoor airflow more than 3000 ft 3 /min

(1.4158 m 3 /s). Exceptions: (1) Systems with exhaust air energy recovery in

accordance with Section E 503.5.10. (2) Multiple-zone systems without DDC of indi vidual zones communicating with a central control panel.

386 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

(3) Systems with a design outdoor airflow less than

750 ft 3 /min (0.3540 m 3 /s). (4) Spaces where more than 75 percent of the space

design outdoor airflow is required for makeup air that is exhausted from the space or transfer air that is required for makeup air that is exhausted from other spaces. (5) Spaces with one of the following occupancy

categories in accordance with Chapter 4 or ASHRAE 62.1: correctional cells, daycare sickrooms, science labs, barbers, beauty and nail salons, and bowling alley seating. [ASHRAE 90.1:6.4.3.8] E 503.4.6.10 Outdoor Heating. Radiant heat systems shall be used to provide heat outdoors. Outdoor radiant heating systems shall be provided with controls that sense the presence of occupants or other device that automatically shuts down the system where no occupants are in the heating area. E 503.4.6.11 Heated or Cooled Vestibules. Heating for vestibules and for air curtains with integral heating shall include automatic controls capable of and configured to shut off the heating system when outdoor air temperatures are more than 45°F (7.2°C) Vestibule heating and cooling systems shall be controlled by a thermostat in the vestibule capable of and configured to limit heating to a maximum of 60°F (15.5°C) and cooling to a minimum of 85°F (29.4°C). Exception: Heating or cooling provided by siterecovered energy or by transfer air that would otherwise be exhausted. [ASHRAE 90.1:6.4.3.9]

zone(s) from the reset algorithm. [ASHRAE 90.1:6.4.3.10.2]

E 503.4.6.12 Direct Digital Control (DDC) Requirements. Direct digital control shall be required in accordance with Section E 503.4.6.12.1 through Section E 503.4.6.12.3. [ASHRAE 90.1:6.4.3.10] E 503.4.6.12.1 DDC Applications. DDC shall be provided in the applications and qualifications in accordance with Table E 503.4.6.12.1. Exception : DDC is not required for systems using the simplified approach to compliance in accordance with Section E 503.3. [ASHRAE 90.1:6.4.3.10.1] E 503.4.6.12.2 DDC Controls. Where DDC is required by Section E 503.4.6.12.1, the DDC system shall be capable of and configured with all of the following, as required, to provide the control logic required in Section E 503.5: (1) Monitoring zone and system demand for

fan pressure, pump pressure, heating, and cooling. (2) Transferring zone and system demand

information from zones to air distribution system controllers and from air distribution systems to heating and cooling plant controllers. (3) Automatically detecting those zones and sys tems that are capable of excessively driving the reset logic and generate an alarm or other indication to the system operator. (4) Readily allowing operator removal of

TABLE E 503.4.6.12.1 DDC APPLICATIONS AND QUALIFICATIONS

[ASHRAE 90.1:6.4.3.10.1]

BUILDING STATUS APPLICATION QUALIFICATIONS
New building Air-handling system and all zones served by
the system
Individual systems supplying more than three zones and
with fan system bhp of 10 hp or more
New building Chilled-water plant and all coils and terminal
units served by the system

Individual plants supplying more than three zones and with
design cooling capacity of 300 000 Btu/h or more
New building Hot-water plant and all coils and terminal
units served by the system
Individual plants supplying more than three zones and with
design heating capacity of 300 000 Btu/h or more
Alteration or addition Zone terminal unit such as VAV box Where existing zones served by the same air-handling,
chilled-water, or hot-water system have DDC
Alteration or addition Air-handling system or fan coil Where existing air-handling system(s) and fan-coil(s)
served by the same chilled- or hot-water plant have DDC
Alteration or addition New air-handling system and all new zones
served by the system
Individual systems with fan system bhp of 10 hp or more
and supplying more than three zones and more than 75 per-
cent of zones are new
Alteration or addition New or upgraded chilled-water plant Where all chillers are new and plant design cooling capac-
ity is 300 000 Btu/h or more
Alteration or addition New or upgraded hot-water plant Where all boilers are new and plant design heating capacity
is 300 000 Btu/h or more

For SI units: 1000 British thermal units = 0.293 kW, 1 horsepower = 0.746 kW

2022 CALIFORNIA MECHANICAL CODE 387

APPENDIX E

E 503.4.6.12.3 DDC Display. Where DDC is required in accordance with Section E 503.4.6.12.1 for new buildings, the DDC system shall be capable of trending and graphically displaying input and output points. [ASHRAE 90.1:6.4.3.10.3]

E 503.4.6.13 Economizer Fault Detection Diagnostics (FDD). Air-cooled direct-expansion cooling units listed in Tables E 503.7.1(1) and E 503.7.1(2), where an air economizer is installed in accordance with Section E 503.5, shall include a fault detection and diagnostics (FDD) system complying with the following: (1) The following temperature sensors shall be per manently installed to monitor system operation: (a) Outdoor air (b) Supply air (c) Return air, where required for economizer

control (2) The system shall have the capability of dis playing the value of each sensor. (3) The FDD system or unit controls shall be capa ble of and configured to provide system status by indicating the following: (a) Free cooling available (b) Economizer enabled (c) Compressor enabled (d) Heating enabled (e) Mixed-air low-limit cycle active (4) The FDD system or unit controls shall have pro visions to manually initiate each operating mode so that the operation of compressors, economizers, fans, and the heating system can be independently tested and verified. (5) The FDD system shall be capable of and con figured to detect the following faults: (a) Air temperature sensor failure/fault (b) Not economizing when the unit should be

active (4) The FDD system or unit controls shall have pro visions to manually initiate each operating mode so that the operation of compressors, economizers, fans, and the heating system can be independently tested and verified. (5) The FDD system shall be capable of and con figured to detect the following faults: (a) Air temperature sensor failure/fault (b) Not economizing when the unit should be

economizing (c) Economizing when the unit should not be

economizing (d) Damper not modulating (e) Excess outdoor air (6) The FDD system shall be capable of and config ured to report faults to a fault management application or DDC system accessible by operating or service personnel, or annunciated locally on zone thermostats. [ASHRAE 90.1:6.4.3.12] E 503.4.7 HVAC System Construction and Insu- lation. HVAC Ducts shall be constructed in accordance with provisions contained in the SMACNA HVAC Duct Construction Standard. HVAC system construction and insulation shall comply with Section E 503.4.7.1 and Section E 503.4.7.2.

E 503.4.7.1 Insulation. Insulation required by this section shall be installed in accordance with industry-accepted standards. These requirements shall not apply to HVAC equipment. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind, but not limited to the following: (1) Insulation exposed to weather shall be suitable

for outdoor service (e.g., protected by aluminum, sheet metal, painted canvas, or plastic cover). Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that is capable of causing degradation of the material. (2) Insulation covering chilled-water piping, refrig erant suction piping, or cooling ducts located outside the conditioned space shall include a vapor retardant located outside the insulation (unless the insulation is inherently vapor retardant), penetrations and joints of which shall be sealed. [ASHRAE 90.1:6.4.4.1.1] E 503.4.7.1.1 Duct and Plenum Insula- tion. Supply and return ducts and plenums installed as part of an HVAC air distribution system shall be thermally insulated in accordance with Table E 503.7.2. Exceptions: (1) Factory-installed plenums, casings, or

ductwork furnished as a part of HVAC equipment tested and rated in accordance with Section E 503.4 through Section E 503.4.4.1. (2) Ducts or plenums located in heated spaces,

semi-heated spaces, or cooled spaces. (3) For runouts less than 10 feet (3048 mm) in

length to air terminals or air outlets, the rated R-value of insulation shall not be required to exceed R-3.5. (4) Backs of air outlets and outlet plenums

exposed to unconditioned or indirectly conditioned spaces with face areas exceeding 5 square feet (0.5 m 2 ) shall not be required to exceed R-2; those not exceeding 5 square feet (0.5 m 2 ) shall not be required to be insulated. [ASHRAE 90.1:6.4.4.1.2] E 503.4.7.1.2 Piping Insulation. Piping shall be thermally insulated in accordance with Table E 503.7.3(1) and Table E 503.7.3(2). Exceptions: (1) Factory-installed piping within HVAC

areas exceeding 5 square feet (0.5 m 2 ) shall not be required to exceed R-2; those not exceeding 5 square feet (0.5 m 2 ) shall not be required to be insulated. [ASHRAE 90.1:6.4.4.1.2] E 503.4.7.1.2 Piping Insulation. Piping shall be thermally insulated in accordance with Table E 503.7.3(1) and Table E 503.7.3(2). Exceptions: (1) Factory-installed piping within HVAC

equipment tested and rated in accordance with Section E 503.4 through Section E 503.4.4.1. (2) Piping that conveys fluids having a design

operating temperature range between 60°F (16°C) and 105°F (41°C), inclusive.

388 2022 CALIFORNIA MECHANICAL CODE

(3) Piping that conveys fluids that have not

been heated or cooled through the use of fossil fuels or electricity (such as roof and condensate drains, domestic cold water supply, and natural gas piping). (4) Where heat gain or heat loss will not

increase energy use (such as liquid refrigerant piping). (5) In piping 1 inch (25.4 mm) or less, insula tion is not required for strainers, control valves, and balancing valves. [ASHRAE 90.1:6.4.4.1.3]

E 503.4.7.1.3 Sensible Heating Panel. Thermally ineffective panel surfaces of sensible heating panels, including U-bends and headers, shall be insulated a minimum of R-3.5. Adjacent building envelope insulation counts toward this requirement. [ASHRAE 90.1:6.4.4.1.4] E 503.4.7.1.4 Radiant Floor Heating. The bottom surfaces of floor structures incorporating radiant heating shall be insulated with a minimum of R-3.5. Adjacent building envelope insulation counts toward this requirement. Exception: Heated slab-on-grade floors incorporating radiant heating shall be in accordance with ASHRAE 90.1. [ASHRAE 90.1:6.4.4.1.5]

E 503.4.7.2 Ductwork and Plenum Leakage. Transverse joints, longitudinal seams, and duct wall penetrations shall be sealed. Pressure-sensitive tape shall not be used as the primary sealant, unless it has been certified to comply with UL 181A or UL 181B by an independent testing laboratory and the tape is used in accordance with that certification. All other connections shall be considered transverse joints, including but not limited to spin-ins, taps, other branch connections, access door frames and jambs, and duct connections to equipment. Exceptions: (1) Rods that penetrate the duct wall that shall be

permitted to move in order to function properly (control rod for volume damper) shall not be sealed in a fashion that prevents them from working properly. (2) Spiral lock seams in a round or flat oval duct.

E 503.4.7.2.1 Duct Leakage Tests. Ductwork shall be leak-tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual. Representative sections totaling not less than 20 percent of the total installed duct area shall be tested. Where the tested 20 percent fail to comply with the requirements of this section, then 40 percent of the total installed duct area shall be tested. Where the tested 40 percent fail to comply with the requirements of this section,

APPENDIX E

then 100 percent of the total installed duct area shall be tested. Sections shall be selected by the building owner or designated representative of the building owner. Positive pressure leakage testing shall be permitted for negative pressure ductwork. The permitted duct leakage shall be not more than the following:

Lmax = CLP 0.65 (Equation E 503.4.7.2.1)

Where: Lmax = maximum permitted leakage, (ft 3 /min)/100 square feet [0.0001 (m 3 /s)/m 2 ] duct surface area. CL = Six, duct leakage class, (ft 3 /min)/100 square feet [0.0001 (m 3 /s)/m 2 ] duct surface area at 1 inch water column (0.2 kPa). P = test pressure, which shall be equal to the design duct pressure class rating, inch water column (kPa). E 503.5 Prescriptive Path, Economizers. Cooling systems shall include either an air economizer or fluid economizer in accordance with Section E 503.5.1 through Section E 503.5.4.1. Exceptions: Economizers shall not be required for the following systems: (1) Individual fan-cooling units with a supply capacity less

than the minimum listed in Table E 503.5(1). (2) Chilled-water cooling systems without a fan or that use

induced airflow, where the total capacity of these systems is less than 1 000 000 Btu/h (293 kW) in Climate Zones 0, 1B, and 2 through 4; less than 1 400 000 Btu/h (410 kW) in Climate Zones 5 through 8; or any size in Climate Zone 1A. (3) Systems that include nonparticulate air treatment in

accordance with ASHRAE 62.1. (4) In hospitals and ambulatory surgery centers, where more

than 75 percent of the air designed to be supplied by the system is to spaces that are required to be humidified more than 35°F (2°C) dew-point temperature to comply with applicable codes or accreditation standards; in all other buildings, where more than 25 percent of the air designed to be supplied by the system is to spaces that are designed to be humidified more than 35°F (2°C) dewpoint temperature to satisfy process needs. This exception shall not apply to computer rooms. (5) Systems that include a condenser heat recovery system

with a minimum capacity in accordance with Section E 503.5.10.1.2. (6) Systems that serve residential spaces where the system

capacity is less than five times the requirement listed in Table E 503.5(1).

2022 CALIFORNIA MECHANICAL CODE 389

APPENDIX E

(7) Systems that serve spaces whose sensible cooling load

at design conditions, excluding transmission and infiltration loads, is less than or equal to transmission and infiltration losses at an outdoor temperature of 60°F (16°C). (8) Systems expected to operate less than 20 hours per week. (9) Where the use of outdoor air for cooling will affect

supermarket open refrigerated casework systems. (10)For comfort cooling where the cooling efficiency is not

less than the efficiency improvement requirements in accordance with Table E 503.5(2). (11)Systems primarily serving computer rooms where in

accordance with one of the following: (a) The total design cooling load of all computer rooms

in the building is less than 3 000 000 Btu/h (879 kW) and the building in which they are located is not served by a centralized chilled water plant. (b) The room total design cooling load is less than 600

000 Btu/h (176 kW) and the building in which they are located is served by a centralized chilled water plant. (c) The local water authority does not permit cooling

towers. (d) Less than 600 000 Btu/h (176 kW) of computer

room cooling equipment capacity is being added to an existing building. (12)Dedicated systems for computer rooms where a mini mum of 75 percent of the design load serves one of the following: (a) Spaces classified as an essential facility. (b) Spaces having a design of Tier IV in accordance

with TIA 942. (c) Spaces classified as Critical Operations Power Sys tems (COPS) in accordance with NFPA 70. (d) Spaces where core clearing and settlement services

are performed such that their failure to settle pending financial transactions is capable of systemic risk in accordance with “The Interagency Paper on Sound Practices to Strengthen the Resilience of the US Financial System” (April 7, 2003). [ASHRAE 90.1:6.5.1]

TABLE E 503.5(1) MINIMUM FAN-COOLING UNIT SIZE WHERE AN ECONOMIZER IS REQUIRED

[ASHRAE 90.1: TABLE 6.5.1-1]

TABLE E 503.5(2) ELIMINATE REQUIRED ECONOMIZER FOR COMFORT

COOLING BY INCREASING COOLING EFFICIENCY

[ASHRAE 90.1: TABLE 6.5.1-2]

CLIMATE ZONES EFFICIENCY IMPROVEMENT*

2A
17%


2B
21%


3A
27%


3B
32%


3C
65%


4A
42%

4B
49%

4C
64%

5A
49%


5B
59%


5C
74%


6A
56%


6B
65%


7
72%

8
77%
  • Where a unit is rated with an IPLV, IEER or SEER, to eliminate the required economizer, the minimum cooling efficiency of the HVAC unit shall be increased by the percentage shown. Where the HVAC unit is rated with a full load metric like EER cooling, these shall be increased by the percentage shown.

E 503.5.1 Air Economizers, Design Capacity. Air economizer systems shall be capable of and configured to modulate outdoor air and return air dampers to provide up to 100 percent of the design supply air quantity as outdoor air for cooling. [ASHRAE 90.1:6.5.1.1.1]

E 503.5.1.1 Control Signal. Economizer controls shall be capable of and configured to sequence the dampers with the mechanical cooling equipment and shall not be controlled by only mixed air temperature. Exception: The use of mixed air temperature limit control shall be permitted for systems controlled from space temperature (such as single-zone systems). [ASHRAE 90.1:6.5.1.1.2] E 503.5.1.2 High-Limit Shutoff. Air economizers shall be capable of and configured to automatically reduce outdoor air intake to the design minimum outdoor air quantity where outdoor air intake will no longer reduce cooling energy use. High-limit shutoff control types and associated setpoints for specific climate zones shall be chosen from Table E 503.5.1.2. [ASHRAE 90.1:6.5.1.1.3] E 503.5.1.3 Dampers. Return, exhaust or relief, and outdoor air dampers shall comply with Section E 503.4.6.4.2. [ASHRAE 90.1:6.5.1.1.4] E 503.5.1.4 Relief of Excess Outdoor Air. Systems shall provide a means to relieve excess outdoor air during air economizer operation to prevent overpressurizing the building. The relief air outlet shall be located so as to avoid recirculation into the building. [ASHRAE 90.1:6.5.1.1.5]

«
CLIMATE ZONES COOLING CAPACITY WHERE AN
ECONOMIZER IS REQUIRED

0A, 0B, 1A, 1B
No economizer requirement



2A, 2B, 3A, 4A, 5A, 6A, 3B,
3C, 4B, 4C, 5B, 5C, 6B, 7, 8

≥54 000 Btu/h

390 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

TABLE E 503.5.1.2 HIGH-LIMIT SHUTOFF CONTROL SETTINGS FOR AIR ECONOMIZERS 2

[ASHRAE 90.1: TABLE 6.5.1.1.3]

CONTROL TYPE ALLOWED ONLY IN CLIMATE ZONE AT
LISTED SETPOINT
REQUIRED HIGH LIMIT (ECONOMIZER OFF WHERE):
CONTROL TYPE ALLOWED ONLY IN CLIMATE ZONE AT
LISTED SETPOINT
EQUATION DESCRIPTION
Fixed dry bulb temperature 0B, 1B, 2B, 3B, 3C,
4B, 4C, 5B, 5C, 6B, 7, 8
Toa> 75°F Outdoor air temperature exceeds 75°F
Fixed dry bulb temperature 5A, 6A Toa> 70°F Outdoor air temperature exceeds 70°F
Fixed dry bulb temperature 0A, 1A, 2A, 3A, 4A
Toa> 65°F
Outdoor air temperature exceeds 65°F
Differential dry bulb tem-
perature
0B, 1B, 2B, 3B, 3C, 4B, 4C,
5A, 5B, 5C, 6A, 6B, 7, 8

Toa> Tra
Outdoor air temperature exceeds return air
temperature
Fixed enthalpy with fixed
dry-bulb temperature
All hoa> 28 Btu/lb1
or_Toa_> 75°F
Outdoor air enthalpy exceeds 28 Btu/lb1 of dry
air1 or outdoor air temperature exceeds 75°F
Differential enthalpy with
fixed dry-bulb temperature
All
hoa> _hra_or
Toa> 75°F
Outdoor air enthalpy exceeds return air enthalpy
or outdoor air temperature exceeds 75°F

For SI units: °C = (°F-32)/1.8, 1 British thermal unit per pound = 2326 J/kg Notes: 1 At altitudes substantially different than sea level, the fixed enthalpy limit shall be set to the enthalpy value at 75°F (24°C) and 50 percent relative humidity. As an example, at approximately 6000 feet (1829 m) elevation, the fixed enthalpy limit shall be approximately 30.7 Btu/lb (71 408 J/kg). 2 Devices with selectable rather than adjustable setpoints shall be capable of being set to within 2°F (1°C) and 2 Btu/lb (4649 J/kg) of the setpoint listed.

TABLE E 503.5.2 WATER ECONOMIZER SIZING DRY-BULB AND WET-BULB REQUIREMENTS FOR COMPUTER ROOMS*

[ASHRAE 90.1: TABLE 6.5.1.2.1]

CLIMATE ZONE WATER COOLED AIR COOLED
CLIMATE ZONE CLIMATE ZONE DRY BULB, °F WET BULB, °F DRY BULB, °F
0 A NR NR NR
0 B NR NR NR
1 A NR NR NR
1 B NR NR NR
2 A 40.0 35.0 30.0
2 B 35.0 30.0 30.0
3 A 40.0 35.0 25.0
3 B 30.0 25.0 25.0
3 C 30.0 25.0 30.0
4 A 40.0 35.0 25.0
4 B 30.0 25.0 25.0
4 C 30.0 25.0 25.0
5 A 40.0 35.0 20.0
5 B 30.0 25.0 20.0
5 C 30.0 25.0 25.0
6 A 35.0 30.0 20.0
6 B 30.0 25.0 20.0
7 –– 30.0 25.0 20.0
8 –– 30.0 25.0 20.0

For SI units: °C = (°F-32)/1.8

  • NR = Not Required

E 503.5.1.5 Sensor Accuracy. Outdoor air, return air, mixed air, and supply air sensors shall be calibrated within the following accuracies: (1) Dry-bulb and wet-bulb temperatures shall be

accurate to ±2°F (1.1°C) over the range of 40°F (4.4°C) to 80°F (27°C). (2) Enthalpy and the value of a differential enthalpy

sensor shall be accurate to ±3 Btu/lb (7 E+03

J/kg) over the range of 20 Btu/lb (4.6 E+04 J/kg) to 36 Btu/lb (8.4 E+04 J/kg). (3) Relative humidity shall be accurate to ±5 per cent over the range of 20 percent to 80 percent relative humidity. [ASHRAE 90.1:6.5.1.1.6]

E 503.5.2 Fluid Economizers, Design Capacity. Fluid economizer systems shall be capable of providing up to 100 percent of the expected system cooling load at

2022 CALIFORNIA MECHANICAL CODE 391

APPENDIX E

outdoor air temperatures of not more than 50°F (10°C) dry bulb or 45°F (7°C) wet bulb. Exceptions: (1) Systems primarily serving computer rooms in which

100 percent of the expected system cooling load at the dry bulb and wet bulb temperatures in accordance with Table E 503.5.2 is met with water-cooled fluid economizers. (2) Systems primarily serving computer rooms in which

100 percent of the expected system cooling load at the dry bulb temperatures listed in Table E 503.5.2 is met with air-cooled fluid economizers. (3) Systems where dehumidification requirements are

not capable of being met using outdoor air temperatures of 50°F (10°C) dry bulb or 45°F (7°C) wet bulb and where 100 percent of the expected system cooling load at 45°F (7°C) dry bulb or 40°F (4°C) wet bulb is met with water-cooled fluid economizers. [ASHRAE 90.1:6.5.1.2.1]

E 503.5.2.1 Maximum Hydronic Pressure Drop. Precooling coils and fluid-to-water heat exchangers used as part of a fluid economizer system shall either have a water-side pressure drop of less than 15 feet of water (45 kPa), or a secondary loop shall be created so that the coil or heat exchanger pressure drop is not seen by the circulating pumps where the system is in the normal cooling (non-economizer) mode. [ASHRAE 90.1:6.5.1.2.2] E 503.5.3 Integrated Economizer Control. Economizer systems shall be integrated with the mechanical cooling system and be capable of and configured to provide partial cooling even where additional mechanical cooling is required to be in accordance with the remainder of the cooling load. Controls shall not false load the mechanical cooling systems by limiting or disabling the economizer or by other means, such as hot gas bypass, except at the lowest stage of mechanical cooling.

Units that include an air economizer shall comply with the following: (1) Unit controls shall have the mechanical cooling

capacity control interlocked with the air economizer controls such that the outdoor air damper is at the 100 percent open position when mechanical cooling is on, and the outdoor air damper does not begin to close to prevent coil freezing due to minimum compressor run time until the leaving air temperature is less than 45°F (7°C). (2) DX units with a rated capacity no less than 65 000

Btu/h (19 kW) that control the capacity of the mechanical cooling directly based on occupied space temperature shall have not less than two stages of mechanical cooling capacity. (3) Other DX units, including those that control space

temperature by modulating the airflow to the space, shall comply with the requirements of Table E 503.5.3. [ASHRAE 90.1:6.5.1.3]

TABLE E 503.5.3 DX COOLING STAGE REQUIREMENTS FOR

MODULATING AIRFLOW UNITS

[ASHRAE 90.1:6.5.1.3]

RATING CAPACITY,
Btu/h
MINIMUM NUMBER
OF MECHANICAL
COOLING STAGES
MINIMUM
COMPRESSOR
DISPLACEMENT*



≥65 000 and <240 000
3 ≤35% of full load

≥240 000
4
≤25% full load

For SI units: 1000 British thermal units = 0.293 kW

  • For mechanical cooling stage control that does not use variable compressor displacement the percent displacement shall be equivalent to the mechanical cooling capacity reduction evaluated at the full load rating conditions for the compressor.

E 503.5.4 Economizer Heating System Impact. HVAC system design and economizer controls shall be such that economizer operation does not increase the building heating energy use during normal operation. Exception: Economizers on variable air valve (VAV) systems that cause zone level heating to increase due to a reduction in supply air temperature. [ASHRAE 90.1:6.5.1.4] E 503.5.4.1 Economizer Humidification Sys- tem Impact. Systems with hydronic cooling and humidification systems designed to maintain inside humidity at a dew-point temperature more than 35°F (2°C) shall use a fluid economizer where an economizer is required in accordance with Section E 503.5 through Section E 503.5.4.1. [ASHRAE 90.1:6.5.1.5] E 503.5.5 Simultaneous Heating and Cooling Limitation, Zone Controls. Zone thermostatic controls shall prevent the following: (1) Reheating. (2) Recooling. (3) Mixing or simultaneously supplying air that has

been previously mechanically heated and air that has been previously cooled, either by mechanical cooling or by economizer systems. (4) Other simultaneous operation of heating and cool ing systems to the same zone. Exceptions: (1) Zones for which the volume of air that is reheated,

recooled, or mixed is less than the larger of the following: (a) Twenty percent of the zone design peak

supply for systems with DDC and 30 percent for other systems. (b) The outdoor airflow rate required to be in

accordance with the ventilation requirements of Chapter 4 or ASHRAE 62.1 for the zone. (c) Any higher rate that can be demonstrated, to

the satisfaction of the Authority Having Jurisdiction, to reduce overall system annual

392 2022 CALIFORNIA MECHANICAL CODE

energy use by offsetting reheat/recool energy losses through a reduction in outdoor air intake for the system. (d) The airflow rate required to be in accor dance with applicable codes or accreditation standards, such as pressure relationships or minimum air change rates. (2) Zones with DDC that comply with the following:

(a) The airflow rate in dead band between

heating and cooling does not exceed the larger of the following: (1) Twenty percent of the zone design

peak supply rate. (2) The outdoor airflow rate required to be

in accordance with the ventilation requirements of Chapter 4 or ASHRAE 62.1 for the zone. (3) A higher rate that can be demonstrated,

to the satisfaction of the Authority Having Jurisdiction, to reduce overall system annual energy use by offsetting reheat/recool energy losses through a reduction in outdoor air intake. (4) The airflow rate required with applica ble codes or accreditation standards, such as pressure relationships or minimum air change rates. (b) The airflow rate that is reheated, recooled,

or mixed shall be less than 50 percent of the zone design peak supply rate. (c) The first stage of heating consists of modu lating the zone supply air temperature setpoint up to a maximum setpoint while the airflow is maintained at the dead band flow rate. (d) The second stage of heating consists of

modulating the airflow rate from the dead band flow rate up to the heating maximum flow rate. (3) Laboratory exhaust systems that comply with

Section E 503.5.11.3. (4) Zones where at least 75 percent of the energy for

reheating or for providing warm air in mixing systems is provided from site-recovered energy (including condenser heat) or site-solar energy.

[ASHRAE 90.1:6.5.2.1]

E 503.5.5.1 Supply Air Temperature Reheat Limit. Where reheating is permitted in accordance with this appendix, zones that have both supply and return or exhaust air openings more than 6 feet (1829 mm) above the floor shall not supply heating air more than 20°F (11°C) above the space temperature setpoint.

APPENDIX E

Exceptions: (1) Laboratory exhaust systems in accordance with

Section E 503.5.11.3. (2) During preoccupancy building warm-up and

setback. [ASHRAE 90.1:6.5.2.1.1] E 503.5.5.2 Hydronic System Controls. The heating of fluids in hydronic systems that have been previously mechanically cooled and the cooling of fluids that have been previously mechanically heated shall be limited in accordance with Section E 503.5.5.2.1 through Section E 503.5.5.2.3.

[ASHRAE 90.1:6.5.2.2]

E 503.5.5.2.1 Three-Pipe System. Hydronic systems that use a common return system for both hot water and chilled water shall not be used. [ASHRAE 90.1:6.5.2.2.1] E 503.5.5.2.2 Two-Pipe Changeover Sys- tem. Systems that use a common distribution system to supply both heated and chilled water are acceptable where in accordance with the following: (1) The system is designed to allow a dead

band between changeover from one mode to the other of not less than 15°F (8°C) outdoor air temperature. (2) The system is designed to operate and is

provided with controls that will allow operation in one mode for not less than 4 hours before changing over to the other mode. (3) Reset controls are provided that allow heat ing and cooling supply temperatures at the changeover point to be not more than 30°F (17°C) apart. [ASHRAE 90.1:6.5.2.2.2] E 503.5.5.2.3 Hydronic (Water Loop) Heat Pump Systems. Hydronic heat pumps connected to a common heat pump water loop with central devices for heat rejection (e.g., cooling tower) and heat addition (e.g., boiler) shall have the following: (1) Controls that are capable of and configured

to provide a heat pump water supply temperature dead band of at least 20°F (11°C) between initiation of heat rejection and heat addition by the central devices (e.g., tower and boiler). (2) For climate zone 3 through zone 8, where a

closed-circuit cooling tower (fluid cooler) is used, either an automatic valve shall be installed to bypass all but a minimal flow of water around the tower (for freeze protection) or low-leakage positive closure dampers shall be provided. Where an opencircuit cooling tower is used directly in the heat pump loop, an automatic valve shall be installed to bypass all heat pump water flow around the tower. Where an open-circuit cooling tower is used in conjunction with a

2022 CALIFORNIA MECHANICAL CODE 393

APPENDIX E

separate heat exchanger to isolate the tower from the heat pump loop then heat loss shall be controlled by shutting down the circulation pump on the cooling tower loop. Exception: Where a system loop temperature optimization controller is used to determine the most efficient operating temperature based on real-time conditions of demand and capacity, dead bands of less than 20°F (11°C) shall be permitted.

[ASHRAE 90.1:6.5.2.2.3] E 503.5.5.3 Dehumidification. Where humidity controls are provided, such controls shall prevent reheating, mixing of hot and cold airstreams, or other means of simultaneous heating and cooling of the same airstream. Exceptions: (1) The system is capable of and configured to

reduce supply air volume to 50 percent or less of the design airflow rate or the minimum outdoor air ventilation rate in accordance with Chapter 4 or ASHRAE 62.1 or other applicable federal, state, or local code or recognized standard, whichever is larger before simultaneous heating and cooling takes place. (2) The individual fan cooling unit has a design

cooling capacity of not more than 65 000 Btu/h (19 kW) and is capable of and configured to unload to 50 percent capacity before simultaneous heating and cooling takes place. (3) The individual mechanical cooling unit has a

design cooling capacity of not more than 40 000 Btu/h (11.7 kW). An individual mechanical cooling unit is a single system composed of a fan or fans and a cooling coil capable of providing mechanical cooling. (4) Systems serving spaces where specific humid ity levels are required to satisfy process needs, such as vivariums, museums, surgical suites, pharmacies, and buildings with refrigerating systems, such as supermarkets, refrigerated

warehouses, and ice arenas, and where the building includes site-recovered energy or site solar energy that provide energy equal to 75 percent or more of the annual energy for reheating or for providing warm air in mixing systems. This exception shall not apply to computer rooms. (5) Not less than 90 percent of the annual energy

for reheating or for providing warm air in mixing systems is provided from site-recovered energy (including condenser heat) or site-solar energy. (6) Systems where the heat added to the airstream

is the result of the use of a desiccant system and 75 percent of the heat added by the desiccant system is removed by a heat exchanger, either before or after the desiccant system with energy recovery. [ASHRAE 90.1:6.5.2.3] E 503.5.5.4 Humidifier Preheat. Humidifiers with preheating jackets mounted in the airstream shall be provided with an automatic valve to shut off preheat where humidification is not required.

[ASHRAE 90.1:6.5.2.4.1]

E 503.5.5.4.1 Insulation. Humidification system dispersion tube hot surfaces in the airstreams of ducts or air-handling units shall be insulated with a product with an insulating value of not less than R-0.5. Exception: Systems where mechanical cooling, including economizer operation, does not occur simultaneously with humidification. [ASHRAE 90.1:6.5.2.4.2] E 503.5.5.5 Preheat Coils. Preheat coils shall have controls that stop their heat output where mechanical cooling, including economizer operation, is occurring. [ASHRAE 90.1:6.5.2.5] E 503.5.6 Air System Design and Control. HVAC air system design and control shall be in accordance with the provisions of Section E 503.5.6.1 through Section E 503.5.6.6. E 503.5.6.1 Fan System Power and Efficiency. Each HVAC system having a total fan system motor

TABLE E 503.5.6.1(1) FAN POWER LIMITATION*

[ASHRAE 90.1: TABLE 6.5.3.1-1]

LIMIT CONSTANT VOLUME VARIABLE VOLUME
Option 1: Fan system motor nameplate (hp) Allowable nameplate motor (hp) hp≤_CFMS _• 0.0011 hpCFMS• 0.0015
Option 2: Fan system (bhp) Allowable fan system (bhp)
bhpCFMS• 0.00094 +A

bhpCFMS• 0.0013 +A

For SI units: 1 horsepower = 0.746 kW, 1 cubic foot per minute = 0.00047 m 3 /s

  • Where: CFMS = the maximum design supply airflow rate to conditioned spaces served by the system in cubic feet per minute (m 3 /s) hp = the maximum combined motor nameplate horsepower (kW) bhp = the maximum combined fan brake horsepower (kW) A = sum of ( PD x CFMD /4131) PD = each applicable pressure drop adjustment from Table E 503.5.6.1(2) in inch water column (kPa) CFMD = the design airflow through each applicable device from Table E 503.5.6.1(2) in cubic feet per minute (m 3 /s)

394 2022 CALIFORNIA MECHANICAL CODE

nameplate horsepower (kW) exceeding 5 hp (3.7 kW) at fan system design conditions shall not exceed the allowable fan system motor nameplate horsepower (kW) (Option 1) or fan system brake horsepower (kW) (Option 2) as shown in Table E 503.5.6.1(1). This shall include supply fans, return or relief fans, exhaust fans, and fan-powered terminal units associated with systems providing heating or cooling capability that operate at fan system design conditions. Single-zone VAV systems shall comply with the constant-volume fan power limitation. Exceptions: (1) Hospital, vivarium, and laboratory systems that

utilize flow control devices on exhaust, return, or both to maintain space pressure relationships necessary for occupant health and safety, or environmental control shall be permitted to use variable-volume fan power limitation. (2) Individual exhaust fans with motor nameplate

horsepower of 1 hp (0.7 kW) or less. [ASHRAE 90.1:6.5.3.1.1] E 503.5.6.1.1 Motor Nameplate Horse- power. For each fan, the selected fan motor shall be no larger than the first available motor size greater than the bhp. The fan bhp shall be indicated on the design documents to allow for compliance verification by the Authority Having Jurisdiction.

