Chapter 4 — VENTILATION AIR
California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Sections in this part
- 402.2 Natural Ventilation. [Not permitted for OSHPD
- 401.1 Applicability. This chapter contains requirements for
- 401.2 Filters. [BSC-CG], [DSA-SS & DSA-SS/CC] In
- 402.1 Occupiable Spaces. Occupiable spaces listed in
- 402.3 Mechanical Ventilation. [Not permitted for
- 402.4 Outdoor Air Intake Protection.
- 403.1 General. The design outdoor air intake flow rate for
- 403.2 Zone Calculations. Ventilation zone parameters
- 403.6 Design for Varying Operating Conditions.
- 403.3 Single-Zone Systems. For ventilation systems
- 403.4 One Hundred Percent Outdoor Air Systems.
- 403.5 Multiple-Zone Recirculating Systems.
- 403.7 Exhaust Ventilation.
- 403.8 Dynamic Reset. The system shall be permitted to
- 403.9 Air Classification and Recirculation. Air shall
- 404.1 General.
- 404.2 Average Outdoor Air Fraction.
- 404.3 Zone Ventilation Efficiency. The zone ventilation
- 405.1 General.
- 405.2 Ventilation Air Rate.
- 405.3 Bathroom Exhaust. A mechanical exhaust directly
- 405.4 Kitchen Exhaust. A mechanical exhaust directly to
- 405.5 Ventilation Openings. Occupiable spaces shall be
- 406.0 Evaporative Cooling System for Health Care
- 407.1 General.
- 407.2 Outdoor Air Intakes and Exhaust Outlets.
- 407.3 Air Balance.
- 407.4 Air Circulation.
- 407.5 Variable Air Volume.
- 407.6 Economizers. Systems with economizers shall include
- 408.1 General. Filter efficiencies shall be certified by the
- 408.2 Filters for Hospitals.
- 408.3 Filters for Skilled Nursing Facilities, Intermedi-
- 408.4 Filters for Outpatient Facilities.
- 409.1 Ducts which penetrate construction, intended for X-
- 409.2 Duct linings and their use shall meet the requirements
- 409.3 Insulation of Ducts. Cold air ducts shall be insu-
- 409.4 The anchorage and supporting structural elements for
- 410.1 Laboratory Ventilating Systems. Laboratory ven-
- 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
- 410.3 Laboratory Fume Hoods. Laboratory fume hoods
- 411.1 The air from dining areas may be used to ventilate the
- 412.1 Boiler, heater and electrical equipment rooms shall be
- 412.2 Floor surfaces in occupied spaces above such rooms
- 413.1 Rooms in areas where excessive heat or moisture is
- 413.2 Kitchen, morgues and laundries located inside a hos-
- 414.1 Exhaust Systems. A separate, dedicated exhaust
- 414.2 Air Distribution. The supply outlets and exhaust
- 415.1 Air Distribution. The supply outlets and exhaust and
- 416.1 An alarm system which is based on static pressure con-
- 416.2 Other acceptable alarm systems will be allowed when
- 416.3 [For OSHPD 4] For correctional treatment centers,
- 416.4 Prior to acceptance of the rooms, the alarm system
- 417.0 Testing and Balancing Airborne Infection Isola-
- 418.1 Air Changes. The ETO sterilization equipment room
- 418.2 Exhaust Requirements.
- 418.3 Ventilation Requirements.
- 418.4 Gas Valves. Installation of gas line hand valves at the
- 418.5 Alarm Systems. An Audible and visual alarm system
- 419.1 Formula Preparation Area. Air shall be supplied
- 419.2 Treatment Area/Room. Air shall be supplied over
- 420.0 Air Distribution Devices. [OSHPD 1, 2, 3, 4 & 5]
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
| Adopting Agency | BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting Agency | **BSC ** | BSC- CG |
SFM | 1 | 2 | 1-AC | **AC ** | SS | SS/CC | 1 | 1R | 2 | 3 | 4 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
| Adopt Entire Chapter | |||||||||||||||||||||||
| Adopt Entire Chapter as amended (amended sections listed below) |
X | X | **X ** | X | X | X | X | ||||||||||||||||
| Adopt only those sections that are listed below |
**X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| Chapter/Section | |||||||||||||||||||||||
| 401.0 | X | X | **X ** | **X ** | X | ||||||||||||||||||
| 401.1 | **X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| 401.2 with exception | X | X | X | ||||||||||||||||||||
| 401.2.1 | X | X | X | ||||||||||||||||||||
