420.0 Air Distribution Devices. [OSHPD 1, 2, 3, 4 & 5]
California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
All air distribution devices and supply air outlets shall meet the requirements of ASHRAE 170-2013, Section 6.7.2 and Table 6.7.2.
2022 CALIFORNIA MECHANICAL CODE 73
VENTILATION AIR
TABLE 4-A PRESSURE RELATIONSHIP AND VENTILATION REQUIREMENTS FOR GENERAL ACUTE CARE HOSPITALS, SKILLED NURSING FACILITIES, INTERMEDIATE CARE FACILITIES, CORRECTIONAL
TREATMENT CENTERS, OUTPATIENT FACILITIES, AND LICENSED CLINICS
>
| FUNCTION OR SPACE | PRESSURE RELATIONSHIP TO ADJACENT AREAS (f) (n) |
MINIMUM OUTDOOR ACH |
MINIMUM TOTAL ACH |
ALL ROOM AIR EXHAUSTED DIRECTLY TO OUTDOORS (j) |
AIR RECIRCULATED BY MEANS OF ROOM UNITS (a) |
DESIGN RELATIVE HUMIDITY(k), % |
DESIGN TEMPERATURE (l),°F/°C |
|---|---|---|---|---|---|---|---|
| Airborne infection isolation anteroom (u) |
(e) | NR | 10 | Yes | No | NR | NR |
| Airborne infection isolation room (u) |
Negative | 2 | 12 | Yes | No | max 60 | 70-75/21-24 |
| Airborne infection isolation treatment/exam room |
Negative | 2 | 12 | Yes | No | NR | NR |
| Angiography room | Positive | 3 | 15 | NR | NR | max 60 | 70-75/21-24 |
| Bathing room | Negative | NR | 10 | Yes | No | NR | 70-75/21-24 |
| Bathroom | Negative | NR | 10 | Yes | No | NR | 72-78/22-26 |
| Bedpan room | Negative | NR | 10 | Yes | No | NR | NR |
| Blood bank/tissue storage | NR | 2 | 6 | NR | NR | NR | NR |
| Blood draw/phlebotomy | NR | 2 | 6 | NR | NR | NR | NR |
| Bronchoscopy, sputum collection, and pentamidine administration (n) |
Negative | 2 | 12 | Yes | No | NR | 68-73/20-23 |
| Cardiac catheterization lab | Positive | 3 | 15 | NR | No | max 60 | 70-75/21-24 |
| Clean linen storage | Positive | NR | 2 | NR | NR | NR | 72-78/22-26 |
| Clean workroom (central med- ical and surgical supply space) |
Positive | 2 | 4 | NR | No | max 60 | 72-78/22-26 |
| Clean workroom or clean hold- ing (support) |
Positive | 2 | 4 | NR | NR | NR | NR |
| Critical and intensive care | NR | 2 | 6 | NR | No | 30-60 | 70-75/21-24 |
| CT Scan | NR | 2 | 6 | NR | NR | max 60 | NR |
| Darkroom (g) | Negative | 2 | 10 | Yes | No | NR | NR |
| Delivery room (caesarean) (m), (n), (o) |
Positive | 4 | 20 | NR | No | 20-60 | 68-75/20-24 |
| Dialysis treatment area | NR | 2 | 6 | NR | NR | NR | 72-78/22-26 |
| Dialyzer reprocessing room | Negative | NR | 10 | Yes | No | NR | NR |
| Dietary storage | NR | NR | 2 | NR | No | NR | 72-78/22-26 |
| Electroconvulsive therapy pro- cedure room |
P | 3 | 15 | NR | NR | NR | NR |
| Emergency department exam/treatment room (p) |
NR | 2 | 6 | NR | NR | max 60 | 70-75/21-24 |
| Endoscope cleaning | Negative | 2 | 10 | Yes | No | NR | NR |
| ER decontamination | Negative | 2 | 12 | Yes | No | NR | NR |
| ER waiting rooms | Negative | 2 | 12 | Yes (q) | NR | max 65 | 70-75/21-24 |
| Examination room | NR | 2 | 6 | NR | NR | max 60 | 70-75/21-24 |
| Fast track room | NR | 2 | 6 | NR | NR | NR | NR |
| Fluoroscopy room | Negative | 2 | 6 | Yes | No | NR | NR |
| Food preparation center (i) | NR | 2 | 10 | NR | No | NR | 72-78/22-26 |
| Gastrointestinal endoscopy pro- cedure room (x) |
NR | 2 | 6 | NR | No | 20-60 | 68-73/20-23 |
| Hazardous material storage | Negative | 2 | 10 | Yes | No | NR | NR |
| Hydrotherapy | Negative | 2 | 6 | NR | NR | NR | 72-80/22-27 |
| Infusion room | Positive | 2 | 6 | NR | NR | NR | NR |
| Intermediate care (s) | NR | 2 | 6 | NR | NR | max 60 | 70-75/21-24 |
| Interventional imaging procedure room |
Positive | 5 | 15 | NR | NR | NR | NR |
74 2022 CALIFORNIA MECHANICAL CODE
VENTILATION AIR
TABLE 4-A (continued) PRESSURE RELATIONSHIP AND VENTILATION REQUIREMENTS FOR GENERAL ACUTE CARE HOSPITALS, SKILLED NURSING FACILITIES, INTERMEDIATE CARE FACILITIES, CORRECTIONAL
TREATMENT CENTERS, OUTPATIENT FACILITIES, AND LICENSED CLINICS
| FUNCTION OR SPACE | PRESSURE RELATIONSHIP TO ADJACENT AREAS (f) (n) |
MINIMUM OUTDOOR ACH |
MINIMUM TOTAL ACH |
ALL ROOM AIR EXHAUSTED DIRECTLY TO OUTDOORS (j) |
AIR RECIRCULATED BY MEANS OF ROOM UNITS (a) |
DESIGN RELATIVE HUMIDITY(k), % |
DESIGN TEMPERATURE (l),°F/°C |
|---|---|---|---|---|---|---|---|
| IV Prep. room | Positive | 2 | 6 | NR | NR | NR | NR |
| Janitor’s closet,housekeeping | Negative | NR | 10 | Yes | No | NR | NR |
| Labor/delivery/recovery (LDR) (s) |
NR | 2 | 6 | NR | NR | max 60 | 70-75/21-24 |
| Labor/delivery/recovery/ postpartum (LDRP) (s) |
NR | 2 | 6 | NR | NR | max 60 | 70-75/21-24 |
| Laboratory, bacteriology (v) | Negative | 2 | 6 | Yes | NR | NR | 70-75/21-24 |
| Laboratory, biochemistry (v) | Negative | 2 | 6 | Yes | NR | NR | 70-75/21-24 |
| Laboratory, cytology (v) | Negative | 2 | 6 | Yes | NR | NR | 70-75/21-24 |
| Laboratory, general (v) | Negative | 2 | 6 | NR | NR | NR | 70-75/21-24 |
| Laboratory, glasswashing | Negative | 2 | 10 | Yes | NR | NR | NR |
| Laboratory, histology (v) | Negative | 2 | 6 | Yes | NR | NR | 70-75/21-24 |
| Laboratory, infectious disease and virus |
Negative | 2 | 6 | Yes | NR | NR | 70-75/21-24 |
| Laboratory, media transfer (v) | Positive | 2 | 4 | NR | NR | NR | 70-75/21-24 |
| Laboratory, microbiology (v) | Negative | 2 | 6 | Yes | NR | NR | 70-75/21-24 |
| Laboratory, nuclear medicine (v) | Negative | 2 | 6 | Yes | NR | NR | 70-75/21-24 |
| Laboratory, pathology (v) | Negative | 2 | 6 | Yes | NR | NR | 70-75/21-24 |
| Laboratory, serology (v) | Negative | 2 | 6 | Yes | NR | NR | 70-75/21-24 |
| Laboratory, sterilizing | Negative | 2 | 10 | Yes | NR | NR | 70-75/21-24 |
| Lactation | NR | 2 | 6 | NR | NR | NR | NR |
| Laser eye room | Positive | 3 | 15 | NR | No | 20-60 | 70-75/21-24 |
| Laundry, general | Negative | 2 | 10 | Yes | No | NR | NR |
| Linen and trash chute room | Negative | NR | 10 | Yes | No | NR | NR |
| Medical/anesthesia gas storage (r) |
Negative | NR | 8 | Yes | NR | NR | NR |
| Medication room | NR | 2 | 4 | NR | NR | max 60 | 70-75/21-24 |
| _Morgues and_autopsy room (n) | Negative | 2 | 12 | Yes | No | NR | 68-75/20-24 |