APPENDIX E

Exceptions: (1) For fans less than 6 bhp (4.5 kW), where the

first available motor larger than the bhp (kW) has a nameplate rating within 50 percent of the bhp (kW), the next larger nameplate motor size shall be permitted to be selected. (2) For fans 6 bhp (4.5 kW) and larger, where

the first available motor larger than the bhp (kW) has a nameplate rating within 30 percent of the bhp (kW), the next larger nameplate motor size shall be permitted to be selected. (3) Systems that are in accordance with Sec tion E 503.5.6.1, Option 1. (4) Fans with motor nameplate horsepower

of less than 1 hp (0.7 kW). [ASHRAE 90.1:6.5.3.1.2] E 503.5.6.1.2 Fan Efficiency. Fans shall have a fan efficiency grade (FEG) of 67 or more, based on manufacturers’ certified data in accordance with AMCA 205. The total efficiency of the fan at the design point of operation shall be within 15 percentage points of the maximum total efficiency of the fan. Exceptions: (1) Individual fans with a motor nameplate

horsepower of 5 hp (3.7 kW) or less that are

TABLE E 503.5.6.1(2) FAN POWER LIMITATION PRESSURE DROP ADJUSTMENT

[ASHRAE 90.1: TABLE 6.5.3.1-2]

DEVICE ADJUSTMENT
CREDITS CREDITS
Return or exhaust systems required by code or accreditation stan-
dards to be fully ducted, or systems required to maintain air pressure
differentials between adjacent rooms
0.5in. w.c. (2.15in w.c. forlaboratoryand vivarium systems)
Return,exhaust, or both airflowcontrol devices 0.5in. w.c.
Exhaust filters, scrubbers, or other exhaust treatment The pressure drop of device calculated at fan system designcondition
Particulate Filtration Credit: MERV 9through 12 0.5in. w.c.
Particulate Filtration Credit: MERV 13through 15 0.9in. w.c.
Particulate Filtration Credit: MERV 16and greater,andelectroni-
cally enhanced filters
Pressure dropcalculated at 2xclean filter pressure dropat fan
system designcondition
Carbonand other gas-phase air cleaners Clean filter pressure dropat fan system designcondition
Biosafety cabinet Pressure drop of device at fan system designcondition
Energy recovery device, other than coil runaroundloop For each airstream [(2.2 x enthalpy recovery ratio) - 0.5] in w.c.
Coil runaroundloop 0.6in. w.c. foreach airstream
Evaporative humidifier orcooler in series with another coolingcoil Pressure drop of device at fan system designcondition
Soundattenuation section (fans serving spaces with design back-
ground noise goals below NC35)
0.15in. w.c.
Exhaust system serving fume hoods 0.35in. w.c.
Laboratoryand vivarium exhaust systems in high-rise buildings 0.25in. w.c. per 100 feet of vertical duct exceeding 75 ft
DEDUCTIONS DEDUCTIONS
Systems without central cooling device –0.6in. w.c.
Systems without central heating device –0.3in. w.c.
Systems with central electric resistance heat –0.2in. w.c.

For SI units: 1 inch water column = 0.249 kPa, 1 foot = 304.8 mm

2022 CALIFORNIA MECHANICAL CODE 395

APPENDIX E

not part of a group operated as the functional equivalent of a single fan. (2) Multiple fans in series or parallel (e.g., fan

arrays) that have a combined motor nameplate horsepower of 5 hp (3.7 kW) or less and are operated as the functional equivalent of a single fan. (3) Fans that are part of equipment listed under

Section E 503.4. (4) Fans included in equipment bearing a third

party-certified seal for air or energy performance of the equipment package. (5) Powered wall/roof ventilators (PRV). (6) Fans outside the scope of AMCA 205. (7) Fans that are intended to only operate dur ing emergency conditions. [ASHRAE 90.1:6.5.3.1.3] E 503.5.6.2 Supply Fan Airflow Control. Each cooling system listed in Table E 503.5.6.2 shall be designed to vary the supply fan airflow as a function of load and shall comply with the following requirements: (1) DX and chilled-water cooling units that control

the capacity of the mechanical cooling directly based on space temperature shall have a minimum of two stages of fan control. Low or minimum speed shall not exceed 66 percent of full speed. At low or minimum speed, the fan system shall draw no more than 40 percent of the fan power at full fan speed. Low or minimum speed shall be used during periods of low cooling load and ventilation-only operation. (2) All other units, including DX cooling units and

chilled-water units that control the space temperature by modulating the airflow to the space, shall have modulating fan control. Minimum speed shall not exceed 50 percent of full speed. At minimum speed, the fan system shall draw no more than 30 percent of the power at full fan speed. Low or minimum speed shall be used during periods of low cooling load and ventilation-only operation. (3) Units that include an air economizer to meet the

requirements of Section E 503.5 through Section E 503.5.4.1 shall have a minimum of two speeds of fan control during economizer operation. Exceptions: (1) Modulating fan control shall not be required for

chilled-water and evaporative cooling units with less than1 hp (0.7 kW) fan motors where the units are not used to provide ventilation air and where the indoor fan cycles with the load. (2) Where the volume of outdoor air required to

meet the ventilation requirements of Chapter 4 or ASHRAE 62.1 at low speed exceeds the air that would be delivered at the speed defined in

COOLING SYSTEM TYPE FAN MOTOR SIZE,
(hp)
MECHANICAL
COOLING CAPACITY,
(Btu/h)


DX cooling
Any ≥65 000


Chilled-water and evapo-
rative cooling
≥1⁄4
Any

= 0.746 kW, 1 cubic foot per minute = 0.00047 m 3 /s

E 503.5.6.2.1 VAV Static Pressure Sensor Location. Static pressure sensors used to control VAV fans shall be located such that the controller setpoint is not more than 1.2 inches water column (0.30 kPa). Where this results in the sensor being located downstream of major duct splits, sensors shall be installed in each major branch to ensure that static pressure is maintained in each. Exception: Systems that are in accordance with Section E 503.5.6.2.2. [ASHRAE 90.1:6.5.3.2.2] E 503.5.6.2.2 VAV Setpoint Reset. For multiple-zone VAV systems having a total fan system motor nameplate horsepower exceeding 5 hp (3.7 kW) with DDC of individual zones reporting to the central control panel, static pressure setpoint shall be reset based on the zone requiring the most pressure, such as the setpoint is reset lower until one zone damper is nearly wide open. Controls shall provide the following: (1) Monitor zone damper positions or other

indicator of need for static pressure. (2) Automatically detect those zones that are

capable of excessively driving the reset logic and generate an alarm to the system operator. (3) Readily allow operator removal of zones

from the reset algorithm. [ASHRAE 90.1:6.5.3.2.3] E 503.5.6.3 Multiple-Zone VAV System Venti- lation Optimization Control. Multiple-zone VAV systems with DDC of individual zone boxes reporting to a central control panel shall include means to automatically reduce outdoor air intake flow below design rates in response to changes in system ventilation efficiency in accordance with Section 404.0. Exceptions: (1) VAV systems with zonal transfer fans that

recirculate air from other zones without directly

Section E 503.5.6.2(1), or Section E 503.5.6.2(2), then the minimum speed shall be selected to provide the required ventilation air.

[ASHRAE 90.1:6.5.3.2.1]

TABLE E 503.5.6.2 FAN AIRFLOW CONTROL

[ASHRAE 90.1: TABLE 6.5.3.2.1]

396 2022 CALIFORNIA MECHANICAL CODE

mixing it with outdoor air, dual-duct dual-fan VAV systems, and VAV systems with fanpowered terminal units. (2) Systems where total design exhaust airflow is

more than 70 percent of total design outdoor air intake flow requirements. [ASHRAE 90.1:6.5.3.3] E 503.5.6.4 Supply Air Temperature Reset Controls. Multiple zone HVAC systems shall include controls that automatically reset the supply air temperature in response to representative building loads, or to outdoor air temperature. The controls shall reset the supply air temperature to at least 25 percent of the difference between the design supply air temperature and the design room air temperature. Controls that adjust the reset based on zone humidity shall be permitted. Zones that are expected

APPENDIX E

to experience relatively constant loads, such as electronic equipment rooms, shall be designed for the fully reset supply temperature. Exceptions: (1) Climate zones 0A, 1A, 2A, and 3A. (2) Systems that prevent reheating, recooling, or

mixing of heated and cooled supply air. (3) Systems where not less than 75 percent of the

energy for reheating (on an annual basis) is from site recovered energy or site-solar energy.

[ASHRAE 90.1:6.5.3.5] E 503.5.6.5 Fractional Horsepower Fan Motors. Motors for fans that are 1 ⁄ 12 hp (62.1 W) or more and less than 1 hp (0.7 kW) shall be electronically-commutated motors or shall have a motor efficiency of not less than 70 percent where rated in

TABLE E 503.5.6.5(1) MINIMUM AVERAGE FULL-LOAD EFFICIENCY FOR POLYPHASE SMALL ELECTRIC MOTORS* [ASHRAE 90.1: TABLE 10.8-3]
FULL-LOAD EFFICIENCY, % FULL-LOAD EFFICIENCY, % FULL-LOAD EFFICIENCY, % FULL-LOAD EFFICIENCY, %
NUMBER OF POLES OPEN MOTORS OPEN MOTORS OPEN MOTORS
NUMBER OF POLES 2 4 6
SYNCHRONOUS SPEED (RPM) 3600 1800 1200
MOTOR HORSEPOWER EFFICIENCY, % EFFICIENCY, % EFFICIENCY, %
0.25 65.6 69.5 67.5
0.33 69.5 73.4 71.4
0.50 73.4 78.2 75.3
0.75 76.8 81.1 81.7
1 77.0 83.5 82.5
1.5 84.0 86.5 83.8
2 85.5 86.5 N/A
3 85.5 86.9 N/A
  • Average full-load efficiencies shall be established in accordance with 10 CFR 431.
TABLE E 503.5.6.5(2) MINIMUM AVERAGE FULL-LOAD EFFICIENCY FOR CAPACITOR-START CAPACITOR-RUN AND CAPACITOR-START INDUCTION-RUN SMALL ELECTRIC MOTORS* [ASHRAE 90.1: TABLE 10.8-4]
FULL-LOAD EFFICIENCY, % FULL-LOAD EFFICIENCY, % FULL-LOAD EFFICIENCY, % FULL-LOAD EFFICIENCY, %
NUMBER OF POLES OPEN MOTORS OPEN MOTORS OPEN MOTORS
NUMBER OF POLES 2 4 6
SYNCHRONOUS SPEED (RPM) 3600 1800 1200
MOTOR HORSEPOWER EFFICIENCY, % EFFICIENCY, % EFFICIENCY, %
0.25 66.6 68.5 62.2
0.33 70.5 72.4 66.6
0.50 72.4 76.2 76.2
0.75 76.2 81.8 80.2
1 80.4 82.6 81.1
1.5 81.5 83.8 N/A
2 82.9 84.5 N/A
3 84.1 N/A N/A

* Average full-load efficiencies shall be established in accordance with 10 CFR 431.

2022 CALIFORNIA MECHANICAL CODE 397

APPENDIX E

accordance with DOE 10 CFR 431. These motors shall also have the means to adjust motor speed for either balancing or remote control. Belt-driven fans shall be permitted to use sheave adjustments for airflow balancing in lieu of a varying motor speed. Exceptions: (1) Motors in the airstream within fan coils and ter minal units that operate when providing heating to the space served. (2) Motors installed in space conditioning equip ment certified in accordance with Section E 503.4 through Section E 503.4.4.1. (3) Motors shown in Table E 503.5.6.5(1) or Table

E 503.5.6.5(2). [ASHRAE 90.1:6.5.3.6] E 503.5.6.6 Ventilation Design. The required minimum outdoor air rate is the larger of the minimum outdoor air rate or the minimum exhaust air rate required by Chapter 4, ASHRAE 62.1, ASHRAE 170, or applicable codes or accreditation standards. Outdoor air ventilation systems shall comply with one of the following: (1) Design minimum system outdoor air provided

3.5.6.5(2). [ASHRAE 90.1:6.5.3.6] E 503.5.6.6 Ventilation Design. The required minimum outdoor air rate is the larger of the minimum outdoor air rate or the minimum exhaust air rate required by Chapter 4, ASHRAE 62.1, ASHRAE 170, or applicable codes or accreditation standards. Outdoor air ventilation systems shall comply with one of the following: (1) Design minimum system outdoor air provided

shall not exceed 135 percent of the required minimum outdoor air rate. (2) Dampers, ductwork, and controls shall be pro vided that allow the system to supply no more than the required minimum outdoor air rate with a single setpoint adjustment. (3) The system includes exhaust air energy recov ery complying with Section E 503.5.10.

[ASHRAE 90.1:6.5.3.7] E 503.5.7 Hydronic System Design and Control. Boiler systems with design input of 1 000 000 Btu/h (293 kW) or more shall comply with the turndown ratio in accordance with Table E 503.5.7.

ble of and configured to reduce pump flow rates to not more than the larger of 25 percent of the design flow rate or the minimum flow required by the heating/cooling equipment manufacturer for the proper operation of equipment. Individual or parallel pumps serving variable-flow heating-water or chilledwater systems, where the nameplate horsepower of the motor or combined parallel motors is not less than the power shown in Table E 503.5.7.1, shall have controls or devices that will result in pump motor demand of not more than 30 percent of design wattage at 50 percent of design water flow. The controls or devices shall be controlled as a function of desired flow or to maintain a minimum required differential pressure. Differential pressure shall be measured at or near the most remote heat exchanger or the heat exchanger requiring the greatest differential pressure. The differential pressure setpoint shall not exceed 110 percent of that required to achieve design flow through the heat exchanger. Where differential pressure control is used to comply with this section, and DDC systems are used, the setpoint shall be reset downward based on valve positions until one valve is nearly wide open. Exceptions: (1) Differential pressure set-point reset is not

required where valve position is used to comply with Section E 503.5.7.3. (2) Variable-pump flow control is not required on

heating-water pumps where more than 50 percent of annual heat is generated by an electric boiler. (3) Variable flow is not required for primary pumps

in a primary/secondary system. (4) Variable flow is not required for a coil pump

provided for freeze protection. (5) Variable flow is not required for heat recovery

coil runaround loops. [ASHRAE 90.1:6.5.4.2]

TABLE E 503.5.7.1 PUMP FLOW CONTROL REQUIREMENTS

[ASHRAE 90.1: TABLE 6.5.4.2]

The system turndown requirement shall use multiple single-input boilers, one or more modulating boilers, or a combination of single-input and modulating boilers.

Boilers shall comply with the minimum efficiency requirements in Table E 503.7.1(6). [ASHRAE 90.1:6.5.4.1]

TABLE E 503.5.7 BOILER TURNDOWN

[ASHRAE 90.1: TABLE 6.5.4.1]

BOILER SYSTEM DESIGN INPUT, Btu/h MINIMUM TURNDOWN RATIO

≥1 000 000 and≤5 000 000
3 to 1

>5 000 000 and≤10 000 000
4 to 1

>10 000 000
5 to 1

For SI units: 1000 British thermal units per hour = 0.293 kW

E 503.5.7.1 Hydronic Variable Flow Systems. Chilled- and hot-water distribution systems that include three or more control valves designed to modulate or step open and close as a function of load shall be designed for variable fluid flow and shall be capa

CHILLED WATER PUMPS
IN THESE
CLIMATE ZONES
HEATING WATER
PUMPS IN THESE
CLIMATE ZONES
MOTOR
NAMEPLATE
HORSEPOWER

0A, 0B, 1A, 1B, 2B
NR ≥2 hp

2A, 3B
NR ≥3 hp

3A, 3C, 4A, 4B
7, 8 ≥5 hp


4C, 5A, 5B, 5C, 6A, 6B
3C, 5A, 5C, 6A, 6B ≥7.5 hp


4A, 4C, 5B ≥10 hp


7, 8
4B ≥15 hp


2A, 2B, 3A, 3B ≥25 hp

1B ≥100 hp

0A, 0B, 1A ≥200 hp

For SI units: 1 horsepower = 0.746 kW

E 503.5.7.2 Chiller and Boiler Isolation. Where a chilled-water plant includes more than one chiller, provisions shall be made so that the fluid flow

398 2022 CALIFORNIA MECHANICAL CODE

through the chiller is automatically shut off where the chiller is shut down. Chillers piped in series for the purpose of increased temperature differential, shall be considered as one chiller. Where constant-speed chilled-water or condenser water pumps are used to serve multiple chillers, the number of pumps shall be not less than the number of chillers and staged on and off with the chillers. [ASHRAE 90.1:6.5.4.3.1]

E 503.5.7.2.1 Boiler Isolation. Where a boiler plant includes more than one boiler, provisions shall be made so that the flow through the boiler is automatically shut off where the boiler is shut down. Where constant-speed hotwater pumps are used to serve multiple boilers, the number of pumps shall be not less than the number of boilers and staged on and off with the boilers. [ASHRAE 90.1:6.5.4.3.2]

E 503.5.7.3 Chilled- and Hot-Water Tempera- ture Reset Controls. Chilled- and hot-water systems with a design capacity exceeding 300 000 Btu/h (88 kW) supplying chilled or heated water to comfort conditioning systems shall include controls that automatically reset supply water temperatures by representative building loads (including return water temperature) or by outdoor air temperature. Where DDC is used to control valves, the set point shall be reset based on valve positions until one valve is nearly wide open or setpoint limits of the system equipment or application have been reached. Exceptions: (1) Where chilled-water supply is already cold,

such as chilled water supplied from a district cooling or thermal energy storage system, such that blending would be required to achieve the reset chilled-water supply temperature. (2) Where a specific temperature is required for a

process.

APPENDIX E

(3) Water temperature reset is not required where

valve position is used to comply with Section E 503.5.7. [ASHRAE 90.1:6.5.4.4]

E 503.5.7.4 Hydronic (Water Loop) Heat Pump and Water-Cooled Unitary Air Condi- tioners. Hydronic heat pumps and water-cooled unitary air-conditioners shall have a two-position automatic valve interlocked to shut off water flow when the compressor is off. Exception: Units employing water economizers.

[ASHRAE 90.1:6.5.4.5.1]

E 503.5.7.4.1 Controls. Hydronic heat pumps and water-cooled unitary air-conditioners having a total pump system power exceeding 5 hp (3.7 kW) shall have controls, devices, or both (such as variable speed control) that will result in pump motor demand of not more than 30 percent of design wattage at 50 percent of design water flow. [ASHRAE 90.1:6.5.4.5.2] E 503.5.7.5 Pipe Sizing. Chilled-water and condenser-water piping shall be designed such that the design flow rate in each piping segment shall not exceed the values listed in Table E 503.5.7.5 for the appropriate total annual hours of operation. Piping size selections for systems that operate under variable flow conditions (e.g., modulating two-way control valves at coils) and that contain variable-speed pump motors shall be permitted to be made from the “Variable Flow/Variable Speed” columns. All others shall be made from the “Other” columns. Exceptions: (1) Design flow rates exceeding the values in Table

E 503.5.7.5 shall be permitted in specific sections of piping if the piping in question is not in the critical circuit at design conditions and is not predicted to be in the critical circuit during more than 30 percent of operating hours.

TABLE E 503.5.7.5 PIPING SYSTEM DESIGN MAXIMUM FLOW RATE (gallons per minute)

[ASHRAE 90.1: TABLE 6.5.4.6]

OPERATING HOURS/YEAR ≤2000 HOURS/YEAR >2000 AND ≤4400 HOURS/YEAR >4400 HOURS/YEAR
NOMINAL PIPE SIZE,
(inches)
OTHER VARIABLE FLOW/
VARIABLE SPEED
OTHER VARIABLE FLOW/
VARIABLE SPEED
OTHER VARIABLE FLOW/
VARIABLE SPEED
21⁄2 120 180 85 130 68 110
3 180 270 140 210 110 170
4 350 530 260 400 210 320
5 410 620 310 470 250 370
6 740 1100 570 860 440 680
8 1200 1800 900 1400 700 1100
10 1800 2700 1300 2000 1000 1600
12 2500 3800 1900 2900 1500 2300
Maximum velocity for pipes over
14-24 inches in size
8.5 ft/s 13.0 ft/s 6.5 ft/s 9.5 ft/s 5.0 ft/s 7.5 ft/s

For SI units: 1 gallon per minute = 0.06 L/s, 1 foot per second = 0.3048 m/s, 1 inch = 25.4 mm

2022 CALIFORNIA MECHANICAL CODE 399

APPENDIX E

(2) Piping systems that have equivalent or lower total

pressure drop than the same system constructed with standard weight steel pipe with piping and fittings sized in accordance with Table E 503.5.7.5. [ASHRAE 90.1:6.5.4.6] E 503.5.8 Heat Rejection Equipment. Section E 503.5.8 through Section E 503.5.9 applies to heat-rejection equipment used in comfort cooling systems, such as air-cooled condensers, dry coolers, open-circuit cooling towers, closed-circuit cooling towers, and evaporative condensers. Exception: Heat-rejection devices whose energy use is included in the equipment efficiency ratings listed in Table E 503.7.1(1) through Table E 503.7.1(4).

[ASHRAE 90.1:6.5.5.1]

E 503.5.8.1 Fan Speed Control. The fan system on a heat-rejection device powered by an individual motor or an array of motors with a connected power, including the motor service factor, totaling 5 hp (3.7 kW) or more shall have controls and/or devices (such as variable-speed control) that shall result in fan motor demand of no more than 30 percent of design wattage at 50 percent of the design airflow and that shall automatically modulate the fan speed to control the leaving fluid temperature or condensing temperature/pressure of the heat-rejection device. Exceptions: (1) Condenser fans serving multiple refrigerant or

fluid cooling circuits. (2) Condenser fans serving flooded condensers.

[ASHRAE 90.1:6.5.5.2.1] E 503.5.8.2 Variable-Speed Fan Drives. Multicell heat rejection equipment with variable-speed fan drives shall: (1) Operate the maximum number of fans allowed

that comply with the manufacturer’s requirements for all system components. (2) Control all fans to the same fan speed required

for the instantaneous cooling duty, as opposed to staged (on/off) operation. Minimum fan speed shall comply with the minimum allowable speed of the fan drive system per the manufacturer’s recommendations. [ASHRAE 90.1:6.5.5.2.2]

E 503.5.9 Limitation on Centrifugal Fan Open- Circuit Cooling Towers. Centrifugal fan open-circuit cooling towers with a combined rated capacity of 1100 gallons per minute (gpm) (69.39 L/s) or greater at 95°F (35°C) condenser water return, 85°F (29°C) condenser water supply, and 75°F (24°C) outdoor air wet-bulb temperature shall comply with the energy efficiency requirement for axial fan open-circuit cooling towers in accordance with Table E 503.7.1(7). Exception: Centrifugal open-circuit cooling towers that are ducted (inlet or discharge) or require external sound attenuation. [ASHRAE 90.1:6.5.5.3]

E 503.5.9.1 Tower Flow Turndown. Open-circuit cooling towers used on water-cooled chiller systems that are configured with multiple- or variable-speed condenser water pumps shall be designed so that all open-circuit cooling tower cells can be run in parallel with the larger of the following: (1) The flow that is produced by the smallest pump

at its minimum expected flow rate. (2) Fifty percent of the design flow for the cell.

[ASHRAE 90.1:6.5.5.4] E 503.5.10 Exhaust Air Energy Recovery. Each fan system shall have an energy recovery system where the design supply fan airflow rate exceeds the value listed in Table E 503.5.10(1) and Table E 503.5.10(2), based on the climate zone and percentage of outdoor air at design airflow conditions. Table E 503.5.10(1) shall be used for all ventilation systems that operate less than 8000 hours per year and Table E 503.5.10(2) shall be used for all ventilation systems that operate 8000 or more hours per year.

Energy recovery systems required by this section shall result in an enthalpy recovery ratio of not less than 50 percent. A fifty percent enthalpy recovery ratio shall mean a change in the enthalpy of the outdoor air supply equal to 50 percent of the difference between the outdoor air and entering exhaust air enthalpies at design conditions. Provision shall be provided to bypass or control the energy recovery system to permit air economizer operation in accordance with Section E 503.5.1. Exceptions: (1) Laboratory systems that are in accordance with Sec tion E 503.5.11.3. (2) Systems serving spaces that are not cooled and that

are heated to less than 60°F (16°C). (3) Where more than 60 percent of the outdoor air heat ing energy is provided from site-recovered energy or site-solar energy. (4) Heating energy recovery in Climate Zones 0, 1, and

(5) Cooling energy recovery in climate zones 3C, 4C,

5B, 5C, 6B, 7, and 8. (6) Where the sum of the airflow rates exhausted and

relieved within 20 feet (6096 mm) of each other is less than 75 percent of the design outdoor airflow rate, excluding exhaust air that is; (a) used for another energy recovery system, (b) not allowed by ASHRAE 170 for use in energy

recovery systems with leakage potential, or (c) of Class 4 as defined in Chapter 2 or ASHRAE

62.1. (7) Systems requiring dehumidification that employ

energy recovery in series with the cooling coil. (8) Systems expected to operate less than 20 hours per

week at the outdoor air percentage in accordance with Table E 503.5.10(1). [ASHRAE 90.1:6.5.6.1]

400 2022 CALIFORNIA MECHANICAL CODE

TABLE E 503.5.10(1) EXHAUST AIR ENERGY RECOVERY REQUIREMENTS FOR VENTILATION

SYSTEMS OPERATING LESS THAN 8000 HOURS PER YEAR*

[ASHRAE 90.1: TABLE 6.5.6.1-1]

APPENDIX E

CLIMATE ZONE PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE
CLIMATE ZONE ≥10% and
<20%
≥20% and
<30%
≥30% and
<40%
≥40% and
<50%
≥50% and
<60%
≥60% and
<70%
≥70% and
<80%
≥80%
CLIMATE ZONE DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute)
3B, 3C, 4B,
4C, 5B
NR NR NR NR NR NR NR NR

0B, 1B, 2B, 5C
NR NR NR NR ≥26 000 ≥12 000 ≥5000 ≥4000
6B ≥28 000 ≥26 500 ≥11 000 ≥5500 ≥4500 ≥3500 ≥2500 ≥1500
0A, 1A, 2A,
3A, 4A, 5A,
6A
≥26 000 ≥16 000 ≥5500 ≥4500 ≥3500 ≥2000 ≥1000 ≥120
7, 8 ≥4500 ≥4000 ≥2500 ≥1000 ≥140 ≥120 ≥100 ≥80

For SI units: 1 cubic foot per minute = 0.00047 m 3 /s

  • NR = Not Required
TABLE E 503.5.10(2) EXHAUST AIR ENERGY RECOVERY REQUIREMENTS FOR VENTILATION SYSTEMS OPERATING NOT LESS THAN 8000 HOURS PER YEAR* [ASHRAE 90.1: TABLE 6.5.6.1-2]
CLIMATE ZONE PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE
CLIMATE ZONE ≥10% and
<20%
≥20% and
<30%
≥30% and
<40%
≥40% and
<50%
≥50% and
<60%
≥60% and
<70%
≥70% and
<80%
≥80%
CLIMATE ZONE DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute) DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute)
3C NR NR NR NR NR NR NR NR
0B, 1B, 2B,
3B, 4C, 5C
NR ≥19 500 ≥9000 ≥5000 ≥4000 ≥3000 ≥1500 ≥120
0A, 1A, 2A,
3A, 4B, 5B
≥2500 ≥2000 ≥1000 ≥500 ≥140 ≥120 ≥100 ≥80
4A, 5A, 6A,
6B, 7, 8
≥200 ≥130 ≥100 ≥80 ≥70 ≥60 ≥50 ≥40

For SI units: 1 cubic foot per minute = 0.00047 m 3 /s

  • NR = Not Required

E 503.5.10.1 Heat Recovery for Service Water Heating. Heat recovery shall comply with Section E 503.5.10.1.1 and Section E 503.5.10.1.2.

E 503.5.10.1.1 Condenser Heat Recovery Systems. Condenser heat recovery systems shall be installed for the heating or preheating of service hot water where the following conditions exist: (1) The facility operates 24 hours a day. (2) The total installed heat rejection capacity of

the water-cooled system is more than 6 000 000 Btu/h (1757 kW) of heat rejection. (3) The design service water heating load is

more than 1 000 000 Btu/h (293 kW).

[ASHRAE 90.1:6.5.6.2.1] E 503.5.10.1.2 Capacity. The required heat recovery system shall have the capacity to provide the smaller of: (1) Sixty percent of the peak heat-rejection

load at design conditions or (2) Preheat of the peak service hot-water draw

to 85°F (29°C).

Exceptions: (1) Facilities that employ condenser heat

recovery for space heating with a heat recovery design exceeding 30 percent of the peak water-cooled condenser load at design conditions. (2) Facilities that provide 60 percent of their

service water heating from site-solar energy or site-recovered energy or from other sources. [ASHRAE 90.1:6.5.6.2.2] E 503.5.11 Exhaust Systems. Exhaust systems shall comply with Section E 503.5.11.1 through Section E 503.5.11.3. E 503.5.11.1 Transfer Air. Conditioned supply air delivered to a space with a mechanical exhaust shall not exceed the greater of the following: (1) The supply flow required to be in accordance

with the space heating or cooling load; (2) The ventilation rate required by the Authority

Having Jurisdiction, the Facility Environmental Health and Safety department, Chapter 4 or ASHRAE 62.1; or

«

2022 CALIFORNIA MECHANICAL CODE 401

APPENDIX E

TABLE E 503.5.11.2.1 MAXIMUM NET EXHAUST FLOW RATE, CFM PER LINEAR FOOT OF HOOD LENGTH

[ASHRAE 90.1: TABLE 6.5.7.2.2]

TYPE OF HOOD LIGHT DUTY
EQUIPMENT
MEDIUM DUTY
EQUIPMENT
HEAVY DUTY
EQUIPMENT
EXTRA HEAVY DUTY
EQUIPMENT
Wall-mounted canopy 140 210 280 385
Single island 280 350 420 490
Double island (per side) 175 210 280 385
Eyebrow 175 175 Not allowed Not allowed
Backshelf/ Pass-over 210 210 280 Not allowed
» »

For SI units: 1 foot = 304.8 mm, 1 cubic foot per minute = 0.00047 m 3 /s

(3) The mechanical exhaust flow minus the avail able transfer air from conditioned spaces or return air plenums on the same floor, not in different smoke or fire compartments, and that at their closest point are within 15 feet (4572 mm) of each other. Available transfer air is that portion of outdoor ventilation air that: (a) is not required to satisfy other exhaust

needs, (b) is not required to maintain pressurization

of other spaces, and (c) is transferable according to applicable

codes and standards and to the class of air recirculation limitations in Chapter 4 or ASHRAE 62.1. Exceptions: (1) Biosafety level classified laboratories 3 or higher. (2) Vivarium spaces. (3) Spaces that are required by applicable codes

and standards to be maintained at positive pressure relative to adjacent spaces. For spaces taking this exception, any transferable air that is not directly transferred shall be made available to the associated air-handling unit and shall be used whenever economizer or other options do not save more energy. (4) Spaces where the demand for transfer air may

exceed the available transfer airflow rate and where the spaces have a required negative pressure relationship. For spaces taking this exception, any transferable air that is not directly transferred shall be made available to the associated air-handling unit and shall be used whenever economizer or other options do not save more energy. [ASHRAE 90.1:6.5.7.1] E 503.5.11.2 Kitchen Exhaust Systems. Replacement air introduced directly into the hood cavity of kitchen exhaust hoods shall not exceed 10 percent of the hood exhaust airflow rate. [ASHRAE 90.1:6.5.7.2.1] E 503.5.11.2.1 Exhaust Flow Rate. Where a kitchen or dining facility has a total kitchen hood exhaust airflow rate exceeding 5000 ft 3 /min (2.3597 m 3 /s), each hood shall have an exhaust rate in accordance with Table E 503.5.11.2.1.

Where a single hood, or hood section, is installed over appliances with different duty ratings, the maximum allowable flow rate for the hood or hood section shall not exceed the values in Table E 503.5.11.2.1 for the highest appliance duty rating under the hood or hood section. Refer to ASHRAE 154 for definitions of hood type, appliance duty, and net exhaust flow rate. Exception: Seventy-five percent or more of the total replacement air is transfer air that would otherwise be exhausted. [ASHRAE 90.1:6.5.7.2.2] E 503.5.11.2.2 Kitchen or Dining Facility. Where a kitchen or dining facility has a total kitchen hood exhaust airflow rate more than 5000 ft 3 /min (2.3597 m 3 /s), then one of the following shall be provided: (1) Fifty percent or more of all replacement air

is transfer air that would otherwise be exhausted. (2) Demand ventilation systems on 75 percent

or more of the exhaust air. Such systems shall be capable of and configured to provide 50 percent or more reduction in exhaust and replacement air system airflow rates, including controls necessary to modulate airflow in response to appliance operation and to maintain full capture and containment of smoke, effluent, and combustion products during cooking and idle. (3) Listed energy recovery devices that result in

xhaust air. Such systems shall be capable of and configured to provide 50 percent or more reduction in exhaust and replacement air system airflow rates, including controls necessary to modulate airflow in response to appliance operation and to maintain full capture and containment of smoke, effluent, and combustion products during cooking and idle. (3) Listed energy recovery devices that result in

a sensible energy recovery ratio of 40 percent or more on 50 percent or more of the total exhaust airflow. A 40 percent sensible energy recovery ratio shall mean a change in the dry-bulb temperature of the outdoor air supply equal to 40 percent of the difference between the outdoor air and entering exhaust air dry-bulb temperatures at design conditions. [ASHRAE 90.1:6.5.7.2.3] E 503.5.11.2.3 Performance Testing. An approved field test method shall be used to evaluate design air flow rates and demonstrate proper capture and containment performance of installed commercial kitchen exhaust systems. Where demand ventilation systems are utilized to be in accordance with Section E 503.5.11.2.2,

« «

402 2022 CALIFORNIA MECHANICAL CODE

additional performance testing shall be required to demonstrate proper capture and containment at minimum airflow. [ASHRAE 90.1:6.5.7.2.4] E 503.5.11.3 Laboratory Exhaust Systems. Buildings with laboratory exhaust systems having a total exhaust rate of more than 5000 ft 3 /min (2.3597 m 3 /s) shall include not less than one of the following features: (1) VAV laboratory exhaust and room supply sys tems capable of and configured to reduce exhaust and makeup airflow rates, incorporate a heat recovery system to precondition makeup air from laboratory exhaust, or both, and shall be in accordance with the following:

A + B •( E/M ) ≥ 50% (Equation E 503.5.11.3)

Where: A = Percentage that the exhaust and makeup air flow rates are capable of being reduced from design conditions. B = Sensible energy recovery ratio. E = Exhaust airflow rate through the heat recovery

device at design conditions. M = Makeup airflow rate of the system at design

conditions. (2) VAV laboratory exhaust and room supply sys tems that are required to have minimum circulation rates to be in accordance with the codes or accreditation standards shall be capable of and configured to reduce zone exhaust and makeup airflow rates to the regulated minimum circulation values, or the minimum required to maintain pressurization relationship requirements. Systems serving nonregulated zones shall be capable of and configured to reduce exhaust and makeup airflow rates to 50 percent of the zone design values, or the minimum required to maintain pressurization relationship requirements. (3) Direct makeup (auxiliary) air supply of 75 per cent or more of the exhaust airflow rate, heated not more than 2°F (1°C) below room setpoint, cooled to not less than 3°F (2°C) above room setpoint, no humidification added, and no simultaneous heating and cooling are used for dehumidification control. [ASHRAE 90.1:6.5.7.3] E 503.5.12 Radiant Heating Systems. Radiant heating shall be used when heating is required for unenclosed spaces. Exception: Loading docks equipped with air curtains.