| 402.0 | **X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| 402.1 | X | X | **X ** | **X ** | **X ** | **X ** | **X ** | X | X | ||||||||||||||
| 402.2 | † | † | † | † | † | ||||||||||||||||||
| 402.1.2 | **X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| 402.3 | **X ** | X | † | † | † | † | † | ||||||||||||||||
| 403.0 | **X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| 403.7.2.1 – 403.7.2.4 | X | **X ** | X | ||||||||||||||||||||
| 405.3 | **X ** | X | |||||||||||||||||||||
| 406.0 | **X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| 407.0 and subsections | **X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| 408.0 and subsections | **X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| 409.0 and subsections | **X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| 410.0 and subsections | **X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| 411.0 and subsections | X | **X ** | **X ** | **X ** | X | ||||||||||||||||||
| 412.0 and subsections | X | **X ** | **X ** | **X ** | X | ||||||||||||||||||
| 413.0 and subsections | X | **X ** | **X ** | **X ** | X | ||||||||||||||||||
| 414.0 and subsections | X | **X ** | **X ** | **X ** | X | ||||||||||||||||||
| 415.0 and subsections | X | **X ** | **X ** | **X ** | X | ||||||||||||||||||
| 416.0 – 416.2 | X | **X ** | **X ** | **X ** | X | ||||||||||||||||||
| 416.3 | X | ||||||||||||||||||||||
| 416.4 | X | **X ** | **X ** | **X ** | X | ||||||||||||||||||
| 417.0 | X | **X ** | **X ** | **X ** | X | ||||||||||||||||||
| 418.0 and subsections | **X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| 419.0 and subsections | X | ||||||||||||||||||||||
| 420.0 | X | **X ** | **X ** | **X ** | X |
2022 CALIFORNIA MECHANICAL CODE 61
CALIFORNIA MECHANICAL CODE – MATRIX ADOPTION TABLE
CHAPTER 4 – VENTILATION AIR (continued) (Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
| Adopting Agency | BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting Agency | **BSC ** | BSC- CG |
SFM | 1 | 2 | 1-AC | **AC ** | SS | SS/CC | 1 | 1R | 2 | 3 | 4 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
| Adopt Entire Chapter | |||||||||||||||||||||||
| Adopt Entire Chapter as amended (amended sections listed below) |
X | X | **X ** | X | X | X | |||||||||||||||||
| Adopt only those sections that are listed below |
**X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| Chapter/Section | |||||||||||||||||||||||
| Table 4-A | **X ** | **X ** | **X ** | **X ** | **X ** | X | |||||||||||||||||
| Table 4-B | **X ** | X | **X ** | X | |||||||||||||||||||
| Table 4-C | X | X | |||||||||||||||||||||
| Table 402.1 | X | X | X | ||||||||||||||||||||
| Table 403.7_Notes 11 & 12_ | **X ** | X |
This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
62 2022 CALIFORNIA MECHANICAL CODE
CHAPTER 4
VENTILATION AIR
Where areas with prescribed ventilation rates in both Standards 62.1 and Table 4-A exist, the higher of the two air change rates shall be used. All supply-air, return air, and exhaust-air systems shall comply with ASHRAE 170. The text of ASHRAE 170 shall be modified as follows: (1) ASHRAE 170. Section 6.1.2.1 -- Not adopted. (2) ASHRAE 170. Section 6.3.2 -- Not adopted. (3) ASHRAE 170. Table 6.4 -- Not adopted. (4) ASHRAE 170. Section 6.4-6.4.4 -- Not adopted. (5) ASHRAE 170. Section 6.9 -- Not adopted. (6) ASHRAE 170. Section 7.1a -- Modify as follows:
Replace reference to Table 7.1 with reference to Table 4-A. (7) ASHRAE 170. Section 7.2.1a through e -- Not
adopted. (8) ASHRAE 170. Section 7.2.2 a through c, and e -- Not
adopted. (9) ASHRAE 170. Section 7.2.3 -- Not adopted. (10)ASHRAE 170. Section 7.3.1 -- Modify as follows:
Replace reference to Table 7.1 with reference to Table 4-A. (11) ASHRAE 170. Section 7.4.1 -- Modify as follows:
Delete the Exception that allows for high return grilles.
401.0 General.¶
402.0 Ventilation Air.¶
403.0 Ventilation Rates. [Not permitted for OSHPD 1,¶
2, 3, 4 & 5 spaces listed in Table 4-A]
404.0 Alternative Procedure for Multiple-Zone Sys-¶
tems Ventilation Efficiency.
405.0 Indoor Air Quality for Residential Occupan-¶
cies.