| MRI room | NR | 2 | 6 | NR | NR | NR | NR |
| Negative-pressure x-ray room | Negative | 2 | 12 | Yes | No | max 60 | 72-78/22-26 |
| Newborn intensive care | Positive | 2 | 6 | NR | No | 30-60 | 72-78/22-26 |
| Newborn intensive care formula room |
P | 2 | 10 | NR | No | NR | NR |
| Newborn/well baby nursery suite |
NR | 2 | 6 | NR | No | 30-60 | 72-78/22-26 |
| Nonrefrigerated body-holding room (h) |
Negative | NR | 10 | Yes | No | NR | 70-75/21-24 |
| Nourishment area or room | NR | NR | 2 | NR | NR | NR | NR |
| Nuclear medicine (Gamma, PET, SPECT) |
Negative | 2 | 6 | Yes | No | NR | NR |
| Nuclear medicine hot lab | Negative | NR | 6 | Yes | No | NR | 70-75/21-24 |
| Nuclear medicine treatment room |
Negative | 2 | 6 | Yes | NR | NR | 70-75/21-24 |
| Nurse station (aa) | (aa) | (aa) | 2 | (aa) | (aa) | (aa) | (aa) |
| Observation | NR | 2 | 6 | NR | NR | NR | 70-75/21-24 |
| Occupational therapy | NR | 2 | 6 | NR | NR | NR | 70-75/21-24 |
| Operating room,hybrid operating room (m), (n), (o) |
Positive | 4 | 20 | NR | No | 20-60 | 68-75/20-24 |
2022 CALIFORNIA MECHANICAL CODE 75
VENTILATION AIR
TABLE 4-A (continued) PRESSURE RELATIONSHIP AND VENTILATION REQUIREMENTS FOR GENERAL ACUTE CARE HOSPITALS, SKILLED NURSING FACILITIES, INTERMEDIATE CARE FACILITIES, CORRECTIONAL
TREATMENT CENTERS, OUTPATIENT FACILITIES, AND LICENSED CLINICS
| FUNCTION OR SPACE | PRESSURE RELATIONSHIP TO ADJACENT AREAS (f) (n) |
MINIMUM OUTDOOR ACH |
MINIMUM TOTAL ACH |
ALL ROOM AIR EXHAUSTED DIRECTLY TO OUTDOORS (j) |
AIR RECIRCULATED BY MEANS OF ROOM UNITS (a) |
DESIGN RELATIVE HUMIDITY(k), % |
DESIGN TEMPERATURE (l),°F/°C |
|---|---|---|---|---|---|---|---|
| Operating/surgical cystoscopic room (m), (n), (o) |
Positive | 4 | 20 | NR | No | 20-60 | 68-75/20-24 |
| Patient corridor | NR | NR | 2 | NR | NR | NR | NR |
| Patient holding preparation | NR | 2 | 6 | NR | No | NR | NR |
| Patient room | NR | 2 | 4 (y) | NR | NR | max 60 | 70-75/21-24 |
| Pediatric play area | NR | 2 | 6 | NR | NR | NR | NR |
| Pharmacy (b) | Positive | 2 | 4 | NR | NR | NR | NR |
| Drug room | NR | 2 | 4 | NR | NR | NR | NR |
| HD ante room (b) | Positive | NR | NR | NR | NR | <60 | ≤68/≤20 |
| HD buffer room (b) | Negative | NR | 30 | Yes | No | <60 | ≤68/≤20 |
| HD segregated compounding area (ab) |
Negative | NR | 12 | Yes | NR | NR | NR |
| HD storage (b) | Negative | NR | 12 | Yes | NR | NR | NR |
| Non-HD ante room (b) | Positive | NR | 30 | NR | NR | <60 | ≤68/≤20 |
| Non-HD buffer room (b) | Positive | NR | 30 | NR | No | <60 | ≤68/≤20 |
| Non-HD segregated compounding area |
NR | NR | NR | NR | NR | NR | NR |
| Physical therapy (nursing facil- ity) |
Negative | 2 | 6 | NR | NR | NR | 70-75/21-24 |
| Physical therapy (diagnostic and treatment) |
Negative | 2 | 6 | NR | NR | max 65 | 72-80/22-27 |
| Post-anesthesia care unit | NR | 2 | 6 | Yes | No | 20-60 | 70-75/21-24 |
| Pre-screening area | Negative | 2 | 12 | Yes (q) | NR | NR | NR |
| Procedure room (o), (d) | Positive | 3 | 15 | NR | No | 20-60 | 70-75/21-24 |
| Protective environment anteroom (t) |
(e) | NR | 10 | NR | No | NR | NR |
| Protective environment room (t) |
Positive | 2 | 12 | NR | No | max 60 | 70-75/21-24 |
| Radiology waiting rooms | Negative | 2 | 12 | Yes (q), (w) | NR | max 60 | 70-75/21-24 |
| Recovery room | NR | 2 | 6 | NR | No | 20-60 | 70-75/21-24 |
| Recreation/activity room | NR | 2 | 6 | NR | NR | NR | NR |
| Resident gathering/activity/din- ing (nursing facility) |
NR | 4 | 4 | NR | NR | NR | 70-75/21-24 |
| Resident room (nursing facility) |
NR | 2 | 2 | NR | NR | NR | 70-75/21-24 |
| Resident unit corridor (nursing facility) |
NR | NR | 4 | NR | NR | NR | NR |
| Seclusion room | NR | 2 | 6 | NR | NR | NR | NR |
| Semi-restricted corridor | NR | 2 | 4 | NR | NR | NR | NR |
| Shower room | Negative | NR | 10 | Yes | No | NR | NR |
| Soiled linen sorting and storage | Negative | NR | 10 | Yes | No | NR | NR |
| Soiled or decontamination room | Negative | 2 | 6 | Yes | No | NR | 72-78/22-26 |
| Soiled workroom or soiled hold- ing,utility room |
Negative | 2 | 10 | Yes | No | NR | NR |
| Special purpose room (SNF & ICF only) |
NR | 2 | 6 | Yes | NR | NR | NR |
| Speech therapy/audiology room | NR | 2 | 6 | NR | NR | NR | NR |
| Sterile storage | Positive | 2 | 4 | NR | NR | max 60 | 72-78/22-26 |
76 2022 CALIFORNIA MECHANICAL CODE
VENTILATION AIR
TABLE 4-A (continued) PRESSURE RELATIONSHIP AND VENTILATION REQUIREMENTS FOR GENERAL ACUTE CARE HOSPITALS, SKILLED NURSING FACILITIES, INTERMEDIATE CARE FACILITIES, CORRECTIONAL
TREATMENT CENTERS, OUTPATIENT FACILITIES, AND LICENSED CLINICS
| FUNCTION OR SPACE | PRESSURE RELATIONSHIP TO ADJACENT AREAS (f) (n) |
MINIMUM OUTDOOR ACH |
MINIMUM TOTAL ACH |
ALL ROOM AIR EXHAUSTED DIRECTLY TO OUTDOORS (j) |
AIR RECIRCULATED BY MEANS OF ROOM UNITS (a) |
DESIGN RELATIVE HUMIDITY(k), % |
DESIGN TEMPERATURE (l),°F/°C |
|---|---|---|---|---|---|---|---|
| Sterilizer equipment room | Negative | NR | 10 | Yes | No | NR | NR |
| Substerile service area | NR | 2 | 6 | NR | No | NR | NR |
| Toilet room | Negative | NR | 10 | Yes | No | NR | NR |
| Trauma/cardiac room (crisis or shock) (c) |
Positive | 3 | 15 | NR | No | 20-60 | 70-75/21-24 |
| Treatment room (surgery and critical care) (p) |
NR | 2 | 6 | NR | NR | 20-60 | 70-75/21-24 |
| Treatment room (diagnostic and treatment) (x) |
NR | 2 | 6 | NR | NR | max 60 | 70-75/21-24 |
| Triage | Negative | 2 | 12 | Yes (q) | NR | max 60 | 70-75/21-24 |
| Ultrasound room | NR | 2 | 6 | NR | NR | NR | NR |
| Unsterile supply | NR | 2 | 2 | NR | NR | NR | NR |
| Waiting area (nuclear medicine) |
Negative | 2 | 12 | Yes | No | NR | NR |
| Waiting area primary care clinic | Negative | 2 | 10 | Yes(q) | NR | NR | NR |
| Warewashing | Negative | NR | 10 | Yes | No | NR | NR |
| Wound intensive care (burn unit) |
NR | 2 | 6 | NR | No | 40-60 | 70-75/21-24 |
| X-ray (diagnostic and treatment) |
NR | 2 | 6 | NR | NR | max 60 | 72-78/22-26 |
| X-ray (surgery/critical care and catheterization) |
Positive | 3 | 15 | NR | No | max 60 | 70-75/21-24 |
Note: NR = No requirement Notes for Table 4-A: a. Except where indicated by a “No” in this column, recirculating room HVAC units (with heating or cooling coils) are acceptable for providing that portion
of the minimum total air changes per hour that is permitted by Section 407.4.1.7 . Because of the cleaning difficulty and potential for buildup of contamination, recirculating room units shall not be used in areas marked “No.” Recirculating devices with HEPA filters shall be permitted in existing facilities as interim, supplemental environmental controls to meet requirements for the control of airborne infectious agents. The design of either portable or fixed systems should prevent stagnation and short circuiting of airflow. The design of such systems shall also allow for easy access for scheduled preventative maintenance and cleaning. b. Additional air change, ISO class, continuous pressure monitoring and filtering requirements for compounding areas shall comply with California Board of
rne infectious agents. The design of either portable or fixed systems should prevent stagnation and short circuiting of airflow. The design of such systems shall also allow for easy access for scheduled preventative maintenance and cleaning. b. Additional air change, ISO class, continuous pressure monitoring and filtering requirements for compounding areas shall comply with California Board of
Pharmacy regulations Title 16 §1735 & §1751, and USP <797> & <800>. Air supplied to the compounding buffer room and ante room must be introduced through 99.97% minimum HEPA filters located in the ceiling. At least 15 air changes per hour (ACPH) shall be provided to nonhazardous drug (non-HD) compounding buffer rooms through the ceiling. The HEPA filtered air from the PEC in the non-HD buffer room, when added to the HVAC-supplied HEPA- filtered air, shall increase the total HEPA-filtered ACPH to at least 30. If the PEC is used to meet the minimum total ACPH requirements, the PEC must not be turned off except for maintenance. All hazardous drug (HD) compounding areas and PECs shall be exhausted externally through 99.97% HEPA filtration. For both hazardous and non-hazardous compounding, minimum air changes shall be met under dynamic operating conditions as defined by USP. Returns and exhaust grilles shall be mounted low on the wall unless a visual smoke study demonstrates dilution of particles and sweeping out of particles from the entire room. One return/exhaust should be placed near the refrigerator compressor. Anteroom shall have a minimum pressure differential of +0.02 inches water column in relation to the adjacent, non-compounding spaces. Non-HD buffer room shall have a pressure differential of +0.02 to +0.05 inches water column in relation to the anteroom. HD buffer room shall have a pressure differential of -0.01 to -0.03 inches water column in relation to the anteroom. c. The term trauma room as used herein is a first-aid room and/or emergency room used for general initial treatment of accident victims. The operating room
within the trauma center that is routinely used for emergency surgery is considered to be an operating room by this standard. d. Pressure relationships need not be maintained when the room is unoccupied. e. See Section 7.2 of ASHRAE 170 and its subsections for pressure-relationship requirements. f. For operating rooms, cardiac catheterization labs, angiography rooms, cystoscopy rooms, delivery rooms, cesarean operating rooms, newborn intensive care,
rgency surgery is considered to be an operating room by this standard. d. Pressure relationships need not be maintained when the room is unoccupied. e. See Section 7.2 of ASHRAE 170 and its subsections for pressure-relationship requirements. f. For operating rooms, cardiac catheterization labs, angiography rooms, cystoscopy rooms, delivery rooms, cesarean operating rooms, newborn intensive care,
and nurseries provide approximately 15% excess supply air to the room or a sufficient quantity of excess supply air to maintain an appropriate positive air balance based on the room tightness and number of doors. For all rooms not listed in this footnote or not listed in Section 322.0 requiring either a positive or negative air balance, provide approximately 10% differential cfm between supply and return/exhaust airflow but not less than 25 cfm differential shall be provided regardless of room size. Room function, size, and tightness may be considered when determining the differential airflow required. Where continuous directional control is not required, variations between supply cfm and return or exhaust cfm shall be minimized in accordance with Section 407.4.1.3. g. All air need not be exhausted if darkroom equipment has a scavenging exhaust duct attached and meets ventilation standards regarding NIOSH, OSHA, and
local employee exposure limits. 2, 3
2022 CALIFORNIA MECHANICAL CODE 77
VENTILATION AIR
h. A nonrefrigerated body-holding room is applicable only to facilities that do not perform autopsies on-site and use the space for short periods while waiting
for the body to be transferred. i. Minimum total air changes per hour (ach) shall be that required to provide proper makeup air to kitchen exhaust systems as specified in ANSI/ASHRAE Standard 154. 4 In some cases, excess exfiltration or infiltration to or from exit corridors compromises the exit corridor restrictions of NFPA 90A, 5 the pressure requirements of NFPA 96, 6 or the maximum defined in the table. During operation, a reduction to the number of air changes to any extent required for odor control shall be permitted when the space is not in use. (See FGI [2010] in Informative Appendix B.) j. In some areas with potential contamination and/or odor problems, exhaust air shall be discharged directly to the outdoors and not recirculated to other areas. Individual circumstances may require special consideration for air exhausted to the outdoors. To satisfy exhaust needs, constant replacement air from the outdoors is necessary when the system is in operation. k. The RH ranges listed are the minimum and/or maximum allowable at any point within the design temperature range required for that space. l. Systems shall be capable of maintaining the rooms within the range during normal operation. Lower or higher temperature shall be permitted when patients’ comfort and/or medical conditions require those conditions. m. National Institute for Occupational Safety and Health (NIOSH) criteria documents regarding occupational exposure to waste anesthetic gases and vapors, and
required for that space. l. Systems shall be capable of maintaining the rooms within the range during normal operation. Lower or higher temperature shall be permitted when patients’ comfort and/or medical conditions require those conditions. m. National Institute for Occupational Safety and Health (NIOSH) criteria documents regarding occupational exposure to waste anesthetic gases and vapors, and
control of occupational exposure to nitrous oxide 7 indicate a need for both local exhaust (scavenging) systems and general ventilation of the areas in which the respective gases are utilized. Refer to NFPA 99 for other requirements. 8 n. If pressure-monitoring device alarms are installed, allowances shall be made to prevent nuisance alarms. Short-term excursions from required pressure rela tionships shall be allowed while doors are moving or temporarily open. Simple visual methods such as smoke trail, ball-in-tube, or flutterstrip shall be permitted for verification of airflow direction. o. Surgeons or surgical procedures may require room temperatures, ventilation rates, humidity ranges, and/or air distribution methods that exceed the minimum
indicated ranges. p. Treatment rooms used for bronchoscopy shall be treated as bronchoscopy rooms. Treatment rooms used for procedures with nitrous oxide shall contain pro visions for exhausting anesthetic waste gases. q. In a recirculating ventilation system, HEPA filters shall be permitted instead of exhausting the air from these spaces to the outdoors provided that the return
air passes through the HEPA filters before it is introduced into any other spaces. The entire minimum total air changes per hour of recirculating airflow shall pass through HEPA filters. When these areas are open to larger, nonwaiting spaces, the exhaust air volume shall be calculated based on the seating area of the waiting area. ( Note: The intent here is to not require the volume calculation to include a very large space [e.g., an atrium] just because a waiting area opens onto it.) r. See NFPA 99 for further requirements. 8 s. For intermediate care, labor/delivery/recovery rooms, and labor/delivery/recovery/postpartum rooms, four total ach shall be permitted when supplemental
ting area of the waiting area. ( Note: The intent here is to not require the volume calculation to include a very large space [e.g., an atrium] just because a waiting area opens onto it.) r. See NFPA 99 for further requirements. 8 s. For intermediate care, labor/delivery/recovery rooms, and labor/delivery/recovery/postpartum rooms, four total ach shall be permitted when supplemental
heating and/or cooling systems (radiant heating and cooling, baseboard heating, etc.) are used. t. The protective environment airflow design specifications protect the patient from common environmental airborne infectious microbes (i.e., Aspergillus spores). The anteroom shall have negative air pressure in relation to the protective environment room. A door louver, transfer grille, or other acceptable means may be provided to allow for airflow from the protective environment room to the anteroom. The protective environment room shall have positive- pressure in relation to the anteroom and adjoining toilet room. Recirculation HEPA filters shall be permitted to increase the equivalent room air exchanges; however, the outdoor air changes are still required. Constant-volume airflow is required for consistent ventilation for the protected environment. The pressure relationship to adjacent areas shall remain unchanged if the PE room is utilized as a normal patient room. Rooms with reversible airflow provisions for the purpose of switching between protective environment and AII functions shall not be permitted. u. The AII room described in this standard shall be used for isolating the airborne spread of infectious diseases, such as measles, varicella, or tuberculosis. The
djacent areas shall remain unchanged if the PE room is utilized as a normal patient room. Rooms with reversible airflow provisions for the purpose of switching between protective environment and AII functions shall not be permitted. u. The AII room described in this standard shall be used for isolating the airborne spread of infectious diseases, such as measles, varicella, or tuberculosis. The
airborne infection isolation room shall have negative pressure in relation to the anteroom, and the adjoining toilet room shall have negative pressure in rela- tion to the airborne infection isolation room. Supplemental recirculating devices using HEPA filters shall be permitted in the AII room to increase the equivalent room air exchanges; however, the minimum outdoor air changes of Table 4-A are still required. AII rooms that are retrofitted from standard patient rooms from which it is impractical to exhaust directly outdoors may be recirculated with air from the AII room, provided that air first passes through a HEPA filter. When the AII room is not utilized for airborne infection isolation, the pressure relationship to adjacent areas, when measured with the door closed, shall remain unchanged and the minimum total air change rate shall be 6 ach. Switching controls for reversible airflow provisions shall not be permitted. The anteroom shall have positive air pressure in relation to the airborne infection isolation room. A door louver, transfer grille, or other acceptable means may be provided to allow for airflow from the anteroom to the airborne infection isolation room. v. When required, appropriate hoods and exhaust devices for the removal of noxious gases or chemical vapors shall be provided in accordance with NFPA 99. 8 w. The requirement that all room air is exhausted directly to outdoors applies only to radiology waiting rooms programmed to hold patients who are waiting for
chest x-rays for diagnosis of respiratory disease. x. If the planned space is designated in the organization’s operational plan to be utilized for both bronchoscopy and gastrointestinal endoscopy, the design param eters for “bronchoscopy, sputum collection, and pentamidine administration” shall be used. y. For single-bed patient rooms using Group D diffusers, a minimum of six total ach shall be provided and calculated based on the volume from finished floor
to 6 ft (1.83 m) above the floor. z. This table is based on Table 7.1 in ASHRAE 170, “Ventilation of Healthcare Facilities”, and is used with expressed written permission from ASHRAE. aa.Nurse station pressure relationship and ventilation requirements shall match the area in which it is located. ab.HD segregated compounding area shall have a differential pressure of -0.01 to -0.03 inches water column in relation to adjacent areas and a minimum of
12 air changes per hour.
78 2022 CALIFORNIA MECHANICAL CODE
VENTILATION AIR
TABLE 4-B FILTER EFFICIENCIES FOR CENTRAL VENTILATION AND AIR-CONDITIONING SYSTEMS IN GENERAL ACUTE
CARE HOSPITALS, ACUTE PSYCHIATRIC HOSPITALS, OUTPATIENT FACILITIES, AND LICENSED CLINICS 1
| AREA DESIGNATION | MINIMUM NUMBER OF FILTER BANKS |
FILTER EFFICIENCY % FILTER BANK | ||
|---|---|---|---|---|
| AREA DESIGNATION |
MINIMUM NUMBER OF FILTER BANKS |
(MINIMUM EFFICIENCY REPORTING VALUE MERV)5 | (MINIMUM EFFICIENCY REPORTING VALUE MERV)5 | (MINIMUM EFFICIENCY REPORTING VALUE MERV)5 |
| AREA DESIGNATION |
MINIMUM NUMBER OF FILTER BANKS |
NO. 11 | NO. 21 | NO. 31 |
| Orthopedic operating room, bone marrow trans- plant operating room, organ transplant operating room, NICU formula preparation room, NICU treat- ment area/room |
3 | 30% | 90% | 99.97%3 |
| Orthopedic operating room, bone marrow trans- plant operating room, organ transplant operating room, NICU formula preparation room, NICU treat- ment area/room |
3 | (8) |
(14) |
(17) |
| Protective environment rooms | 3 | 30% |
90% |
99.97%4 |
| Protective environment rooms | 3 | (8) | (14) | (17) |
| Angiography; cardiac catheterization labs; operat- ing rooms; interventional imaging procedure rooms;delivery rooms nurseries; patient care, treat- ment, cystoscopy, cesarean operating room, diag- nostic, and related areas; airborne infection isolation rooms; areas providing direct patient serv- ice or clean supplies such as sterile and clean processes, and patient area corridors |
2 | 30% | 90% | –– |
| Angiography; cardiac catheterization labs; operat- ing rooms; interventional imaging procedure rooms;delivery rooms nurseries; patient care, treat- ment, cystoscopy, cesarean operating room, diag- nostic, and related areas; airborne infection isolation rooms; areas providing direct patient serv- ice or clean supplies such as sterile and clean processes, and patient area corridors |
2 | (8) |
(14) |
–– |
| Laboratories |
2 | 30% |
80% |
–– |
| Laboratories |
2 | (8) | (13) | –– |
| Administrative, med staff support areas, bulk stor- age, soiled holding areas, food preparation areas, public cafeterias, and laundries |
1 | 30% | –– | –– |
| Administrative, med staff support areas, bulk stor- age, soiled holding areas, food preparation areas, public cafeterias, and laundries |
1 | (8) | –– | –– |
| Psychiatric hospitals intended for the care and treatment of inpatients who do not require acute medical services |
1 | 30% | –– | –– |
| Psychiatric hospitals intended for the care and treatment of inpatients who do not require acute medical services |
1 | (8) | –– | –– |
1 Based on ASHRAE 52.2. 2 Based on DOP test in accordance with MIL-STD-282 or based on ASHRAE 52.2. 3 HEPA filters at air outlet or other locations when approved by the Authority Having Jurisdiction. 4 HEPA filter located in the supply duct which serves the positive-pressure isolation room or rooms may serve more than one supply outlet and more than one positive-pressure isolation room. HEPA filter or a filter with minimum efficiency reporting value (MERV) of 17 installation shall be designed and equipped to permit safe removal, disposal and replacement of filters. 5 The numbers in parentheses represent MERV rating based on ASHRAE 52.2.
TABLE 4-C FILTER EFFICIENCIES FOR CENTRAL VENTILATION AND AIR-CONDITIONING SYSTEMS IN SKILLED NURSING FACILITIES AND INTERMEDIATE CARE FACILITIES AND CORRECTIONAL TREATMENT CENTERS 1
| AREA DESIGNATION | MINIMUM NUMBER OF FILTER BANKS |
FILTER EFFICIENCY % FILTER BANK | |
|---|---|---|---|
| AREA DESIGNATION | MINIMUM NUMBER OF FILTER BANKS |
(MINIMUM EFFICIENCY REPORTING VALUE MERV)3 | (MINIMUM EFFICIENCY REPORTING VALUE MERV)3 |
| AREA DESIGNATION | MINIMUM NUMBER OF FILTER BANKS |
NO. 11 | NO. 21 |
| All areas for inpatient care, treatment and/or diagno- sis, and those areas providing direct service or clean- ing supplies) |
2 | 30% | 80% |
| All areas for inpatient care, treatment and/or diagno- sis, and those areas providing direct service or clean- ing supplies) |
2 | (8) |
(13) |
Administrative, bulk storage, soiled holding, laun- dries and food prep areas |
1 | 30%2 | –– |
Administrative, bulk storage, soiled holding, laun- dries and food prep areas |
1 | (8) | –– |
2 Filters are not required for evaporative coolers serving laundries and food preparation areas. 3 The numbers in parentheses represent MERV rating based on ASHRAE 52.2.
2022 CALIFORNIA MECHANICAL CODE 79
VENTILATION AIR
TABLE 402.1 MINIMUM VENTILATION RATES IN BREATHING ZONE 1, 2
[ASHRAE 62.1: TABLE 6.2.2.1] Note: Ventilation air supply requirements for occupancies regulated by the California Energy Commission are found in the California Energy Code.
| OCCUPANCY CATEGORY4 | PEOPLE OUTDOOR Air Rate Rp (CFM/person) |
AREA OUTDOOR Air Rate Ra (CFM/ft2) |
DEFAULT OCCUPANT DENSITY3 (people/1000 ft2) |
AIR CLASS |
|---|---|---|---|---|
| CORRECTIONAL FACILITIES | CORRECTIONAL FACILITIES | CORRECTIONAL FACILITIES | CORRECTIONAL FACILITIES | CORRECTIONAL FACILITIES |
| Booking/waiting | 7.5 | 0.06 | 50 | 2 |
| Cell | 5 | 0.12 | 25 | 2 |
| Day room | 5 | 0.06 | 30 | 1 |
Guard stations |
5 | 0.06 | 15 | 1 |
EDUCATIONAL FACILITIES |
||||
| Art classroom | 10 | 0.18 | 20 | 2 |
Classrooms (ages 5-8) |
10 | 0.12 | 25 | 1 |
Classrooms (age 9 plus) |
10 | 0.12 | 35 | 1 |
Computer lab |
10 | 0.12 | 25 | 1 |
Daycare (through age 4) |
10 | 0.18 | 25 | 2 |
Daycare sickroom |
10 | 0.18 | 25 | 3 |
Lecture classroomh |
7.5 | 0.06 | 65 | 1 |
| Lecture hall (fixed seats)h | 7.5 | 0.06 | 150 | 1 |
| Media centera | 10 | 0.12 | 25 | 1 |
| Multi-use assemblyh | 7.5 | 0.06 | 100 | 1 |
| Music/theater/danceh | 10 | 0.06 | 35 | 1 |
| Science laboratories | 10 | 0.18 | 25 | 2 |
University/college laboratories |
10 | 0.18 | 25 | 2 |
Wood/metal shop |
10 | 0.18 | 20 | 2 |
FOOD AND BEVERAGE SERVICE |
||||
| Bars, cocktail lounges | 7.5 | 0.18 | 100 | 2 |
Cafeteria/fast food dining |
7.5 | 0.18 | 100 | 2 |
Kitchen (cooking) |
7.5 | 0.12 | 20 | 2 |
Restaurant dining rooms |
7.5 | 0.18 | 70 | 2 |
GENERAL |
GENERAL |
GENERAL |
GENERAL |
GENERAL |
| Break roomsh | 5 | 0.06 | 25 | 1 |
| Coffee stationsh | 5 | 0.06 | 20 | 1 |
| Conference/meetingh | 5 | 0.06 | 50 | 1 |
| Corridorsh | – | 0.06 | – | 1 |
| Occupiable storage rooms for liquids or gelsb | 5 | 0.12 | 2 | 2 |
| HOTELS, MOTELS, RESORTS, DORMITORIES | ||||
| Barracks sleeping areash | 5 | 0.06 | 20 | 1 |
| Bedroom/living roomh | 5 | 0.06 | 10 | 1 |
| Laundry rooms, central | 5 | 0.12 | 10 | 2 |
Laundry rooms within dwelling units |
5 | 0.12 | 10 | 1 |
Lobbies/pre-functionh |
7.5 | 0.06 | 30 | 1 |
| Multipurpose assemblyh | 5 | 0.06 | 120 | 1 |
| OFFICE BUILDINGS | OFFICE BUILDINGS | OFFICE BUILDINGS | OFFICE BUILDINGS | OFFICE BUILDINGS |
| Break Rooms | 5 | 0.12 | 50 | 1 |
Main entry lobbiesh |
5 | 0.06 | 10 | 1 |
| Occupiable storage rooms for dry materials | 5 | 0.06 | 2 | 1 |
Office spaceh |
5 | 0.06 | 5 | 1 |
| Reception areash | 5 | 0.06 | 30 | 1 |
| Telephone/data entryh | 5 | 0.06 | 60 | 1 |
| MISCELLANEOUS SPACES | MISCELLANEOUS SPACES | MISCELLANEOUS SPACES | MISCELLANEOUS SPACES | MISCELLANEOUS SPACES |
| Bank or bank lobbiesh | 7.5 | 0.06 | 15 | 1 |
| Bank vaults/safe deposith | 5 | 0.06 | 5 | 2 |
| Computer (not printing)h | 5 | 0.06 | 4 | 1 |
| Freezer and refrigerated spaces (<50°F)e | 10 | – | – | 2 |
| General manufacturing (excludes heavy industrial and processes using chemicals) |
10 | 0.18 | 7 | 3 |
Pharmacy (prep. area) |
5 | 0.18 | 10 | 2 |
Photo studios |
5 | 0.12 | 10 | 1 |
80 2022 CALIFORNIA MECHANICAL CODE
TABLE 402.1 (continued) MINIMUM VENTILATION RATES IN BREATHING ZONE 1, 2
[ASHRAE 62.1: TABLE 6.2.2.1]
VENTILATION AIR
| OCCUPANCY CATEGORY4 | PEOPLE OUTDOOR Air Rate Rp (CFM/person) |
AREA OUTDOOR Air Rate Ra (CFM/ft2) |
DEFAULT OCCUPANT DENSITY3 (people/1000 ft2) |
AIR CLASS |
|---|---|---|---|---|
| Shipping/receivingb | 10 | 0.12 | 2 | 2 |
| Sorting, packing, light assembly | 7.5 | 0.12 | 7 | 2 |
Telephone closets |
– | – | – | 1 |
Transportation waitingh |
7.5 | 0.06 | 100 | 1 |
| Warehousesb | 10 | 0.06 | – | 2 |
| PUBLIC ASSEMBLY SPACES | PUBLIC ASSEMBLY SPACES | PUBLIC ASSEMBLY SPACES | PUBLIC ASSEMBLY SPACES | PUBLIC ASSEMBLY SPACES |
| Auditorium seating areah | 5 | 0.06 | 150 | 1 |
| Courtroomsh | 5 | 0.06 | 70 | 1 |
| Legislative chambersh | 5 | 0.06 | 50 | 1 |
| Libraries | 5 | 0.12 | 10 | 1 |
| Lobbiesh | 5 | 0.06 | 150 | 1 |
| Museums (children’s) | 7.5 | 0.12 | 40 | 1 |
Museums/galleriesh |
7.5 | 0.06 | 40 | 1 |
| Places of religious worshiph | 5 | 0.06 | 120 | 1 |
| RESIDENTIAL | RESIDENTIAL | RESIDENTIAL | RESIDENTIAL | RESIDENTIAL |
| Common corridorsh | – | 0.06 | – | 1 |
| Dwelling unitf, g, h | 5 | 0.06 | See footnotef | 1 |
| RETAIL | RETAIL | RETAIL | RETAIL | RETAIL |
| Sales (except as below) | 7.5 | 0.12 | 15 | 2 |
Barber shoph |
7.5 | 0.06 | 25 | 2 |
| Beauty and nail salons | 20 | 0.12 | 25 | 2 |
Coin-operated laundries |
7.5 | 0.12 | 20 | 2 |
Mall common areash |
7.5 | 0.06 | 40 | 1 |
| Pet shops (animal areas) | 7.5 | 0.18 | 10 | 2 |
Supermarketh |
7.5 | 0.06 | 8 | 1 |
| SPORTS AND ENTERTAINMENT | SPORTS AND ENTERTAINMENT | SPORTS AND ENTERTAINMENT | SPORTS AND ENTERTAINMENT | SPORTS AND ENTERTAINMENT |
| Bowling alley (seating) | 10 | 0.12 | 40 | 1 |
Disco/dance floorsh |
20 | 0.06 | 100 | 2 |
| Gambling casinos | 7.5 | 0.18 | 120 | 1 |
Game arcades |
7.5 | 0.18 | 20 | 1 |
Gym, sports arena (play area)e |
20 | 0.18 | 7 | 2 |
| Health club/aerobics room | 20 | 0.06 | 40 | 2 |
Health club/weight rooms |
20 | 0.06 | 10 | 2 |
Spectator areash |
7.5 | 0.06 | 150 | 1 |
| Stages, studiosd, h | 10 | 0.06 | 70 | 1 |
| Swimming (pool & deck)c | – | 0.48 | – | 2 |
For SI units: 1 cubic foot per minute = 0.0283 m 3 /min, 1 square foot = 0.0929 m 2 Notes: 1 This table applies to no-smoking areas. Rates for smoking-permitted spaces shall be determined using other methods. 2 Volumetric airflow rates are based on dry air density of 0.075 pounds of dry air per cubic foot (lbda/ft3) (1.201 kgda/m3) at a barometric pressure of 1 atm (101 kPa) and an air temperature of 70°F (21°C). Rates shall be permitted to be adjusted for actual density. 3 The default occupant density shall be used where actual occupant density is not known. 4 Where the occupancy category for a proposed space or zone is not listed, the requirements for the listed occupancy category that is most similar in terms of occupant density, activities, and building construction shall be used.
ature of 70°F (21°C). Rates shall be permitted to be adjusted for actual density. 3 The default occupant density shall be used where actual occupant density is not known. 4 Where the occupancy category for a proposed space or zone is not listed, the requirements for the listed occupancy category that is most similar in terms of occupant density, activities, and building construction shall be used.
ITEM-SPECIFIC NOTES FOR TABLE 402.1 a For high school and college libraries, the values shown for “Public Assembly Spaces – Libraries” shall be used. b Rate may not be sufficient where stored materials include those having potentially harmful emissions. c Rate does not allow for humidity control. “Deck area” refers to the area surrounding the pool that is capable of being wetted during pool use or when the
pool is occupied. Deck area that is not expected to be wetted shall be designated as an occupancy category. d Rate does not include special exhaust for stage effects such as dry ice vapors and smoke. e Where combustion equipment is intended to be used on the playing surface or in the space, additional dilution ventilation, source control, or both shall be pro vided. f Default occupancy for dwelling units shall be two persons for studio and one-bedroom units, with one additional person for each additional bedroom. g Air from one residential dwelling shall not be recirculated or transferred to other spaces outside of that dwelling. h Ventilation air for this occupancy category shall be permitted to be reduced to zero where the space is in occupied-standby mode.