[ASHRAE 90.1:6.5.8.1]

E 503.5.12.1 Heating Enclosed Spaces. Radiant heating systems that are used as primary or supplemental heating for enclosed spaces shall be in conformance with the governing provisions of the standard, including, but not limited to the following:

APPENDIX E

(1) Radiant hydronic ceiling or floor panels (used

for heating or cooling). (2) Combination or hybrid systems incorporating

radiant heating (or cooling) panels. (3) Radiant heating (or cooling) panels used in con junction with other systems such as VAV or thermal storage systems. [ASHRAE 90.1:6.5.8.2] E 503.5.13 Hot Gas Bypass Limitation. Cooling systems shall not use hot gas bypass or other evaporator pressure control systems unless the system is designed with multiple steps of unloading or continuous capacity modulation. The capacity of the hot gas bypass shall be limited as indicated in Table E 503.5.13 for VAV units and single-zone VAV units. Hot-gas bypass shall not be used on constant-volume units. [ASHRAE 90.1:6.5.9]

TABLE E 503.5.13 HOT GAS BYPASS LIMITATION

[ASHRAE 90.1: TABLE 6.5.9]

RATED CAPACITY MAXIMUM HOT GAS BYPASS
(percent of total capacity)


≤240 000 Btu/h
15%

>240 000 Btu/h
10%

For SI units: 1000 British thermal units per hour = 0.293 kW

E 503.5.14 Door Switches. Conditioned spaces with doors, including doors with more than one-half glass, opening to the outdoors shall be provided with controls that when any such door is open, the following shall occur: (1) Disable mechanical heating or reset the heating set point to 55°F (13°C) or lower within five minutes of the door opening. (2) Disable mechanical cooling or reset the cooling set point to 90°F (32°C) or more within five minutes of the door opening. Mechanical cooling shall be permitted to remain enabled where outdoor air temperature is less than the space temperature. Exceptions: (1) Building entries with automatic closing devices. (2) Any space without a thermostat. (3) Alterations to existing buildings. (4) Loading docks. [ASHRAE 90.1:6.5.10] E 503.6 Submittals. The Authority Having Jurisdiction shall require submittal of compliance documentation and supplemental information in accordance with Section E 503.6.1 through Section E 503.6.3.

E 503.6.1 Construction Details. Compliance documents shall show the pertinent data and features of the building, equipment, and systems in sufficient detail to permit a determination of compliance by the building official and to indicate compliance with the requirements of this appendix. [ASHRAE 90.1:4.2.2.1] E 503.6.2 Supplemental Information. Supplemental information necessary to verify compliance with this appendix, such as calculations, worksheets, compliance forms, vendor literature, or other data, shall be made

2022 CALIFORNIA MECHANICAL CODE 403

APPENDIX E

available where required by the Authority Having Jurisdiction. [ASHRAE 90.1:4.2.2.2] E 503.6.3 Manuals. Operating and maintenance information shall be provided to the building owner. This information shall include, but not be limited to, the information specified in Section E 503.6.3.1, Section E 503.6.3.2, and Section E 503.6.5.2. [ASHRAE 90.1:4.2.2.3]

E 503.6.3.1 Required Information. Construction documents shall require that an operating manual and maintenance manual be provided to the building owner. The manuals shall include, at a minimum, the following: (1) Submittal data stating equipment rating and

selected options for each piece of equipment requiring maintenance. (2) Operation manuals and maintenance manuals

for each piece of equipment requiring maintenance. Required routine maintenance actions shall be clearly identified. (3) Names and addresses of not less than one qual ified service agency. (4) A complete narrative of how each system is

intended to operate. The Authority Having Jurisdiction shall only check to ensure that the construction documents require this information to be transmitted to the owner and should not expect copies of any of the materials.

[ASHRAE 90.1:8.7.2] E 503.6.3.2 Lighting Manuals. Construction documents shall require for all lighting equipment and lighting controls that an operating and maintenance manual be provided to the building owner or the designated representative of the building owner within 90 days after the date of system acceptance. These manuals shall include, at a minimum, the following: (1) Submittal data indicating all selected options

for each piece of lighting equipment, including but not limited to lamps, ballasts, drivers, and lighting controls. (2) Operation and maintenance manuals for each

piece of lighting equipment and lighting controls with routine maintenance clearly identified including, as a minimum, a recommended relamping or cleaning program and a schedule for inspecting and recalibrating all lighting controls. (3) A complete narrative of how each lighting con trol system is intended to operate including recommended settings. [ASHRAE 90.1:9.7.2.2] E 503.6.4 Labeling of Material and Equipment. Materials and equipment shall be labeled in a manner that will allow for determination of their compliance with the applicable provisions of this appendix. [ASHRAE 90.1:4.2.3] E 503.6.5 Completion Requirements. Section E 503.6.5.1 through Section E 503.6.5.4.1 are mandatory provisions and are necessary to comply with this appendix. [ASHRAE 90.1:6.7.2]

E 503.6.5.1 Drawings. Construction documents shall require that, within 90 days after the date of system acceptance, record drawings of the actual installation be provided to the building owner or the designated representative of the building owner. Record drawings shall include, as a minimum, the location and performance data on each piece of equipment, general configuration of duct and pipe distribution system including sizes, and the terminal air or water design flow rates. [ASHRAE 90.1:6.7.2.1] E 503.6.5.2 Manuals. Construction documents shall require that an operating manual and a maintenance manual be provided to the building owner or the designated representative of the building owner within 90 days after the date of system acceptance. These manuals shall be in accordance with industryaccepted standards and shall include, at a minimum, the following: (1) Submittal data stating equipment size and

selected options for each piece of equipment requiring maintenance. (2) Operation manuals and maintenance manuals

for each piece of equipment and system requiring maintenance, except equipment not furnished as part of the project. Required routine maintenance actions shall be clearly identified. (3) Names and addresses of not less than one serv ice agency. (4) HVAC controls system maintenance and cali bration information, including wiring diagrams, schematics, and control sequence descriptions. Desired or field-determined setpoints shall be permanently recorded on control drawings at control devices or, for digital control systems, in programming comments. (5) A complete narrative of how each system is

addresses of not less than one serv ice agency. (4) HVAC controls system maintenance and cali bration information, including wiring diagrams, schematics, and control sequence descriptions. Desired or field-determined setpoints shall be permanently recorded on control drawings at control devices or, for digital control systems, in programming comments. (5) A complete narrative of how each system is

intended to operate, including suggested setpoints. [ASHRAE 90.1:6.7.2.2] E 503.6.5.3 System Balancing. Construction documents shall require that HVAC systems be balanced in accordance with generally accepted engineering standards. Construction documents shall require that a written balance report be provided to the building owner or the designated representative of the building owner for HVAC systems serving zones with a total conditioned area exceeding 5000 square feet (464.52 m 2 ). [ASHRAE 90.1:6.7.2.3.1]

E 503.6.5.3.1 Air System Balancing. Air systems shall be balanced in a manner to first minimize throttling losses. Then, for fans with fan system power greater than 1 hp (0.7 kW), fan speed shall be adjusted to meet design flow conditions. [ASHRAE 90.1:6.7.2.3.2] E 503.6.5.3.2 Hydronic System Balanc- ing. Hydronic systems shall be proportionately balanced in a manner to first minimize throttling losses; then the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions.

404 2022 CALIFORNIA MECHANICAL CODE

Exceptions: Impellers need not be trimmed nor pump speed adjusted. (1) For pumps with pump motors of 10 hp (7.5

kW) or less. (2) Where throttling results is not greater than

5 percent of the nameplate horsepower draw, or 3 hp (2.2 kW), whichever is greater, above that required where the impeller was trimmed. [ASHRAE 90.1:6.7.2.3.3] E 503.6.5.4 System Commissioning. HVAC control systems shall be tested to ensure that control elements are calibrated, adjusted, and in proper working condition. For projects larger than 50 000 square feet (4645.15 m 2 ) conditioned area, except warehouses and semiheated spaces, detailed instructions for commissioning HVAC systems shall be provided by the designer in plans and specifications.

[ASHRAE 90.1:6.7.2.4]

E 503.6.5.4.1 Minimum Level of Com- mission. Commissioning shall be performed for HVAC systems in accordance with Level 1, Basic Commissioning of the SMACNA HVAC Systems Commissioning Manual. (See Section E 801.0 for additional information on HVAC system commissioning) E 503.7 Minimum Equipment Efficiency Tables. The minimum efficiency requirements for equipment shall comply with Section E 503.7.1; duct insulation shall comply with Section E 503.7.2, and pipe insulation shall comply with Section E 503.7.3.

evel 1, Basic Commissioning of the SMACNA HVAC Systems Commissioning Manual. (See Section E 801.0 for additional information on HVAC system commissioning) E 503.7 Minimum Equipment Efficiency Tables. The minimum efficiency requirements for equipment shall comply with Section E 503.7.1; duct insulation shall comply with Section E 503.7.2, and pipe insulation shall comply with Section E 503.7.3.

E 503.7.1 Minimum Efficiency Requirement Listed Equipment – Standard Rating and Oper- ating Conditions. The minimum efficiency requirements for equipment shall comply with Table E 503.7.1(1) through Table E 503.7.1(16). E 503.7.2 Duct Insulation Tables. Duct insulation shall comply with Table E 503.7.2. E 503.7.3 Pipe Insulation Tables. Pipe insulation shall comply with Table E 503.7.3(1) through Table E 503.7.3(2). E 503.8 Alternative Compliance Path. HVAC systems serving heating, cooling, or ventilation needs of a computer room shall be in accordance with Section E 503.1, Section E 503.4, Section E 503.8.1 or Section E 503.8.2, Section E 503.8.3, Section E 502.7 through Section E 502.7.2, and Section E 503.7. [ASHRAE 90.1:6.6.1]

E 503.8.1 Computer Room ( PUE1 ). The computer room PUE1 shall be not more than the values listed in Table E 503.8.1. Hourly simulation of the proposed design, for purposes of calculating PUE1, shall be in accordance with ASHRAE 90.1. Exception: The compliance path shall not be permitted for a proposed computer room design utilizing a combined heat and power system. [ASHRAE 90.1:6.6.1.1]

APPENDIX E

TABLE E 503.8.1 POWER USAGE EFFECTIVENESS (PUE) MAXIMUM

[ASHRAE 90.1: TABLE 6.6.1]

CLIMATE ZONE PUE*

0A
1.64

0B
1.62


1A
1.61


1B
1.53

2A
1.49

2B
1.45


3A
1.41


3B
1.42

3C
1.39

4A
1.36


4B
1.38


4C
1.38


5A
1.36

5B
1.33

5C
1.36


6A
1.34


6B
1.33

7
1.32


8
1.30

E 503.8.2 Computer Room ( PUE0 ). The computer room PUE0 is less than or equal to the values listed in Table E 503.8.1, shall be the highest value determined at outdoor cooling design temperatures, and shall be limited to systems only using electricity for an energy source. PUE0 shall be calculated for two conditions: (1) One hundred percent design IT equipment energy

and (2) Fifty percent design IT equipment energy.

[ASHRAE 90.1:6.6.1.2] E 503.8.3 Documentation. Documentation on the following components shall be provided, including a breakdown of energy consumption or demand: (1) IT equipment (2) Power distribution losses external to the IT equip ment (3) HVAC systems (4) Lighting [ASHRAE 90.1:6.6.1.3]

E 504.0 Solar Energy Systems. E 504.1 General. Solar energy systems shall be installed in accordance with the Uniform Solar, Hydronics and Geothermal Code (USHGC).

2022 CALIFORNIA MECHANICAL CODE 405

APPENDIX E

TABLE E 503.7.1(1) ELECTRICALLY OPERATED UNITARY AIR CONDITIONERS AND CONDENSING UNITS

MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-1]

EQUIPMENT TYPE SIZE CATEGORY HEATING SECTION TYPE SUBCATEGORY OR RATING
CONDITION
MINIMUM EFFICIENCY TEST
PROCEDURE1
Air conditioners, air
cooled
<65 000 Btu/h2 All Split system, three phase 13.0 SEER AHRI 210/240
Air conditioners, air
cooled
<65 000 Btu/h2 All Single package, three phase 14 SEER 14 SEER
Through the wall, air
cooled
≤30 000 Btu/h2 All Split system, three phase 12.0 SEER AHRI 210/240
Through the wall, air
cooled
≤30 000 Btu/h2 All Single package, three phase 12.0 SEER 12.0 SEER
Small duct, high
velocity, air cooled
<65 000 Btu/h2 All Split system, three phase 11.0 SEER AHRI 210/240
Air conditioners, air
cooled
≥65 000 Btu/h and
<135 000 Btu/h
Electric resistance
(or none)
Split system and single
package
11.2 EER
12.9 IEER
AHRI 340/360
Air conditioners, air
cooled
≥65 000 Btu/h and
<135 000 Btu/h
All other All other 11.0 EER
12.7 IEER
11.0 EER
12.7 IEER
Air conditioners, air
cooled
≥135 000 Btu/h and
<240 000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
11.0 EER
12.4 IEER
11.0 EER
12.4 IEER
Air conditioners, air
cooled
≥135 000 Btu/h and
<240 000 Btu/h
All other All other 10.8 EER
12.2 IEER
10.8 EER
12.2 IEER
Air conditioners, air
cooled
≥240 000 Btu/h and
<760 000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
10.0 EER
11.6 IEER
10.0 EER
11.6 IEER
Air conditioners, air
cooled
≥240 000 Btu/h and
<760 000 Btu/h
All other All other 9.8 EER
11.4 IEER
9.8 EER
11.4 IEER
Air conditioners, air
cooled
≥760 000 Btu/h Electric resistance
(or none)
Electric resistance
(or none)
9.7 EER
11.2 IEER
9.7 EER
11.2 IEER
Air conditioners, air
cooled
≥760 000 Btu/h All other All other 9.5 EER
11.0 IEER
9.5 EER
11.0 IEER
Air conditioners,
water cooled
<65 000 Btu/h All Split system and single
package
12.1 EER
12.3 IEER
AHRI 210/240
Air conditioners,
water cooled
≥65 000 Btu/h and
<135 000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.1 EER
13.9 IEER
AHRI 340/360
Air conditioners,
water cooled
≥65 000 Btu/h and
<135 000 Btu/h
All other All other 11.9 EER
13.7 IEER
11.9 EER
13.7 IEER
Air conditioners,
water cooled
≥135 000 Btu/h and
<240 000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.5 EER
13.9 IEER
12.5 EER
13.9 IEER
Air conditioners,
water cooled
≥135 000 Btu/h and
<240 000 Btu/h
All other All other 12.3 EER
13.7 IEER
12.3 EER
13.7 IEER
Air conditioners,
water cooled
≥240 000 Btu/h and
<760 000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.4 EER
13.6 IEER
12.4 EER
13.6 IEER
Air conditioners,
water cooled
≥240 000 Btu/h and
<760 000 Btu/h
All other All other 12.2 EER
13.4 IEER
12.2 EER
13.4 IEER
Air conditioners,
water cooled
≥760 000 Btu/h Electric resistance
(or none)
Electric resistance
(or none)
12.2 EER
13.5 IEER
12.2 EER
13.5 IEER
Air conditioners,
water cooled
≥760 000 Btu/h All other All other 12.0 EER
13.3 IEER
12.0 EER
13.3 IEER

406 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

TABLE E 503.7.1(1) (continued) ELECTRICALLY OPERATED UNITARY AIR CONDITIONERS AND CONDENSING UNITS

MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-1]

EQUIPMENT TYPE SIZE CATEGORY HEATING SECTION TYPE SUBCATEGORY OR RATING
CONDITION
MINIMUM EFFICIENCY TEST
PROCEDURE1
Air conditioners,
evaporatively cooled
<65 000 Btu/h2 All Split system and single
package
12.1 EER
12.3 IEER
AHRI 210/240
Air conditioners,
evaporatively cooled
≥65 000 Btu/h and
<135 000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.1 EER
12.3 IEER
AHRI 340/360
Air conditioners,
evaporatively cooled
≥65 000 Btu/h and
<135 000 Btu/h
All other All other 11.9 EER
12.1 IEER
11.9 EER
12.1 IEER
Air conditioners,
evaporatively cooled
≥135 000 Btu/h and
<240 000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
12.0 EER
12.2 IERR
12.0 EER
12.2 IERR
Air conditioners,
evaporatively cooled
≥135 000 Btu/h and
<240 000 Btu/h
All other All other 11.8 EER
12.0 IEER
11.8 EER
12.0 IEER
Air conditioners,
evaporatively cooled
≥240 000 Btu/h and
<760 000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
11.9 EER
12.1 IEER
11.9 EER
12.1 IEER
Air conditioners,
evaporatively cooled
≥240 000 Btu/h and
<760 000 Btu/h
All other All other 11.7 EER
11.9 IEER
11.7 EER
11.9 IEER
Air conditioners,
evaporatively cooled
≥760 000 Btu/h Electric resistance
(or none)
Electric resistance
(or none)
11.7 EER
11.9 IEER
11.7 EER
11.9 IEER
Air conditioners,
evaporatively cooled
≥760 000 Btu/h All other All other 11.5 EER
11.7 IEER
11.5 EER
11.7 IEER
Condensing units, air
cooled
≥135 000 Btu/h 10.5 EER
11.8 IEER
AHRI 365
Condensing units,
water cooled
≥135 000 Btu/h 13.5 EER
14.0 IEER
AHRI 365
Condensing units,
evaporatively cooled
≥135 000 Btu/h 13.5 EER
14.0 IEER
AHRI 365

For SI units: 1000 British thermal units per hour = 0.293 kW Notes:

1 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. 2 Single-phase, air-cooled air conditioners less than 65 000 Btu/h (19 kW) are regulated by the U.S. Department of Energy Code of Federal Regulations 10 CFR 430. SEER values for single-phase products are set by the U.S. Department of Energy.

2022 CALIFORNIA MECHANICAL CODE 407

APPENDIX E

TABLE E 503.7.1(2) ELECTRICALLY OPERATED UNITARY AND APPLIED HEAT PUMPS

MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-2]

EQUIPMENT TYPE SIZE CATEGORY HEATING SECTION TYPE SUBCATEGORY OR RATING
CONDITION
MINIMUM EFFICIENCY TEST
PROCEDURE1
Air cooled (cooling
mode)
<65 000 Btu/h2 All Split system, three phase 14 SEER AHRI 210/240
Air cooled (cooling
mode)
<65 000 Btu/h2 All Single package, three phase 14 SEER 14 SEER
Through the wall, air
cooled (cooling mode)
≤30 000 Btu/h2 All Split system, three phase 12.0 SEER AHRI 210/240
Through the wall, air
cooled (cooling mode)
≤30 000 Btu/h2 All Single package, three phase 12.0 SEER 12.0 SEER
Small duct, high
velocity, air cooled
<65 000 Btu/h2 All Split System, three phase 11.0 SEER AHRI 210/240
Air cooled (cooling
mode)
≥65 000 Btu/h and
<135 000 Btu/h
Electric resistance
(or none)
Split system and single
package
11.0 EER
12.2 IEER
AHRI 340/360
Air cooled (cooling
mode)
≥65 000 Btu/h and
<135 000 Btu/h
All other All other 10.8 EER
12.0 IEER
10.8 EER
12.0 IEER
Air cooled (cooling
mode)
≥135 000 Btu/h and
<240 000 Btu/h
Electric resistance
(or none)
Electric resistance
(or none)
10.6 EER
11.6 IEER
10.6 EER
11.6 IEER
Air cooled (cooling
mode)
≥135 000 Btu/h and
<240 000 Btu/h
All other All other 10.4 EER
11.4 IEER
10.4 EER
11.4 IEER
Air cooled (cooling
mode)
≥240 000 Btu/h Electric resistance
(or none)
Electric resistance
(or none)
9.5 EER
10.6 IEER
9.5 EER
10.6 IEER
Air cooled (cooling
mode)
≥240 000 Btu/h All other All other 9.3 EER
10.4 IEER
9.3 EER
10.4 IEER
Water to air, water
loop (cooling mode)
<17 000 Btu/h All 86°F entering water 12.2 EER ISO 13256-1
Water to air, water
loop (cooling mode)
≥17 000 Btu/h and
<65 000 Btu/h
≥17 000 Btu/h and
<65 000 Btu/h
≥17 000 Btu/h and
<65 000 Btu/h
13.0 EER 13.0 EER
Water to air, water
loop (cooling mode)
≥65 000 Btu/h and
<135 000 Btu/h
≥65 000 Btu/h and
<135 000 Btu/h
≥65 000 Btu/h and
<135 000 Btu/h
13.0 EER 13.0 EER
Water to air, ground-
water (cooling mode)
<135 000 Btu/h All 59°F entering water 18.0 EER ISO 13256-1
Brine to air, ground
loop (cooling mode)
<135 000 Btu/h All 77°F entering water 14.1 EER ISO 13256-1
Water to water, water
loop (cooling mode)
<135 000 Btu/h All 86°F entering water 10.6 EER ISO 13256-2
Water to water,
groundwater (cooling
mode)
<135 000 Btu/h All 59°F entering water 16.3 EER ISO 13256-2
Brine to water,
ground loop (cooling
mode)
<135 000 Btu/h All 77°F entering water 12.1 EER ISO 13256-2
Air cooled (heating
mode)
<65 000 Btu/h2
(cooling capacity)
Split system, three phase 8.2 HSPF AHRI 210/240
Air cooled (heating
mode)
<65 000 Btu/h2
(cooling capacity)
Single package, three phase 8.0 HSPF 8.0 HSPF
Through the wall, air
cooled (heating
mode)
≤30 000 Btu/h2
(cooling capacity)
Split system, three phase 7.4 HSPF AHRI 210/240
Through the wall, air
cooled (heating
mode)
≤30 000 Btu/h2
(cooling capacity)
Single package, three phase 7.4 HSPF 7.4 HSPF
Small duct high
velocity, air cooled
(heating mode)
<65 000 Btu/h2 Split system, three phase 6.8 HSPF AHRI 210/240

408 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

TABLE E 503.7.1(2) (continued) ELECTRICALLY OPERATED UNITARY AND APPLIED HEAT PUMPS

MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-2]

EQUIPMENT TYPE SIZE CATEGORY HEATING SECTION TYPE SUBCATEGORY OR RATING
CONDITION
MINIMUM EFFICIENCY TEST
PROCEDURE1
Air cooled (heating
mode)
≥65 000 Btu/hc and
<135 000 Btu/h
(cooling capacity)
47°F db/43°F wb outdoor air 3.3 COPH AHRI 340/360
Air cooled (heating
mode)
≥65 000 Btu/hc and
<135 000 Btu/h
(cooling capacity)
17°F db/15°F wb outdoor air 2.25 COPH 2.25 COPH
Air cooled (heating
mode)
≥135 000 Btu/hc
(cooling capacity)
≥135 000 Btu/hc
(cooling capacity)
47°F db/43°F wb outdoor air 3.2 COPH 3.2 COPH
Air cooled (heating
mode)
≥135 000 Btu/hc
(cooling capacity)
≥135 000 Btu/hc
(cooling capacity)
17°F db/15°F wb outdoor air 2.05 COPH 2.05 COPH
Water to air, water
loop (heating mode)
<135 000 Btu/h
(cooling capacity)
68°F entering water 4.3 COPH ISO 13256-1
Water to air, ground-
water (heating mode)
<135 000 Btu/h
(cooling capacity)
50°F entering water 3.7 COPH ISO 13256-1
Brine to air, ground
loop (heating mode)
<135 000 Btu/h
(cooling capacity)
32°F entering fluid 3.2 COPH ISO 13256-1
Water to water, water
loop (heating mode)
<135 000 Btu/h
(cooling capacity)
68°F entering water 3.7 COPH ISO 13256-2
Water to water,
groundwater (heating
mode)
<135 000 Btu/h
(cooling capacity)
50°F entering water 3.1 COPH ISO 13256-2
Brine to water,
ground loop (heating
mode)
<135 000 Btu/h
(cooling capacity)
32°F entering fluid 2.5 COPH ISO 13256-2

For SI units: 1000 British thermal units per hour = 0.293 kW, °C = (°F-32)/1.8 Notes:

1 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. 2 Single-phase, air-cooled heat pumps less than 65 000 Btu/h (19 kW) are regulated by the U.S. Department of Energy Code of Federal Regulations 10 CFR 430. SEER and HSPF values for single-phase products are set by the U.S. Department of Energy.

2022 CALIFORNIA MECHANICAL CODE 409

APPENDIX E

TABLE E 503.7.1(3) WATER-CHILLING PACKAGES MINIMUM EFFICIENCY REQUIREMENTS 1, 2, 5

[ASHRAE 90.1: TABLE 6.8.1-3]

EQUIPMENT TYPE SIZE CATEGORY UNITS PATH A PATH B TEST
PROCEDURE3
Air-cooled chillers <150 tons EER
(Btu/Wh)
≥10.100_FL_ ≥9.700_FL_ AHRI 550/590
Air-cooled chillers <150 tons EER
(Btu/Wh)
≥13.700_IPLV.IP_ ≥15.800_IPLV.IP_ ≥15.800_IPLV.IP_
Air-cooled chillers ≥150 tons ≥150 tons ≥10.100_ FL_ ≥9.700_ FL_ ≥9.700_ FL_
Air-cooled chillers ≥150 tons ≥150 tons ≥14.000_IPLV.IP_ ≥16.100_IPLV.IP_ ≥16.100_IPLV.IP_
Air-cooled without condenser,
electrically operated
All capacities EER
(Btu/Wh)
Air-cooled chillers without condenser must be
rated with matching condensers and comply
with air-cooled chiller efficiency requirements
Air-cooled chillers without condenser must be
rated with matching condensers and comply
with air-cooled chiller efficiency requirements
AHRI 550/590
Water-cooled, electrically oper-
ated positive displacement
<75 tons kW/ton ≤0.750_FL_ ≤0.780_ FL_ AHRI 550/590
Water-cooled, electrically oper-
ated positive displacement
<75 tons kW/ton ≤0.600_IPLV.IP_ ≤0.500_IPLV.IP_ ≤0.500_IPLV.IP_
Water-cooled, electrically oper-
ated positive displacement
≥75 tons and
<150 tons
≥75 tons and
<150 tons
≤0.720_FL_ ≤0.750_FL_ ≤0.750_FL_
Water-cooled, electrically oper-
ated positive displacement
≥75 tons and
<150 tons
≥75 tons and
<150 tons
≤0.560_IPLV.IP_ ≤0.490_IPLV.IP_ ≤0.490_IPLV.IP_
Water-cooled, electrically oper-
ated positive displacement
≥150 tons and
<300 tons
≥150 tons and
<300 tons
≤0.660_ FL_ ≤0.680_FL_ ≤0.680_FL_
Water-cooled, electrically oper-
ated positive displacement
≥150 tons and
<300 tons
≥150 tons and
<300 tons
≤0.540_IPLV.IP_ ≤0.440_IPLV.IP_ ≤0.440_IPLV.IP_
Water-cooled, electrically oper-
ated positive displacement
≥300 tons and
<600 tons
≥300 tons and
<600 tons
≤0.610_ FL_ ≤0.625_FL_ ≤0.625_FL_
Water-cooled, electrically oper-
ated positive displacement
≥300 tons and
<600 tons
≥300 tons and
<600 tons
≤0.520_IPLV.IP_ ≤0.410_IPLV.IP_ ≤0.410_IPLV.IP_
Water-cooled, electrically oper-
ated positive displacement
≥600 tons ≥600 tons ≤0.560_FL_ ≤0.585_FL_ ≤0.585_FL_
Water-cooled, electrically oper-
ated positive displacement
≥600 tons ≥600 tons ≤0.500_IPLV.IP_ ≤0.380_IPLV.IP_ ≤0.380_IPLV.IP_
Water cooled, electrically oper-
ated centrifugal
<150 tons kW/ton ≤0.610 FL ≤0.695_FL_ AHRI 550/590
Water cooled, electrically oper-
ated centrifugal
<150 tons kW/ton ≤0.550_IPLV.IP_ ≤0.440_IPLV.IP_ ≤0.440_IPLV.IP_
Water cooled, electrically oper-
ated centrifugal
≥150 tons and
<300 tons
≥150 tons and
<300 tons
≤0.610_FL_ ≤0.635_FL_ ≤0.635_FL_
Water cooled, electrically oper-
ated centrifugal
≥150 tons and
<300 tons
≥150 tons and
<300 tons
≤0.550_IPLV.IP_ ≤0.400_IPLV.IP_ ≤0.400_IPLV.IP_
Water cooled, electrically oper-
ated centrifugal
≥300 tons and
<400 tons
≥300 tons and
<400 tons
≤0.560_ FL_ ≤0.595_ FL_ ≤0.595_ FL_
Water cooled, electrically oper-
ated centrifugal
≥300 tons and
<400 tons
≥300 tons and
<400 tons
≤0.520_IPLV.IP_ ≤0.390_IPLV.IP_ ≤0.390_IPLV.IP_
Water cooled, electrically oper-
ated centrifugal
≥400 tons and
<600 tons
≥400 tons and
<600 tons
≤0.560_FL_ ≤0.585_FL_ ≤0.585_FL_
Water cooled, electrically oper-
ated centrifugal
≥400 tons and
<600 tons
≥400 tons and
<600 tons
≤0.500_IPLV.IP_ ≤0.380_IPLV.IP_ ≤0.380_IPLV.IP_
Water cooled, electrically oper-
ated centrifugal
≥600 tons ≥600 tons ≤0.560_FL_ ≤0.585_FL_ ≤0.585_FL_
Water cooled, electrically oper-
ated centrifugal
≥600 tons ≥600 tons ≤0.500_IPLV.IP_ ≤0.380_IPLV.IP_ ≤0.380_IPLV.IP_
Air-cooled absorption, single
effect
All capacities COP (W/W) ≥0.600_FL_ NA4 AHRI 560
Water-cooled absorption, single
effect
All capacities COP (W/W) ≥0.700_ FL_ NA4 AHRI 560
Absorption double effect, indi-
rect fired
All capacities COP (W/W) ≥1.000_FL_ NA4 AHRI 560
Absorption double effect, indi-
rect fired
All capacities COP (W/W) ≥1.050_IPLV.IP_ ≥1.050_IPLV.IP_ ≥1.050_IPLV.IP_
Absorption double effect, direct
fired
All capacities COP (W/W) ≥1.000_FL_ NA4 AHRI 560
Absorption double effect, direct
fired
All capacities COP (W/W) ≥1.000_IPLV_ ≥1.000_IPLV_ ≥1.000_IPLV_

For SI units: 1 metric ton = 1000 kg, 1000 British thermal units per hour = 0.293 kW Notes:

1 The requirements for centrifugal chillers shall be adjusted for nonstandard rating conditions per Section E 503.4.1 and are only applicable for the range of conditions listed there. The requirements for air-cooled, water-cooled positive displacement and absorption chillers are at standard rating conditions defined in the reference test procedure. 2 Both the full-load and IPLV.IP requirements must be met or exceeded to comply with this appendix. When there is a Path B, compliance can be with either Path A or Path B for any application. 3 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. 4 NA means the requirements are not applicable for Path B, and only Path A can be used for compliance. 5 FL is the full-load performance requirements, and IPLV.IP is for the part-load performance requirements.