407.0 Ventilation System Details. [OSHPD 1, 1R, 2, 3, 4¶
& 5]
408.0 Filters. [OSHPD 1, 1R, 2, 3, 4 & 5]¶
409.0 Ducts. [OSHPD 1, 1R, 2, 3, 4 & 5]¶
410.0 Laboratory Ventilating Systems and Hoods.¶
[OSHPD 1, 1R, 2, 3, 4 & 5]
411.0 Kitchen and Dining Areas. [OSHPD 1, 2, 3, 4 & 5]¶
412.0 Boiler, Mechanical, and Electrical Rooms.¶
[OSHPD 1, 2, 3, 4 & 5]
413.0 Odorous Rooms. [OSHPD 1, 2, 3, 4 & 5]¶
414.0 Airborne Infection Isolation Rooms. [OSHPD¶
1, 2, 3, 4 & 5]
415.0 Protective Environment Rooms. [OSHPD 1, 2, 3,¶
4 & 5]
416.0 Alarms – Airborne Infection Isolation Rooms¶
and Protective Environment Rooms. [OSHPD 1, 2, 3, 4 & 5]
418.0 Design Requirements for Ethylene Oxide (ETO)¶
Sterilization Areas. [OSHPD 1, 1R, 2, 3, 4 & 5]
419.0 Neonatal Intensive Care Units. [OSHPD 1]¶
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
▸Chapter 4 — VENTILATION AIR
Overview- 402.2 Natural Ventilation. [Not permitted for OSHPD
- 401.1 Applicability. This chapter contains requirements for
- 401.2 Filters. [BSC-CG], [DSA-SS & DSA-SS/CC] In
- 402.1 Occupiable Spaces. Occupiable spaces listed in
- 402.3 Mechanical Ventilation. [Not permitted for
- 402.4 Outdoor Air Intake Protection. Required outdoorair intak…
- 403.1 General. The design outdoor air intake flow rate for
- 403.2 Zone Calculations. Ventilation zone parameters
- 403.6 Design for Varying Operating Conditions. Ventilation sys…
- 403.3 Single-Zone Systems. For ventilation systems
- 403.4 One Hundred Percent Outdoor Air Systems.
- 403.5 Multiple-Zone Recirculating Systems. For ventilation sys…
- 403.7 Exhaust Ventilation. Exhaust airflow shall be provided i…
- 403.8 Dynamic Reset. The system shall be permitted to
- 403.9 Air Classification and Recirculation. Air shall
- 404.1 General. This section presents an alternative procedure …
- 404.2 Average Outdoor Air Fraction. The average outdoor air fr…
- 404.3 Zone Ventilation Efficiency. The zone ventilation
- 405.1 General. Rooms or occupied spaces within residential occ…
- 405.2 Ventilation Air Rate. The required mechanical ventilatio…
- 405.3 Bathroom Exhaust. A mechanical exhaust directly
- 405.4 Kitchen Exhaust. A mechanical exhaust directly to
- 405.5 Ventilation Openings. Occupiable spaces shall be
- 406.0 Evaporative Cooling System for Health Care
- 407.1 General.
- 407.2 Outdoor Air Intakes and Exhaust Outlets.
- 407.3 Air Balance.
- 407.4 Air Circulation.
- 407.5 Variable Air Volume.
- 407.6 Economizers. Systems with economizers shall include
- 408.1 General. Filter efficiencies shall be certified by the
- 408.2 Filters for Hospitals.
- 408.3 Filters for Skilled Nursing Facilities, Intermedi-
- 408.4 Filters for Outpatient Facilities.
- 409.1 Ducts which penetrate construction, intended for X-
- 409.2 Duct linings and their use shall meet the requirements
- 409.3 Insulation of Ducts. Cold air ducts shall be insu-
- 409.4 The anchorage and supporting structural elements for
- 410.1 Laboratory Ventilating Systems. Laboratory ven-
- 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
- 410.3 Laboratory Fume Hoods. Laboratory fume hoods
- 411.1 The air from dining areas may be used to ventilate the
- 412.1 Boiler, heater and electrical equipment rooms shall be
- 412.2 Floor surfaces in occupied spaces above such rooms
- 413.1 Rooms in areas where excessive heat or moisture is
- 413.2 Kitchen, morgues and laundries located inside a hos-
- 414.1 Exhaust Systems. A separate, dedicated exhaust
- 414.2 Air Distribution. The supply outlets and exhaust
- 415.1 Air Distribution. The supply outlets and exhaust and
- 416.1 An alarm system which is based on static pressure con-
- 416.2 Other acceptable alarm systems will be allowed when
- 416.3 [For OSHPD 4] For correctional treatment centers,
- 416.4 Prior to acceptance of the rooms, the alarm system
- 417.0 Testing and Balancing Airborne Infection Isola-
- 418.1 Air Changes. The ETO sterilization equipment room
- 418.2 Exhaust Requirements.
- 418.3 Ventilation Requirements.
- 418.4 Gas Valves. Installation of gas line hand valves at the
- 418.5 Alarm Systems. An Audible and visual alarm system
- 419.1 Formula Preparation Area. Air shall be supplied
- 419.2 Treatment Area/Room. Air shall be supplied over
- 420.0 Air Distribution Devices. [OSHPD 1, 2, 3, 4 & 5]
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — GEOTHERMAL ENERGY SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE