Chapter 4 — VENTILATION AIR

420.0 Air Distribution Devices. [OSHPD 1, 2, 3, 4 & 5]

California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

All air distribution devices and supply air outlets shall meet the requirements of ASHRAE 170-2013, Section 6.7.2 and Table 6.7.2.

2022 CALIFORNIA MECHANICAL CODE 73

VENTILATION AIR

TABLE 4-A PRESSURE RELATIONSHIP AND VENTILATION REQUIREMENTS FOR GENERAL ACUTE CARE HOSPITALS, SKILLED NURSING FACILITIES, INTERMEDIATE CARE FACILITIES, CORRECTIONAL

TREATMENT CENTERS, OUTPATIENT FACILITIES, AND LICENSED CLINICS

>
FUNCTION OR SPACE PRESSURE
RELATIONSHIP
TO ADJACENT
AREAS (f) (n)
MINIMUM
OUTDOOR
ACH
MINIMUM
TOTAL
ACH
ALL ROOM AIR
EXHAUSTED
DIRECTLY TO
OUTDOORS (j)
AIR
RECIRCULATED
BY MEANS
OF ROOM UNITS
(a)
DESIGN
RELATIVE
HUMIDITY(k),
%
DESIGN
TEMPERATURE
(l),°F/°C
Airborne infection isolation
anteroom (u)
(e) NR 10 Yes No NR NR
Airborne infection isolation
room (u)
Negative 2 12 Yes No max 60 70-75/21-24
Airborne infection isolation
treatment/exam room
Negative 2 12 Yes No NR NR
Angiography room Positive 3 15 NR NR max 60 70-75/21-24
Bathing room Negative NR 10 Yes No NR 70-75/21-24
Bathroom Negative NR 10 Yes No NR 72-78/22-26
Bedpan room Negative NR 10 Yes No NR NR
Blood bank/tissue storage NR 2 6 NR NR NR NR
Blood draw/phlebotomy NR 2 6 NR NR NR NR
Bronchoscopy, sputum
collection, and pentamidine
administration (n)
Negative 2 12 Yes No NR 68-73/20-23
Cardiac catheterization lab Positive 3 15 NR No max 60 70-75/21-24
Clean linen storage Positive NR 2 NR NR NR 72-78/22-26
Clean workroom (central med-
ical and surgical supply space)
Positive 2 4 NR No max 60 72-78/22-26
Clean workroom or clean hold-
ing (support)
Positive 2 4 NR NR NR NR
Critical and intensive care NR 2 6 NR No 30-60 70-75/21-24
CT Scan NR 2 6 NR NR max 60 NR
Darkroom (g) Negative 2 10 Yes No NR NR
Delivery room (caesarean) (m),
(n), (o)
Positive 4 20 NR No 20-60 68-75/20-24
Dialysis treatment area NR 2 6 NR NR NR 72-78/22-26
Dialyzer reprocessing room Negative NR 10 Yes No NR NR
Dietary storage NR NR 2 NR No NR 72-78/22-26
Electroconvulsive therapy pro-
cedure room
P 3 15 NR NR NR NR
Emergency department
exam/treatment room (p)
NR 2 6 NR NR max 60 70-75/21-24
Endoscope cleaning Negative 2 10 Yes No NR NR
ER decontamination Negative 2 12 Yes No NR NR
ER waiting rooms Negative 2 12 Yes (q) NR max 65 70-75/21-24
Examination room NR 2 6 NR NR max 60 70-75/21-24
Fast track room NR 2 6 NR NR NR NR
Fluoroscopy room Negative 2 6 Yes No NR NR
Food preparation center (i) NR 2 10 NR No NR 72-78/22-26
Gastrointestinal endoscopy pro-
cedure room (x)
NR 2 6 NR No 20-60 68-73/20-23
Hazardous material storage Negative 2 10 Yes No NR NR
Hydrotherapy Negative 2 6 NR NR NR 72-80/22-27
Infusion room Positive 2 6 NR NR NR NR
Intermediate care (s) NR 2 6 NR NR max 60 70-75/21-24
Interventional imaging
procedure room
Positive 5 15 NR NR NR NR

74 2022 CALIFORNIA MECHANICAL CODE

VENTILATION AIR

TABLE 4-A (continued) PRESSURE RELATIONSHIP AND VENTILATION REQUIREMENTS FOR GENERAL ACUTE CARE HOSPITALS, SKILLED NURSING FACILITIES, INTERMEDIATE CARE FACILITIES, CORRECTIONAL

TREATMENT CENTERS, OUTPATIENT FACILITIES, AND LICENSED CLINICS

FUNCTION OR SPACE PRESSURE
RELATIONSHIP
TO ADJACENT
AREAS (f) (n)
MINIMUM
OUTDOOR
ACH
MINIMUM
TOTAL
ACH
ALL ROOM AIR
EXHAUSTED
DIRECTLY TO
OUTDOORS (j)
AIR
RECIRCULATED
BY MEANS
OF ROOM UNITS
(a)
DESIGN
RELATIVE
HUMIDITY(k),
%
DESIGN
TEMPERATURE
(l),°F/°C
IV Prep. room Positive 2 6 NR NR NR NR
Janitor’s closet,housekeeping Negative NR 10 Yes No NR NR
Labor/delivery/recovery (LDR)
(s)
NR 2 6 NR NR max 60 70-75/21-24
Labor/delivery/recovery/
postpartum (LDRP) (s)
NR 2 6 NR NR max 60 70-75/21-24
Laboratory, bacteriology (v) Negative 2 6 Yes NR NR 70-75/21-24
Laboratory, biochemistry (v) Negative 2 6 Yes NR NR 70-75/21-24
Laboratory, cytology (v) Negative 2 6 Yes NR NR 70-75/21-24
Laboratory, general (v) Negative 2 6 NR NR NR 70-75/21-24
Laboratory, glasswashing Negative 2 10 Yes NR NR NR
Laboratory, histology (v) Negative 2 6 Yes NR NR 70-75/21-24
Laboratory, infectious disease
and virus
Negative 2 6 Yes NR NR 70-75/21-24
Laboratory, media transfer (v) Positive 2 4 NR NR NR 70-75/21-24
Laboratory, microbiology (v) Negative 2 6 Yes NR NR 70-75/21-24
Laboratory, nuclear medicine (v) Negative 2 6 Yes NR NR 70-75/21-24
Laboratory, pathology (v) Negative 2 6 Yes NR NR 70-75/21-24
Laboratory, serology (v) Negative 2 6 Yes NR NR 70-75/21-24
Laboratory, sterilizing Negative 2 10 Yes NR NR 70-75/21-24
Lactation NR 2 6 NR NR NR NR
Laser eye room Positive 3 15 NR No 20-60 70-75/21-24
Laundry, general Negative 2 10 Yes No NR NR
Linen and trash chute room Negative NR 10 Yes No NR NR
Medical/anesthesia gas
storage (r)
Negative NR 8 Yes NR NR NR
Medication room NR 2 4 NR NR max 60 70-75/21-24
_Morgues and_autopsy room (n) Negative 2 12 Yes No NR 68-75/20-24
MRI room NR 2 6 NR NR NR NR
Negative-pressure x-ray room Negative 2 12 Yes No max 60 72-78/22-26
Newborn intensive care Positive 2 6 NR No 30-60 72-78/22-26
Newborn intensive care
formula room
P 2 10 NR No NR NR
Newborn/well baby nursery
suite
NR 2 6 NR No 30-60 72-78/22-26
Nonrefrigerated body-holding
room (h)
Negative NR 10 Yes No NR 70-75/21-24
Nourishment area or room NR NR 2 NR NR NR NR
Nuclear medicine (Gamma,
PET, SPECT)
Negative 2 6 Yes No NR NR
Nuclear medicine hot lab Negative NR 6 Yes No NR 70-75/21-24
Nuclear medicine treatment
room
Negative 2 6 Yes NR NR 70-75/21-24
Nurse station (aa) (aa) (aa) 2 (aa) (aa) (aa) (aa)
Observation NR 2 6 NR NR NR 70-75/21-24
Occupational therapy NR 2 6 NR NR NR 70-75/21-24
Operating room,hybrid
operating room (m), (n), (o)
Positive 4 20 NR No 20-60 68-75/20-24

2022 CALIFORNIA MECHANICAL CODE 75

VENTILATION AIR

TABLE 4-A (continued) PRESSURE RELATIONSHIP AND VENTILATION REQUIREMENTS FOR GENERAL ACUTE CARE HOSPITALS, SKILLED NURSING FACILITIES, INTERMEDIATE CARE FACILITIES, CORRECTIONAL

TREATMENT CENTERS, OUTPATIENT FACILITIES, AND LICENSED CLINICS

FUNCTION OR SPACE PRESSURE
RELATIONSHIP
TO ADJACENT
AREAS (f) (n)
MINIMUM
OUTDOOR
ACH
MINIMUM
TOTAL
ACH
ALL ROOM AIR
EXHAUSTED
DIRECTLY TO
OUTDOORS (j)
AIR
RECIRCULATED
BY MEANS
OF ROOM UNITS
(a)
DESIGN
RELATIVE
HUMIDITY(k),
%
DESIGN
TEMPERATURE
(l),°F/°C
Operating/surgical cystoscopic
room (m), (n), (o)
Positive 4 20 NR No 20-60 68-75/20-24
Patient corridor NR NR 2 NR NR NR NR
Patient holding preparation NR 2 6 NR No NR NR
Patient room NR 2 4 (y) NR NR max 60 70-75/21-24
Pediatric play area NR 2 6 NR NR NR NR
Pharmacy (b) Positive 2 4 NR NR NR NR
Drug room NR 2 4 NR NR NR NR
HD ante room (b) Positive NR NR NR NR <60 ≤68/≤20
HD buffer room (b) Negative NR 30 Yes No <60 ≤68/≤20
HD segregated
compounding area (ab)
Negative NR 12 Yes NR NR NR
HD storage (b) Negative NR 12 Yes NR NR NR
Non-HD ante room (b) Positive NR 30 NR NR <60 ≤68/≤20
Non-HD buffer room (b) Positive NR 30 NR No <60 ≤68/≤20
Non-HD segregated
compounding area
NR NR NR NR NR NR NR
Physical therapy (nursing facil-
ity)
Negative 2 6 NR NR NR 70-75/21-24
Physical therapy (diagnostic and
treatment)
Negative 2 6 NR NR max 65 72-80/22-27
Post-anesthesia care unit NR 2 6 Yes No 20-60 70-75/21-24
Pre-screening area Negative 2 12 Yes (q) NR NR NR
Procedure room (o), (d) Positive 3 15 NR No 20-60 70-75/21-24
Protective environment
anteroom (t)
(e) NR 10 NR No NR NR
Protective environment
room (t)
Positive 2 12 NR No max 60 70-75/21-24
Radiology waiting rooms Negative 2 12 Yes (q), (w) NR max 60 70-75/21-24
Recovery room NR 2 6 NR No 20-60 70-75/21-24
Recreation/activity room NR 2 6 NR NR NR NR
Resident gathering/activity/din-
ing (nursing facility)
NR 4 4 NR NR NR 70-75/21-24
Resident room
(nursing facility)
NR 2 2 NR NR NR 70-75/21-24
Resident unit corridor
(nursing facility)
NR NR 4 NR NR NR NR
Seclusion room NR 2 6 NR NR NR NR
Semi-restricted corridor NR 2 4 NR NR NR NR
Shower room Negative NR 10 Yes No NR NR
Soiled linen sorting and storage Negative NR 10 Yes No NR NR
Soiled or decontamination room Negative 2 6 Yes No NR 72-78/22-26
Soiled workroom or soiled hold-
ing,utility room
Negative 2 10 Yes No NR NR
Special purpose room
(SNF & ICF only)
NR 2 6 Yes NR NR NR
Speech therapy/audiology room NR 2 6 NR NR NR NR
Sterile storage Positive 2 4 NR NR max 60 72-78/22-26

76 2022 CALIFORNIA MECHANICAL CODE

VENTILATION AIR

TABLE 4-A (continued) PRESSURE RELATIONSHIP AND VENTILATION REQUIREMENTS FOR GENERAL ACUTE CARE HOSPITALS, SKILLED NURSING FACILITIES, INTERMEDIATE CARE FACILITIES, CORRECTIONAL

TREATMENT CENTERS, OUTPATIENT FACILITIES, AND LICENSED CLINICS

FUNCTION OR SPACE PRESSURE
RELATIONSHIP
TO ADJACENT
AREAS (f) (n)
MINIMUM
OUTDOOR
ACH
MINIMUM
TOTAL
ACH
ALL ROOM AIR
EXHAUSTED
DIRECTLY TO
OUTDOORS (j)
AIR
RECIRCULATED
BY MEANS
OF ROOM UNITS
(a)
DESIGN
RELATIVE
HUMIDITY(k),
%
DESIGN
TEMPERATURE
(l),°F/°C
Sterilizer equipment room Negative NR 10 Yes No NR NR
Substerile service area NR 2 6 NR No NR NR
Toilet room Negative NR 10 Yes No NR NR
Trauma/cardiac room
(crisis or shock) (c)
Positive 3 15 NR No 20-60 70-75/21-24
Treatment room
(surgery and critical care) (p)
NR 2 6 NR NR 20-60 70-75/21-24
Treatment room (diagnostic and
treatment) (x)
NR 2 6 NR NR max 60 70-75/21-24
Triage Negative 2 12 Yes (q) NR max 60 70-75/21-24
Ultrasound room NR 2 6 NR NR NR NR
Unsterile supply NR 2 2 NR NR NR NR
Waiting area
(nuclear medicine)
Negative 2 12 Yes No NR NR
Waiting area primary care clinic Negative 2 10 Yes(q) NR NR NR
Warewashing Negative NR 10 Yes No NR NR
Wound intensive care
(burn unit)
NR 2 6 NR No 40-60 70-75/21-24
X-ray (diagnostic and
treatment)
NR 2 6 NR NR max 60 72-78/22-26
X-ray (surgery/critical care and
catheterization)
Positive 3 15 NR No max 60 70-75/21-24

Note: NR = No requirement Notes for Table 4-A: a. Except where indicated by a “No” in this column, recirculating room HVAC units (with heating or cooling coils) are acceptable for providing that portion

of the minimum total air changes per hour that is permitted by Section 407.4.1.7 . Because of the cleaning difficulty and potential for buildup of contamination, recirculating room units shall not be used in areas marked “No.” Recirculating devices with HEPA filters shall be permitted in existing facilities as interim, supplemental environmental controls to meet requirements for the control of airborne infectious agents. The design of either portable or fixed systems should prevent stagnation and short circuiting of airflow. The design of such systems shall also allow for easy access for scheduled preventative maintenance and cleaning. b. Additional air change, ISO class, continuous pressure monitoring and filtering requirements for compounding areas shall comply with California Board of

rne infectious agents. The design of either portable or fixed systems should prevent stagnation and short circuiting of airflow. The design of such systems shall also allow for easy access for scheduled preventative maintenance and cleaning. b. Additional air change, ISO class, continuous pressure monitoring and filtering requirements for compounding areas shall comply with California Board of

Pharmacy regulations Title 16 §1735 & §1751, and USP <797> & <800>. Air supplied to the compounding buffer room and ante room must be introduced through 99.97% minimum HEPA filters located in the ceiling. At least 15 air changes per hour (ACPH) shall be provided to nonhazardous drug (non-HD) compounding buffer rooms through the ceiling. The HEPA filtered air from the PEC in the non-HD buffer room, when added to the HVAC-supplied HEPA- filtered air, shall increase the total HEPA-filtered ACPH to at least 30. If the PEC is used to meet the minimum total ACPH requirements, the PEC must not be turned off except for maintenance. All hazardous drug (HD) compounding areas and PECs shall be exhausted externally through 99.97% HEPA filtration. For both hazardous and non-hazardous compounding, minimum air changes shall be met under dynamic operating conditions as defined by USP. Returns and exhaust grilles shall be mounted low on the wall unless a visual smoke study demonstrates dilution of particles and sweeping out of particles from the entire room. One return/exhaust should be placed near the refrigerator compressor. Anteroom shall have a minimum pressure differential of +0.02 inches water column in relation to the adjacent, non-compounding spaces. Non-HD buffer room shall have a pressure differential of +0.02 to +0.05 inches water column in relation to the anteroom. HD buffer room shall have a pressure differential of -0.01 to -0.03 inches water column in relation to the anteroom. c. The term trauma room as used herein is a first-aid room and/or emergency room used for general initial treatment of accident victims. The operating room

within the trauma center that is routinely used for emergency surgery is considered to be an operating room by this standard. d. Pressure relationships need not be maintained when the room is unoccupied. e. See Section 7.2 of ASHRAE 170 and its subsections for pressure-relationship requirements. f. For operating rooms, cardiac catheterization labs, angiography rooms, cystoscopy rooms, delivery rooms, cesarean operating rooms, newborn intensive care,

rgency surgery is considered to be an operating room by this standard. d. Pressure relationships need not be maintained when the room is unoccupied. e. See Section 7.2 of ASHRAE 170 and its subsections for pressure-relationship requirements. f. For operating rooms, cardiac catheterization labs, angiography rooms, cystoscopy rooms, delivery rooms, cesarean operating rooms, newborn intensive care,

and nurseries provide approximately 15% excess supply air to the room or a sufficient quantity of excess supply air to maintain an appropriate positive air balance based on the room tightness and number of doors. For all rooms not listed in this footnote or not listed in Section 322.0 requiring either a positive or negative air balance, provide approximately 10% differential cfm between supply and return/exhaust airflow but not less than 25 cfm differential shall be provided regardless of room size. Room function, size, and tightness may be considered when determining the differential airflow required. Where continuous directional control is not required, variations between supply cfm and return or exhaust cfm shall be minimized in accordance with Section 407.4.1.3. g. All air need not be exhausted if darkroom equipment has a scavenging exhaust duct attached and meets ventilation standards regarding NIOSH, OSHA, and

local employee exposure limits. 2, 3

2022 CALIFORNIA MECHANICAL CODE 77

VENTILATION AIR

h. A nonrefrigerated body-holding room is applicable only to facilities that do not perform autopsies on-site and use the space for short periods while waiting

for the body to be transferred. i. Minimum total air changes per hour (ach) shall be that required to provide proper makeup air to kitchen exhaust systems as specified in ANSI/ASHRAE Standard 154. 4 In some cases, excess exfiltration or infiltration to or from exit corridors compromises the exit corridor restrictions of NFPA 90A, 5 the pressure requirements of NFPA 96, 6 or the maximum defined in the table. During operation, a reduction to the number of air changes to any extent required for odor control shall be permitted when the space is not in use. (See FGI [2010] in Informative Appendix B.) j. In some areas with potential contamination and/or odor problems, exhaust air shall be discharged directly to the outdoors and not recirculated to other areas. Individual circumstances may require special consideration for air exhausted to the outdoors. To satisfy exhaust needs, constant replacement air from the outdoors is necessary when the system is in operation. k. The RH ranges listed are the minimum and/or maximum allowable at any point within the design temperature range required for that space. l. Systems shall be capable of maintaining the rooms within the range during normal operation. Lower or higher temperature shall be permitted when patients’ comfort and/or medical conditions require those conditions. m. National Institute for Occupational Safety and Health (NIOSH) criteria documents regarding occupational exposure to waste anesthetic gases and vapors, and

required for that space. l. Systems shall be capable of maintaining the rooms within the range during normal operation. Lower or higher temperature shall be permitted when patients’ comfort and/or medical conditions require those conditions. m. National Institute for Occupational Safety and Health (NIOSH) criteria documents regarding occupational exposure to waste anesthetic gases and vapors, and

control of occupational exposure to nitrous oxide 7 indicate a need for both local exhaust (scavenging) systems and general ventilation of the areas in which the respective gases are utilized. Refer to NFPA 99 for other requirements. 8 n. If pressure-monitoring device alarms are installed, allowances shall be made to prevent nuisance alarms. Short-term excursions from required pressure rela tionships shall be allowed while doors are moving or temporarily open. Simple visual methods such as smoke trail, ball-in-tube, or flutterstrip shall be permitted for verification of airflow direction. o. Surgeons or surgical procedures may require room temperatures, ventilation rates, humidity ranges, and/or air distribution methods that exceed the minimum

indicated ranges. p. Treatment rooms used for bronchoscopy shall be treated as bronchoscopy rooms. Treatment rooms used for procedures with nitrous oxide shall contain pro visions for exhausting anesthetic waste gases. q. In a recirculating ventilation system, HEPA filters shall be permitted instead of exhausting the air from these spaces to the outdoors provided that the return

air passes through the HEPA filters before it is introduced into any other spaces. The entire minimum total air changes per hour of recirculating airflow shall pass through HEPA filters. When these areas are open to larger, nonwaiting spaces, the exhaust air volume shall be calculated based on the seating area of the waiting area. ( Note: The intent here is to not require the volume calculation to include a very large space [e.g., an atrium] just because a waiting area opens onto it.) r. See NFPA 99 for further requirements. 8 s. For intermediate care, labor/delivery/recovery rooms, and labor/delivery/recovery/postpartum rooms, four total ach shall be permitted when supplemental

ting area of the waiting area. ( Note: The intent here is to not require the volume calculation to include a very large space [e.g., an atrium] just because a waiting area opens onto it.) r. See NFPA 99 for further requirements. 8 s. For intermediate care, labor/delivery/recovery rooms, and labor/delivery/recovery/postpartum rooms, four total ach shall be permitted when supplemental

heating and/or cooling systems (radiant heating and cooling, baseboard heating, etc.) are used. t. The protective environment airflow design specifications protect the patient from common environmental airborne infectious microbes (i.e., Aspergillus spores). The anteroom shall have negative air pressure in relation to the protective environment room. A door louver, transfer grille, or other acceptable means may be provided to allow for airflow from the protective environment room to the anteroom. The protective environment room shall have positive- pressure in relation to the anteroom and adjoining toilet room. Recirculation HEPA filters shall be permitted to increase the equivalent room air exchanges; however, the outdoor air changes are still required. Constant-volume airflow is required for consistent ventilation for the protected environment. The pressure relationship to adjacent areas shall remain unchanged if the PE room is utilized as a normal patient room. Rooms with reversible airflow provisions for the purpose of switching between protective environment and AII functions shall not be permitted. u. The AII room described in this standard shall be used for isolating the airborne spread of infectious diseases, such as measles, varicella, or tuberculosis. The

djacent areas shall remain unchanged if the PE room is utilized as a normal patient room. Rooms with reversible airflow provisions for the purpose of switching between protective environment and AII functions shall not be permitted. u. The AII room described in this standard shall be used for isolating the airborne spread of infectious diseases, such as measles, varicella, or tuberculosis. The

airborne infection isolation room shall have negative pressure in relation to the anteroom, and the adjoining toilet room shall have negative pressure in rela- tion to the airborne infection isolation room. Supplemental recirculating devices using HEPA filters shall be permitted in the AII room to increase the equivalent room air exchanges; however, the minimum outdoor air changes of Table 4-A are still required. AII rooms that are retrofitted from standard patient rooms from which it is impractical to exhaust directly outdoors may be recirculated with air from the AII room, provided that air first passes through a HEPA filter. When the AII room is not utilized for airborne infection isolation, the pressure relationship to adjacent areas, when measured with the door closed, shall remain unchanged and the minimum total air change rate shall be 6 ach. Switching controls for reversible airflow provisions shall not be permitted. The anteroom shall have positive air pressure in relation to the airborne infection isolation room. A door louver, transfer grille, or other acceptable means may be provided to allow for airflow from the anteroom to the airborne infection isolation room. v. When required, appropriate hoods and exhaust devices for the removal of noxious gases or chemical vapors shall be provided in accordance with NFPA 99. 8 w. The requirement that all room air is exhausted directly to outdoors applies only to radiology waiting rooms programmed to hold patients who are waiting for

chest x-rays for diagnosis of respiratory disease. x. If the planned space is designated in the organization’s operational plan to be utilized for both bronchoscopy and gastrointestinal endoscopy, the design param eters for “bronchoscopy, sputum collection, and pentamidine administration” shall be used. y. For single-bed patient rooms using Group D diffusers, a minimum of six total ach shall be provided and calculated based on the volume from finished floor

to 6 ft (1.83 m) above the floor. z. This table is based on Table 7.1 in ASHRAE 170, “Ventilation of Healthcare Facilities”, and is used with expressed written permission from ASHRAE. aa.Nurse station pressure relationship and ventilation requirements shall match the area in which it is located. ab.HD segregated compounding area shall have a differential pressure of -0.01 to -0.03 inches water column in relation to adjacent areas and a minimum of

12 air changes per hour.

78 2022 CALIFORNIA MECHANICAL CODE

VENTILATION AIR

TABLE 4-B FILTER EFFICIENCIES FOR CENTRAL VENTILATION AND AIR-CONDITIONING SYSTEMS IN GENERAL ACUTE

CARE HOSPITALS, ACUTE PSYCHIATRIC HOSPITALS, OUTPATIENT FACILITIES, AND LICENSED CLINICS 1

AREA DESIGNATION MINIMUM NUMBER OF
FILTER BANKS
FILTER EFFICIENCY % FILTER BANK
AREA DESIGNATION
MINIMUM NUMBER OF
FILTER BANKS
(MINIMUM EFFICIENCY REPORTING VALUE MERV)5 (MINIMUM EFFICIENCY REPORTING VALUE MERV)5 (MINIMUM EFFICIENCY REPORTING VALUE MERV)5
AREA DESIGNATION
MINIMUM NUMBER OF
FILTER BANKS
NO. 11 NO. 21 NO. 31
Orthopedic operating room, bone marrow trans-
plant operating room, organ transplant operating
room, NICU formula preparation room, NICU treat-
ment area/room
3 30% 90% 99.97%3
Orthopedic operating room, bone marrow trans-
plant operating room, organ transplant operating
room, NICU formula preparation room, NICU treat-
ment area/room
3 (8)
(14)
(17)
Protective environment rooms 3 30%
90%
99.97%4
Protective environment rooms 3 (8) (14) (17)
Angiography; cardiac catheterization labs; operat-
ing rooms; interventional imaging procedure
rooms;delivery rooms nurseries; patient care, treat-
ment, cystoscopy, cesarean operating room, diag-
nostic, and related areas; airborne infection
isolation rooms; areas providing direct patient serv-
ice or clean supplies such as sterile and clean
processes, and patient area corridors
2 30% 90% ––
Angiography; cardiac catheterization labs; operat-
ing rooms; interventional imaging procedure
rooms;delivery rooms nurseries; patient care, treat-
ment, cystoscopy, cesarean operating room, diag-
nostic, and related areas; airborne infection
isolation rooms; areas providing direct patient serv-
ice or clean supplies such as sterile and clean
processes, and patient area corridors
2 (8)
(14)
––
Laboratories
2 30%
80%
––
Laboratories
2 (8) (13) ––
Administrative, med staff support areas, bulk stor-
age, soiled holding areas, food preparation areas,
public cafeterias, and laundries
1 30% –– ––
Administrative, med staff support areas, bulk stor-
age, soiled holding areas, food preparation areas,
public cafeterias, and laundries
1 (8) –– ––
Psychiatric hospitals intended for the care and
treatment of inpatients who do not require acute
medical services
1 30% –– ––
Psychiatric hospitals intended for the care and
treatment of inpatients who do not require acute
medical services
1 (8) –– ––

1 Based on ASHRAE 52.2. 2 Based on DOP test in accordance with MIL-STD-282 or based on ASHRAE 52.2. 3 HEPA filters at air outlet or other locations when approved by the Authority Having Jurisdiction. 4 HEPA filter located in the supply duct which serves the positive-pressure isolation room or rooms may serve more than one supply outlet and more than one positive-pressure isolation room. HEPA filter or a filter with minimum efficiency reporting value (MERV) of 17 installation shall be designed and equipped to permit safe removal, disposal and replacement of filters. 5 The numbers in parentheses represent MERV rating based on ASHRAE 52.2.

TABLE 4-C FILTER EFFICIENCIES FOR CENTRAL VENTILATION AND AIR-CONDITIONING SYSTEMS IN SKILLED NURSING FACILITIES AND INTERMEDIATE CARE FACILITIES AND CORRECTIONAL TREATMENT CENTERS 1

AREA DESIGNATION MINIMUM NUMBER OF
FILTER BANKS
FILTER EFFICIENCY % FILTER BANK
AREA DESIGNATION MINIMUM NUMBER OF
FILTER BANKS
(MINIMUM EFFICIENCY REPORTING VALUE MERV)3 (MINIMUM EFFICIENCY REPORTING VALUE MERV)3
AREA DESIGNATION MINIMUM NUMBER OF
FILTER BANKS
NO. 11 NO. 21
All areas for inpatient care, treatment and/or diagno-
sis, and those areas providing direct service or clean-
ing supplies)
2 30% 80%
All areas for inpatient care, treatment and/or diagno-
sis, and those areas providing direct service or clean-
ing supplies)
2 (8)
(13)

Administrative, bulk storage, soiled holding, laun-
dries and food prep areas
1 30%2 ––

Administrative, bulk storage, soiled holding, laun-
dries and food prep areas
1 (8) ––

2 Filters are not required for evaporative coolers serving laundries and food preparation areas. 3 The numbers in parentheses represent MERV rating based on ASHRAE 52.2.

2022 CALIFORNIA MECHANICAL CODE 79

VENTILATION AIR

TABLE 402.1 MINIMUM VENTILATION RATES IN BREATHING ZONE 1, 2

[ASHRAE 62.1: TABLE 6.2.2.1] Note: Ventilation air supply requirements for occupancies regulated by the California Energy Commission are found in the California Energy Code.

OCCUPANCY CATEGORY4 PEOPLE OUTDOOR
Air Rate Rp
(CFM/person)
AREA OUTDOOR
Air Rate Ra
(CFM/ft2)
DEFAULT OCCUPANT
DENSITY3
(people/1000 ft2)
AIR CLASS
CORRECTIONAL FACILITIES CORRECTIONAL FACILITIES CORRECTIONAL FACILITIES CORRECTIONAL FACILITIES CORRECTIONAL FACILITIES
Booking/waiting 7.5 0.06 50 2
Cell 5 0.12 25 2
Day room 5 0.06 30 1

Guard stations
5 0.06 15 1





EDUCATIONAL FACILITIES
Art classroom 10 0.18 20 2

Classrooms (ages 5-8)
10 0.12 25 1

Classrooms (age 9 plus)
10 0.12 35 1

Computer lab
10 0.12 25 1

Daycare (through age 4)
10 0.18 25 2

Daycare sickroom
10 0.18 25 3

Lecture classroomh
7.5 0.06 65 1
Lecture hall (fixed seats)h 7.5 0.06 150 1
Media centera 10 0.12 25 1
Multi-use assemblyh 7.5 0.06 100 1
Music/theater/danceh 10 0.06 35 1
Science laboratories 10 0.18 25 2

University/college laboratories
10 0.18 25 2

Wood/metal shop
10 0.18 20 2





FOOD AND BEVERAGE SERVICE
Bars, cocktail lounges 7.5 0.18 100 2

Cafeteria/fast food dining
7.5 0.18 100 2

Kitchen (cooking)
7.5 0.12 20 2

Restaurant dining rooms
7.5 0.18 70 2





GENERAL





GENERAL





GENERAL





GENERAL





GENERAL
Break roomsh 5 0.06 25 1
Coffee stationsh 5 0.06 20 1
Conference/meetingh 5 0.06 50 1
Corridorsh 0.06 1
Occupiable storage rooms for liquids or gelsb 5 0.12 2 2
HOTELS, MOTELS, RESORTS, DORMITORIES
Barracks sleeping areash 5 0.06 20 1
Bedroom/living roomh 5 0.06 10 1
Laundry rooms, central 5 0.12 10 2

Laundry rooms within dwelling units
5 0.12 10 1

Lobbies/pre-functionh
7.5 0.06 30 1
Multipurpose assemblyh 5 0.06 120 1
OFFICE BUILDINGS OFFICE BUILDINGS OFFICE BUILDINGS OFFICE BUILDINGS OFFICE BUILDINGS
Break Rooms 5 0.12 50 1

Main entry lobbiesh
5 0.06 10 1
Occupiable storage rooms for dry materials 5 0.06 2 1

Office spaceh
5 0.06 5 1
Reception areash 5 0.06 30 1
Telephone/data entryh 5 0.06 60 1
MISCELLANEOUS SPACES MISCELLANEOUS SPACES MISCELLANEOUS SPACES MISCELLANEOUS SPACES MISCELLANEOUS SPACES
Bank or bank lobbiesh 7.5 0.06 15 1
Bank vaults/safe deposith 5 0.06 5 2
Computer (not printing)h 5 0.06 4 1
Freezer and refrigerated spaces (<50°F)e 10 2
General manufacturing (excludes heavy
industrial and processes using chemicals)
10 0.18 7 3

Pharmacy (prep. area)
5 0.18 10 2

Photo studios
5 0.12 10 1

80 2022 CALIFORNIA MECHANICAL CODE

TABLE 402.1 (continued) MINIMUM VENTILATION RATES IN BREATHING ZONE 1, 2

[ASHRAE 62.1: TABLE 6.2.2.1]

VENTILATION AIR

OCCUPANCY CATEGORY4 PEOPLE OUTDOOR
Air Rate Rp
(CFM/person)
AREA OUTDOOR
Air Rate Ra
(CFM/ft2)
DEFAULT OCCUPANT
DENSITY3
(people/1000 ft2)
AIR
CLASS
Shipping/receivingb 10 0.12 2 2
Sorting, packing, light assembly 7.5 0.12 7 2

Telephone closets
1

Transportation waitingh
7.5 0.06 100 1
Warehousesb 10 0.06 2
PUBLIC ASSEMBLY SPACES PUBLIC ASSEMBLY SPACES PUBLIC ASSEMBLY SPACES PUBLIC ASSEMBLY SPACES PUBLIC ASSEMBLY SPACES
Auditorium seating areah 5 0.06 150 1
Courtroomsh 5 0.06 70 1
Legislative chambersh 5 0.06 50 1
Libraries 5 0.12 10 1
Lobbiesh 5 0.06 150 1
Museums (children’s) 7.5 0.12 40 1

Museums/galleriesh
7.5 0.06 40 1
Places of religious worshiph 5 0.06 120 1
RESIDENTIAL RESIDENTIAL RESIDENTIAL RESIDENTIAL RESIDENTIAL
Common corridorsh 0.06 1
Dwelling unitf, g, h 5 0.06 See footnotef 1
RETAIL RETAIL RETAIL RETAIL RETAIL
Sales (except as below) 7.5 0.12 15 2

Barber shoph
7.5 0.06 25 2
Beauty and nail salons 20 0.12 25 2

Coin-operated laundries
7.5 0.12 20 2

Mall common areash
7.5 0.06 40 1
Pet shops (animal areas) 7.5 0.18 10 2

Supermarketh
7.5 0.06 8 1
SPORTS AND ENTERTAINMENT SPORTS AND ENTERTAINMENT SPORTS AND ENTERTAINMENT SPORTS AND ENTERTAINMENT SPORTS AND ENTERTAINMENT
Bowling alley (seating) 10 0.12 40 1

Disco/dance floorsh
20 0.06 100 2
Gambling casinos 7.5 0.18 120 1

Game arcades
7.5 0.18 20 1

Gym, sports arena (play area)e
20 0.18 7 2
Health club/aerobics room 20 0.06 40 2

Health club/weight rooms
20 0.06 10 2

Spectator areash
7.5 0.06 150 1
Stages, studiosd, h 10 0.06 70 1
Swimming (pool & deck)c 0.48 2

For SI units: 1 cubic foot per minute = 0.0283 m 3 /min, 1 square foot = 0.0929 m 2 Notes: 1 This table applies to no-smoking areas. Rates for smoking-permitted spaces shall be determined using other methods. 2 Volumetric airflow rates are based on dry air density of 0.075 pounds of dry air per cubic foot (lbda/ft3) (1.201 kgda/m3) at a barometric pressure of 1 atm (101 kPa) and an air temperature of 70°F (21°C). Rates shall be permitted to be adjusted for actual density. 3 The default occupant density shall be used where actual occupant density is not known. 4 Where the occupancy category for a proposed space or zone is not listed, the requirements for the listed occupancy category that is most similar in terms of occupant density, activities, and building construction shall be used.

ature of 70°F (21°C). Rates shall be permitted to be adjusted for actual density. 3 The default occupant density shall be used where actual occupant density is not known. 4 Where the occupancy category for a proposed space or zone is not listed, the requirements for the listed occupancy category that is most similar in terms of occupant density, activities, and building construction shall be used.

ITEM-SPECIFIC NOTES FOR TABLE 402.1 a For high school and college libraries, the values shown for “Public Assembly Spaces – Libraries” shall be used. b Rate may not be sufficient where stored materials include those having potentially harmful emissions. c Rate does not allow for humidity control. “Deck area” refers to the area surrounding the pool that is capable of being wetted during pool use or when the

pool is occupied. Deck area that is not expected to be wetted shall be designated as an occupancy category. d Rate does not include special exhaust for stage effects such as dry ice vapors and smoke. e Where combustion equipment is intended to be used on the playing surface or in the space, additional dilution ventilation, source control, or both shall be pro vided. f Default occupancy for dwelling units shall be two persons for studio and one-bedroom units, with one additional person for each additional bedroom. g Air from one residential dwelling shall not be recirculated or transferred to other spaces outside of that dwelling. h Ventilation air for this occupancy category shall be permitted to be reduced to zero where the space is in occupied-standby mode.

2022 CALIFORNIA MECHANICAL CODE 81

VENTILATION AIR

TABLE 403.2.2 ZONE AIR DISTRIBUTION EFFECTIVENESS1, 2, 3, 4, 5 [ASHRAE 62.1: TABLE 6.2.2.2]

AIR DISTRIBUTION CONFIGURATION
Ceiling supply of cool air.
Ceiling supply of warm air and floor return.
Ceiling supply of warm air 15°F or more above space temperature and ceiling return.
Ceiling supply of warm air less than 15°F above space temperature and ceiling return provided that the 150 feet per
minute (fpm) supply air jet reaches to within 4.5 feet of floor level.
Floor supply of cool air and ceiling return provided that the vertical throw is more than 50 fpm at a height of 4.5 feet or
more above the floor.
Floor supply of cool air and ceiling return, provided low-velocity displacement ventilation achieves unidirectional flow
and thermal stratification, or underfloor air distribution systems where the vertical throw is 50 fpm or less at a height of
4.5 feet above the floor.
Floor supply of warm air and floor return.
Floor supply of warm air and ceiling return.
Makeup supply drawn in on the opposite side of the room from the exhaust, return, or both.
Makeup supply drawn in near to the exhaust, return, or both locations.
Ez
1.0
1.0
0.8
1.06
1.0
1.2
1.0
0.7
0.8
0.5
For SI units: °C = (°F-32)/1.8, 1 foot per minute = 0.005 m/s, 1 foot = 304.8 mm
Notes:

1 “Cool air” is air cooler than space temperature. 2 “Warm air” is air warmer than space temperature. 3 “Ceiling supply” includes any point above the breathing zone. 4 “Floor supply” includes any point below the breathing zone. 5 As an alternative to using the above values, Ez shall be permitted to be regarded as equal to air change effectiveness determined in accordance with ASHRAE 129 for air distribution configurations except unidirectional flow. 6 For lower velocity supply air, Ez = 0.8

82 2022 CALIFORNIA MECHANICAL CODE

VENTILATION AIR

TABLE 403.7 MINIMUM EXHAUST RATES

[ASHRAE 62.1: TABLE 6.5]

OCCUPANCY CATEGORY8 EXHAUST RATE (CFM/unit) EXHAUST RATE (CFM/ft2) AIR CLASS
Arenas2 0.50 1
Art classrooms 0.70 2
Auto repair rooms1 1.50 2
Barber shops 0.50 2
Bathroom11,12 20/50 2
Beauty and nail salons 0.60 2
Cells with toilet 1.00 2
Copy, printing rooms 0.50 2
Darkrooms 1.00 2
Educational science laboratories 1.00 2
Janitor closets, trash rooms, recy-
cling
1.00 3
Kitchens – commercial 0.70 2
Kitchenettes 0.30 2
Locker rooms for athletic, indus-
trial and health care facilities
0.50 2
Other locker rooms 0.25 2
Shower rooms7,10 20/50 2
Paint spray booths 4
Parking garages3 0.75 2
Pet shops (animal areas) 0.90 2
Refrigerating machinery rooms6 3
Residential – kitchens7 50/100 2
Soiled laundry storage rooms 1.00 3
Storage rooms, chemical 1.50 4
Toilets – private5, 9 25/50 2
Toilets – public4, 9 50/70 2
Woodwork shop/classrooms 0.50 2

For SI units: 1 cubic foot per minute = 0.0283 m 3 ⁄ min, 1 square foot = 0.0929 m 2 Notes: 1 Stands where engines are run shall have exhaust systems that directly connect to the engine exhaust and prevent escape of fumes. 2 Where combustion equipment is intended to be used on the playing surface, additional dilution ventilation, source control, or both shall be provided. 3 Exhaust shall not be required where two or more sides comprise walls that are at least 50 percent open to the outside. 4 Rate is per water closet, urinal, or both. Provide the higher rate where periods of heavy use are expected to occur. The lower rate shall be permitted to be used otherwise. 5 Rate is for a toilet room intended to be occupied by one person at a time. For continuous system operation during normal hours of use, the lower rate shall be permitted to be used. Otherwise the higher rate shall be used. 6 For refrigeration machinery rooms, the exhaust rate shall comply with Chapter 11. 7 For continuous system operation, the lower rates shall be permitted. Otherwise the higher rate shall be used. 8 For unlisted occupancies for a proposed space not listed in the table, the requirements for the listed occupancy that is most similar in terms of occupant density and occupancy type shall be used. 9 Exhaust air that has been cleaned in accordance with the criteria of Class 1 shall be permitted to be recirculated. 10 Rate is per shower head. 11 [HCD 1 & HCD 2] A bathroom is any room containing a bathtub, a shower, a spa, or a similar source of moisture. 12 [HCD 1 & HCD 2] ANSI/ASHRAE 62.2: Tables 5.1 and 5.2.

2022 CALIFORNIA MECHANICAL CODE 83

84 2022 CALIFORNIA MECHANICAL CODE

CALIFORNIA MECHANICAL CODE – MATRIX ADOPTION TABLE

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
    Overview
    1. 402.2 Natural Ventilation. [Not permitted for OSHPD
    2. 401.1 Applicability. This chapter contains requirements for
    3. 401.2 Filters. [BSC-CG], [DSA-SS & DSA-SS/CC] In
    4. 402.1 Occupiable Spaces. Occupiable spaces listed in
    5. 402.3 Mechanical Ventilation. [Not permitted for
    6. 402.4 Outdoor Air Intake Protection. Required outdoorair intak…
    7. 403.1 General. The design outdoor air intake flow rate for
    8. 403.2 Zone Calculations. Ventilation zone parameters
    9. 403.6 Design for Varying Operating Conditions. Ventilation sys…
    10. 403.3 Single-Zone Systems. For ventilation systems
    11. 403.4 One Hundred Percent Outdoor Air Systems.
    12. 403.5 Multiple-Zone Recirculating Systems. For ventilation sys…
    13. 403.7 Exhaust Ventilation. Exhaust airflow shall be provided i…
    14. 403.8 Dynamic Reset. The system shall be permitted to
    15. 403.9 Air Classification and Recirculation. Air shall
    16. 404.1 General. This section presents an alternative procedure …
    17. 404.2 Average Outdoor Air Fraction. The average outdoor air fr…
    18. 404.3 Zone Ventilation Efficiency. The zone ventilation
    19. 405.1 General. Rooms or occupied spaces within residential occ…
    20. 405.2 Ventilation Air Rate. The required mechanical ventilatio…
    21. 405.3 Bathroom Exhaust. A mechanical exhaust directly
    22. 405.4 Kitchen Exhaust. A mechanical exhaust directly to
    23. 405.5 Ventilation Openings. Occupiable spaces shall be
    24. 406.0 Evaporative Cooling System for Health Care
    25. 407.1 General.
    26. 407.2 Outdoor Air Intakes and Exhaust Outlets.
    27. 407.3 Air Balance.
    28. 407.4 Air Circulation.
    29. 407.5 Variable Air Volume.
    30. 407.6 Economizers. Systems with economizers shall include
    31. 408.1 General. Filter efficiencies shall be certified by the
    32. 408.2 Filters for Hospitals.
    33. 408.3 Filters for Skilled Nursing Facilities, Intermedi-
    34. 408.4 Filters for Outpatient Facilities.
    35. 409.1 Ducts which penetrate construction, intended for X-
    36. 409.2 Duct linings and their use shall meet the requirements
    37. 409.3 Insulation of Ducts. Cold air ducts shall be insu-
    38. 409.4 The anchorage and supporting structural elements for
    39. 410.1 Laboratory Ventilating Systems. Laboratory ven-
    40. 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
    41. 410.3 Laboratory Fume Hoods. Laboratory fume hoods
    42. 411.1 The air from dining areas may be used to ventilate the
    43. 412.1 Boiler, heater and electrical equipment rooms shall be
    44. 412.2 Floor surfaces in occupied spaces above such rooms
    45. 413.1 Rooms in areas where excessive heat or moisture is
    46. 413.2 Kitchen, morgues and laundries located inside a hos-
    47. 414.1 Exhaust Systems. A separate, dedicated exhaust
    48. 414.2 Air Distribution. The supply outlets and exhaust
    49. 415.1 Air Distribution. The supply outlets and exhaust and
    50. 416.1 An alarm system which is based on static pressure con-
    51. 416.2 Other acceptable alarm systems will be allowed when
    52. 416.3 [For OSHPD 4] For correctional treatment centers,
    53. 416.4 Prior to acceptance of the rooms, the alarm system
    54. 417.0 Testing and Balancing Airborne Infection Isola-
    55. 418.1 Air Changes. The ETO sterilization equipment room
    56. 418.2 Exhaust Requirements.
    57. 418.3 Ventilation Requirements.
    58. 418.4 Gas Valves. Installation of gas line hand valves at the
    59. 418.5 Alarm Systems. An Audible and visual alarm system
    60. 419.1 Formula Preparation Area. Air shall be supplied
    61. 419.2 Treatment Area/Room. Air shall be supplied over
    62. 420.0 Air Distribution Devices. [OSHPD 1, 2, 3, 4 & 5]
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — GEOTHERMAL ENERGY SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  25. Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.