410 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

TABLE E 503.7.1(4) ELECTRICALLY OPERATED PACKAGED TERMINAL AIR CONDITIONERS, PACKAGED TERMINAL HEAT PUMPS, SINGLE-PACKAGE VERTICAL AIR CONDITIONERS, SINGLE-PACKAGE VERTICAL HEAT PUMPS, ROOM AIR CONDITIONERS,

AND ROOM AIR CONDITIONER HEAT PUMPS MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-4]

EQUIPMENT TYPE SIZE CATEGORY (INPUT) SUBCATEGORY OR RATING
CONDITION
MINIMUM EFFICIENCY TEST
PROCEDURE1
PTAC (cooling mode)
standard size
All capacities 95°F db outdoor air 13.8 – (0.300 × Cap/1000)3
(before 1/1/2015)
AHRI 310/ 380
PTAC (cooling mode)
standard size
All capacities 95°F db outdoor air 14.0 – (0.300 × Cap/1000)3
(as of 1/1/2015)
14.0 – (0.300 × Cap/1000)3
(as of 1/1/2015)
PTAC (cooling mode)
nonstandard size1
All capacities 95°F db outdoor air 10.9 – (0.213 × Cap/1000) EER3 AHRI 310/ 380
PTHP (cooling mode)
standard size
All capacities 95°F db outdoor air 14.0 – (0.300 × Cap/1000)3 AHRI 310/ 380
PTHP (cooling mode)
nonstandard size2
All capacities 95°F db outdoor air 10.8 – (0.213 × Cap/1000) EER3 AHRI 310/ 380
PTHP (heating mode)
standard size
All capacities 3.7 – (0.052 × Cap/1000) COPH3 AHRI 310/ 380
PTHP (heating mode)
nonstandard size2
All capacities 2.9 – (0.026 × Cap/1000) COPH3 AHRI 310/ 380
SPVAC (cooling mode) <65,000 Btu/h 95°F db/75°F wb outdoor air 10.0 EER AHRI 390
SPVAC (cooling mode) ≥65 000 Btu/h and
<135 000 Btu/h
≥65 000 Btu/h and
<135 000 Btu/h
10.0 EER 10.0 EER
SPVAC (cooling mode) ≥135 000 Btu/h and
<240 000 Btu/h
≥135 000 Btu/h and
<240 000 Btu/h
10.0 EER 10.0 EER
SPVHP (cooling mode) <65 000 Btu/h 95°F db/75°F wb outdoor air 10.0 EER AHRI 390
SPVHP (cooling mode) ≥65 000 Btu/h and
<135 000 Btu/h
≥65 000 Btu/h and
<135 000 Btu/h
10.0 EER 10.0 EER
SPVHP (cooling mode) ≥135 000 Btu/h and
<240 000 Btu/h
≥135 000 Btu/h and
<240 000 Btu/h
10.0 EER 10.0 EER
SPVHP (heating mode) <65 000 Btu/h 47°F db/43°F wb outdoor air 3.0 COPH AHRI 390
SPVHP (heating mode) ≥65 000 Btu/h and
<135 000 Btu/h
≥65 000 Btu/h and
<135 000 Btu/h
3.0 COPH 3.0 COPH
SPVHP (heating mode) ≥135 000 Btu/h and
<240 000 Btu/h
≥135 000 Btu/h and
<240 000 Btu/h
3.0 COPH 3.0 COPH
Room air conditioners
with louvered sides
<6000 Btu/h 9.7 SEER AHAM RAC-1
Room air conditioners
with louvered sides
≥6000 Btu/h and
<8000 Btu/h
≥6000 Btu/h and
<8000 Btu/h
9.7 SEER 9.7 SEER
Room air conditioners
with louvered sides
≥8000 Btu/h and
<14 000 Btu/h
≥8000 Btu/h and
<14 000 Btu/h
9.8 EER 9.8 EER
Room air conditioners
with louvered sides
≥14 000 Btu/h and
<20 000 Btu/h
≥14 000 Btu/h and
<20 000 Btu/h
9.7 SEER 9.7 SEER
Room air conditioners
with louvered sides
≥20 000 Btu/h ≥20 000 Btu/h 8.5 EER 8.5 EER
SPVAC (cooling
mode), nonweatherized
space constrained
≤30 000 Btu/h 95°F db/75°F wb outdoor air 9.2 EER AHRI 390
SPVAC (cooling
mode), nonweatherized
space constrained
>30 000 Btu/h and
≤36 000 Btu/h
>30 000 Btu/h and
≤36 000 Btu/h
9.0 EER 9.0 EER
SPVHP (cooling mode),
nonweatherized space
constrained
≤30 000 Btu/h 95°F db/75°F wb outdoor air 9.2 EER AHRI 390
SPVHP (cooling mode),
nonweatherized space
constrained
>30 000 Btu/h and
≤36 000 Btu/h
>30 000 Btu/h and
≤36 000 Btu/h
9.0 EER 9.0 EER
SPVHP (heating mode),
nonweatherized space
constrained
≤30 000 Btu/h 47°F db/43°F wb outdoor air 3.0 COPH AHRI 390
SPVHP (heating mode),
nonweatherized space
constrained
>30 000 Btu/h and
≤36 000 Btu/h
>30 000 Btu/h and
≤36 000 Btu/h
3.0 COPH 3.0 COPH

2022 CALIFORNIA MECHANICAL CODE 411

APPENDIX E

TABLE E 503.7.1(4) (continued) ELECTRICALLY OPERATED PACKAGED TERMINAL AIR CONDITIONERS, PACKAGED TERMINAL HEAT PUMPS, SINGLE-PACKAGE VERTICAL AIR CONDITIONERS, SINGLE-PACKAGE VERTICAL HEAT PUMPS, ROOM AIR CONDITIONERS,

AND ROOM AIR CONDITIONER HEAT PUMPS MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-4]

EQUIPMENT TYPE SIZE CATEGORY (INPUT) SUBCATEGORY OR RATING
CONDITION
MINIMUM EFFICIENCY TEST
PROCEDURE1
Room air conditioners
without louvered sides
<8000 Btu/h 9.0 EER AHAM RAC-1
Room air conditioners
without louvered sides
≥8000 Btu/h and
<20 000 Btu/h
8.5 EER 8.5 EER
Room air conditioners
without louvered sides
≥20 000 Btu/h 8.5 EER 8.5 EER
Room air conditioner
heat pumps with lou-
vered sides
<20 000 Btu/h 9.0 EER AHAM RAC-1
Room air conditioner
heat pumps with lou-
vered sides
≥20 000 Btu/h ≥20 000 Btu/h 8.5 EER 8.5 EER
Room air conditioner
heat pumps without lou-
vered sides
<14 000 Btu/h 8.5 EER AHAM RAC-1
Room air conditioner
heat pumps without lou-
vered sides
≥14 000 Btu/h ≥14 000 Btu/h 8.0 EER 8.0 EER
Room air conditioner,
casement only
All capacities 8.7 EER AHAM RAC-1
Room air conditioner,
casement slider
All capacities 9.5 EER AHAM RAC-1

For SI units: 1000 British thermal units per hour = 0.293 kW, °C = (°F-32)/1.8 Notes:

1 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. 2 Nonstandard size units must be factory labeled as follows: “MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY; NOT TO BE INSTALLED IN NEW STANDARD PROJECTS.” Nonstandard size efficiencies apply only to units being installed in existing sleeves having an external wall opening of less than 16 inch (406 mm) high or less than 42 inch (1067 mm) wide and having a cross-sectional area less than 670 square inches (0.432 m 2 ). 3 “Cap” means the rated cooling capacity of the product in Btu/h (kW). If the unit’s capacity is less than 7000 Btu/h (2.05 kW), use 7000 Btu/h (2.05 kW) in the calculation. Where the unit’s capacity is more than 15 000 Btu/h (4.4 kW), use 15 000 Btu/h (4.4 kW) in the calculation.

TABLE E 503.7.1(5) WARM-AIR FURNACES AND COMBINATION WARM-AIR FURNACES/AIR-CONDITIONING UNITS,

WARM-AIR DUCT FURNACES, AND UNIT HEATERS MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-5]

EQUIPMENT TYPE SIZE CATEGORY
(INPUT)
SUBCATEGORY OR
RATING CONDITION
MINIMUM
EFFICIENCY
TEST PROCEDURE1
Warm-air furnace, gas fired <225 000 Btu/h Maximum capacity3 78%_AFUE_or
80%Et
2, 4
DOE 10 CFR Part 430 or Section 2.39,
Thermal Efficiency, CSA Z21.47
Warm-air furnace, gas fired ≥225 000 Btu/h ≥225 000 Btu/h 80%Et
4
Section 2.39, Thermal Efficiency, CSA Z21.47
Warm-air furnace, oil fired <225 000 Btu/h Maximum capacity3 78%_AFUE_or
80%Et
2, 4
DOE 10 CFR Part 430 or Section 42,
Combustion, UL 727
Warm-air furnace, oil fired ≥225 000 Btu/h ≥225 000 Btu/h 81%Et
4
Section 42, Combustion, UL 727
Warm-air duct furnaces, gas fired All capacities Maximum capacity3 80%Ec
5
Section 2.10, Efficiency, CSA Z83.8
Warm-air unit heaters, gas fired All capacities Maximum capacity3 80%Ec
5, 6
Section 2.10, Efficiency, CSA Z83.8
Warm-air unit heaters, oil fired All capacities Maximum capacity3 80%Ec
5, 6
Section 40, Combustion, UL 731

For SI units: 1000 British thermal units per hour = 0.293 kW Notes: 1 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. 2 Combination units not covered by the U.S. Department of Energy Code of Federal Regulations 10 CFR 430 [three-phase power or cooling capacity greater than or equal to 65 000 Btu/h (19 kW)] may comply with either rating. 3 Compliance of multiple firing rate units shall be at the maximum firing rate. 4 Et = thermal efficiency. Units must also include an interrupted or intermittent ignition device (IID), have jacket losses not exceeding 0.75 percent of the input rating, and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space. 5 Ec = combustion efficiency (100 percent less flue losses). See test procedure for detailed discussion. 6 As of August 8, 2008, according to the Energy Policy Act of 2005, units must also include an interrupted or intermittent ignition device (IID) and have either power venting or an automatic flue damper.

412 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

TABLE E 503.7.1(6) GAS- AND OIL-FIRED BOILERS MINIMUM EFFICIENCY REQUIREMENTS 2, 3

[ASHRAE 90.1: TABLE 6.8.1-6]

EQUIPMENT TYPE1 SUBCATEGORY OR
RATING CONDITION
SIZE CATEGORY
(INPUT)
MINIMUM EFFICIENCY EFFICIENCY AS OF
3/2/2020
TEST PROCEDURE
Boilers, hot water Gas fired <300 000 Btu/h6 82%AFUE 82%AFUE 10 CFR Part 430
Boilers, hot water Gas fired ≥300 000 Btu/h and
≤2 500 000 Btu/h4
80%Et 80%Et 10 CFR Part 431
Boilers, hot water Gas fired >2 500 000 Btu/h1 82%Ec 82%Ec 82%Ec
Boilers, hot water Oil fired5 <300 000 Btu/h7 84%AFUE 84%AFUE 10 CFR Part 430
Boilers, hot water Oil fired5 ≥300 000 Btu/h and
≤2 500 000 Btu/h4
82%Et 82%Et 10 CFR Part 431
Boilers, hot water Oil fired5 >2 500 000 Btu/h1 84%Ec 84%Ec 84%Ec
Boilers, steam Gas fired <300 000 Btu/h6 80%AFUE 80%AFUE 10 CFR Part 430
Boilers, steam Gas fired— all,
except natural draft
≥300 000 Btu/h and
≤2 500 000 Btu/h4
79%Et 79%Et 10 CFR Part 431
Boilers, steam Gas fired— all,
except natural draft
>2 500 000 Btu/h1 79%Et 79%Et 79%Et
Boilers, steam Gas fired— natural
draft
≥300 000 Btu/h and
≤2 500 000 Btu/h4
77%Et 79%Et 79%Et
Boilers, steam Gas fired— natural
draft
>2 500 000 Btu/h1 77%Et 79%Et 79%Et
Boilers, steam Oil fired5 <300 000 Btu/h 82%AFUE 82%AFUE 10 CFR Part 430
Boilers, steam Oil fired5 ≥300 000 Btu/h and
≤2 500 000 Btu/h4
81%Et 81%Et 10 CFR Part 431
Boilers, steam Oil fired5 >2 500 000 Btu/h1 81%Et 81%Et 81%Et

For SI units: 1000 British thermal units per hour = 0.293 kW Notes:

1 These requirements apply to boilers with rated input of 8 000 000 Btu/h (2343 kW) or less that are not packaged boilers and to all packaged boilers. Minimum efficiency requirements for boilers cover all capacities of packaged boilers. 2 Ec = combustion efficiency (100 percent less flue losses). See reference document for detailed information. 3 Et = thermal efficiency. See reference document for detailed information. 4 Maximum capacity—minimum and maximum ratings as provided for and allowed by the unit’s controls. 5 Includes oil-fired (residual). 6 Boilers shall not be equipped with a constant burning pilot light. 7 A boiler not equipped with a tankless domestic water-heating coil shall be equipped with an automatic means for adjusting the temperature of the water such that an incremental change in inferred heat load produces a corresponding incremental change in the temperature of the water supplied.

2022 CALIFORNIA MECHANICAL CODE 413

APPENDIX E

TABLE E 503.7.1(7) PERFORMANCE REQUIREMENTS FOR HEAT REJECTION EQUIPMENT

MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-7]

EQUIPMENT TYPE TOTAL SYSTEM HEAT-
REJECTION CAPACITY
AT RATED CONDITIONS
SUBCATEGORY OR
RATING CONDITION8
PERFORMANCE
REQUIRED1,2,3,6,7
TEST PROCEDURE4,5
Propeller or axial fan open-
circuit cooling towers
All 95°F entering water
85°F leaving water
75°F entering wb
≥40.2 gpm/hp CTI ATC-105 and
CTI STD-201 RS
Centrifugal fan open-circuit
cooling towers
All 95°F entering water
85°F leaving water
75°F entering wb
≥20.0 gpm/hp CTI ATC-105 and
CTI STD-201 RS
Propeller or axial fan closed-
circuit cooling towers
All 102°F entering water
90°F leaving water
75°F entering wb
≥16.1 gpm/hp CTI ATC-105S and
CTI STD-201 RS
Centrifugal closed- circuit
cooling towers
All 102°F entering water
90°F leaving water
75°F entering wb
≥7.0 gpm/hp CTI ATC-105S and
CTI STD-201 RS
Propeller or axial fan evapo-
rative condensers
All R-507A test fluid
165°F entering gas temperature
105°F condensing temperature
75°F entering wb
≥157 000 Btu/h·hp CTI ATC-106
Propeller or axial fan evapo-
rative condensers
All Ammonia test fluid
140°F entering gas temperature
96.3°F condensing temperature
75°F entering wb
≥134 000 Btu/h·hp CTI ATC-106
Centrifugal fan evaporative
condensers
All R-507A test fluid
165°F entering gas temperature
105°F condensing temperature
75°F entering wb
≥135 000 Btu/h·hp CTI ATC-106
Centrifugal fan evaporative
condensers
All Ammonia test fluid
140°F entering gas temperature
96.3°F condensing temperature
75°F entering wb
≥110 000 Btu/h·hp CTI ATC-106
Air cooled condensers All 125°F condensing temperature
190°F entering gas temperature
15°F subcooling
95°F entering db
≥176 000 Btu/h·hp AHRI 460

For SI units: °C = (°F-32)/1.8, 1 gallon per minute per horsepower = 0.085 [(L/s)/kW], 1000 British thermal units per hour = 0.293 kW, 1 horsepower = 0.746 kW Notes:

1 For purposes of this table, open-circuit cooling tower performance is defined as the water flow rating of the tower at the thermal rating condition listed in Table E 503.7.1(7) divided by the fan motor nameplate power. 2 For purposes of this table, closed-circuit cooling tower performance is defined as the process water flow rating of the tower at the thermal rating condition listed in Table E 503.7.1(7) divided by the sum of the fan motor nameplate power and the integral spray pump motor nameplate power. 3 For purposes of this table, air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the fan motor nameplate power. 4 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure. 5 The efficiencies and test procedures for both open- and closed-circuit cooling towers are not applicable to hybrid cooling towers that contain a combination of separate wet and dry heat exchange sections. The certification requirements do not apply to field-erected cooling towers. 6 All cooling towers shall comply with the minimum efficiency listed in the table for that specific type of tower with the capacity effect of any project-specific accessories and/or options included in the capacity of the cooling tower. 7 For purposes of this table, evaporative condenser performance is defined as the heat rejected at the specified rating condition in the table, divided by the sum of the fan motor nameplate power and the integral spray pump nameplate power. 8 Requirements for evaporative condensers are listed with ammonia (R-717) and R-507A as test fluids in the table. Evaporative condensers intended for use with halocarbon refrigerants other than R-507A must meet the minimum efficiency requirements listed above with R-507A as the test fluid.

414 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

TABLE E 503.7.1(8) HEAT TRANSFER EQUIPMENT MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-8]

EQUIPMENT TYPE SUBCATEGORY MINIMUM EFFICIENCY1 TEST PROCEDURE2
Liquid-to-liquid heat exchangers Plate type NR AHRI 400

Notes:

1 NR = No Requirement 2 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.

TABLE E 503.7.1(9) ELECTRICALLY OPERATED VARIABLE-REFRIGERANT-FLOW AIR CONDITIONERS MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-9]

EQUIPMENT TYPE SIZE CATEGORY HEATING SECTION
TYPE
SUBCATEGORY OR RATING
CONDITION
MINIMUM EFFICIENCY TEST PROCEDURE
VRF air conditioners,
air cooled
<65 000 Btu/h All VRF multisplit system 13.0 SEER AHRI 1230
VRF air conditioners,
air cooled
≥65 000 Btu/h and
<135 000 Btu/h
Electric resistance
(or none)
VRF multisplit system 11.2 EER
13.1 IEER
(before 1/1/2017)
15.5 IEER
(as of 1/1/2017)
11.2 EER
13.1 IEER
(before 1/1/2017)
15.5 IEER
(as of 1/1/2017)
VRF air conditioners,
air cooled
≥135 000 Btu/h and
<240 000 Btu/h
Electric resistance
(or none)
VRF multisplit system 11.0 EER
12.9 IEER
(before 1/1/2017)
14.9 IEER
(as of 1/1/2017)
11.0 EER
12.9 IEER
(before 1/1/2017)
14.9 IEER
(as of 1/1/2017)
VRF air conditioners,
air cooled
≥240 000 Btu/h Electric resistance
(or none)
VRF multisplit system 10.0 EER
11.6 IEER
(before 1/1/2017)
13.9 IEER
(as of 1/1/2017)
10.0 EER
11.6 IEER
(before 1/1/2017)
13.9 IEER
(as of 1/1/2017)

For SI units: 1000 British thermal units per hour = 0.293 kW

2022 CALIFORNIA MECHANICAL CODE 415

APPENDIX E

TABLE E 503.7.1(10) ELECTRICALLY OPERATED VARIABLE-REFRIGERANT-FLOW AND APPLIED

HEAT PUMPS MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-10]

EQUIPMENT TYPE SIZE CATEGORY HEATING SECTION
TYPE
SUBCATEGORY OR
RATING CONDITION
MINIMUM EFFICIENCY TEST PROCEDURE
VRF air cooled
(cooling mode)
<65 000 Btu/h All VRF multisplit system 13.0 SEER AHRI 1230
VRF air cooled
(cooling mode)
≥65 000 Btu/h and
<135 000 Btu/h
Electric resist-
ance (or none)
Electric resist-
ance (or none)
11.0 EER
12.9 IEER
(before 1/1/2017)
14.6 IEER
(as of 1/1/2017)
11.0 EER
12.9 IEER
(before 1/1/2017)
14.6 IEER
(as of 1/1/2017)
VRF air cooled
(cooling mode)
≥65 000 Btu/h and
<135 000 Btu/h
Electric resist-
ance (or none)
VRF multisplit system with heat
recovery
10.8 EER
12.7 IEER
(before 1/1/2017)
14.4 IEER
(as of 1/1/2017)
10.8 EER
12.7 IEER
(before 1/1/2017)
14.4 IEER
(as of 1/1/2017)
VRF air cooled
(cooling mode)
≥135 000 Btu/h and
<240 000 Btu/h
≥135 000 Btu/h and
<240 000 Btu/h
VRF multisplit system 10.6 EER
12.3 IEER
(before 1/1/2017)
13.9 IEER
(as of 1/1/2017)
10.6 EER
12.3 IEER
(before 1/1/2017)
13.9 IEER
(as of 1/1/2017)
VRF air cooled
(cooling mode)
≥135 000 Btu/h and
<240 000 Btu/h
≥135 000 Btu/h and
<240 000 Btu/h
VRF multisplit system with heat
recovery
10.4 EER
12.1 IEER
(before 1/1/2017)
13.7 IEER
(as of 1/1/2017)
10.4 EER
12.1 IEER
(before 1/1/2017)
13.7 IEER
(as of 1/1/2017)
VRF air cooled
(cooling mode)
≥240 000 Btu/h ≥240 000 Btu/h VRF multisplit system 9.5 EER
11.0 IEER
(before 1/1/2017)
12.7 IEER
(as of 1/1/2017)
9.5 EER
11.0 IEER
(before 1/1/2017)
12.7 IEER
(as of 1/1/2017)
VRF air cooled
(cooling mode)
≥240 000 Btu/h ≥240 000 Btu/h VRF multisplit system with heat
recovery
9.3 EER
10.8 IEER
(before 1/1/2017)
12.5 IEER
(as of 1/1/2017)
9.3 EER
10.8 IEER
(before 1/1/2017)
12.5 IEER
(as of 1/1/2017)
VRF water
source
(cooling mode)
<65 000 Btu/h All VRF multisplit systems 86°F
entering water
12.0 EER
16.0 IEER
(as of 1/1/2018)
AHRI 1230
VRF water
source
(cooling mode)
<65 000 Btu/h All VRF multisplit systems with heat
recovery 86°F entering water
11.8 EER
15.8 IEER
(as of 1/1/2018)
11.8 EER
15.8 IEER
(as of 1/1/2018)
VRF water
source
(cooling mode)
≥65 000 Btu/h and
<135 000 Btu/h
≥65 000 Btu/h and
<135 000 Btu/h
VRF multisplit system 86°F
entering water
12.0 EER
16.0 IEER
(as of 1/1/2018)
12.0 EER
16.0 IEER
(as of 1/1/2018)
VRF water
source
(cooling mode)
≥65 000 Btu/h and
<135 000 Btu/h
≥65 000 Btu/h and
<135 000 Btu/h
VRF multisplit system with heat
recovery 86°F entering water
11.8 EER
15.8 IEER
(as of 1/1/2018)
11.8 EER
15.8 IEER
(as of 1/1/2018)
VRF water
source
(cooling mode)
≥135 000 Btu/h and
<240 000 Btu/h
≥135 000 Btu/h and
<240 000 Btu/h
VRF multisplit system 86°F
entering water
10.0 EER
14.0 IEER
(as of 1/1/2018)
10.0 EER
14.0 IEER
(as of 1/1/2018)
VRF water
source
(cooling mode)
≥135 000 Btu/h and
<240 000 Btu/h
≥135 000 Btu/h and
<240 000 Btu/h
VRF multisplit system with heat
recovery 86°F entering water
9.8 EER
13.8 IEER
(as of 1/1/2018)
9.8 EER
13.8 IEER
(as of 1/1/2018)
VRF water
source
(cooling mode)
≥240 000 Btu/h ≥240 000 Btu/h VRF multisplit system 86°F
entering water
10.0 EER
(before 1/1/2018)
12.0 IEER
(as of 1/1/2018)
10.0 EER
(before 1/1/2018)
12.0 IEER
(as of 1/1/2018)
VRF water
source
(cooling mode)
≥240 000 Btu/h ≥240 000 Btu/h VRF multisplit system with heat
recovery 86°F entering water
9.8 EER
(before 1/1/2018)
11.8 IEER
(as of 1/1/2018)
9.8 EER
(before 1/1/2018)
11.8 IEER
(as of 1/1/2018)

416 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

TABLE E 503.7.1(10) (continued) ELECTRICALLY OPERATED VARIABLE-REFRIGERANT-FLOW AND APPLIED

HEAT PUMPS MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-10]

EQUIPMENT TYPE SIZE CATEGORY HEATING SECTION
TYPE
SUBCATEGORY OR
RATING CONDITION
MINIMUM EFFICIENCY TEST PROCEDURE
VRF groundwa-
ter source
(cooling mode)
<135 000 Btu/h All VRF multisplit system with heat
recovery 59°F entering water
16.2 EER AHRI 1230
VRF groundwa-
ter source
(cooling mode)
<135 000 Btu/h All VRF multisplit system with heat
recovery 59°F entering water
16.0 EER 16.0 EER
VRF groundwa-
ter source
(cooling mode)
≥135 000 Btu/h ≥135 000 Btu/h VRF multisplit system with heat
recovery 59°F entering water
13.8 EER 13.8 EER
VRF groundwa-
ter source
(cooling mode)
≥135 000 Btu/h ≥135 000 Btu/h VRF multisplit system with heat
recovery 59°F entering water
13.6 EER 13.6 EER
VRF ground
source
(cooling mode)
<135 000 Btu/h All VRF multisplit system 77°F enter-
ing water
13.4 EER AHRI 1230
VRF ground
source
(cooling mode)
<135 000 Btu/h All VRF multisplit system with heat
recovery 77°F entering water
13.2 EER 13.2 EER
VRF ground
source
(cooling mode)
≥135 000 Btu/h ≥135 000 Btu/h VRF multisplit system 77°F enter-
ing water
11.0 EER 11.0 EER
VRF ground
source
(cooling mode)
≥135 000 Btu/h ≥135 000 Btu/h VRF multisplit system with heat
recovery 77°F entering water
10.8 EER 10.8 EER
VRF Air cooled
(heating mode)
<65 000 Btu/h
(cooling capacity)
VRF Multi-split system 7.7 HSPF AHRI 1230
VRF Air cooled
(heating mode)
≥65 000 Btu/h and
<135 000 Btu/h
(cooling capacity)
VRF Multi-split system 47°F
db/43°F wb outdoor air
3.3 COPH 3.3 COPH
VRF Air cooled
(heating mode)
≥65 000 Btu/h and
<135 000 Btu/h
(cooling capacity)
17°F db/15°F wb outdoor air 2.25 COPH 2.25 COPH
VRF Air cooled
(heating mode)
≥135 000 Btu/h
(cooling capacity)
VRF Multi-split system 47°F
db/43°F wb outdoor air

3.2 COPH

3.2 COPH
VRF Air cooled
(heating mode)
≥135 000 Btu/h
(cooling capacity)
17°F db/15°F wb outdoor air 2.05 COPH 2.05 COPH
VRF Water
source
(heating mode)
<65 000 Btu/h
(cooling capacity)
VRF multisplit system
68°F entering water
4.2 COPH
(before 1/1/2018)
4.3 COPH
(as of 1/1/2018)
AHRI 1230
VRF Water
source
(heating mode)
≥65 000 Btu/h and
<135 000 Btu/h
(cooling capacity)
VRF multisplit system
68°F entering water
4.2 COPH
(before 1/1/2018)
4.3 COPH
(as of 1/1/2018)
4.2 COPH
(before 1/1/2018)
4.3 COPH
(as of 1/1/2018)
VRF Water
source
(heating mode)
≥135 000 Btu/h and
<240 000 Btu/h
(cooling capacity)
VRF multisplit system
68°F entering water
3.9 COPH
(before 1/1/2018)
4.0 COPH
(as of 1/1/2018)
3.9 COPH
(before 1/1/2018)
4.0 COPH
(as of 1/1/2018)
VRF Water
source
(heating mode)
≥240 000 Btu/h
(cooling capacity)
VRF multisplit system
68°F entering water
3.9 COPH 3.9 COPH
VRF Groundwa-
ter source
(heating mode)
<135 000 Btu/h
(cooling capacity)
VRF Multi-split system 50°F
entering water
3.6 COPH AHRI 1230
VRF Groundwa-
ter source
(heating mode)
≥135 000 Btu/h
(cooling capacity)
VRF Multi-split system 50°F
entering water
3.3 COPH 3.3 COPH
VRF Ground
source
(heating mode)
<135 000 Btu/h
(cooling capacity)
VRF Multi-split system 32°F
entering water
3.1 COPH AHRI 1230
VRF Ground
source
(heating mode)
≥135 000 Btu/h
(cooling capacity)
VRF Multi-split system 32°F
entering water
2.8 COPH 2.8 COPH

For SI units: 1000 British thermal units per hour = 0.293 kW, °C=(°F-32)/1.8

2022 CALIFORNIA MECHANICAL CODE 417

APPENDIX E

TABLE E 503.7.1(11) AIR CONDITIONERS AND CONDENSING UNITS SERVING COMPUTER ROOMS

MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-11]

EQUIPMENT
TYPE
NET SENSIBLE COOL-
ING CAPACITY
STANDARD MODEL MINIMUM NET SENSIBLE COPc TEST PROCEDURE
EQUIPMENT
TYPE
NET SENSIBLE COOL-
ING CAPACITY
STANDARD MODEL RETURN AIR DRY-BULB TEMPERATURE/
DEW-POINT TEMPERATURE
RETURN AIR DRY-BULB TEMPERATURE/
DEW-POINT TEMPERATURE
RETURN AIR DRY-BULB TEMPERATURE/
DEW-POINT TEMPERATURE
RETURN AIR DRY-BULB TEMPERATURE/
DEW-POINT TEMPERATURE
EQUIPMENT
TYPE
NET SENSIBLE COOL-
ING CAPACITY
STANDARD MODEL CLASS 1 CLASS 2 CLASS 3 CLASS 3
EQUIPMENT
TYPE
NET SENSIBLE COOL-
ING CAPACITY
STANDARD MODEL 75°F/52°F 85°F/52°F 95°F/52°F 95°F/52°F
Air cooled <65 000 Btu/h Downflow unit 2.30 AHRI 1360
Air cooled <65 000 Btu/h Upflow unit**─**ducted 2.10
Air cooled <65 000 Btu/h Upflow unit**─**nonducted 2.09
Air cooled <65 000 Btu/h Horizontal-flow unit 2.45 2.45
Air cooled ≥65 000 Btu/h and
<240 000 Btu/h
Downflow unit 2.20
Air cooled ≥65 000 Btu/h and
<240 000 Btu/h
Upflow unit**─**ducted 2.05
Air cooled ≥65 000 Btu/h and
<240 000 Btu/h
Upflow unit**─**nonducted 1.99
Air cooled ≥65 000 Btu/h and
<240 000 Btu/h
Horizontal-flow unit 2.35 2.35
Air cooled ≥240 000 Btu/h Downflow unit 2.00
Air cooled ≥240 000 Btu/h Upflow unit**─**ducted 1.85
Air cooled ≥240 000 Btu/h Upflow unit**─**nonducted 1.79
Air cooled ≥240 000 Btu/h Horizontal-flow unit 2.15 2.15
Water cooled <65 000 Btu/h Downflow unit 2.50 AHRI 1360
Water cooled <65 000 Btu/h Upflow unit**─**ducted 2.30
Water cooled <65 000 Btu/h Upflow unit**─**nonducted 2.25
Water cooled <65 000 Btu/h Horizontal-flow unit 2.70 2.70
Water cooled ≥65 000 Btu/h and
<240 000 Btu/h
Downflow unit 2.40
Water cooled ≥65 000 Btu/h and
<240 000 Btu/h
Upflow unit**─**ducted 2.20
Water cooled ≥65 000 Btu/h and
<240 000 Btu/h
Upflow unit**─**nonducted 2.15
Water cooled ≥65 000 Btu/h and
<240 000 Btu/h
Horizontal-flow unit 2.60 2.60
Water cooled ≥240 000 Btu/h Downflow unit 2.25
Water cooled ≥240 000 Btu/h Upflow unit**─**ducted 2.10
Water cooled ≥240 000 Btu/h Upflow unit**─**nonducted 2.05
Water cooled ≥240 000 Btu/h Horizontal-flow unit 2.45 2.45
Water cooled with
fluid economizer
<65 000 Btu/h Downflow unit 2.45 AHRI 1360
Water cooled with
fluid economizer
<65 000 Btu/h Upflow unit**─**ducted 2.25
Water cooled with
fluid economizer
<65 000 Btu/h Upflow unit**─**nonducted 2.20
Water cooled with
fluid economizer
<65 000 Btu/h Horizontal-flow unit 2.60 2.60
Water cooled with
fluid economizer
≥65 000 Btu/h and
<240 000 Btu/h
Downflow unit 2.35
Water cooled with
fluid economizer
≥65 000 Btu/h and
<240 000 Btu/h
Upflow unit**─**ducted 2.15
Water cooled with
fluid economizer
≥65 000 Btu/h and
<240 000 Btu/h
Upflow unit**─**nonducted 2.10
Water cooled with
fluid economizer
≥65 000 Btu/h and
<240 000 Btu/h
Horizontal-flow unit 2.55 2.55
Water cooled with
fluid economizer
≥240 000 Btu/h Downflow unit 2.20
Water cooled with
fluid economizer
≥240 000 Btu/h Upflow unit**─**ducted 2.05
Water cooled with
fluid economizer
≥240 000 Btu/h Upflow unit**─**nonducted 2.00
Water cooled with
fluid economizer
≥240 000 Btu/h Horizontal-flow unit 2.40 2.40

418 2022 CALIFORNIA MECHANICAL CODE

TABLE E 503.7.1(11) (continued) AIR CONDITIONERS AND CONDENSING UNITS SERVING COMPUTER ROOMS

MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-11]

APPENDIX E

EQUIPMENT TYPE NET SENSIBLE COOL-
ING CAPACITY
STANDARD MODEL MINIMUM NET SENSIBLE COPc TEST PROCEDURE
EQUIPMENT TYPE NET SENSIBLE COOL-
ING CAPACITY
STANDARD MODEL RETURN AIR DRY-BULB TEMPERATURE/
DEW-POINT TEMPERATURE
RETURN AIR DRY-BULB TEMPERATURE/
DEW-POINT TEMPERATURE
RETURN AIR DRY-BULB TEMPERATURE/
DEW-POINT TEMPERATURE
RETURN AIR DRY-BULB TEMPERATURE/
DEW-POINT TEMPERATURE
EQUIPMENT TYPE NET SENSIBLE COOL-
ING CAPACITY
STANDARD MODEL CLASS 1 CLASS 2 CLASS 3 CLASS 3
EQUIPMENT TYPE NET SENSIBLE COOL-
ING CAPACITY
STANDARD MODEL 75°F/52°F 85°F/52°F 95°F/52°F 95°F/52°F
Glycol cooled <65 000 Btu/h Downflow unit 2.30 AHRI 1360
Glycol cooled <65 000 Btu/h Upflow unit**─**ducted 2.10
Glycol cooled <65 000 Btu/h Upflow unit**─**nonducted 2.00
Glycol cooled <65 000 Btu/h Horizontal-flow unit 2.40 2.40
Glycol cooled ≥65 000 Btu/h and
<240 000 Btu/h
Downflow unit 2.05
Glycol cooled ≥65 000 Btu/h and
<240 000 Btu/h
Upflow unit**─**ducted 1.85
Glycol cooled ≥65 000 Btu/h and
<240 000 Btu/h
Upflow unit**─**nonducted 1.85
Glycol cooled ≥65 000 Btu/h and
<240 000 Btu/h
Horizontal-flow unit 2.15 2.15
Glycol cooled ≥240 000 Btu/h Downflow unit 1.95
Glycol cooled ≥240 000 Btu/h Upflow unit**─**ducted 1.80
Glycol cooled ≥240 000 Btu/h Upflow unit**─**nonducted 1.75
Glycol cooled ≥240 000 Btu/h Horizontal-flow unit 2.10 2.10
Glycol cooled with
fluid economizer
<65 000 Btu/h Downflow unit 2.25 AHRI 1360
Glycol cooled with
fluid economizer
<65 000 Btu/h Upflow unit**─**ducted 2.10
Glycol cooled with
fluid economizer
<65 000 Btu/h Upflow unit**─**nonducted 2.00
Glycol cooled with
fluid economizer
<65 000 Btu/h Horizontal-flow unit 2.35 2.35
Glycol cooled with
fluid economizer
≥65 000 Btu/h and
<240 000 Btu/h
Downflow unit 1.95
Glycol cooled with
fluid economizer
≥65 000 Btu/h and
<240 000 Btu/h
Upflow unit**─**ducted 1.80
Glycol cooled with
fluid economizer
≥65 000 Btu/h and
<240 000 Btu/h
Upflow unit**─**nonducted 1.75
Glycol cooled with
fluid economizer
≥65 000 Btu/h and
<240 000 Btu/h
Horizontal-flow unit 2.10 2.10
Glycol cooled with
fluid economizer
≥240 000 Btu/h Downflow unit 1.90
Glycol cooled with
fluid economizer
≥240 000 Btu/h Upflow unit**─**ducted 1.80
Glycol cooled with
fluid economizer
≥240 000 Btu/h Upflow unit**─**nonducted 1.70
Glycol cooled with
fluid economizer
≥240 000 Btu/h Horizontal-flow unit 2.10 2.10

For SI units: 1000 British thermal units per hour = 0.293 kW, °C=(°F-32)/1.8

TABLE E 503.7.1(12) COMMERCIAL REFRIGERATOR AND FREEZERS MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-12]

EQUIPMENT TYPE APPLICATION ENERGY USE LIMITS, KWH/DAY* TEST PROCEDURE
Refrigerator with solid doors Holding temperature 0.10 ×_V _+ 2.04 AHRI 1200
Refrigerator with transparent doors Holding temperature 0.12 ×_V _+ 3.34 AHRI 1200
Freezers with solid doors Holding temperature 0.40 ×_V _+ 1.38 AHRI 1200
Freezers with transparent doors Holding temperature 0.75 ×_V _+ 4.10 AHRI 1200
Refrigerators/freezers with solid doors Holding temperature the greater of 0.12 ×_V _+ 3.34 or 0.70 AHRI 1200
Commercial refrigerators Pulldown 0.126 ×_V _+ 3.51 AHRI 1200

For SI units: 1000 British thermal units per hour per day = 0.293 kW/day

  • V = the chiller or frozen compartment volume (ft 3 ) as defined in Association of Home Appliance Manufacturers.

2022 CALIFORNIA MECHANICAL CODE 419

APPENDIX E

TABLE E 503.7.1(13) COMMERCIAL REFRIGERATION MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-13]

EQUIPMENT TYPE EQUIPMENT TYPE EQUIPMENT TYPE EQUIPMENT TYPE ENERGY USE
**LIMITS2,3 **
KWH/DAY
TEST
PROCEDURE
EQUIPMENT CLASS1 FAMILY CODE OPERATING MODE RATING TEMPERATURE RATING TEMPERATURE RATING TEMPERATURE
VOP.RC.M Vertical open Remote condensing Medium temperature 0.82 ×TDA + 4.07 AHRI 1200
SVO.RC.M Semivertical open Remote condensing Medium temperature 0.83 ×TDA + 3.18 AHRI 1200
HZO.RC.M Horizontal open Remote condensing Medium temperature 0.35 ×TDA + 2.88 AHRI 1200
VOP.RC.L Vertical open Remote condensing Low temperature 2.27 ×TDA + 6.85 AHRI 1200
HZO.RC.L Horizontal open Remote condensing Low temperature 0.57 ×TDA + 6.88 AHRI 1200
VCT.RC.M Vertical transparent door Remote condensing Medium temperature 0.22 ×TDA + 1.95 AHRI 1200
VCT.RC.L Vertical transparent door Remote condensing Low temperature 0.56 ×TDA + 2.61 AHRI 1200
SOC.RC.M Service over counter Remote condensing Medium temperature 0.51 ×TDA + 0.11 AHRI 1200
VOP.SC.M Vertical open Self contained Medium temperature 1.74 ×TDA+ 4.71 AHRI 1200
SVO.SC.M Semivertical open Self contained Medium temperature 1.73 ×TDA + 4.59 AHRI 1200
HZO.SC.M Horizontal open Self contained Medium temperature 0.77 ×TDA + 5.55 AHRI 1200
HZO.SC.L Horizontal open Self contained Low temperature 1.92 ×TDA + 7.08 AHRI 1200
VCT.SC.I Vertical transparent door Self contained Ice cream 0.67 ×TDA + 3.29 AHRI 1200
VCS.SC.I Vertical solid door Self contained Ice cream 0.38 ×_V _+ 0.88 AHRI 1200
HCT.SC.I Horizontal transparent door Self contained Ice cream 0.56 ×TDA + 0.43 AHRI 1200
SVO.RC.L Semivertical open Remote condensing Low temperature 2.27 ×TDA + 6.85 AHRI 1200
VOP.RC.I Vertical open Remote condensing Ice cream 2.89 ×TDA + 8.7 AHRI 1200
SVO.RC.I Semivertical open Remote condensing Ice cream 2.89 ×TDA + 8.7 AHRI 1200
HZO.RC.I Horizontal open Remote condensing Ice cream 0.72 ×TDA + 8.74 AHRI 1200
VCT.RC.I Vertical transparent door Remote condensing Ice cream 0.66 ×TDA + 3.05 AHRI 1200
HCT.RC.M Horizontal transparent door Remote condensing Medium temperature 0.16 ×TDA + 0.13 AHRI 1200
HCT.RC.L Horizontal transparent door Remote condensing Low temperature 0.34 ×TDA + 0.26 AHRI 1200
HCT.RC.I Horizontal transparent door Remote condensing Ice cream 0.4 ×TDA + 0.31 AHRI 1200
VCS.RC.M Vertical solid door Remote condensing Medium temperature 0.11 ×_V _+ 0.26 AHRI 1200
VCS.RC.L Vertical solid door Remote condensing Low temperature 0.23 ×_V _+ 0.54 AHRI 1200
VCS.RC.I Vertical solid door Remote condensing Ice cream 0.27 ×_V _+ 0.63 AHRI 1200
HCS.RC.M Horizontal solid door Remote condensing Medium temperature 0.11 ×_V _+ 0.26 AHRI 1200
HCS.RC.L Horizontal solid door Remote condensing Low temperature 0.23 ×_V _+ 0.54 AHRI 1200
HCS.RC.I Horizontal solid door Remote condensing Ice cream 0.27 ×_V _+ 0.63 AHRI 1200
HCS.RC.I Horizontal solid door Remote condensing Ice cream 0.27 ×_V _+ 0.63 AHRI 1200
SOC.RC.L Service over counter Remote condensing Low temperature 1.08 ×TDA + 0.22 AHRI 1200
SOC.RC.I Service over counter Remote condensing Ice cream 1.26 ×TDA + 0.26 AHRI 1200
VOP.SC.L Vertical open Self contained Low temperature 4.37 ×TDA + 11.82 AHRI 1200
VOP.SC.I Vertical open Self contained Ice cream 5.55 ×TDA + 15.02 AHRI 1200
SVO.SC.L Semivertical open Self contained Low temperature 4.34 ×TDA + 11.51 AHRI 1200
SVO.SC.I Semivertical open Self contained Ice cream 5.52 ×TDA + 14.63 AHRI 1200
HZO.SC.I Horizontal open Self contained Ice cream 2.44 ×TDA + 9.0 AHRI 1200
SOC.SC.I Service over counter Self contained Ice cream 1.76 ×TDA+ 0.36 AHRI 1200
HCS.SC.I Horizontal solid door Self contained Ice cream 0.38 ×_V _+ 0.88 AHRI 1200

For SI units: 1000 British thermal units per hour per day = 0.293 kW/day, °C = (°F-32)/1.8 Notes: 1 Equipment class designations consist of a combination [in sequential order separated by periods (AAA).(BB).(C)] of the following: (a) (AAA)—An equipment family code (VOP = vertical open, SVO = semivertical open, HZO = horizontal open, VCT = vertical transparent doors,

VCS = vertical solid doors, HCT = horizontal transparent doors, HCS = horizontal solid doors, and SOC = service over counter). (b) (BB)—An operating mode code (RC = remote condensing and SC = self contained). (c) (C)—A rating temperature code (M = medium temperature [38°F], L = low temperature [0°F], or I = ice cream temperature [15°F]). For example,

“VOP.RC.M” refers to the “vertical open, remote condensing, medium temperature” equipment class. 2 V is the volume of the case (ft) as measured in accordance with AHRI 1200. 3 TDA is the total display area of the case (ft) as measured in accordance with AHRI 1200.

420 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

TABLE E 503.7.1(14) VAPOR COMPRESSION BASED INDOOR POOL DEHUMIDIFIERS – MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-14]
EQUIPMENT TYPE SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE
Single package indoor*
(with or without economizer)
Rating Conditions: A, B, or C 3.5 MRE AHRI 910
Single package indoor water-cooled
(with or without economizer)
Single package indoor water-cooled
(with or without economizer)
3.5 MRE 3.5 MRE
Single package indoor air-cooled
(with or without economizer)
Single package indoor air-cooled
(with or without economizer)
3.5 MRE 3.5 MRE
Split system indoor air-cooled
(with or without economizer)
Split system indoor air-cooled
(with or without economizer)
3.5 MRE 3.5 MRE

TABLE E 503.7.1(15) ELECTRICALLY OPERATED DX-DOAS UNITS, SINGLE-PACKAGE AND REMOTE CONDENSER,

WITHOUT ENERGY RECOVERY – MINIMUM EFFICIENCY REQUIREMENTS

[ASHRAE 90.1: TABLE 6.8.1-15]
EQUIPMENT TYPE SUBCATEGORY OR CONDITION MINIMUM EFFICIENCY TEST PROCEDURE
Air cooled
(dehumidification mode)
4.0_ISMRE_ AHRI 920
Air source heat pumps
(dehumidification mode)
4.0_ISMRE_ AHRI 920
Water cooled
(dehumidification mode)
Cooling tower condenser water 4.9_ISMRE_ AHRI 920
Water cooled
(dehumidification mode)
Chilled Water 6.0_ISMRE_ 6.0_ISMRE_
Air source heat pump
(heating mode)
2.7_ISCOP_ AHRI 920
Water source heat pump
(dehumidification mode)
Ground source, closed loop 4.8_ISMRE_ AHRI 920
Water source heat pump
(dehumidification mode)
Ground-water source 5.0_ISMRE_ 5.0_ISMRE_
Water source heat pump
(dehumidification mode)
Water source 4.0_ISMRE_ 4.0_ISMRE_
Water source heat pump
(heating mode)
Ground source, closed loop 2.0_ISCOP_ AHRI 920
Water source heat pump
(heating mode)
Ground-water source 3.2_ISCOP_ 3.2_ISCOP_
Water source heat pump
(heating mode)
Water source 3.5_ISCOP_ 3.5_ISCOP_

TABLE E 503.7.1(16) ELECTRICALLY OPERATED DX-DOAS UNITS, SINGLE PACKAGE AND REMOTE CONDENSER,

WITH ENERGY RECOVERY – MINIMUM EFFICIENCY [ASHRAE 90.1: TABLE 6.8.1-16] REQUIREMENTS
EQUIPMENT TYPE SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE
Air cooled
(dehumidification mode)
5.2_ISMRE_ AHRI 920
Air source heat pumps
(dehumidification mode)
5.2_ISMRE_ AHRI 920
Water cooled
(dehumidification mode)
Cooling tower condenser water 5.3_ISMRE_ AHRI 920
Water cooled
(dehumidification mode)
Chilled Water 6.6_ISMRE_ 6.6_ISMRE_
Air source heat pump
(heating mode)
3.3_ISCOP_ AHRI 920
Water source heat pump
(dehumidification mode)
Ground source, closed loop 5.2_ISMRE_ AHRI 920
Water source heat pump
(dehumidification mode)
Ground-water source 5.8_ISMRE_ 5.8_ISMRE_
Water source heat pump
(dehumidification mode)
Water source 4.8_ISMRE_ 4.8_ISMRE_
Water source heat pump
(heating mode)
Ground source, closed loop 3.8_ISCOP_ AHRI 920
Water source heat pump
(heating mode)
Ground-water source 4.0_ISCOP_ 4.0_ISCOP_
Water source heat pump
(heating mode)
Water source 4.8_ISCOP_ 4.8_ISCOP_

2022 CALIFORNIA MECHANICAL CODE 421

APPENDIX E

TABLE E 503.7.2 MINIMUM DUCT INSULATION R-VALUE1 [ASHRAE 90.1: TABLE 6.8.2]
CLIMATE ZONE DUCT LOCATION DUCT LOCATION DUCT LOCATION
CLIMATE ZONE EXTERIOR2 UNCONDITIONED SPACE AND
BURIED DUCTS
INDIRECTLY CONDITIONED
SPACE3, 4
SUPPLY AND RETURN DUCTS FOR HEATING AND COOLING
0 to 4 R-8 R-6 R-1.9
5 to 8 R-12 R-6 R-1.9
SUPPLY AND RETURN DUCTS FOR HEATING ONLY
0 to 1 none none none
2 to 4 R-6 R-6 R-1.9
5 to 8 R-12 R-6 R-1.9
SUPPLY AND RETURN DUCTS FOR COOLING ONLY
0 to 6 R-8 R-6 R-1.9
7 to 8 R-1.9 R-1.9 R-1.9

Notes:

  1. Insulation R-values, measured in [°F•h•ft2/(Btu•in)] [(m•K)/W], are for the insulation as installed and do not include film resistance. The required minimum thicknesses do not consider water vapor transmission and possible surface condensation. Where portions of the building envelope are used as a plenum enclosure, building envelope insulation shall be as required by the most restrictive condition of Section E 503.4.7.1 or ASHRAE 90.1, depending on whether the plenum is located in the roof, wall, or floor. Insulation resistance measured on a horizontal plane in accordance with ASTM C518 at a mean temperature of 75°F (24°C) at the installed thickness.
  2. Includes attics above insulated ceilings, parking garages and crawl spaces.
  3. Includes return air plenums, with or without exposed roofs above.
  4. Return ducts in this duct location do not require insulation.

TABLE E 503.7.3(1) MINIMUM PIPE INSULATION THICKNESS FOR HEATING AND HOT WATER SYSTEMS 1, 2, 3, 4, 5

(STEAM, STEAM CONDENSATE, HOT WATER HEATING, AND DOMESTIC WATER SYSTEMS)

[ASHRAE 90.1: TABLE 6.8.3-1]

FLUID OPERATING
TEMPERATURE RANGE
(F°) AND USAGE
INSULATION CONDUCTIVITY NOMINAL PIPE SIZE OR TUBE SIZE (inches)
FLUID OPERATING
TEMPERATURE RANGE
(F°) AND USAGE
CONDUCTIVITY
Btu•inch/(h•ft2•°F)
MEAN RATING
TEMPERATURE
°F
<1 1 to <11_/_2 11_/_2 to <4 4 to <8 ≥8
INSULATION THICKNESS (inches) INSULATION THICKNESS (inches) INSULATION THICKNESS (inches) INSULATION THICKNESS (inches) INSULATION THICKNESS (inches)
>350 0.32 to 0.34 250 4.5 5.0 5.0 5.0 5.0
251 to 350 0.29 to 0.32 200 3.0 4.0 4.5 4.5 4.5
201 to 250 0.27 to 0.30 150 2.5 2.5 2.5 3.0 3.0
141 to 200 0.25 to 0.29 125 1.5 1.5 2.0 2.0 2.0
105 to 140 0.22 to 0.28 100 1.0 1.0 1.5 1.5 1.5

For SI units: °C=(°F-32)/1.8, 1 inch = 25 mm, 1 British thermal unit inch per hour square foot degree Fahrenheit = [0.1 W/(m•K)] Notes: 1 For insulation outside the stated conductivity range, the minimum thickness ( T ) shall be determined as follows: T = r {(1 + t / r ) K / k - 1}

Where:

T = minimum insulation thickness (inches). r = actual outside radius of pipe (inches). t = insulation thickness listed in this table for applicable fluid temperature and pipe size. K = conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature [Btu•in/(h•ft 2 •°F)] [W/(m•K)]. k = the upper value of the conductivity range listed in this table for the applicable fluid temperature. 2 These thicknesses are on energy efficiency considerations only. Additional insulation is sometimes required relative to safety issues/surface temperature. 3 For piping smaller than 11 ⁄ 2 inches (40 mm) or less and located in partitions within conditioned spaces, reduction of these thicknesses by 1 inch (25.4 mm) shall be permitted (before thickness adjustment required in footnote 1) but not to thicknesses below 1 inch (25.4 mm). 4 For direct-buried heating and hot water system piping, reduction of these thicknesses by 11 ⁄ 2 inch (40 mm) shall be permitted (before thickness adjustment required in footnote 1) but not to thicknesses below 1 inch (25.4 mm). 5 Table E 503.7.3(1) is based on steel pipe. Nonmetallic pipes schedule 80 thickness or less shall use the table values. For other nonmetallic pipes having thermal resistance more than that of steel pipe, reduced insulation thicknesses are permitted where documentation is provided showing that the pipe with the proposed insulation has no more heat transfer per foot (mm) than a steel pipe of the same size with the insulation thickness shown in Table E 503.7.3(1).

422 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

TABLE E 503.7.3(2) MINIMUM PIPE INSULATION THICKNESS FOR COOLING SYSTEMS (CHILLED WATER, BRINE, AND REFRIGERANT) 1,2,3,4

[ASHRAE 90.1: TABLE 6.8.3-2]

INSULATION CONDUCTIVITY NOMINAL PIPE SIZE OR TUBE SIZE (inches)
FLUID OPERATING TEMPERATURE
RANGE (°F) AND USAGE
CONDUCTIVITY
Btu•inch/(h•f2•°F)
MEAN RATING
TEMPERATURE °F
<1 1 to <11_/_2 11_/_2 to <4 4 to <8 ≥8
INSULATION THICKNESS (inches) INSULATION THICKNESS (inches) INSULATION THICKNESS (inches) INSULATION THICKNESS (inches) INSULATION THICKNESS (inches)
40 to 60 021 to 0.27 75 0.5 0.5 1.0 1.0 1.0
<40 0.20 to 0.26 50 0.5 1.0 1.0 1.0 1.5

For SI units: °C = (°F-32)/1.8, 1 inch = 25 mm, 1 British thermal unit inch per hour square foot degree Fahrenheit = [0.1 W/(m•k)] Notes: 1 For insulation outside the stated conductivity range, the minimum thickness ( T ) shall be determined as follows: T = r {(1 + t/r ) K/k - 1}

Where: T = minimum insulation thickness (inches). r = actual outside radius of pipe (inches). t = insulation thickness listed in this table for applicable fluid temperature and pipe size. K = conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature [Btu inch/(h ft 2 °F)] [W/(m•K)]. k = the upper value of the conductivity range listed in this table for the applicable fluid temperature. 2 These thicknesses are based on energy efficiency considerations only. Issues such as water, vapor permeability, or surface condensation require vapor retarders or additional insulation. 3 For direct-buried cooling system piping, insulation is not required. 4 Table E 503.7.3(2) is based on steel pipe. Nonmetallic pipes schedule 80 thickness or less shall use the table values. For other nonmetallic pipes having thermal resistance more than that of steel pipe, reduced insulation thicknesses are permitted where documentation is provided showing that the pipe with the proposed insulation has no more heat transfer per foot (mm) than a steel pipe of the same size with the insulation thickness shown in Table E 503.7.3(2).

E 601.0 Indoor Environment. E 601.1 Scope. The provisions of this section shall establish the means of reducing the quantity of air contaminants that are odorous, irritating, or harmful to the comfort and wellbeing of a building’s installers, occupants, and neighbors.

E 602.0 Fireplaces. E 602.1 Requirements. A direct vent sealed-combustion gas or sealed wood-burning fireplace, or a sealed wood stove shall be installed. The fireplace shall comply with Section E 602.1.1 and Section E 602.1.2. E 602.1.1 Masonry or Factory-Built Fireplace. Masonry and factory-built fireplaces located in conditioned spaces shall be in accordance with Section E 602.1.1.1 through Section E 602.1.1.3. E 602.1.1.1 Opening Cover. Closeable metal or glass doors covering the entire opening of the firebox shall be installed. E 602.1.1.2 Combustion Air Intake. A combustion air intake to draw air from the outside of the building directly into the firebox, which is an area of not less than 6 square inches (0.004 m 2 ) and is equipped with a readily accessible, operable, and tight-fitting damper or combustion air control device.

E 602.1.1.3 Accessible Damper Control. The flue damper shall have a readily accessible control. Exception: Where a gas log, log lighter, or decorative gas appliance is installed in a fireplace, the flue damper shall be blocked open where required by this code or the manufacturer’s installation instructions.

E 602.1.2 Prohibited. Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, where the indoor air is vented to the outside of the building, are prohibited.

E 603.0 Pollutant Control. E 603.1 Indoor Air Quality During Construction. Indoor air quality of a building shall be maintained in accordance with Section E 603.1.1 through Section E 603.1.3.

E 603.1.1 Temporary Ventilation During Con- struction. Temporary ventilation during construction shall be provided in accordance with the following: (1) Ventilation during construction shall be achieved

through openings in the building shell using fans to produce not less than three air changes per hour. (2) During dust-producing operations, the supply and

return HVAC system openings shall be protected from dust in accordance with Section E 603.1.3. (3) Where the building is occupied during demolition

or construction, ventilation shall be provided in accordance with the Control Measures of the SMACNA IAQ Guidelines for Occupied Buildings Under Construction. (4) The permanent HVAC system shall not be used dur ing construction to condition and ventilate the building within the required temperature range for material and equipment installation. Where required, a supplemental HVAC system shall be used during construction, return air shall be equipped with filters with a minimum efficiency reporting value (MERV) of 8, in accordance with ASHRAE 52.2, or an average efficiency of 30 percent in accordance with

2022 CALIFORNIA MECHANICAL CODE 423

APPENDIX E

ASHRAE 52.2. Before occupancy, filters shall be replaced with filters having a MERV 13 rating in accordance with Section E 603.3. Exception: Embedded hydronics system shall be permitted to be used to condition the building during construction. E 603.1.2 Indoor Air Quality After Construction. After construction ends and interior finishes are installed, flush-out the building to reduce contaminant concentrations by supplying a total outdoor air volume of 14 000 cubic feet per square foot (ft 3 /ft 2 ) (4267.2 m 3 /m 2 ) of occupiable building area. An internal temperature of not less than 60°F (16°C) and relative humidity not higher than 60 percent shall be maintained during the flush-out process. Occupancy shall begin on condition of 3500 ft 3 /ft 2 (1066.8 m 3 /m 2 ) of building area, with the remaining 10 500 ft 3 /ft 2 (3200.4 m 3 /m 2 ) being accomplished as soon as possible. Exception: Other means of reducing the contaminant concentration levels shall be permitted where approved by the Authority Having Jurisdiction. E 603.1.3 Covering of Duct Openings and Pro- tection of Mechanical Equipment During Con- struction. At the time of rough installation, or during storage on the construction site and until final startup of the heating and cooling equipment, duct and other related air distribution component openings shall be covered with tape, plastic, sheet metal, or other methods acceptable to the enforcing agency to reduce the amount of dust or debris that collects in the system. E 603.2 Isolation of Pollutant Sources. Rooms where activities produce hazardous fumes or chemicals, including commercial kitchens, garages, janitorial or laundry rooms, and copy or printing rooms, shall be exhausted and isolated from adjacent spaces in accordance with this code. E 603.3 Filters. In mechanically ventilated buildings, particle filters, or air-cleaning devices shall be provided to clean outdoor and return air prior to its delivery to occupied spaces. The particle or air cleaner shall have a MERV of 13. Exception: A filter or air cleaning device with a lower MERV value shall be permitted provided it is the highest value commercially available for the specific equipment that is installed. E 603.4 Ozone Depletion and Global Warming Reductions. Installations of HVAC and refrigeration shall not contain CFCs and shall be in accordance with this code.

E 604.0 Indoor Moisture Control. E 604.1 Rainwater Control. Roof drainage systems shall discharge to a place of disposal in accordance with the plumbing code. Storm water shall be directed away from the building.

E 605.0 Indoor Air Quality for Low-Rise Residential. E 605.1 General. Rooms or occupied spaces within singlefamily homes and multifamily structures of three stories or less above grade shall be designed to have ventilation (outdoor) air for occupants in accordance with Section E 605.1.1 through Section E 605.1.3.2, or the applicable local code.

E 605.1.1 Natural Ventilation. Naturally ventilated spaces shall be permanently open to and within 20 feet (6096 mm) of operable wall or roof openings to the outdoors, the openable area of which is not less than 5 percent of the conditioned floor area of the naturally ventilated space. Where openings are covered with louvers or otherwise obstructed, openable area shall be based on the free unobstructed area through the opening.

E 605.1.1.1 Access to Operable Openings. The means to open required operable openings shall be readily accessible to building occupants where the space is occupied. E 605.1.2 Mechanical Ventilation. Each space that is not naturally ventilated in accordance with Section E 605.1.1 shall be ventilated with a mechanical system capable of providing an outdoor air rate not less than 15 ft 3 /min (0.007 m 3 /s) per person times the expected number of occupants. Mechanical ventilation shall comply with this code. E 605.1.3 Dwelling-Unit Ventilation. A Mechanical exhaust system, supply system, or combination thereof shall be installed to operate for each dwelling unit to provide continuous dwelling-unit ventilation with outdoor air at a rate not less than the rate specified in Section E 605.1.3.1. [ASHRAE 62.2:4.1] E 605.1.3.1 Total Ventilation Rate. The total required ventilation rate ( Qtot ) shall be as specified in Table E 605.1.3.1 or, alternatively, calculated using Equation E 605.1.3.1.

(Equation E 605.1.3.1) Qtot = 0.03 Afloor + 7.5( Nbr + 1)

Where: Qtot = total required ventilation rate, cubic feet per minute (ft 3 /min) Afloor = dwelling unit floor area, square foot (ft 2 ) Nbr = number of bedrooms (not to be less than one)

For SI units: 1 cubic foot per minute = 0.00047 m 3 /s, 1 square foot = 0.0929 m 2 Exceptions: Dwelling-unit mechanical ventilation systems shall not be required where the Authority Having Jurisdiction determines that window operation is a locally permissible method of providing ventilation and provided one or more of the following conditions is met: (1) The building has no mechanical cooling and is

in zone 1 or 2 of the climate zone map. (2) The building is thermally conditioned for

human occupancy for less than 876 hours per year. [ASHRAE 62.2:4.1.1] E 605.1.3.2 Effective Annual Average Infiltra- tion Rate ( Qinf ). Effective Annual Average Infiltration Rate ( Qinf ) shall be calculated using Equation E 605.1.3.2:

424 2022 CALIFORNIA MECHANICAL CODE

(Equation E 605.1.3.2) Qinf (CFM) = ( NL x wsf x Afloor ) / (7.3)*

Where: NL = normalized leakage wsf = weather and shielding factor from ASHRAE

62.2. Afloor = floor area of residence, ft 2 (m 2 )

  • Replace 7.3 with 1.44 for metric units. [ASHRAE 62.2:4.1.2(e)] E 605.1.3.3 Required Mechanical Ventilation Rate ( Qfan ). Required Mechanical Ventilation Rate ( Qfan ) shall be calculated using Equation E 605.1.3.3:

(Equation E 605.1.3.3) Qfan = Qtot - ( Qinf × Aext )

Where: Qfan = required mechanical ventilation rate, CFM

(L/s) Qtot = total required ventilation rate, CFM (L/s) Qinf = may be not greater than 2 / 3 × Qtot (see ASHRAE 62.2 for exceptions for existing buildings) Aext = 1 for single-family detached homes, or the

ratio of exterior envelope surface area that is not attached to garages or other dwelling units to total envelope surface area for single-family attached homes. [ASHRAE 62.2:4.1.2(f)] E 605.1.3.4 Different Occupant Density. Table E 605.1.3.1 and Equation E 605.1.3.1 assume two persons in a studio or one-bedroom dwelling unit and an additional person for each additional bedroom. Where higher occupant densities are known, the rate shall be increased by 7.5 ft 3 /min (0.003 m 3 /s) for each additional person. Where approved by the Authority Having Jurisdiction, lower occupant densities shall be permitted to be used. [ASHRAE 62.2:4.1.3] E 605.1.4 System Type. The dwelling-unit mechanical ventilation system shall consist of one or more supply or exhaust fans and associated ducts and controls. Local exhaust fans shall be permitted to be part of a mechanical exhaust system. Where local exhaust fans are used to provide dwelling-unit ventilation, the local exhaust airflow shall be permitted to be credited toward the dwelling-unit ventilation airflow requirement. Outdoor air ducts connected to the return side of an air handler shall be permitted as supply ventilation where manufacturer’s requirements for return air temperature are met. See ASHRAE 62.2 for guidance on selection of methods. [ASHRAE 62.2:4.2] E 605.1.5 Airflow Measurement. The airflow required by this section shall be the quantity of outdoor ventilation air supplied and/or indoor air exhausted by the mechanical ventilation system as installed and shall

APPENDIX E

be measured according to the ventilation equipment manufacturer’s instructions, or by using a flow hood, flow grid, or other airflow measuring device at the mechanical ventilation fan’s inlet terminals/grilles, outlet terminals/grilles, or in the connected ventilation ducts. Ventilation airflow of systems with multiple operating modes shall be tested in all modes designed to meet this section. [ASHRAE 62.2:4.3] E 605.1.6 Control and Operation. A readily accessible manual ON-OFF control, including but not limited to a fan switch or a dedicated branch-circuit overcurrent device, shall be provided. Controls shall include text or an icon indicating the system’s function. Exception: For multifamily dwelling units, the manual ON-OFF control shall not be required to be readily accessible. [ASHRAE 62.2:4.4] E 605.1.7 Variable Mechanical Ventilation. Dwelling-unit mechanical ventilation systems designed to provide variable ventilation shall comply with Section E 605.1.7.1 or Section E 605.1.7.2 or Section E 605.1.7.3. Section E 605.1.7.2 and Section E 605.1.7.3 also require compliance with ASHRAE 62.2 and require verification with supporting documentation from the manufacturer, designer, or specifier of the ventilation control system that the system meets the requirements of these sections. Where the dwelling-unit ventilation rate varies based on occupancy, occupancy shall be determined by occupancy sensors or by an occupant-programmable schedule. [ASHRAE 62.2:4.5]

E 605.1.7.1 Short-Term Average Ventilation. To comply with this section, a variable ventilation system shall be installed to provide an average dwelling-unit ventilation rate over any three-hour period that is greater than or equal to Qfan as calculated using Section E 605.1.3.3. [ASHRAE 62.2:4.5.1] E 605.1.7.2 Scheduled Ventilation. This section shall only be allowed to be used where one or more fixed patterns of designed ventilation are known at the time compliance to Section E 605.0 is being determined. Such patterns include those both clockdriven and driven by typical meteorological data. Compliance with this section shall be demonstrated with either Section E 605.1.7.2.1 or Section E 605.1.7.2.2. [ASHRAE 62.2:4.5.2] E 605.1.7.2.1 Annual Average Schedule. An annual schedule of ventilation complies with this section when the annual average relative exposure during occupied periods is not more than unity as calculated in accordance with ASHRAE 62.2. [ASHRAE 62.2:4.5.2.1] E 605.1.7.2.2 Block Scheduling. The schedule of ventilation complies with this section when it is broken into blocks of time and each block individually has an average relative exposure during occupied periods that is not more than unity as calculated in ASHRAE 62.2.

[ASHRAE 62.2:4.5.2.2]

2022 CALIFORNIA MECHANICAL CODE 425

APPENDIX E

E 605.1.7.3 Real-Time Control. A real-time ventilation controller complies with this section when it is designed to adjust the ventilation system based on real-time input to the ventilation calculations so that the average relative exposure during occupied periods is not more than unity as calculated in ASHRAE 62.2. The averaging period shall be not less than one day but not more than one year and shall be based on simple, recursive or running average, but not extrapolation. [ASHRAE 62.2:4.5.3] E 605.1.8 Equivalent Ventilation. A dwelling-unit ventilation system shall be designed and operated in such a way as to provide the same or lower annual exposure as would be provided in accordance with Section E 605.1.3. The calculations shall be based on a single zone with a constant contaminant emission rate. The manufacturer, specifier, or designer of the equivalent ventilation system shall certify that the system is in accordance with this intent and provide supporting documentation.

[ASHRAE 62.2:4.6] E 605.2 Bathroom Exhaust Fans. Except where a whole house energy recovery system is used, a mechanical exhaust fan vented to the outdoors shall be provided in each room containing a bathtub, shower, or tub/shower combination. The ventilation rate shall be not less than 50 ft 3 /min (0.02 m 3 /s) for intermittent operation and 20 ft 3 /min (0.009 m 3 /s) for continuous operation. Fans shall comply with the Energy Star Program. E 605.3 Filters. Heating and air conditioning filters shall have a MERV rating of 6 or higher. The air distribution system shall be designed for the pressure drop across the filter.

E 606.0 Indoor Air Quality for Other than Low-Rise Residential Buildings. E 606.1 Minimum Indoor Air Quality. The building shall comply with Chapter 4 or ASHRAE 62.1 for ventilation air supply.

E 607.0 Environmental Comfort. E 607.1 Thermal Comfort Controls. The mechanical systems and controls of building shall be designed to provide and maintain indoor comfort conditions in accordance with ASHRAE 55.

E 607.2 Heating and Air-Conditioning System Design. Heating and air-conditioning systems shall be sized, designed, and have their equipment selected in accordance with the following: (1) Heat loss and heat gain are established in accordance

with ACCA Manual J, ASHRAE handbooks, or other equivalent methods. (2) Duct systems shall be sized in accordance with ACCA

Manual D, ASHRAE handbooks, or other equivalent methods. (3) Heating and cooling equipment in accordance with

ACCA Manual S or other equivalent methods.

E 608.0 Low VOC Solvent Cement and Primer. E 608.1 General. Primers and solvent cements used to join plastic pipe, and fittings shall be in accordance with Section E 608.1.1 and Section E 608.1.2.

E 608.1.1 Solvent Cement. Solvent cement, including one-step solvent cement, shall have a volatile organic compound (VOC) content of less than or equal to 65 ounces per gallon (oz/gal) (487 g/L) for CPVC cement, 68 oz/gal (509 g/L) for PVC cement, and 43 oz/gal (322 g/L) for ABS cement, as determined by the South Coast Air Quality Management District’s Laboratory Methods of Analysis for Enforcement Samples, Method 316A. E 608.1.2 Primer. Primer shall have a volatile organic compound (VOC) content of less than or equal to 73 oz/gal (546 g/L), as determined by the South Coast Air Quality Management District’s Laboratory Methods of Analysis for Enforcement Samples, Method 316A.

TABLE E 605.1.3.1 VENTILATION AIR REQUIREMENTS, (cubic foot per minute) [ASHRAE 62.2: TABLE 4.1a]
FLOOR AREA (ft2) BEDROOMS BEDROOMS BEDROOMS BEDROOMS BEDROOMS
FLOOR AREA (ft2) 1 2 3 4 5
<500 30 38 45 53 60
501-1000 45 53 60 68 75
1001-1500 60 68 75 83 90
1501-2000 75 83 90 98 105
2001-2500 90 98 105 113 120
2501-3000 105 113 120 128 135
3001-3500 120 128 135 143 150
3501-4000 135 143 150 158 165
4001-4500 150 158 165 173 180
4501-5000 165 173 180 188 195

For SI units: 1 square foot = 0.0929 m 2, 1 cubic foot per minute = 0.00047 m 3 /s

426 2022 CALIFORNIA MECHANICAL CODE

E 701.0 Installer Qualifications. E 701.1 Scope. The provisions of this section address minimum qualifications of installers of mechanical systems covered within the scope of this appendix.

E 702.0 Qualifications. E 702.1 General. Where permits are required, the Authority Having Jurisdiction shall have the authority to require contractors, installers, or service technicians to demonstrate competency. Where determined by the Authority Having Jurisdiction, the contractor, installer, or service technician shall be licensed to perform such work.

Part I

E 801.0 Heating, Ventilation, and Air Conditioning Systems Commissioning. E 801.1 Applicability. The provisions of this section apply to the commissioning of commercial and institutional HVAC systems.

E 802.0 Commissioning. E 802.1 Commissioning Requirements. HVAC commissioning shall be included in the design and construction processes of the project to verify that the HVAC systems and components meet the owner’s project requirements and in accordance with this appendix. Commissioning shall be performed in accordance with this appendix by personnel trained and certified in commissioning by a nationally recognized organization. Commissioning requirements shall include the following: (1) Owner’s project requirements (2) Basis of design (3) Commissioning measures shown in the construction doc uments (4) Commissioning plan (5) Functional performance (6) Testing (7) Post construction documentation and training (8) Commissioning report

y personnel trained and certified in commissioning by a nationally recognized organization. Commissioning requirements shall include the following: (1) Owner’s project requirements (2) Basis of design (3) Commissioning measures shown in the construction doc uments (4) Commissioning plan (5) Functional performance (6) Testing (7) Post construction documentation and training (8) Commissioning report

HVAC systems and components covered by this appendix as well as process equipment and controls, and renewable energy systems shall be included in the scope of the commissioning requirements. E 802.2 Owner’s Project Requirements (OPR). The performance goals and requirements of the HVAC system shall be documented before the design phase of the project begins. This documentation shall include not less than the following: (1) Environmental and sustainability goals (2) Energy efficiency goals (3) Indoor environmental quality requirements (4) Equipment and systems performance goals (5) Building occupant and O&M personnel expectations

APPENDIX E

E 802.3 Basis of Design (BOD). A written explanation of how the design of the HVAC system meets the owner’s project requirements shall be completed at the design phase of the building project, and updated as necessary during the design and construction phases. The basis of design document shall cover not less than the following systems: (1) Heating, ventilation, air conditioning (HVAC) systems

and controls (2) Water heating systems (3) Renewable energy systems E 802.4 Commissioning Plan. A commissioning plan shall be completed to document the approach to how the project will be commissioned, and shall be started during the design phase of the building project. The commissioning plan shall include not less than the following: (1) General project information (2) Commissioning goals (3) Systems to be commissioned. Plans to test systems and

components shall include not less than the following: (a) A detailed explanation of the original design intent. (b) Equipment and systems to be tested, including the

extent of tests. (c) Functions to be tested. (d) Conditions under which the test shall be performed. (e) Measurable criteria for acceptable performance. (4) Commissioning team information. (5) Commissioning process activities, schedules, and

responsibilities. Plans for the completion of commissioning requirements listed in Section E 802.5 through Section E 802.7 shall be included. E 802.5 Functional Performance Testing. Functional performance tests shall demonstrate the correct installation and operation of each component, system, and system-to-system interface in accordance with the approved plans and specifications. Functional performance testing reports shall contain information addressing each of the building components tested, the testing methods utilized, and readings and adjustments made.

E 802.6 Post Construction Documentation and Train- ing. A system manual and systems operations training are required.

E 802.6.1 Systems Manual. Documentation of the operational aspects of the HVAC system shall be completed within the systems manual and delivered to the building owner and facilities operator. The systems manual shall include not less than the following: (1) Site information, including facility description, his tory, and current requirements. (2) Site contact information. (3) Basic O&M, including general site operating proce dures, basic troubleshooting, recommended maintenance requirements, and site events log. (4) Major systems. (5) Site equipment inventory and maintenance notes.

2022 CALIFORNIA MECHANICAL CODE 427

APPENDIX E

(6) Equipment/system warranty documentation and

information. (7) “As-Built” design drawings. (8) Other resources and documentation. E 802.6.2 Systems Operations Training. The training of the appropriate maintenance staff for each equipment type or system shall include not less than the following: (1) System/Equipment overview (what it is, what it

does, and what other systems or equipment it interfaces with). (2) Review of the information in the systems manual. (3) Review of the record drawings on the system/equip ment. E 802.7 Commissioning Report. A complete report of commissioning process activities undertaken through the design, construction, and post-construction phases of the building project shall be completed and provided to the owner.

Part II

E 803.0 Commissioning Acceptance. E 803.1 General. Part II of this appendix provides a means of verifying the commissioning requirements of Section E 802.1. The activities specified in Part II of this appendix includes three aspects, as described as follows: (1) Visual inspection of the equipment and installation. (2) Review of the certification requirements. (3) Functional tests of the systems and controls. E 803.2 Construction Documents. Details of commissioning acceptance requirements shall be incorporated into the construction documents, including information that describes the details of the functional tests to be performed. This information shall be permitted to be integrated into the specifications for testing and air balancing, energy management and control system, equipment startup procedures or commissioning. It is possible that the work will be performed by a combination of the test and balance (TAB) contractor, mechanical/electrical contractor, and the energy management control system (EMCS) contractor, so applicable roles and responsibilities shall be clearly called out.

E 803.2.1 Roles and Responsibilities. The roles and responsibilities of the persons involved in commissioning acceptance are included in Section E 803.2.1.1 through Section E 803.2.1.3.

E 803.2.1.1 Field Technician. The field technician shall be responsible for performing and documenting the results of the acceptance procedures on the certificate of acceptance forms. The field technician shall sign the certificate of acceptance to certify that the information he provides on the certificate of acceptance is true and correct.

E 803.2.1.2 Responsible Person. The responsible person shall be the contractor or registered design professional of record. A certificate of acceptance shall be signed by a responsible person to take responsibility for the scope of work specified by the certificate of acceptance document. The responsible person shall perform the field testing and verification work, and where this is the case, the responsible person shall complete and sign both the field technician’s signature block and the responsible person’s signature block on the certificate of acceptance form. The responsible person assumes responsibility for the acceptance testing work performed by the field technician agent or employee. E 803.2.1.3 Certificate of Acceptance. The certificate of acceptance shall be submitted to the Authority Having Jurisdiction in order to receive the final certificate of occupancy. The Authority Having Jurisdiction shall not release a final certificate of occupancy unless the submitted certificate of acceptance demonstrates that the specified systems and equipment have been shown to be performing in accordance with the applicable acceptance requirements. The Authority Having Jurisdiction has the authority to require the field technician and responsible person to demonstrate competence, to its satisfaction. Certificate of acceptance forms are located in Section E 806.0.

E 804.0 Commissioning Tests. E 804.1 General. Functional tests shall be performed on new equipment and systems installed in either new construction or retrofit applications in accordance with this section. The appropriate certificate of acceptance form along with each specific test shall be completed and submitted to the Authority Having Jurisdiction before a final occupancy permit can be granted. E 804.2 Tests. Functional testing shall be performed on the devices and systems listed in this section. The functional test results are documented using the applicable certificate of acceptance forms shown in parenthesis and located in Section E 806.0. The functional tests shall be performed in accordance with Section E 805.0 using the following forms: (1) Minimum ventilation controls for constant and variable

air volume systems (Form MECH-2A). (2) Zone temperature and scheduling controls for constant

volume, single-zone, unitary air conditioner and heat pump systems (Form MECH-3A). (3) Duct leakage on a subset of small single-zone systems

depending on the ductwork location (Form MECH-4A). (4) Air economizer controls for economizers that are not fac tory installed and tested (Form MECH-5A). (5) Demand-controlled ventilation control systems (Form

MECH-6A). (6) Supply fan variable flow controls (Form MECH-7A).

428 2022 CALIFORNIA MECHANICAL CODE

(7) Valve leakage for hydronic variable flow systems and

isolation valves on chillers and boilers in plants with more than one chiller or boiler being served by the same primary pumps through a common header (Form MECH8A). (8) Supply water temperature reset control strategies pro grammed into the building automation system for water systems (e.g., chilled, hot, or condenser water) (Form MECH-9A). (9) Hydronic variable flow controls on a water system where

the pumps are controlled by variable frequency drives (e.g., chilled and hot water systems; water-loop heat pump systems) (Form MECH-10A). (10)Automatic demand shed control (Form MECH-11A). (11)Fault detection and diagnostic for DX units (Form

MECH-12A). (12)Automatic fault detection and diagnostic systems

(AFDD) (Form MECH-13A). (13)Distributed energy storage DEC/DX AC systems (Form

MECH-14A). (14)Thermal energy storage (TES) systems (Form MECH 15A). E 804.3 Acceptance Process. The functional testing process shall comply with Section E 804.3.1 through Section E 804.3.4.

E 804.3.1 Plan Review. The installing contractor, registered design professional of record, owner’s agent, or the person responsible for certification of the acceptance testing on the certificate of acceptance (responsible person) shall review the plans and specifications to ensure that they are in accordance with the acceptance requirements. This is typically done prior to signing a certificate of compliance. E 804.3.2 Construction Inspection. The installing contractor, registered design professional of record, owner’s agent, or the person responsible for certification of the acceptance testing on the certificate of acceptance (responsible person) shall perform a construction inspection prior to testing to ensure that the equipment that is installed is capable of complying with the requirements of this appendix and is calibrated. The installation of associated systems and equipment necessary for proper system operation is required to be completed prior to the testing. E 804.3.3 Acceptance Testing. One or more field technicians shall perform the acceptance testing; identify performance deficiencies; ensure that they are corrected; and where necessary, repeat the acceptance procedures until the specified systems and equipment are performing in accordance with the acceptance requirements. The field technician who performs the testing shall sign the certificate of acceptance to certify the information has been provided to document the results of the acceptance procedures is true and correct.

The responsible person shall review the test results from the acceptance requirement procedures provided by the field technician and sign the certificate of acceptance

APPENDIX E

to certify compliance with the acceptance requirements. The responsible person shall be permitted to perform the field technician’s responsibilities, and shall then sign the field technician declaration on the certificate of acceptance to certify that the information on the form is true and correct. E 804.3.4 Certificate of Occupancy. The Authority Having Jurisdiction shall not issue the final certificate of occupancy until required certificates of acceptance are submitted. Copies of completed, signed certificates of acceptance are required to be posted, or made available with the permit(s), and shall be made available to the Authority Having Jurisdiction.

E 805.0 HVAC System Tests.

E 805.1 Variable Air Volume Systems (Form MECH- 2A). This test ensures that adequate outdoor air ventilation is provided through the variable air volume air handling unit at two representative operating conditions. The test consists of measuring outdoor air values at maximum flow and at or near minimum flow. The test verifies that the minimum volume of outdoor air is introduced to the air handling unit where the system is in occupied mode at these two conditions of supply airflow. This test shall be performed in conjunction with supply fan variable flow controls test procedures to reduce the overall system testing time as both tests use the same two conditions of airflow for their measurements.

E 805.1.1 Test Procedure. The procedure for performing a functional test for variable air volume systems shall be in accordance with Section E 805.1.1.1 and Section E 805.1.1.2.

E 805.1.1.1 Construction Inspection. Prior to functional testing, verify and document that the system controlling outside airflow is calibrated either in the field or factory. E 805.1.1.2 Functional Testing. The functional testing shall be in accordance with the following steps: Step 1: Where the system has an outdoor air economizer, force the economizer high limit to disable economizer control (e.g., for a fixed drybulb high limit, lower the setpoint below the current outdoor air temperature). Step 2: Adjust supply airflow to either the sum of the minimum zone airflows or 30 percent of the total design airflow. Verify and document the following: (1) Measured outside airflow reading is within 10

percent of the total ventilation air called for in the certificate of compliance. (2) OSA controls stabilize within 5 minutes. Step 3: Adjust supply airflow to achieve design airflow. Verify and document the following: (1) Measured outside airflow reading is within 10

percent of the total ventilation air called for in the certificate of compliance.

2022 CALIFORNIA MECHANICAL CODE 429

APPENDIX E

(2) OSA controls stabilize within 5 minutes. Step 4: Restore system to “as-found” operating conditions. E 805.1.2 Acceptance Criteria. System controlling outdoor air flow shall be calibrated in the field or at the factory.

Measured outdoor airflow reading shall be within 10 percent of the total value found on the certificate of compliance under the following conditions: (1) Minimum system airflow. (2) Thirty percent of total design flow design supply air flow.

E 805.2 Constant Volume Systems (Form MECH-2A). The purpose of this test is to ensure that adequate outdoor air ventilation is provided through the constant volume air handling unit to the spaces served under operating conditions. The intent of this test is to verify that the minimum volume of outdoor air is introduced to the air handling unit during typical space occupancy.

E 805.2.1 Test Procedure. The procedure for performing a functional test for constant air volume systems shall be in accordance with Section E 805.2.1.1 and Section E 805.2.1.2.

E 805.2.1.1 Construction Inspection. Prior to functional testing, verify and document the following: (1) Minimum position is marked on the outside air

damper. (2) The system has means of maintaining the min imum outdoor air damper position. E 805.2.1.2 Functional Testing. Where the system has an outdoor air economizer, force the economizer to the minimum position and stop outside air damper modulation (e.g., for a fixed drybulb high limit, lower the setpoint below the current outdoor air temperature). E 805.2.2 Acceptance Criteria. The system has a means of maintaining the minimum outdoor air damper position. The minimum damper position is marked on the outdoor air damper. The measured outside airflow reading shall be within 10 percent of the total ventilation air called for in the certificate of compliance.

E 805.3 Constant Volume, Single-Zone, Unitary Air Conditioner and Heat Pumps Systems Acceptance (Form MECH-3A). The purpose of this test is to verify the individual components of a constant volume, single-zone, unitary air conditioner and heat pump system function correctly; including: thermostat installation and programming, supply fan, heating, cooling, and damper operation.

E 805.3.1 Test Procedure. The procedure for performing a functional test for constant volume, singlezone, unitary air conditioner and heat pump systems shall be in accordance with Section E 805.3.1.1 and Section E 805.3.1.2.

E 805.3.1.1 Construction Inspection. Prior to functional testing, verify and document the following: (1) Thermostat is located within the space-condi tioning zone that is served by the HVAC system. (2) Thermostat shall be in accordance with temper ature adjustment and dead band requirements. (3) Occupied, unoccupied, and holiday schedules

shall be programmed per the facility’s schedule. (4) Preoccupancy purge is programmed. E 805.3.1.2 Functional Testing. The functional testing shall be in accordance with the following steps: Step 1: Disable economizer and demand control ventilation systems (where applicable). Step 2: Simulate a heating demand during the occupied condition. Verify and document the following: (1) Supply fan operates continually. (2) The unit provides heating. (3) No cooling is provided by the unit. (4) Outside air damper is at minimum position. Step 3: Simulate operation in the dead band during occupied condition. Verify and document the following: (1) Supply fan operates continually. (2) Neither heating nor cooling is provided by the

unit. (3) Outside air damper is at minimum position. Step 4: Simulate cooling demand during occupied condition. Lock out economizer (where applicable). Verify and document the following: (1) Supply fan operates continually. (2) The unit provides cooling. (3) No heating is provided by the unit. (4) Outside air damper is at minimum position. Step 5: Simulate operation in the dead band during unoccupied mode. Verify and document the following: (1) Supply fan is off. (2) Outside air damper is fully closed. (3) Neither heating nor cooling is provided by the

unit. Step 6: Simulate heating demand during unoccupied conditions. Verify and document the following: (1) Supply fan is on (either continuously or

cycling). (2) Heating is provided by the unit. (3) No cooling is provided by the unit. (4) Outside air damper is either closed or at mini mum position.

430 2022 CALIFORNIA MECHANICAL CODE

Step 7: Simulate cooling demand during unoccupied condition. Lock out economizer (where applicable). Verify and document the following: (1) Supply fan is on (either continuously or

cycling). (2) Cooling is provided by the unit. (3) No heating is provided by the unit. (4) Outside air damper is either closed or at mini mum position. Step 8: Simulate manual override during unoccupied condition. Verify and document the following: (1) System operates in “occupied” mode. (2) System reverts to “unoccupied” mode where

APPENDIX E

(1) Duct connections shall comply with the require ments of this appendix and this code. (2) Flexible ducts are not compressed. (3) Ducts are fully accessible for testing. (4) Joints and seams are properly sealed in accor dance with the requirements of this appendix. (5) Insulation R-Values shall comply with the min imum requirements of this appendix. E 805.4.1.2 Functional Testing. Perform duct leakage test in accordance with Section E 503.4.7.2.1. E 805.4.2 Acceptance Criteria. Flexible ducts are not compressed or constricted. Duct connections shall comply with the requirements of this appendix and this code (new ducts only). Joints and seams are properly sealed in accordance with the requirements of this appendix and this code (new ducts only). Duct R-values shall comply with the minimum requirements of this appendix (new ducts only). Insulation is protected from damage and suitable for outdoor usage where applicable (new ducts only). The leakage shall not exceed the rate in accordance with Section E 503.4.7.2. E 805.5 Air Economizer Controls Acceptance (Form MECH-5A). The purpose of functionally testing an air economizer cycle is to verify that an HVAC system uses outdoor air to satisfy space cooling loads where outdoor air conditions are acceptable. There are two types of economizer controls; stand-alone packages and DDC controls. The stand-alone packages are commonly associated with small unitary rooftop HVAC equipment, and DDC controls are typically associated with built-up or large packaged air handling systems. Test procedures for both economizer control types are provided.

For units with economizers that are factory installed and certified operational by the manufacturer to economizer quality control requirements, the in-field economizer functional tests do not have to be conducted. A copy of the manufacturer’s certificate shall be attached to the Form MECH-5A. However, the construction inspection, including compliance with high-temperature lockout temperature setpoint, shall be completed regardless of whether the economizer is field or factory installed.

facturer to economizer quality control requirements, the in-field economizer functional tests do not have to be conducted. A copy of the manufacturer’s certificate shall be attached to the Form MECH-5A. However, the construction inspection, including compliance with high-temperature lockout temperature setpoint, shall be completed regardless of whether the economizer is field or factory installed.

manual override time period expires. Step 9: Restore economizer and demand control ventilation systems (where applicable), and remove system overrides initiated during the test. E 805.3.2 Acceptance Criteria. Thermostat is located within the space-conditioning zone that is served by the respective HVAC system. The thermostat shall comply with temperature adjustment and dead band requirements. Occupied, unoccupied, and holiday schedules shall be programmed per the facility’s schedule. Preoccupancy purge is programmed in accordance with the requirements. E 805.4 Air Distribution Systems (Form MECH-4A). The purpose of this test is to verify duct work associated with non-exempt constant volume, single-zone, HVAC units (e.g., air conditioners, heat pumps, and furnaces) meet the material, installation, and insulation R-values and leakage requirements outlined in this appendix. This test is required for single-zone units serving less than 5000 square feet (464.52 m 2 ) of floor area where 25 percent or more of the duct surface area is in one of the following spaces: (1) Outdoors. (2) In a space directly under a roof where the U-factor of the

roof is greater than the U-factor of the ceiling. (3) In a space directly under a roof with fixed vents or open

ings to the outside or unconditioned spaces. (4) In an unconditioned crawl space. (5) In other unconditioned spaces.

This test applies to both new duct systems and to existing duct systems being extended or the space conditioning system is altered by the installation or replacement of space conditioning equipment, including: replacement of the air handler; outdoor condensing unit of a split system air conditioner or heat pump; cooling or heating coil; or the furnace heat exchanger. Existing duct systems do not have to be tested where they are insulated or sealed with asbestos.

E 805.4.1 Test Procedure. The procedure for performing a functional test for air distribution systems shall be in accordance with Section E 805.4.1.1 and Section E 805.4.1.2. E 805.4.1.1 Construction Inspection. Prior to functional testing, verify and document the following:

E 805.5.1 Test Procedure. The procedure for performing a functional test for air economizer controls shall comply with Section E 805.5.1.1 and Section E 805.5.1.2. E 805.5.1.1 Construction Inspection. Prior to functional testing, verify and document the following: (1) Economizer lockout setpoint is in accordance

with this appendix. (2) Economizer lockout control sensor is located to

prevent false readings. (3) System is designed to provide up to 100 percent

outside air without over-pressurizing the building. (4) For systems with DDC controls lockout sensor(s)

are either factory calibrated or field calibrated.

2022 CALIFORNIA MECHANICAL CODE 431

APPENDIX E

(5) For systems with non-DDC controls, manufac turer’s startup and testing procedures are applied. E 805.5.1.2 Functional Testing. The functional testing shall be in accordance with the following steps: Step 1: Disable demand control ventilation systems (where applicable). Step 2: Enable the economizer, and simulate a cooling demand large enough to drive the economizer fully open. Verify and document the following: (1) Economizer damper is 100 percent opened and

return air damper is 100 percent closed. (2) Where applicable, verify that the economizer

remains 100 percent open where the cooling demand can no longer be met by the economizer alone. (3) Applicable fans and dampers operate as

intended to maintain building pressure. (4) The unit heating is disabled. Step 3: Disable the economizer and simulate a cooling demand. Verify and document the following: (1) Economizer damper shall close to its minimum

position. (2) Applicable fans and dampers shall operate as

intended to maintain building pressure. (3) The unit heating is disabled. Step 4: Simulate a heating demand, and set the economizer so that it is capable of operating (e.g., actual outdoor air conditions are below lockout setpoint). Verify the economizer is at minimum position. Step 5: Restore demand control ventilation systems (where applicable) and remove system overrides initiated during the test. E 805.5.2 Acceptance Criteria. Air economizer controls acceptance criteria shall be as follows: (1) Where the economizer is factory installed and certi fied, a valid factory certificate is required for acceptance. No additional equipment tests are necessary. (2) Air economizer lockout setpoint is in accordance

with this appendix. Outside sensor location accurately reads true outdoor air temperature and is not affected by exhaust air or other heat sources. (3) Sensors are located to achieve the desired control. (4) During economizer mode, the outdoor air damper

shall modulate open to a maximum position and return air damper to 100 percent closed. (5) The outdoor air damper is 100 percent open before

mechanical cooling is enabled and for units 75 000 Btu/h (22 kw) and larger remains at 100 percent open while mechanical cooling is enabled (economizer integration where used for compliance). (6) Where the economizer is disabled, the outdoor air

damper closes to a minimum position; the return

damper modulates 100 percent open, and mechanical cooling remains enabled.

E 805.6 Demand-Controlled Ventilation Systems Acceptance (Form MECH-6A). The purpose of this test is to verify that systems required to employ demand-controlled ventilation shall be permitted to vary outside ventilation flow rates based on maintaining interior carbon dioxide (CO2) concentration setpoints. Demand-controlled ventilation refers to an HVAC system’s ability to reduce outdoor air ventilation flow below design values where the space served is at less than design occupancy. Carbon dioxide is a good indicator of occupancy load and is the basis used for modulating ventilation flow rates.

utside ventilation flow rates based on maintaining interior carbon dioxide (CO2) concentration setpoints. Demand-controlled ventilation refers to an HVAC system’s ability to reduce outdoor air ventilation flow below design values where the space served is at less than design occupancy. Carbon dioxide is a good indicator of occupancy load and is the basis used for modulating ventilation flow rates.

E 805.6.1 Test Procedure. The procedure for performing a functional test for demand-control ventilation (DVC) systems shall be in accordance with Section E 805.6.1.1 and Section E 805.6.1.2. E 805.6.1.1 Construction Inspection. Prior to functional testing, verify and document the following: (1) Carbon dioxide control sensor is factory cali brated or field-calibrated in accordance with this appendix. (2) The sensor is located in the high-density space

between 3 feet (914 mm) and 6 feet (1829 mm) above the floor or at the anticipated level of the occupants’ heads. (3) DCV control setpoint is at or below the carbon

dioxide concentration permitted by this appendix. E 805.6.1.2 Functional Testing. The functional testing shall be in accordance with the following steps: Step 1: Disable economizer controls. Step 2: Simulate a signal at or slightly above the carbon dioxide concentration setpoint required by this appendix. Verify and document the following: (1) For single zone units, outdoor air damper mod ulates open to satisfy the total ventilation air called for in the certificate of compliance. (2) For multiple zone units, either outdoor air

damper or zone damper modulate open to satisfy the zone ventilation requirements. Step 3: Simulate signal well below the carbon dioxide setpoint. Verify and document the following: (1) For single zone units, outdoor air damper mod ulates to the design minimum value. (2) For multiple zone units, either outdoor air

damper or zone damper modulate to satisfy the reduced zone ventilation requirements. Step 4: Restore economizer controls and remove system overrides initiated during the test. Step 5: With controls restored, apply carbon dioxide calibration gas at a concentration slightly above the setpoint to the sensor. Verify that the outdoor air

432 2022 CALIFORNIA MECHANICAL CODE

damper modulates open to satisfy the total ventilation air called for in the certificate of compliance. E 805.6.2 Acceptance Criteria. Demand-controlled ventilation systems acceptance criteria shall be as follows: (1) Each carbon dioxide sensor is factory calibrated

(with calibration certificate) or field calibrated. (2) Each carbon dioxide sensor is wired correctly to the

controls to ensure proper control of the outdoor air damper. (3) Each carbon dioxide sensor is located correctly

within the space 1 foot (305 mm) to 6 feet (1829 mm) above the floor. (4) Interior carbon dioxide concentration setpoint is not

more than 600 parts per million (ppm) plus outdoor air carbon dioxide value where dynamically measured or not more than 1000 ppm where no OSA sensor is provided. (5) A minimum OSA setting is provided where the sys tem is in occupied mode in accordance with this appendix regardless of space carbon dioxide readings. (6) A maximum OSA damper position for DCV control

shall be established in accordance with this appendix, regardless of space carbon dioxide readings. (7) The outdoor air damper shall modulate open where

the carbon dioxide concentration within the space exceeds setpoint. (8) The outdoor air damper modulates closed (toward

minimum position) where the carbon dioxide concentration within the space is below setpoint.

E 805.7 Supply Fan Variable Flow Controls (Form MECH-7A). The purpose of this test is to ensure that the supply fan in a variable air volume application modulates to meet system airflow demand. In most applications, the individual VAV boxes serving each space will modulate the amount of air delivered to the space based on heating and cooling requirements. As a result, the total supply airflow provided by the central air handling unit shall vary to maintain sufficient airflow through each VAV box. Airflow shall be controlled using a variable frequency drive (VFD) to modulate supply fan speed and vary system airflow. The most common strategy for controlling the VFD is to measure and maintain static pressure within the duct.

E 805.7.1 Test Procedure. The procedure for performing a functional test for supply fan variable controls shall be in accordance with Section E 805.7.1.1 and Section E 805.7.1.2.

E 805.7.1.1 Construction Inspection. Prior to functional testing, verify and document the following: (1) Supply fan controls modulate to increase capac ity. (2) Supply fan maintains discharge static pressure

within plus or minus 10 percent of the current operating set point.

APPENDIX E

(3) Supply fan controls stabilize within a 5 minute

period. E 805.7.1.2 Functional Testing. The functional testing shall be in accordance with the following steps: Step 1: Simulate demand for design airflow. Verify and document the following: (1) Supply fan controls modulate to increase capac ity. (2) Supply fan maintains discharge static pressure

within plus or minus 10 percent of the current operating set point. (3) Supply fan controls stabilize within a 5 minute

period. Step 2: Simulate demand for minimum airflow. Verify and document the following: (1) Supply fan controls modulate to decrease

capacity. (2) Current operating setpoint has decreased (for

systems with DDC to the zone level). (3) Supply fan maintains discharge static pressure

within plus or minus 10 percent of the current operating setpoint. (4) Supply fan controls stabilize within a 5 minute

period. Step 3: Restore system to correct operating conditions. E 805.7.2 Acceptance Criteria. Supply fan variable flow controls acceptance criteria shall be as follows: (1) Static pressure sensor(s) is factory calibrated (with

calibration certificate) or field calibrated. (2) For systems without DDC controls to the zone level,

the pressure sensor setpoint is less than one-third of the supply fan design static pressure. (3) For systems with DDC controls with VAV boxes

reporting to the central control panel, the pressure setpoint is reset by zone demand (box damper position or a trim and respond algorithm). At full flow: (1) Supply fan maintains discharge static pressure

within plus or minus 10 percent of the current operating control static pressure setpoint. (2) Supply fan controls stabilizes within a 5 minute

period. (3) At minimum flow (not less than 30 percent of total

design flow). (4) Supply fan controls modulate to decrease capacity. (5) Current operating setpoint has decreased (for sys tems with DDC to the zone level). (6) Supply fan maintains discharge static pressure

within plus or minus 10 percent of the current operating setpoint.

2022 CALIFORNIA MECHANICAL CODE 433

APPENDIX E

E 805.8 Valve Leakage (Form MECH-8A). The purpose of this test is to ensure that control valves serving variable flow systems are designed to withstand the pump pressure over the full range of operation. Valves with insufficient actuators will lift under certain conditions causing water to leak through and loss of control. This test applies to the variable flow systems, chilled and hot-water variable flow systems, chiller isolation valves, boiler isolation valves, and watercooled air conditioner and hydronic heat pump systems.

E 805.8.1 Test Procedure. The procedure for performing a functional test for valve leakage shall be in accordance with Section E 805.8.1.1 and Section E 805.8.1.2. E 805.8.1.1 Construction Inspection. Prior to functional testing, verify and document the valve and piping arrangements were installed in accordance with the design drawings. E 805.8.1.2 Functional Testing. The functional testing shall be in accordance with the following steps: Step 1: For each pump serving the distribution system, dead head the pumps using the discharge isolation valves at the pumps. Document the following: (1) Record the differential pressure across the

pumps. (2) Verify that this is within 5 percent of the sub mittal data for the pump. Step 2: Reopen the pump discharge isolation valves. Automatically close valves on the systems being tested. Where three-way valves are present, close off the bypass line. Verify and document the following: (1) The valves automatically close. (2) Record the pressure differential across the

pump. (3) Verify that the pressure differential is within 5

percent of the reading from Step 1 for the pump that is operating during the valve test. Step 3: Restore system to correct operating conditions. E 805.8.2 Acceptance Criteria. System has no flow where coils are closed and the pump is turned on.

E 805.9 Supply Water Temperature Reset Controls (Form MECH-9A). The purpose of this test is to ensure that both the chilled water and hot water supply temperatures are automatically reset based on either building loads or outdoor air temperature, as indicated in the control sequences. Many HVAC systems are served by central chilled and heating hot water plants. The supply water operating temperatures shall meet peak loads where the system is operating at design conditions. As the loads vary, the supply water temperatures shall be permitted to be adjusted to satisfy the new operating conditions. The chilled water supply temperature shall be permitted to be raised as the cooling load decreases, and heating hot water supply temperature shall be permitted to be lowered as the heating load decreases.

cent of the control setpoint. E 805.9.2 Acceptance Criteria. The supply water temperature sensors are either factory calibrated (with calibration certificates) or field-calibrated. Sensor performance shall comply with the specifications. The supply water reset is operational. E 805.10 Hydronic System Variable Flow Controls (Form MECH-10A). The purpose of this test is to ensure that hydronic variable flow chilled water and water-loop heat pump systems with circulating pumps larger than 5 hp (3.7 kW) vary system flow rate by modulating pump speed using a variable frequency drive (VFD) or equivalent. As the loads within the building fluctuate, control valves modulate the amount of water passing through each coil and add or remove the desired amount of energy from the air stream to satisfy the load. In the case of water-loop heat pumps, each two-way control valve associated with a heat pump will be closed where that unit is not operating. As each control valve mod

This requirement applies to chilled and hot water systems that are not designed for variable flow, and that have a design capacity greater than or equal to 500 000 Btu/h (147 kW).

E 805.9.1 Test Procedure. The procedure for performing a functional test for supply water temperature reset controls shall be in accordance with Section E 805.9.1.1 and Section E 805.9.1.2. E 805.9.1.1 Construction Inspection. Prior to functional testing, verify and document the supply water temperature sensors shall be either factory or field calibrated. E 805.9.1.2 Functional Testing. The functional testing shall be in accordance with the following steps: Step 1: Change reset control variable to its maximum value. Verify and document the following: (1) Chilled or hot water temperature setpoint is

reset to appropriate value. (2) Actual supply temperature changes to meet set point. (3) Verify that supply temperature is within 2 per cent of the control setpoint. Step 2: Change reset control variable to its minimum value. Verify and document the following: (1) Chilled or hot water temperature setpoint is

reset to appropriate value. (2) Actual supply temperature changes to meet set point. (3) Verify that supply temperature is within 2 per cent of the control setpoint. Step 3: Restore reset control variable to automatic control. Verify and document the following: (1) Chilled or hot water temperature setpoint is

reset to appropriate value. (2) Actual supply temperature changes to meet set point. (3) Verify that supply temperature is within 2 per

434 2022 CALIFORNIA MECHANICAL CODE

ulates, the pump variable frequency drive (VFD) responds accordingly to meet system water flow requirements. This is not required on heating hot water systems with variable flow designs or for condensing water serving water cooled chillers.

E 805.10.1 Test Procedure. The procedure for performing a functional test for hydronic system variable flow controls shall be in accordance with Section E 805.10.1.1 and Section E 805.10.1.2. E 805.10.1.1 Construction Inspection. Prior to functional testing, verify and document the pressure sensors are either factory or field calibrated. E 805.10.1.2 Functional Testing. The functional testing shall comply with the following steps: Step 1: Open control valves to increase water flow to not less than 90 percent design flow. Verify and document the following: (1) Pump speed increases. (2) System pressure is either within plus or minus

5 percent of current operating setpoint, or the pressure is below the setpoint, and the pumps are operating at 100 percent speed. (3) System operation shall stabilize within 5 min utes after test procedures are initiated. Step 2: Modulate control valves to reduce water flow to 50 percent of the design flow or less, but not lower than the pump minimum flow. Verify and document the following: (1) Pump speed decrease. (2) Current operating setpoint has decreased (for

systems with DDC to the zone level). (3) Current operating setpoint has not increased

(for all other systems). (4) System pressure is within 5 percent of current

operating setpoint. (5) System operation stabilizes within 5 minutes

after test procedures are initiated. E 805.10.2 Acceptance Criteria. The differential pressure sensor is either factory calibrated (with calibration certificates) or field calibrated. The pressure sensor shall be located at or near the most remote HX or control valve. The setpoint system controls shall stabilize.

E 805.11 Automatic Demand Shed Control (Form MECH-11A). The purpose of this test is to ensure that the central demand shed sequences have been properly programmed into the DDC system.

E 805.11.1 Test Procedure. The procedure for performing a functional test for automatic demand shed controls shall be in accordance with Section E 805.11.1.1 and Section E 805.11.1.2.

E 805.11.1.1 Construction Inspection. Prior to functional testing, verify and document that the EMCS interface enables activation of the central demand shed controls.

APPENDIX E

E 805.11.1.2 Functional Testing. The functional testing shall comply with the following steps: Step 1: Engage the global demand shed system. Verify and document the following: (1) That the cooling setpoint in noncritical spaces

increases by the proper amount. (2) That the cooling setpoint in critical spaces do

not change. Step 2: Disengage the global demand shed system. Verify and document the following: (1) That the cooling setpoint in noncritical spaces

return to their original values. (2) That the cooling setpoint in critical spaces do

not change. E 805.11.2 Acceptance Criteria. The control system changes the setpoints of noncritical zones on activation of a single central hardware or software point then restores the initial setpoints where the point is released.

E 805.12 Fault Detection and Diagnostics (FDD) for Packaged Direct-Expansion (DX) Units (Form MECH-12A). The purpose of this test is to verify proper fault detection and reporting for automated fault detection and diagnostics systems for packaged units. Automated FDD systems ensure proper equipment operation by identifying and diagnosing common equipment problems such as improper refrigerant charge, low airflow, or faulty economizer operation. Qualifying FDD systems receive a compliance credit where using the performance approach. A system that does not meet the eligibility requirements shall be permitted to be installed, but no compliance credit will be given.

E 805.12.1 Test Procedure. The procedure for performing a functional test for fault detection and diagnostics (FDD) for packaged direct-expansion (DX) units shall be in accordance with Section E 805.12.1.1 and Section E 805.12.1.2.

E 805.12.1.1 Construction Inspection. Prior to functional testing, verify and document that the FDD hardware is installed on equipment by the manufacturer, and that equipment make and model include factory-installed FDD hardware that match the information indicated on copies of the manufacturer’s cut sheets and on the plans and specifications.

This procedure applies to fault detection and diagnostics (FDD) system for direct-expansion packaged units containing the following features: (1) The unit shall include a factory-installed econ omizer and shall limit the economizer dead band to not more than 2°F (-17°C). (2) The unit shall include direct-drive actuators on

outside air and return air dampers. (3) The unit shall include an integrated economizer

with either differential drybulb or differential enthalpy control.

2022 CALIFORNIA MECHANICAL CODE 435

APPENDIX E

(4) The unit shall include a low temperature lock out on the compressor to prevent coil freeze-up or comfort problems. (5) Outside air and return air dampers shall have

maximum leakage rates in accordance to this appendix. (6) The unit shall have an adjustable expansion

control device such as a thermostatic expansion valve (TXV). (7) To improve the ability to troubleshoot charge

and compressor operation, a high-pressure refrigerant port will be located on the liquid line. A low-pressure refrigerant port will be located on the suction line. (8) The following sensors shall be permanently

installed to monitor system operation, and the controller shall have the capability of displaying the value of each parameter: (a) Refrigerant suction pressure (b) Refrigerant suction temperature (c) Liquid line pressure (d) Liquid line temperature (e) Outside air temperature (f) Outside air relative humidity (g) Return air temperature (h) Return air relative humidity (i) Supply air temperature (j) Supply air relative humidity The controller will provide system status by indicating the following conditions: (1) Compressor enabled (2) Economizer enabled (3) Free cooling available (4) Mixed air low limit cycle active (5) Heating enabled

The unit controller shall have the capability to manually initiate each operating mode so that the operation of compressors, economizers, fans, and heating system can be independently tested and verified. E 805.12.1.2 Functional Testing. The functional testing shall be in accordance with the following steps: Step 1: Test low airflow condition by replacing the

existing filter with a dirty filter or appropriate obstruction. Step 2: Verify that the fault detection and diagnos tics system reports the fault. Step 3: Verify that the system is able to verify the

correct refrigerant charge.

Step 4: Calibrate outside air, return air, and supply

air temperature sensors. E 805.12.2 Acceptance Criteria. The system is able to detect a low airflow condition and report the fault. The system is able to detect where refrigerant charge is low or high and the fault is reported.

E 805.13 Automatic Fault Detection Diagnostics (FDD) for Air Handling Units (AHU) and Zone Termi- nal Units (Form MECH-13A). The purpose of this test is to verify that the system detects common faults in air handling units and terminal units. FDD systems for air handling units and zone terminal units require DDC controls to the zone level. Successful completion of this test provides a compliance credit where using the performance approach. An FDD system that does not pass this test shall be permitted to be installed, but no compliance credit will be given.

E 805.13.1 Test Procedure. The procedure for performing a functional test for automatic fault detection diagnostics (FDD) for Air Handling Units and Zone Terminal Units shall be in accordance with Section E 805.13.1.1.

E 805.13.1.1 Functional Testing. The functional testing shall be in accordance with Section E 805.13.1.1.1 and Section E 805.13.1.1.2.

E 805.13.1.1.1 Functional Testing for Air Handling Units. The functional testing of AHU with FDD controls shall be in accordance with the following steps: Step 1: Sensor drift/failure: (1) Disconnect outside air temperature sensor

from unit controller. (2) Verify that the FDD system reports a fault. (3) Connect OAT sensor to the unit controller. (4) Verify that FDD indicates normal system

operation. Step 2: Damper/actuator fault: (1) From the control system workstation, com mand the mixing box dampers to full open (100 percent outdoor air). (2) Disconnect power to the actuator and ver ify that a fault is reported at the control workstation. (3) Reconnect power to the actuator and com mand the mixing box dampers to full open. (4) Verify that the control system does not

report a fault. (5) From the control system workstation, com mand the mixing box dampers to a fullclosed position (0 percent outdoor air). (6) Disconnect power to the actuator and ver ify that a fault is reported at the control workstation. (7) Reconnect power to the actuator and com mand the dampers closed.

436 2022 CALIFORNIA MECHANICAL CODE

(8) Verify that the control system does not

report a fault during normal operation. Step 3: Valve/actuator fault: (1) From the control system workstation, com mand the heating and cooling coil valves to full open or closed, then disconnect power to the actuator and verify that a fault is reported at the control workstation. Step 4: Inappropriate simultaneous heating, mechanical cooling, and economizing or all functions: (1) From the control system workstation, over ride the heating coil valve and verify that a fault is reported at the control workstation. (2) From the control system workstation, over ride the cooling coil valve and verify that a fault is reported at the control workstation. (3) From the control system workstation, over ride the mixing box dampers and verify that a fault is reported at the control workstation.

E 805.13.1.1.2 Functional Testing for Zone Terminal Units. The functional testing of one of each type of terminal unit (VAV box) in the project not less than 5 percent of the terminal boxes shall be in accordance with the following steps: Step 1: Sensor drift/failure: (1) Disconnect the tubing to the differential

pressure sensor of the VAV box. (2) Verify that control system detects and

reports the fault. (3) Reconnect the sensor and verify proper

sensor operation. (4) Verify that the control system does not

report a fault. Step 2: Damper/actuator fault: (1) Damper stuck open.

(a) Command the damper to full open

(room temperature above setpoint). (b) Disconnect the actuator to the damper. (c) Adjust the cooling setpoint so that the

room temperature is below the cooling setpoint to command the damper to the minimum position. Verify that the control system reports a fault. (d) Reconnect the actuator and restore to

normal operation. (2) Damper stuck closed.

(a) Set the damper to the minimum posi tion.

APPENDIX E

(b) Disconnect the actuator to the damper. (c) Set the cooling setpoint below the

room temperature to simulate a call for cooling. Verify that the control system reports a fault. (d) Reconnect the actuator and restore to

normal operation. Step 3: Valve/actuator fault (for systems with hydronic reheat): (1) Command the reheat coil valve to full

open. (2) Disconnect power to the actuator. Set the

heating setpoint temperature to be lower than the current space temperature, to command the valve closed. Verify that the fault is reported at the control workstation. (3) Reconnect the actuator and restore normal

operation. Step 4: Feedback loop tuning fault (unstable airflow): (1) Set the integral coefficient of the box con troller to a value 50 times the current value. (2) The damper cycles continuously and air flow is unstable. Verify that the control system detects and reports the fault. (3) Reset the integral coefficient of the con troller to the original value to restore normal operation. Step 5: Disconnected inlet duct: (1) From the control system workstation, com mand the damper to full closed; then disconnect power to the actuator, and verify that a fault is reported at the control workstation. E 805.13.2 Acceptance Criteria. The system is able to detect common faults with air-handling units, such as a sensor failure, a failed damper, an actuator, or an improper operating mode.

The system is able to detect and report common faults with zone terminal units, such as a failed damper, an actuator, or a control tuning issue.

E 805.14 Distributed Energy Storage DX AC System (Form MECH-14A). The purpose of this test is to verify the proper operation of distributed energy storage DX systems. Distributed energy systems (DES) reduce peak demand by operating during off-peak hours and storing cooling, usually in the form of ice. During peak cooling hours the ice is melted to avoid compressor operation. The system typically consists of a water tank containing refrigerant coils that cool the water and convert it to ice. As with a standard direction expansion (DX) air conditioner, the refrigerant is compressed in a compressor and then cooled in an air-cooled condenser. The liq

2022 CALIFORNIA MECHANICAL CODE 437

APPENDIX E

uid refrigerant then is directed through the coils in the water tank to make ice or to air handler coils to cool the building. This applies to constant or variable volume, direct expansion (DX) systems with distributed energy storage (DES/DXAC).

E 805.14.1 Test Procedure. The procedure for performing a functional test for distributed energy storage DX AC systems shall be in accordance with Section E 805.14.1.1 through Section E 805.14.1.3. E 805.14.1.1 Construction Inspection. Prior to functional testing, verify and document the following: (1) The water tank is filled to the proper level. (2) The water tank is sitting on a foundation with

adequate structural strength. (3) The water tank is insulated and the top cover is

in place. (4) The DES/DXAC is installed correctly (e.g.,

refrigerant piping, etc.). (5) Verify that the correct model number is

installed and configured. E 805.14.1.2 Functional Testing. The functional testing shall be in accordance with the following steps: Step 1: Simulate cooling load during daytime period (e.g., by setting time schedule to include actual time and placing thermostat cooling setpoint below actual temperature). Verify and document the following: (1) Supply fan operates continually. (2) Where the DES/DXAC has cooling capacity,

DES/DXAC shall run to meet the cooling demand (in ice melt mode). (3) Where the DES/DXAC has no ice and there is

a call for cooling, the DES/DXAC shall run in direct cooling mode. Step 2: Simulate no cooling load during daytime condition. Verify and document the following: (1) Supply fan operates in accordance with the

facility thermostat or control system. (2) The DES/DXAC and the condensing unit do

not run. Step 3: Simulate no cooling load during morning shoulder time period. Verify and document the following: (1) The DES/DXAC is idle. Step 4: Simulate a cooling load during morning shoulder time period. Verify and document the following: (1) The DES/DXAC runs in direct cooling mode. E 805.14.1.3 Calibrating Controls. Set the proper time and date in accordance with the manufacturer’s instructions for approved installers.

E 805.14.2 Acceptance Criteria. Distributed energy storage DXAC system acceptance criteria shall be as follows: (1) Verify night time ice making operation. (2) Verify that tank discharges during on-peak cooling

periods. (3) Verify that the compressor does not run and the tank

does not discharge where there is no cooling demand during on-peak periods. (4) Verify that the system does not operate during a

morning shoulder period where there is no cooling demand. (5) Verify that the system operates in direct mode (with

compressor running) during the morning shoulder time period.

E 805.15 Thermal Energy Storage (TES) System (Form MECH-15A). The purpose of this test is to verify the proper operation of thermal energy storage (TES) systems. TES systems reduce energy consumption during peak demand periods by shifting energy consumption to nighttime. Operation of the thermal energy storage compressor during the night produces cooling energy which is stored in the form of cooled fluid or ice in tanks. During peak cooling hours the thermal storage is used for cooling to prevent the need for chiller operation. This section is limited to the following types of TES systems: (1) Chilled water storage (2) Ice-on-coil (3) Ice harvester (4) Brine (5) Ice-slurry (6) Eutectic salt (7) Clathrate hydrate slurry (CHS)

E 805.15.1 Test Procedure. The procedure for performing a functional test for thermal energy storage (TES) system shall be in accordance with Section E 805.15.1.1 and Section E 805.15.1.2. E 805.15.1.1 Construction Inspection. Prior to functional testing, verify and document the following for the chiller and storage tank: (1) Chiller:

(a) Brand and Model (b) Type (centrifugal, reciprocating, other) (c) Capacity (tons) (SIZE) (d) Starting efficiency (kW/ton) at beginning

of ice production (COMP - kW/TON START) (e) Ending efficiency (kW/ton) at end of ice

production (COMP - kW/TON/END) (f) Capacity reduction (percent/°F) (PER – COMP - REDUCT/F)

438 2022 CALIFORNIA MECHANICAL CODE

(g) Verify that the efficiency of the chiller

meets or exceeds the requirements of Section E 501.0. (2) Storage Tank:

(a) Storage type (TES-TYPE) (b) Number of tanks (SIZE) (c) Storage capacity per tank (ton-hours)

(SIZE) (d) Storage rate (tons) (COOL – STORE RATE) (e) Discharge rate (tons) (COOL – SUPPLY RATE) (f) Auxiliary power (watts) (PUMPS + AUX kW) (g) Tank area (CTANK – LOSS - COEFF) (h) Tank insulation (R-Value) (CTANK –

LOSS – COEFF) (3) TES System:

(a) The TES system is one of the above eligi ble systems. (b) Initial charge rate of the storage tanks

(tons). (c) Final charge rate of the storage tank (tons). (d) Initial discharge rate of the storage tanks

(tons). (e) Final discharge rate of the storage tank

(tons). (f) Charge test time (hrs). (g) Discharge test time (hrs). (h) Tank storage capacity after charge (ton hrs). (i) Tank storage capacity after discharge (tonhrs). (j) Tank standby storage losses (UA). (k) Initial chiller efficiency (kW/ton) during

charging. (l) Final chiller efficiency (kW/ton) during charging. E 805.15.1.2 Functional Testing. The functional testing shall be in accordance with the following steps: Step 1: Verify that the TES system and the chilled water plant is controlled and monitored by an energy management system (EMS). Step 2: Force the time to be between 9:00 p.m. and 9:00 a.m., and simulate a partial or no charge of the tank. Simulate no cooling load by setting the indoor temperature setpoint(s) higher than the ambient temperature.

Where the tank is full or nearly full of ice, it shall be permitted to adjust the control settings for this test. In some cases, the control system will not permit the chiller to start the ice-making process

APPENDIX E

unless a portion of the ice has been melted. The controls designer shall be permitted to use an inventory meter (a 4-20 mA sensor that indicates water level) to determine whether or not ice-making can commence (e.g., not allow ice-making unless the inventory meter signal is less than 17 mA). Where this is the case, this limit can be reset to 20 mA during testing to allow ice making to occur.

Verify that the TES system starts charging (storing energy). This shall be checked by verifying flow and inlet and outlet temperatures of the storage tank, or directly by reading an inventory meter where the system has one. Step 3: Force the time to be between 6:00 p.m. and 9:00 p.m., and simulate a partial charge on the tank. Simulate a cooling load by setting the indoor temperature setpoint lower than the ambient temperature. Verify that the TES system starts discharging. This shall be checked by observing tank inlet and outlet temperatures and system flow, or directly by reading an inventory meter where the system has one. Where the system has no charge, verify that the system will still attempt to meet the load through storage. Step 4: Force the time to be between noon and 6:00 p.m., and simulate a cooling load by lowering the indoor air temperature setpoint below the ambient temperature. Verify that the tank starts discharging and the compressor is off. Step 5: Force the time to be between 9:00 a.m. to noon, and simulate a cooling load by lowering the indoor air temperature setpoint below the ambient temperature. Verify that the tank does not discharge and the cooling load is met by the compressor. Step 6: Force the time to be between 9:00 p.m. and 9:00 a.m. and simulate a full tank charge. This can be done in a couple of ways: (1) By changing the inventory sensor limit that

indicates tank capacity to the energy management system so that it indicates a full tank. (2) By resetting the coolant temperature that indi cates a full charge to a higher temperature than the current tank leaving temperature. Verify that the tank charging is stopped. Step 7: Force the time to be between noon and 6:00 p.m. and simulate no cooling load by setting the indoor temperature setpoint above the ambient temperature. Verify that the tank does not discharge and the compressor is off. E 805.15.2 Acceptance Criteria. Thermal energy storage (TES) system acceptance criteria shall be as follows: (1) Verify that the system is able to charge the storage

tank during off-peak periods where there is no cooling load. (2) Verify that tank discharges during on-peak cooling

periods.

2022 CALIFORNIA MECHANICAL CODE 439

APPENDIX E

(3) Verify that the compressor does not run and the tank

does not discharge where there is no cooling demand during on-peak periods. (4) Verify that the system does not operate during a

morning shoulder period where there is no cooling demand. (5) Verify that the system operates in direct mode (with

compressor running) during the morning shoulder time period.

E 806.0 Certificate of Acceptance Forms. E 806.1 General. This section includes the certificate of acceptance forms referenced in Section E 804.0 and Section E 805.0.

440 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-2A
Outdoor Air Acceptance (Page 1 of 3)
Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:
Enforcement Agency: Permit Number:
Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date
must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

  • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

  • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

Company Name:

Field Technician’s Name: Field Technician’s Signature:
Date Signed: Position with Company (Title):

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

  • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

  • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the

builder provides to the building owner at occupancy.

Company Name: Company Name: Company Name: Phone:
Responsible Person’s Name: Responsible Person’s Name: Responsible Person’s Signature: Responsible Person’s Signature:
License: Date Signed: Position With Company (Title): Position With Company (Title):

2022 CALIFORNIA MECHANICAL CODE 441

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-2A
Outdoor Air Acceptance Outdoor Air Acceptance (Page 2 of 3)
Project Name/Address: Project Name/Address:
System Name or Identification/Tag: System Name or Identification/Tag: System Location or Area Served: System Location or Area Served:
Verify measured outside airflow reading is within ± 10% of the total required outside airflow value found in Section E 805.1
through Section E 805.2.2
Intent:
Construction Inspection Construction Inspection
1. Instrumentation to perform test includes, but not limited to: Instrumentation to perform test includes, but not limited to:
a.
Watch.
b.
Calibrated means to measure airflow.
2. Check one of the following:

Variable Air Volume (VAV) - Check as appropriate:
a.
Sensor used to control outdoor air flow must have calibration certificate or be field calibrated.

Calibration certificate (attach calibration certification).

Field calibration (attach results).

Constant Air Volume (CAV) - Check as appropriate:

System is designed to provide a fixed minimum OSA when the unit is on.
Outdoor Air Acceptance Outdoor Air Acceptance
A. Functional Testing. (Check appropriate column) CAV VAV
a. Verify unit is not in economizer mode during test - check appropriate column. Verify unit is not in economizer mode during test - check appropriate column.
Step 1: CAV and VAV testing at full supply airflow.
a. Adjust supply to achieve design airflow.
b. Measured outdoor airflow reading (ft3/min).
c. Required outdoor airflow (ft3/min).
d. Time for outside air damper to stabilize after VAV boxes open (minutes).
e. Return to initial conditions (check).
Step 2: VAV testing at reduced supply airflow.
a. Adjust supply airflow to either the sum of the minimum zone airflows or 30% of the total design airflow. Adjust supply airflow to either the sum of the minimum zone airflows or 30% of the total design airflow. Adjust supply airflow to either the sum of the minimum zone airflows or 30% of the total design airflow. Adjust supply airflow to either the sum of the minimum zone airflows or 30% of the total design airflow.
b. Measured outdoor airflow reading (ft3/min).
c. Required outdoor airflow (ft3/min).
d. Time for outside air damper to stabilize after VAV boxes
flow achieved (minutes).
open and minimum air
e. Return to initial conditions (check).
B. Testing Calculations and Results. CAV VAV
Percent OSA at full supply airflow (%OAFA for Step 1).
a. %OAFA = Measured outside air reading /Required outside air (Step 1b / Step 1c) %OAFA = Measured outside air reading /Required outside air (Step 1b / Step 1c) % %
b. 90%≤ %OAFA ≤ 110% Y / N Y / N
c. Outside air damper position stabilizes within 15 minutes (Step 1d < 15 minutes) Y / N Y / N
Percent OSA at reduced supply airflow (%OARA for Step Percent OSA at reduced supply airflow (%OARA for Step ** 2).**
a. %OARA = Measured outside air reading/required outside air (Step 2b / Step 2c). % %
b. 90%≤ %OARA ≤ 110%. Y / N
c. Outside air damper position stabilizes within 15 minutes (Step 2d < 15 minutes). Y / N
Not e: Shaded boxes do not apply for CAV systems.

For SI units: 1 cubic foot per minute = 0.00047 m 3 /s

442 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-2A
Outdoor Air Acceptance
(Page 3 of 3)
Project Name/Address:
System Name or Identification/Tag:
System Location or Area Served:
C. PASS/FAIL Evaluation (check one):
PASS: All Construction Inspection responses are complete and Testing Calculations & Results responses are posi-
tive (Y – yes).
FAIL: Any Construction Inspection responses are incomplete_OR_ there is one or more negative (N – no) responses
in Testing Calculations & Results section. Provide explanation below. Use and attach additional pages if necessary.

2022 CALIFORNIA MECHANICAL CODE 443

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-3A
Constant Volume Single Zone Unitary Air Conditioner and Heat Pump Systems Constant Volume Single Zone Unitary Air Conditioner and Heat Pump Systems (Page 1 of 3)
Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:
Enforcement Agency: Permit Number:
Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date
must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

  • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

  • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

Company Name:

Field Technician’s Name: Field Technician’s Signature:
Date Signed: Position with Company (Title):

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

  • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

    • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

    • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder

provides to the building owner at occupancy.

Company Name: Company Name: Company Name: Phone:
Responsible Person’s Name: Responsible Person’s Name: Responsible Person’s Signature: Responsible Person’s Signature:
License: Date Signed: Position With Company (Title): Position With Company (Title):

444 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

Verify the individual components of a constant volume, single-zone, unitary air conditioner and heat pump system func- Intent: tion correctly, including: thermostat installation and programming, supply fan, heating, cooling, and damper operation.

Construction Inspection

  1. Instrumentation to perform test includes, but not limited to: a. None required
  2. Installation Thermostat is located within the space-conditioning zone that is served by the HVAC system.
  3. Programming (check all of the following): Thermostat meets the temperature adjustment and dead band requirements. Occupied, unoccupied, and holiday schedules have been programmed per the facility’s schedule. Preoccupancy purge has been programmed to meet the requirements of Section E 805.3 through Section E 805.3.2.

2022 CALIFORNIA MECHANICAL CODE 445

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-3A
Constant Volume Single Zone Unitary Air Conditioner and Heat Pump Systems Constant Volume Single Zone Unitary Air Conditioner and Heat Pump Systems Constant Volume Single Zone Unitary Air Conditioner and Heat Pump Systems (Page 3 of 3)
Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:
C. PASS/FAIL Evaluation. (check one):
PASS: AllConstruction Inspection responses are complete andTesting Results responses are “Pass” (P).
FAIL: AnyConstruction Inspection responses are incomplete OR there is one or more “Fail” (F) responses in
Testing Results section. Provide explanation below. Use and attach additional pages if necessary.

446 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-4A


Air Distribution Systems Acceptance
(Page 1 of 3)



Project Name/Address:



System Name or Identification/Tag:
System Location or Area Served:



Enforcement Agency:
Permit Number:


Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date

must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

  • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

  • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

Company Name:

Field Technician’s Name: Field Technician’s Signature:
Date Signed: Position with Company (Title):

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

    • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

    • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

    • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

    • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder

provides to the building owner at occupancy.



Company Name:


Company Name:


Company Name:
Phone:


Responsible Person’s Name:


Responsible Person’s Name:
Responsible Person’s Signature: Responsible Person’s Signature:

License:
Date Signed: Position With Company (Title): Position With Company (Title):

2022 CALIFORNIA MECHANICAL CODE 447

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-4A
Air Distribution Systems Acceptance
(Page 2 of 3)
Project Name/Address: Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:

Intent:

New single zone supply ductwork must be less than 6% leakage rate per Section E 805.4 through Section E 805.4.2, existing single zone ductwork must be less than 15% leakage or other compliance path per Section E 805.4 through Section E 805.4.2.

448 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-4A
Air Distribution Systems Acceptance
(Page 3 of 3)
Project Name/Address: Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:
Air Distribution System Leakage Diagnostic. The installing contractor must pressure test every new HVAC systems that meet the requirements of Section E 805.4 through
The installing contractor must pressure test every new HVAC systems that meet the requirements of Section E 805.4 through
Section E 805.4.2 and every retrofit to existing HVAC systems that meet the requirements of Section E 805.4 through Section
E 805.4.2.
RATED FAN FLOW (applies to all systems) RATED FAN FLOW (applies to all systems) Measured Values Measured Values
1. Cooling capacity or for heating only units heating capacity.
(a) Cooling capacity (for all units but heating only units) in tons.
(b) Heating capacity (for heating only units) kBtu/h.
2. Fan flow calculation
(a) Cooling capacity in tons [ (Line # 1a) x 400 ft3/min/ton].
(b) Heating only cap. kBtu/h [ (Line # 1b) x 21.7 ft3/min/kBtu/h].
3. Total calculated supply fan flow 2(a) or 2(b) ft3/min.
NEW CONSTRUCTION OR ENTIRE NEW DUCT SYSTEM ALTERATION:
Duct pressurization test results (ft3/min @ 25 Pa).
4. Enter tested leakage flow in ft3/min: P P
5. Pass if leakage percentage≤6%: [(Line #4)/(Line #3)] x 100 % Pass Fail
ALTERATIONS: Pre-existing duct system with duct alteration and/or HVAC equipment change-out.
6. Enter tested leakage flow (cubic feet per minute): Pre-test of existing duct system
prior to duct system alteration, equipment change-out, or both.
7. Enter tested leakage flow (cubic feet per minute): Final test of new duct system or
altered duct system for duct system alteration, equipment change-out, or both.
TEST OR VERIFICATION STANDARDS: For altered duct system and/or HVAC equipment change-out use one of
the following three tests or verification standards for compliance:
8. Pass if leakage percentage <15%
[ (Line # 7) / (Line # 3)] x 100
% Pass Fail
9. Pass if leakage reduction percentage >60%
Leakage reduction = [1 - [ (Line#7) / (Line#6)] } x 100
% Pass Fail
10. Pass if all accessible leaks are sealed as confirmed by visual inspection and verifica-
tion by HERS rater (sampling rate 100%).
% Pass Fail
Pass if One of Lines #8 through #10 pass Pass Fail

For SI units: 1000 British thermal units per hour = 0.293 kW, 1 cubic foot per minute = 0.00047 m 3 /s, 1 metric ton = 1000 kg

2022 CALIFORNIA MECHANICAL CODE 449

APPENDIX E

\ CERTIFICATE OF ACCEPTANCE MECH-5A

Air Economizer Controls Acceptance
(Page 1 of 3)


Project Name/Address:



System Name or Identification/Tag:
System Location or Area Served:


Enforcement Agency:
Permit Number:


Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date


must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

  • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

  • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

  • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

  • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder

provides to the building owner at occupancy.

Company Name: Company Name: Company Name: Phone:
Responsible Person’s Name: Responsible Person’s Name: Responsible Person’s Signature: Responsible Person’s Signature:
License: Date Signed: Position With Company (Title): Position With Company (Title):

450 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-5A
Air Economizer Controls Acceptance
(Page 2 of 3)
Project Name/Address: Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:

Intent: Verify that airside economizers function properly.

Construction Inspection

  1. Instrumentation to perform test includes, but not limited to: a. Handheld temperature probes calibration. Date: (must be within last year). b. Multimeter capable of measuring ohms and milliamps.
  2. Test method (check one of the following): Economizer comes from HVAC system manufacturer installed by and has been factory calibrated and tested. Attach documentation and complete certification statement. No functional testing required. Economizer field installed and field tested or factory installed and field tested.
  3. Installation (check all of the following first level boxes). Economizer lockout setpoint complies with Section E 805.5 through Section E 805.5.2. Economizer lockout control sensor is located to prevent false readings. System is designed to provide up to 100% outside air without over-pressurizing the building. For systems with DDC controls lockout sensor(s) are either factory calibrated or field calibrated. For systems with non-DDC controls, manufacturer’s startup and testing procedures have been applied.

A. Functional Testing.

Step 1: Disable demand control ventilation systems (if applicable).

Step 2: Enable the economizer and simulate a cooling demand large enough to drive the economizer fully open (check and verify the following).

Economizer damper modulates 100% open.

Return air damper modulates 100% closed.

Where applicable, verify that the economizer remains 100% open when the cooling demand can no longer be met by the economizer alone. All applicable fans and dampers operate as intended to maintain building pressure.

The unit heating is disabled.

Step 3: Simulate a cooling load and disable the economizer (check and verify the following).

Economizer damper closes to its minimum position.

All applicable fans and dampers operate as intended to maintain building pressure.

The unit heating is disabled.

Step 4: Simulate a heating demand and enable the economizer (check and verify the following).

Economizer damper closes to its minimum position.

Step 5: System returned to initial operating conditions. Y/N

B. Testing Results. PASS / FAIL

Step 1: Simulate cooling load and enable the economizer (all check boxes are complete). Step 2: Simulate cooling load and disable the economizer (all check boxes are complete). Step 3: Simulate heating demand and enable the economizer (all check boxes are complete).

2022 CALIFORNIA MECHANICAL CODE 451

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-5A
Air Economizer Controls Acceptance Air Economizer Controls Acceptance (Page 3 of 3)
Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:
C. PASS/FAIL Evaluation (check one):
PASS: AllConstruction Inspection responses are complete andTesting Results responses are “Pass.”
FAIL: AnyConstruction Inspection responses are incomplete_OR_ there is one or more “Fail” responses inTesting
Results section. Provide explanation below. Use and attach additional pages if necessary.

452 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-6A

Demand Control Ventilation Systems Acceptance
(Page 1 of 3)


Project Name/Address:



System Name or Identification/Tag:
System Location or Area Served:


Enforcement Agency:
Permit Number:


Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date

must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

  • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

  • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

Company Name:

Field Technician’s Name: Field Technician’s Signature:
Date Signed: Position with Company (Title):

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

    • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

    • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

    • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder provides to the building owner at occupancy.

Company Name: Phone:

Responsible Person’s Name: Responsible Person’s Signature:

License:
Date Signed: Position With Company (Title):

2022 CALIFORNIA MECHANICAL CODE 453

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-6A
Demand Control Ventilation Systems Acceptance
(Page 2 of 3)
Project Name/Address: Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:

Verify that systems required to employ demand controlled ventilation can vary outside ventilation flow rates based on Intent: maintaining interior carbon dioxide (CO2) concentration setpoints.

Construction Inspection
1.
Instrumentation to perform test includes, but not limited to:
a.
Calibrated handheld CO2 analyzer.
b.
Manufacturer’s calibration kit.
c.
Calibrated CO2/air mixtures.
2.
Installation.
The sensor is located in the high density space between 3 feet and 6 feet above the floor or at the anticipated level
of the occupants heads.
3.
Documentation of all carbon dioxide control sensors includes (check one of the following):
a.
Calibration method.

Factory-calibration certificate (certificate must be attached).

Field calibrated.
b.
Sensor accuracy.

Certified by manufacturer to be no more than +/- 75 ppm calibration certificate must be attached.
A. Functional Testing. Results
a.
Disable economizer controls.
b.
Outside air CO2 concentration (select one of the following).

Measured dynamically using CO2 sensor.
ppm
c.
Interior CO2 concentration setpoint (Outside CO2 concentration + 600 ppm).
ppm
Step 1: Simulate a signal at or slightly above the CO2 setpoint or follow manufacturers recommended testing proce-
dures.

For single zone units, outdoor air damper modulates opens to satisfy the total ventilation air called for in the certificate
of compliance.

For multiple zone units, either outdoor air damper or zone damper modulate open to satisfy the zone ventilation
requirements.
Step 2: Simulate signal well below the CO2 setpoint or follow manufacturers recommended procedures.

For single zone units, outdoor air damper modulates to the design minimum value.

For multiple zone units, either outdoor air damper or zone damper modulate to satisfy the reduced zone ventilation
requirements.
Step 3: System returned to initial operating conditions.
Y/N
B. Testing Results.
PASS / FAIL
Step 1: Simulate a high CO2 load (check box complete).
Step 2: Simulate a low CO2 load (check box complete).

For SI units: 1 inch = 25.4 mm

454 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-6A

Demand Control Ventilation Systems Acceptance
(Page 3 of 3)


Project Name/Address:


Project Name/Address:



System Name or Identification/Tag:
System Location or Area Served:

C. PASS/FAIL Evaluation (check one): PASS: All Construction Inspection responses are complete and Testing Results responses are “Pass.”

FAIL: Any Construction Inspection responses are incomplete OR there is one or more “Fail” responses in Testing

Results section. Provide explanation below. Use and attach additional pages if necessary.

2022 CALIFORNIA MECHANICAL CODE 455

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-7A

Supply Fan VFD Acceptance
(Page 1 of 2)


Project Name/Address:



System Name or Identification/Tag:
System Location or Area Served:


Enforcement Agency:
Permit Number:


Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date


must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

  • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

  • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

  • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

    • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

    • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder provides to the building owner at occupancy.

Company Name: Phone:

Responsible Person’s Name: Responsible Person’s Signature:

License:
Date Signed: Position With Company (Title):

456 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-7A
Supply Fan VFD Acceptance
(Page 2 of 2)
Project Name/Address: Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:

Intent: Verify that the supply fan in a variable air volume application modulates to meet system airflow demand.

Construction Inspection

1 Instrumentation to perform test includes, but not limited to: a. Calibrated differential pressure gauge. 2 Installation. Discharge static pressure sensors are either factory calibrated or field-calibrated.

The static pressure location, setpoint, and reset control meets the requirements of Section E 805.7 E 805.7.2. 3 Documentation of all discharge static pressure sensors including (check one of the following): Field-calibrated. Calibration complete, all pressure sensors within 10% of calibrated reference sensor. through Section
A. Functional Testing. A. Functional Testing. Results
Step 1: Drive all VAV boxes to achieve design airflow.
a. Supply fan controls modulate to increase capacity. a. Supply fan controls modulate to increase capacity. Y / N
b. Supply fan maintains discharge static pressure within +/-10% of the current operating setpoint. b. Supply fan maintains discharge static pressure within +/-10% of the current operating setpoint. Y / N
c. Supply fan controls stabilize within a 5 minute period. c. Supply fan controls stabilize within a 5 minute period. Y / N
Step 2: Drive all VAV boxes to minimum flow.
a. Supply fan controls modulate to decrease capacity. a. Supply fan controls modulate to decrease capacity. Y / N
b. Current operating setpoint has decreased (for systems with DDC to the zone level). b. Current operating setpoint has decreased (for systems with DDC to the zone level). Y / N
c. Supply fan maintains discharge static pressure within +/-10% of the current operating setpoint. c. Supply fan maintains discharge static pressure within +/-10% of the current operating setpoint. Y / N
d. Supply fan controls stabilize within a 5 minute period. d. Supply fan controls stabilize within a 5 minute period. Y / N
Step 3: System returned to initial operating conditions. Y / N Y / N

B. Testing Results. PASS / FAIL

Step 1: Drive all VAV boxes to achieve design airflow. Step 2: Drive all VAV boxes to minimum flow.

C. PASS / FAIL Evaluation (check one):

PASS: All Construction Inspection responses are complete and all Testing Results responses are “Pass.”

FAIL: Any Construction Inspection responses are incomplete OR there is one or more “Fail” responses in Testing

Results section. Provide explanation below. Use and attach additional pages if necessary.

2022 CALIFORNIA MECHANICAL CODE 457

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-8A

Valve Leakage Test
(Page 1 of 2)


Project Name/Address:



System Name or Identification/Tag:
System Location or Area Served:


Enforcement Agency:
Permit Number:


Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date


must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

    • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

    • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

    • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

  • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

  • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder

provides to the building owner at occupancy.




Company Name:



Company Name:



Company Name:
Phone:


Responsible Person’s Name:


Responsible Person’s Name:
Responsible Person’s Signature: Responsible Person’s Signature:

License:
Date Signed: Position With Company (Title): Position With Company (Title):

458 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-8A
Valve Leakage Test
(Page 2 of 2)
Project Name/Address: Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:

Ensure that control valves serving variable flow systems are designed to withstand the pump pressure over the full range Intent: of operation.

Construction Inspection

1 Instrumentation to perform test includes, but not limited to: a. Calibrated differential pressure gauge. b. Pump curve submittals showing the shutoff head. 2 Installation. Valve and piping arrangements were installed per the design drawings.

A. Functional Testing.
Pump Tag (Id)
Results
Step 1: Determine pump dead head pressure.
a. Close pump discharge isolation valve. a. Close pump discharge isolation valve. Y / N
b. Measure and record the differential pump pressure. Feet Water
Column =
c. Record the shutoff head from the submittal. Feet Water
Column =
d. The measurement across the pump in step 1b is within 5% of the pump submittal in step 1c. d. The measurement across the pump in step 1b is within 5% of the pump submittal in step 1c. Y / N
e. Open pump discharge isolation valve.
e. Open pump discharge isolation valve.
Y / N
Step 2: Automatically close all valves on the systems being tested. If three-way valves are present, close off the
bypass line(s).
a. The 2-way valves automatically close. a. The 2-way valves automatically close. Y / N
b. Measure and record the differential pump pressure in feet of water column. Feet Water
Column =
c. The measurement across the pump in step 2b is within 5% of the measurement in step 1b. c. The measurement across the pump in step 2b is within 5% of the measurement in step 1b. Y / N
Step 3: System returned to initial operating conditions. Y / N Y / N

B. Testing Results. PASS / FAIL Step 1: Pressure measurement is within 5% of submittal data for all pumps. Step 2: Pressure measurements are within 5%.

C. PASS / FAIL Evaluation (check one):

PASS: All Construction Inspection responses are complete and all Testing Results responses are “Pass.”

FAIL: Any Construction Inspection responses are incomplete OR there is one or more “Fail” responses in Testing

Results section. Provide explanation below. Use and attach additional pages if necessary.

For SI units: 1 inch water column = 0.249 kPa

2022 CALIFORNIA MECHANICAL CODE 459

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-9A

Supply Water Temperature Reset Controls Acceptance
(Page 1 of 2)


Project Name/Address:



System Name or Identification/Tag:
System Location or Area Served:


Enforcement Agency:
Permit Number:


Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date


must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

  • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

  • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

Company Name:

Field Technician’s Name: Field Technician’s Signature:
Date Signed: Position with Company (Title):

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

  • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

  • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder provides to the building owner at occupancy.

Company Name: Phone:

Responsible Person’s Name: Responsible Person’s Signature:

License:
Date Signed: Position With Company (Title):

460 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-9A
Supply Water Temperature Reset Controls Acceptance
(Page 2 of 2)
Project Name/Address: Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:

Ensure that both the chilled water and hot water supply temperatures are automatically reset based on either building Intent: loads or outdoor air temperature, as indicated in the control sequences.

Construction Inspection 1 Instrumentation to perform test includes, but not limited to: a. Calibrated reference temperature sensor or drywell bath. 2 Installation Supply water temperature sensors have been either factory or field calibrated. 3 Documentation of hydronic system supply temperature sensors including (check one of the following): Field-calibrated Calibration complete, hydronic system supply temperature sensors within 1% of calibrated reference sensor or drywell bath.

A. Functional Testing.
Step 1: Test maximum reset value. Step 1: Test maximum reset value.
a. Change reset control variable to its maximum value. Y / N
b. Verify that chilled or hot water temperature setpoint is reset to appropriate value. Y / N
c. Verify that actual system temperature changes to within 2% of the new setpoint.
Y / N
Step 2: Test minimum reset value.
a. Change reset control variable to its minimum value. Y / N
b. Verify that chilled or hot water temperature setpoint is reset to appropriate value. Y / N
c. Verify that actual system temperature changes to within 2% of the new setpoint. Y / N
Step 3: Test maximum reset value. Step 3: Test maximum reset value.
a. Restore reset control variable to automatic control. Y / N
b. Verify that chilled or hot water temperature setpoint is reset to appropriate value. Y / N
c. Verify that actual supply temperature changes to meet setpoint. Y / N
d. Verify that actual supply temperature changes to within 2% of the new setpoint. Y / N

B. Testing Results. PASS / FAIL System passes criteria in 1c, 2c, and 3d.

2022 CALIFORNIA MECHANICAL CODE 461

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-10A

Hydronic System Variable Flow Control Acceptance
(Page 1 of 3)


Project Name/Address:



System Name or Identification/Tag:
System Location or Area Served:


Enforcement Agency:
Permit Number:


Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date


must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

  • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

    • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

    • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

  • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

  • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder

provides to the building owner at occupancy.




Company Name:



Company Name:



Company Name:
Phone:

Responsible Person’s Name:

Responsible Person’s Name:
Responsible Person’s Signature: Responsible Person’s Signature:
License: Date Signed: Position With Company (Title): Position With Company (Title):

462 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-10A
Hydronic System Variable Flow Control Acceptance
(Page 2 of 3)
Project Name/Address: Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:

Ensure that when loads within the building fluctuate, control valves modulate the amount of water passing through each Intent: coil and add or remove the desired amount of energy from the air stream to satisfy the load.

Construction Inspection

1.
Instrumentation to perform test includes, but not limited to:
a.
Calibrated differential pressure gauge.
2.
Installation

Pressure sensors are either factory calibrated or field-calibrated.

Pressure sensor location, setpoint, and reset control meets the requirements of
E 805.8.2.

Pressure sensor location, setpoint, and reset control meets the requirements of
E 805.8.2.
Section E 805.8 through Section Section E 805.8 through Section
3.
Documentation of all control pressure sensors including (check one of the following):
a.
Factory-calibrated (proof required).

Factory-calibration certificate.
b.
Field-calibrated.

Calibration complete, all pressure sensors within 10% of calibrated reference sensor.
A. Functional Testing. Results
Step 1: Design flow test.
a.
Open control valves to achieve a minimum of 90% of design flow.
b.
Verify that the pump speed increases.
c.
Are the pumps operating at 100% speed?
Y / N
Y / N
Y / N
d.
Record the system pressure as measured at the control sensor.
(Feet Water Column) = (Feet Water Column) =
e.
Record the system pressure setpoint.
(Feet Water Column) =
f.
Is the pressure reading 1d within 5% of pressure setpoint 1e?
g.
Did the system operation stabilize within 5 minutes after completion of step 1a?
e.
Record the system pressure setpoint.
(Feet Water Column) =
f.
Is the pressure reading 1d within 5% of pressure setpoint 1e?
g.
Did the system operation stabilize within 5 minutes after completion of step 1a?
e.
Record the system pressure setpoint.
(Feet Water Column) =
f.
Is the pressure reading 1d within 5% of pressure setpoint 1e?
g.
Did the system operation stabilize within 5 minutes after completion of step 1a?
Y / N
Y / N
Step 2: Low flow test
a.
Close coil control valves to achieve a maximum of 50% of design flow.
b.
Verify that the current operating speed decreases (for systems with DDC to the zone level).
c.
Verify that the current operating speed has not increased (for all other systems that are not DDC).
a.
Close coil control valves to achieve a maximum of 50% of design flow.
b.
Verify that the current operating speed decreases (for systems with DDC to the zone level).
c.
Verify that the current operating speed has not increased (for all other systems that are not DDC).
a.
Close coil control valves to achieve a maximum of 50% of design flow.
b.
Verify that the current operating speed decreases (for systems with DDC to the zone level).
c.
Verify that the current operating speed has not increased (for all other systems that are not DDC).
Y / N
Y / N
Y / N
d.
Record the system pressure as measured at the control sensor.
(Feet Water Column) = (Feet Water Column) =
e.
Record the system pressure setpoint.
(Feet Water Column) =
f.
Is the setpoint in 2e is less than the setpoint in 1d?
g.
Is the pressure reading 2d within 5% of pressure setpoint 2e?
h.
Did the system operation stabilize within 5 minutes after completion of step 2a?
e.
Record the system pressure setpoint.
(Feet Water Column) =
f.
Is the setpoint in 2e is less than the setpoint in 1d?
g.
Is the pressure reading 2d within 5% of pressure setpoint 2e?
h.
Did the system operation stabilize within 5 minutes after completion of step 2a?
e.
Record the system pressure setpoint.
(Feet Water Column) =
f.
Is the setpoint in 2e is less than the setpoint in 1d?
g.
Is the pressure reading 2d within 5% of pressure setpoint 2e?
h.
Did the system operation stabilize within 5 minutes after completion of step 2a?
Y / N
Y / N
Y / N
Step 3: System returned to initial operating conditions. Y / N
B. Testing Results PASS / FAIL PASS / FAIL
Step 1: Select pass if either 1c or 1f are true.
Step 2: Select pass if 2b, 2e, 2f and 2g are true.

For SI units: 1 inch water column = 0.249 kPa

2022 CALIFORNIA MECHANICAL CODE 463

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-10A
Hydronic System Variable Flow Control Acceptance (Page 3 of 3)
Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:
C. PASS / FAIL Evaluation (check one):
PASS: AllConstruction Inspection responses are complete and allTesting Results responses are “Pass.”
FAIL: AnyConstruction Inspection responses are incomplete_OR_ there is one or more “Fail” responses inTesting
Results section. Provide explanation below. Use and attach additional pages if necessary.

464 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-11A

Automatic Demand Shed Control Acceptance
(Page 1 of 2)


Project Name/Address:



System Name or Identification/Tag:
System Location or Area Served:


Enforcement Agency:
Permit Number:


Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date


must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

  • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

  • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

Company Name:

Field Technician’s Name: Field Technician’s Signature:
Date Signed: Position with Company (Title):

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

  • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

    • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

    • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder

provides to the building owner at occupancy.




Company Name:



Company Name:



Company Name:
Phone:

Responsible Person’s Name:

Responsible Person’s Name:
Responsible Person’s Signature: Responsible Person’s Signature:
License: Date Signed: Position With Company (Title): Position With Company (Title):

2022 CALIFORNIA MECHANICAL CODE 465

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-11A
Automatic Demand Shed Control Acceptance
(Page 2 of 2)
Project Name/Address: Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:

Intent: Ensure that the central demand shed sequences have been properly programmed into the DDC system.

Construction Inspection 1. Instrumentation to perform test includes, but not limited to: a. None. 2. Installation. The EMCS front end interface enables activation of the central demand shed controls.
A. Functional Testing.
Pump Tag (Id)
Step 1: Engage the demand shed controls.
a.
Engage the central demand shed control signal.
a.
Engage the central demand shed control signal.
Y / N
b.
Verify that the current operating temperature setpoint in a sample of noncritical spaces increases by
the proper amount.
b.
Verify that the current operating temperature setpoint in a sample of noncritical spaces increases by
the proper amount.
Y / N
c.
Verify that the current operating temperature setpoint in a sample of critical spaces does not change.
c.
Verify that the current operating temperature setpoint in a sample of critical spaces does not change.
Y / N
Step 2: Disengage the demand shed controls.
a.
Disengage the central demand shed control signal.
a.
Disengage the central demand shed control signal.
Y / N
b.
Verify that the current operating temperature setpoint in the sample of noncritical spaces returns to
their original value.
b.
Verify that the current operating temperature setpoint in the sample of noncritical spaces returns to
their original value.
Y / N
c.
Verify that the current operating temperature setpoint in the sample of critical spaces does not
change.
c.
Verify that the current operating temperature setpoint in the sample of critical spaces does not
change.
Y / N
Step 3: System returned to initial operating conditions.
B. Testing Results.
PASS Y / N
** FAIL**


Test passes if all answers are yes in Step 1 and Step 2.

C. PASS / FAIL Evaluation (check one):

PASS: All Construction Inspection responses are complete and all Testing Results responses are “Pass.”
FAIL: AnyConstruction Inspection responses are incomplete_OR_ there is one or more “Fail” responses in
Testing Results section. Provide explanation below. Use and attach additional pages if necessary.

466 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-12A


Fault Detection and Diagnostics (FDD) for Packaged Direct-Expansion Units


Fault Detection and Diagnostics (FDD) for Packaged Direct-Expansion Units
(Page 1 of 3)


Project Name/Address:


System Name or Identification/Tag:
System Location or Area Served:



Enforcement Agency:
Permit Number:


Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date


must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

    • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

    • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

    • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

Company Name:

Field Technician’s Name: Field Technician’s Signature:
Date Signed: Position with Company (Title):

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

  • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

  • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder

provides to the building owner at occupancy.




Company Name:



Company Name:



Company Name:
Phone:


Responsible Person’s Name:


Responsible Person’s Name:
Responsible Person’s Signature: Responsible Person’s Signature:

License:
Date Signed: Position With Company (Title): Position With Company (Title):

2022 CALIFORNIA MECHANICAL CODE 467

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-12A


Fault Detection and Diagnostics (FDD) for Packaged Direct-Expansion Units
(Page 2 of 3)


Project Name/Address:


System Name or Identification/Tag:
System Location or Area Served:



The purpose of this test is to verify proper fault detection and reporting for automated fault detection and
diagnostics systems for packaged units.
Intent:

Construction Inspection



1.
Instrumentation to perform test includes, but not limited to:
a.
List of instrumentation may be needed or included.
2.
Installation.





Verify that FDD hardware is installed on equipment by the manufacturer and that equipment make and model
include factory-installed FDD hardware that matches the information indicated on copies of the manufacturer’s cut
sheets and on the plans and specifications.


A. Eligibility Criteria Results.
Results














a.
A fault detection and diagnostics (FDD) system for direct-expansion packaged units shall contain the following
features to be eligible for credit in the performance calculation method:
b.
The unit shall include a factory-installed economizer and shall limit the economizer dead band to no
more than 2°F.
Y / N
c.
The unit shall include direct-drive actuators on outside air and return air dampers.
Y / N
d.
The unit shall include an integrated economizer with either differential dry-bulb or differential
enthalpy control.
Y / N
e.
The unit shall include a low temperature lockout on the compressor to prevent coil freeze-up or
comfort problems.
Y / N
f.
Outside air and return air dampers shall have maximum leakage rates conforming to Section E 805.12
through Section E 805.12.2.
Y / N
g.
The unit shall have an adjustable expansion control device such as a thermostatic expansion valve
(TXV).
Y / N
h.
To improve the ability to troubleshoot charge and compressor operation, a high-pressure refrigerant
port will be located on the liquid line. A low-pressure refrigerant port will be located on the suction line.
Y / N








i.
The following sensors should be permanently installed to monitor system operation and the controller
should have the capability of displaying the value of each parameter:
Refrigerant suction pressure
Supply air relative humidity
Return air temp
Supply air relative
Refrigerant suction temp
Outside air relative humidity Supply air temp
humidity
Liquid line pressure
Return air relative humidity
Outside air temp
j.
The controller will provide system status by indicating the following conditions:
Compressor enabled
Economizer enabled
Free cooling available
Heating enabled
Mixed air low limit cycle active
Y / N
Y / N

k.
The unit controller shall have the capability to manually initiate each operating mode so that the operation
of compressors, economizers, fans, and heating system can be independently tested and verified.
Y / N

For SI units: °C = (°F-32)/1.8

468 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-12A
Fault Detection and Diagnostics (FDD) for Packaged Direct-Expansion Units (Page 3 of 3)
Project Name/Address:
System Name or Identification/Tag:
System Location or Area Served:
B. Functional Testing. Results
Step 1: Low airflow test.
a. Test low airflow condition by replacing the existing filter with a dirty filter or appropriate obstruction.
b. Verify that the fault detection and diagnostics system reports the fault.
Y / N
c. Verify that the system is able to verify the correct refrigerant charge.
Y / N
d. Verify that you are able to calibrate the following:
Outside Air Temperature Sensor.
Return Air Temperature Sensors.
Supply Air Temperature Sensors.
Y / N
C. Testing Results PASS / FAIL PASS / FAIL
Test passes if all answers are yes underEligibility Criteria andFunctional Testing.

PASS: AllConstruction Inspection responses are complete and allTesting Results responses are “Pass.”

FAIL: AnyConstruction Inspection responses are incomplete_OR_ there is one or more “Fail” responses in
Testing Results section. Provide explanation below. Use and attach additional pages if necessary.

2022 CALIFORNIA MECHANICAL CODE 469

APPENDIX E

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

  • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

  • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

  • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

  • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder

provides to the building owner at occupancy.



Company Name:


Company Name:


Company Name:
Phone:


Responsible Person’s Name:


Responsible Person’s Name:
Responsible Person’s Signature: Responsible Person’s Signature:

License:
Date Signed: Position With Company (Title): Position With Company (Title):

470 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-13A



Automatic Fault Detection and Diagnostics (FDD) for Packaged Direct-Expansion Units and Zone
(Page 2 of 4)
Terminal Units Acceptance


Project Name/Address:


Project Name/Address:


System Name or Identification/Tag:
System Location or Area Served:


Intent: Verify that the system detects common faults in air handling units and zone terminal units.

Construction Inspection

  1. Instrumentation to perform test includes, but not limited to: a. No instrumentation is required – changes are implemented at the building automation system control station.
  2. Installation. a. The functional testing verifies proper installation of the controls for FDD for air handling units and zone terminal units. No additional installation checks are required.

Construction Inspection**

  1. Instrumentation to perform test includes, but not limited to: a. No instrumentation is required – changes are implemented at the building automation system control station.
  2. Installation. a. The functional testing verifies proper installation of the controls for FDD for air handling units and zone terminal units. No additional installation checks are required.
A. Eligibility Criteria Results. Results

Testing of each AHU with FDD controls shall include the following tests:


Step 1: Sensor Drift/Failure:


a.
Disconnect outside air temperature sensor from unit controller.
Y / N


b.
Verify that the FDD system reports a fault.
Y / N


c.
Connect OAT sensor to the unit controller.
Y / N


d.
Verify that FDD indicates normal system operation.
Y / N


Step 2: Damper/actuator fault.



a.
From the control system workstation, command the mixing box dampers to full open (100% outdoor
air).
Y / N

b.
Disconnect power to the actuator and verify that a fault is reported at the control workstation.
Y / N

c.
Reconnect power to the actuator and command the mixing box dampers to full open.
Y / N

d.
Verify that the control system does not report a fault.
Y / N


e.
From the control system workstation, command the mixing box dampers to a full-closed position
(0% outdoor air).
Y / N


f.
Disconnect power to the actuator and verify that a fault is reported at the control workstation.
Y / N


g.
Reconnect power to the actuator and command the dampers closed.
Y / N


h.
Verify that the control system does not report a fault during normal operation.
Y / N


Step 3: Valve/actuator fault.



a.
From the control system workstation, command the heating and cooling coil valves to full open or
closed, then disconnect power to the actuator and verify that a fault is reported at the control workstation.
Y / N


Step 4: Inappropriate simultaneous heating, mechanical cooling, and/or economizing.


a.
From the control system workstation, override the heating coil valve and verify that a fault is
reported at the control workstation.
Y / N


b.
From the control system workstation, override the cooling coil valve and verify that a fault is
reported at the control workstation.
Y / N

c.
From the control system workstation, override the mixing box dampers and verify that a fault is
reported at the control workstation.
Y / N

2022 CALIFORNIA MECHANICAL CODE 471

APPENDIX E

B. Functional Testing for Zone Terminal Units. Results



Testing shall be performed on one of each type of terminal unit (VAV box) in the project. A
minimum of 5% of results the terminal boxes shall be tested.


Step 1: Sensor Drift/Failure:


a.
Disconnect the tubing to the differential pressure sensor of the VAV box.
Y / N


b.
Verify that control system detects and reports the fault.
Y / N


c.
Reconnect the sensor and verify proper sensor operation.
Y / N

d.
Verify that the control system does not report a fault.
Y / N

Step 2: Damper/actuator fault.

If the damper is stuck open:

a.
Command the damper to be fully open (room temperature above setpoint).
Y / N

b.
Disconnect the actuator to the damper.
Y / N


c.
Adjust the cooling setpoint so that the room temperature is below the cooling setpoint to command
the damper to the minimum position. Verify that the control system reports a fault.
Y / N


d.
Reconnect the actuator and restore to normal operation.
Y / N


If the damper is stuck closed:


a.
Set the damper to the minimum position.
Y / N


b.
Disconnect the actuator to the damper.
Y / N


c.
Set the cooling setpoint below the room temperature to simulate a call for cooling. Verify that the
control system reports a fault.
Y / N

d.
Reconnect the actuator and restore to normal operation.
Y / N

Step 3: Valve/actuator fault (for systems with hydronic reheat).

a.
Command the reheat coil valve to full open.
Y / N



b.
Disconnect power to the actuator. Set the heating setpoint temperature to be lower than the current
space temperature, to command the valve closed. Verify that the fault is reported at the control work-
station.
Y / N


c.
Reconnect the actuator and restore normal operation.
Y / N


Step 4: Feedback loop tuning fault (unstable airflow).



a.
Set the integral coefficient of the box controller to a value 50 times the current value. Lower the
space cooling setpoint to simulate a call for cooling.
Y / N



b.
The damper cycles continuously and airflow is unstable. Verify that the control system detects and
reports the fault.
Y / N

c.
Reset the integral coefficient of the controller to the original value to restore normal operation.
Y / N

Step 5: Disconnected inlet duct.
a.
From the control system workstation, command the damper to full closed, then disconnect power to
the actuator and verify that a fault is reported at the control workstation.
Y / N

472 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

C. Testing Results PASS / FAIL

Test passes if all answers are yes under Functional Testing Sections .

D. PASS / FAIL Evaluation (check one):

PASS: All Construction Inspection responses are complete and all Testing Results responses are “Pass.”

FAIL: Any Construction Inspection responses are incomplete OR there is one or more “Fail” responses in

Testing Results section. Provide explanation below. Use and attach additional pages if necessary.

2022 CALIFORNIA MECHANICAL CODE 473

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-14A


Distributed Energy Storage DX AC Systems Acceptance
(Page 1 of 3)


Project Name/Address:


System Name or Identification/Tag:
System Location or Area Served:



Enforcement Agency:
Permit Number:


Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date


must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

  • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

  • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

  • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

    • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder

provides to the building owner at occupancy.




Company Name:



Company Name:



Company Name:
Phone:


Responsible Person’s Name:


Responsible Person’s Name:
Responsible Person’s Signature: Responsible Person’s Signature:
License: Date Signed: Position With Company (Title): Position With Company (Title):

474 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-14A
Distributed Energy Storage DX AC Systems Acceptance
(Page 2 of 3)
Project Name/Address: Project Name/Address:
System Name or Identification/Tag: System Location or Area Served:

Intent: Verify that the system detects common faults in air handling units and zone terminal units.

Construction Inspection

  1. Instrumentation to perform test includes, but not limited to: a. No special instrumentation is required to perform these tests.
  2. Installation. Prior to Performance Testing, verify and document the following: The water tank is filled to the proper level. The water tank is sitting on a foundation with adequate structural strength. The water tank is insulated and the top cover is in place. The DES/DXAC is installed correctly (refrigerant piping, etc.). Verify that the correct model number is installed and configured.

Installation. Prior to Performance Testing, verify and document the following: The water tank is filled to the proper level. The water tank is sitting on a foundation with adequate structural strength. The water tank is insulated and the top cover is in place. The DES/DXAC is installed correctly (refrigerant piping, etc.). Verify that the correct model number is installed and configured.

A. Functional Testing Results
Step 1: Simulate no cooling load during a nighttime period by setting system time to between 9:00 p.m. and 6:00 a.m.
Raise the space temperature setpoint above the current space temperature. Verify and document the
following:
a.
The system charges the tank.
Y / N
b.
The system does not provide cooling to the building.

Y / N
Step 2:
Simulate cooling load during daytime period (e.g., by setting time schedule to include actual time and placing
thermostat cooling set-point below actual temperature). Verify and document the following:
a.
Supply fan operates continually during occupied hours.
Y / N
b.
If the DES/DXAC has cooling capacity, DES/DXAC runs to meet the cooling demand (in ice melt
mode).
Y / N / N/A
c.
If the DES/DXAC has no ice and there is a call for cooling, the DES/DXAC runs in direct cooling
mode.
Y / N / N/A
Step 3: Simulate no cooling load during daytime condition. Verify and document the following:
a.
Supply fan operates as per the facility thermostat or control system.
Y / N
b.
The DES/DXAC and the condensing unit do not run.
Step 4: Simulate no cooling load during morning shoulder time period. Verify and document the following:
a.
The DES/DXAC is idle (the condensing unit and the refrigerant pumps remain off).
Y / N

B. Calibrating Controls. Results a. Verify that you are able to set the proper time and date, as per manufacturer’s installation manual for Y / N approved installers.

C. Testing Results. PASS / FAIL

Test passes if all answers are yes under Functional Testing and Calibrating Controls .

For SI units: 1 metric ton = 1000 kg, 1000 British thermal units per hour = 0.293 kW

2022 CALIFORNIA MECHANICAL CODE 475

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-14A


Distributed Energy Storage DX AC Systems Acceptance
(Page 3 of 3)


Project Name/Address:


Project Name/Address:


System Name or Identification/Tag:
System Location or Area Served:

PASS: All Construction Inspection responses are complete and all Testing Results responses are “Pass.”

FAIL: Any Construction Inspection responses are incomplete OR there is one or more “Fail” responses in

Testing Results section. Provide explanation below. Use and attach additional pages if necessary.

476 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

CERTIFICATE OF ACCEPTANCE MECH-15A


Thermal Energy Storage (TES) System Acceptance
(Page 1 of 3)


Project Name/Address:


System Name or Identification/Tag:
System Location or Area Served:



Enforcement Agency:
Permit Number:


Note: Submit one Certificate of Acceptance for each system that
Enforcement Agency Use: Checked by/Date


must demonstrate compliance.

FIELD TECHNICIAN’S DECLARATION STATEMENT

  • I certify under penalty of perjury the information provided on this form is true and correct.

  • I am the person who performed the acceptance requirements verification reported on this Certificate of Acceptance (Field Technician).

  • I certify that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

  • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the building permit(s) issued for the building.

Company Name:

Field Technician’s Name: Field Technician’s Signature:
Date Signed: Position with Company (Title):

RESPONSIBLE PERSON’S DECLARATION STATEMENT

  • I certify under penalty of perjury that I am the Field Technician, or the Field Technician is acting on my behalf as my employee or my agent and I have reviewed the information provided on this form.

  • I am a licensed contractor or registered design professional who is eligible per the requirements of the Authority Having Jurisdiction to take responsibility for the scope of work specified on this document and attest to the declarations in this statement (responsible person).

  • I certify that the information provided on this form substantiates that the construction/installation identified on this form complies with the acceptance requirements indicated in the plans and specifications approved by the enforcement agency, and conforms to the applicable acceptance requirements and procedures specified in Section E 801.0 through Section E 806.0.

    • I have confirmed that the Installation Certificate(s) for the construction/installation identified on this form has been completed and is posted or made available with the permit(s) issued for the building.

    • I will ensure that a completed, signed copy of this Certificate of Acceptance shall be posted, or made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a signed copy of this Certificate of Acceptance is required to be included with the documentation the builder

provides to the building owner at occupancy.

Company Name: Company Name: Company Name: Phone:
Responsible Person’s Name: Responsible Person’s Name: Responsible Person’s Signature: Responsible Person’s Signature:
License: Date Signed: Position With Company (Title): Position With Company (Title):

2022 CALIFORNIA MECHANICAL CODE 477

APPENDIX E

Intent: Verify proper operation of distributed energy storage DX systems.

Construction Inspection 1. Instrumentation to perform test includes, but not limited to: a. No special instrumentation is required for the acceptance tests.
A. Certificate of Compliance Information
The following Certificate of Compliance information for both the chiller and the storage tank shall be provided on the plans
to document the key TES System parameters and allow plan check comparison to the inputs used in the DOE-2 simulation.
DOE-2 keywords are shown in ALL CAPITALS in parentheses.
a.
Chiller
Brand and Model:
Type (centrifugal, reciprocating, etc):
Capacity (tons):
(Size)
Starting Efficiency (kW/ton):
(at beginning of ice production)
(COMP-kW/TON-START)
Ending Efficiency (kW/ton):
(at end of ice production)
(COMP-kW/TON-END)
Capacity Reduction (% / F):
(PER-COMP-REDUCT/F)
b.
Storage
Tank

Storage Type (Check):
(TES-TYPE)
Chilled Water
Storage
Ice-on-Coil Ice-on-Coil CHS
b.
Storage
Tank


Ice Harvester Ice Harvester Brine Brine
b.
Storage
Tank


Ice-Slurry Ice-Slurry Eutectic Salt Eutectic Salt
b.
Storage
Tank
Number of tanks (SIZE)
b.
Storage
Tank
Storage Capacity per Tank (ton-hours)
b.
Storage
Tank
Storage Rate (tons):
(COOL-STORE-RATE)
b.
Storage
Tank
Discharge Rate (tons):
(COOL-SUPPLY-RATE)
b.
Storage
Tank
Auxiliary Power (watts):
(PUMP+AUX-kW)
b.
Storage
Tank
Tank Area (square feet):
(CTANK-LOSS-COEFF)
b.
Storage
Tank
Tank Insulation (R-Value):
(CTANK-LOSS-COEFF)

For SI units: 1 metric ton = 1000 kg, 1000 British thermal units per hour = 0.293 kW

478 2022 CALIFORNIA MECHANICAL CODE

APPENDIX E

B. Functional Testing Results
Step 1: TES System Design Verification
a.
In the TES System Design Verification part, the installing contractor shall certify the
following information, which verifies proper installation of the TES System consistent
with system design expectations:

The TES system is one of the above
eligible systems

Initial charge rate of the storage
tanks (tons)

Final charge rate of the storage tank
(tons)

Tank standby storage losses (UA)

Initial discharge rate of the storage
tanks (tons)

Final discharge rate of the storage
tank (tons)

Charge test time (hours)

Initial chiller efficiency (kW/ton)
during charging

Discharge test time (hours)

Tank storage capacity after charge
(ton-hours)

Tank storage capacity after
discharge (ton-hours)

Final chiller efficiency (kW/ton)
during charging
Y / N
Y / N
Step 2: TES System Controls and Operation Verification
a.
The TES system and the chilled water plant is controlled and monitored by an EMS.

Pass
a.
The TES system and the chilled water plant is controlled and monitored by an EMS.

Fail
b.
Force the time between 9:00 p.m. and 9:00 a.m. and simulate a partial or no charge of the tank and
simulate no cooling load by setting the indoor temperature setpoint higher than the ambient tempera-
ture. Verify that the TES system starts charging (storing energy).

Pass
b.
Force the time between 9:00 p.m. and 9:00 a.m. and simulate a partial or no charge of the tank and
simulate no cooling load by setting the indoor temperature setpoint higher than the ambient tempera-
ture. Verify that the TES system starts charging (storing energy).

Fail
c.
Force the time to be between 6:00 p.m. and 9:00 p.m. and simulate a partial charge on the tank and
simulate a cooling load by setting the indoor temperature set point lower than the ambient tempera-
ture. Verify that the TES system starts discharging.

Pass
c.
Force the time to be between 6:00 p.m. and 9:00 p.m. and simulate a partial charge on the tank and
simulate a cooling load by setting the indoor temperature set point lower than the ambient tempera-
ture. Verify that the TES system starts discharging.

Fail
d.
Force the time to be between noon and 6:00 p.m. and simulate a cooling load by lowering the indoor
air temperature set point below the ambient temperature. Verify that the tank starts discharging and
the compressor is off. For systems designed to meet partial loads the system should be run until the
TES storage is fully depleted. The number of hours of operation must meet or exceed the designed
operational hours for the system.

Pass
d.
Force the time to be between noon and 6:00 p.m. and simulate a cooling load by lowering the indoor
air temperature set point below the ambient temperature. Verify that the tank starts discharging and
the compressor is off. For systems designed to meet partial loads the system should be run until the
TES storage is fully depleted. The number of hours of operation must meet or exceed the designed
operational hours for the system.

Fail
e.
Force the time to be between 9:00 a.m. to noon, and simulate a cooling load by lowering the indoor
air temperature set point below the ambient temperature. Verify that the tank does not discharge and
the cooling load is met by the compressor only.

Pass
e.
Force the time to be between 9:00 a.m. to noon, and simulate a cooling load by lowering the indoor
air temperature set point below the ambient temperature. Verify that the tank does not discharge and
the cooling load is met by the compressor only.

Fail
f.
Force the time to be between 9:00 p.m. and 9:00 a.m. and simulate a full tank charge by changing the
output of the sensor to the EMS. Verify that the tank charging is stopped.

Pass
f.
Force the time to be between 9:00 p.m. and 9:00 a.m. and simulate a full tank charge by changing the
output of the sensor to the EMS. Verify that the tank charging is stopped.

Fail
g.
Force the time to be between noon and 6:00 p.m. and simulate no cooling load by setting the indoor
temperature set point above the ambient temperature. Verify that the tank does not discharge and the
compressor is off.

Pass
g.
Force the time to be between noon and 6:00 p.m. and simulate no cooling load by setting the indoor
temperature set point above the ambient temperature. Verify that the tank does not discharge and the
compressor is off.

Fail

For SI units: 1 metric ton = 1000 kg, 1000 British thermal units per hour = 0.293 kW

2022 CALIFORNIA MECHANICAL CODE 479