2022 CALIFORNIA MECHANICAL CODE 81
VENTILATION AIR
TABLE 403.2.2 ZONE AIR DISTRIBUTION EFFECTIVENESS1, 2, 3, 4, 5 [ASHRAE 62.1: TABLE 6.2.2.2]
| AIR DISTRIBUTION CONFIGURATION Ceiling supply of cool air. Ceiling supply of warm air and floor return. Ceiling supply of warm air 15°F or more above space temperature and ceiling return. Ceiling supply of warm air less than 15°F above space temperature and ceiling return provided that the 150 feet per minute (fpm) supply air jet reaches to within 4.5 feet of floor level. Floor supply of cool air and ceiling return provided that the vertical throw is more than 50 fpm at a height of 4.5 feet or more above the floor. Floor supply of cool air and ceiling return, provided low-velocity displacement ventilation achieves unidirectional flow and thermal stratification, or underfloor air distribution systems where the vertical throw is 50 fpm or less at a height of 4.5 feet above the floor. Floor supply of warm air and floor return. Floor supply of warm air and ceiling return. Makeup supply drawn in on the opposite side of the room from the exhaust, return, or both. Makeup supply drawn in near to the exhaust, return, or both locations. |
Ez 1.0 1.0 0.8 1.06 1.0 1.2 1.0 0.7 0.8 0.5 |
|---|---|
| For SI units: °C = (°F-32)/1.8, 1 foot per minute = 0.005 m/s, 1 foot = 304.8 mm | |
| Notes: |
1 “Cool air” is air cooler than space temperature. 2 “Warm air” is air warmer than space temperature. 3 “Ceiling supply” includes any point above the breathing zone. 4 “Floor supply” includes any point below the breathing zone. 5 As an alternative to using the above values, Ez shall be permitted to be regarded as equal to air change effectiveness determined in accordance with ASHRAE 129 for air distribution configurations except unidirectional flow. 6 For lower velocity supply air, Ez = 0.8
82 2022 CALIFORNIA MECHANICAL CODE
VENTILATION AIR
TABLE 403.7 MINIMUM EXHAUST RATES
[ASHRAE 62.1: TABLE 6.5]
| OCCUPANCY CATEGORY8 | EXHAUST RATE (CFM/unit) | EXHAUST RATE (CFM/ft2) | AIR CLASS |
|---|---|---|---|
| Arenas2 | – | 0.50 | 1 |
| Art classrooms | – | 0.70 | 2 |
| Auto repair rooms1 | – | 1.50 | 2 |
| Barber shops | – | 0.50 | 2 |
| Bathroom11,12 | 20/50 | – | 2 |
| Beauty and nail salons | – | 0.60 | 2 |
| Cells with toilet | – | 1.00 | 2 |
| Copy, printing rooms | – | 0.50 | 2 |
| Darkrooms | – | 1.00 | 2 |
| Educational science laboratories | – | 1.00 | 2 |
| Janitor closets, trash rooms, recy- cling |
– | 1.00 | 3 |
| Kitchens – commercial | – | 0.70 | 2 |
| Kitchenettes | – | 0.30 | 2 |
| Locker rooms for athletic, indus- trial and health care facilities |
– | 0.50 | 2 |
| Other locker rooms | – | 0.25 | 2 |
| Shower rooms7,10 | 20/50 | – | 2 |
| Paint spray booths | – | – | 4 |
| Parking garages3 | – | 0.75 | 2 |
| Pet shops (animal areas) | – | 0.90 | 2 |
| Refrigerating machinery rooms6 | – | – | 3 |
| Residential – kitchens7 | 50/100 | – | 2 |
| Soiled laundry storage rooms | – | 1.00 | 3 |
| Storage rooms, chemical | – | 1.50 | 4 |
| Toilets – private5, 9 | 25/50 | – | 2 |
| Toilets – public4, 9 | 50/70 | – | 2 |
| Woodwork shop/classrooms | – | 0.50 | 2 |
For SI units: 1 cubic foot per minute = 0.0283 m 3 ⁄ min, 1 square foot = 0.0929 m 2 Notes: 1 Stands where engines are run shall have exhaust systems that directly connect to the engine exhaust and prevent escape of fumes. 2 Where combustion equipment is intended to be used on the playing surface, additional dilution ventilation, source control, or both shall be provided. 3 Exhaust shall not be required where two or more sides comprise walls that are at least 50 percent open to the outside. 4 Rate is per water closet, urinal, or both. Provide the higher rate where periods of heavy use are expected to occur. The lower rate shall be permitted to be used otherwise. 5 Rate is for a toilet room intended to be occupied by one person at a time. For continuous system operation during normal hours of use, the lower rate shall be permitted to be used. Otherwise the higher rate shall be used. 6 For refrigeration machinery rooms, the exhaust rate shall comply with Chapter 11. 7 For continuous system operation, the lower rates shall be permitted. Otherwise the higher rate shall be used. 8 For unlisted occupancies for a proposed space not listed in the table, the requirements for the listed occupancy that is most similar in terms of occupant density and occupancy type shall be used. 9 Exhaust air that has been cleaned in accordance with the criteria of Class 1 shall be permitted to be recirculated. 10 Rate is per shower head. 11 [HCD 1 & HCD 2] A bathroom is any room containing a bathtub, a shower, a spa, or a similar source of moisture. 12 [HCD 1 & HCD 2] ANSI/ASHRAE 62.2: Tables 5.1 and 5.2.
2022 CALIFORNIA MECHANICAL CODE 83
84 2022 CALIFORNIA MECHANICAL CODE
CALIFORNIA MECHANICAL CODE – MATRIX ADOPTION TABLE
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
▸Chapter 4 — VENTILATION AIR
Overview- 402.2 Natural Ventilation. [Not permitted for OSHPD
- 401.1 Applicability. This chapter contains requirements for
- 401.2 Filters. [BSC-CG], [DSA-SS & DSA-SS/CC] In
- 402.1 Occupiable Spaces. Occupiable spaces listed in
- 402.3 Mechanical Ventilation. [Not permitted for
- 402.4 Outdoor Air Intake Protection. Required outdoorair intak…
- 403.1 General. The design outdoor air intake flow rate for
- 403.2 Zone Calculations. Ventilation zone parameters
- 403.6 Design for Varying Operating Conditions. Ventilation sys…
- 403.3 Single-Zone Systems. For ventilation systems
- 403.4 One Hundred Percent Outdoor Air Systems.
- 403.5 Multiple-Zone Recirculating Systems. For ventilation sys…
- 403.7 Exhaust Ventilation. Exhaust airflow shall be provided i…
- 403.8 Dynamic Reset. The system shall be permitted to
- 403.9 Air Classification and Recirculation. Air shall
- 404.1 General. This section presents an alternative procedure …
- 404.2 Average Outdoor Air Fraction. The average outdoor air fr…
- 404.3 Zone Ventilation Efficiency. The zone ventilation
- 405.1 General. Rooms or occupied spaces within residential occ…
- 405.2 Ventilation Air Rate. The required mechanical ventilatio…
- 405.3 Bathroom Exhaust. A mechanical exhaust directly
- 405.4 Kitchen Exhaust. A mechanical exhaust directly to
- 405.5 Ventilation Openings. Occupiable spaces shall be
- 406.0 Evaporative Cooling System for Health Care
- 407.1 General.
- 407.2 Outdoor Air Intakes and Exhaust Outlets.
- 407.3 Air Balance.
- 407.4 Air Circulation.
- 407.5 Variable Air Volume.
- 407.6 Economizers. Systems with economizers shall include
- 408.1 General. Filter efficiencies shall be certified by the
- 408.2 Filters for Hospitals.
- 408.3 Filters for Skilled Nursing Facilities, Intermedi-
- 408.4 Filters for Outpatient Facilities.
- 409.1 Ducts which penetrate construction, intended for X-
- 409.2 Duct linings and their use shall meet the requirements
- 409.3 Insulation of Ducts. Cold air ducts shall be insu-
- 409.4 The anchorage and supporting structural elements for
- 410.1 Laboratory Ventilating Systems. Laboratory ven-
- 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
- 410.3 Laboratory Fume Hoods. Laboratory fume hoods
- 411.1 The air from dining areas may be used to ventilate the
- 412.1 Boiler, heater and electrical equipment rooms shall be
- 412.2 Floor surfaces in occupied spaces above such rooms
- 413.1 Rooms in areas where excessive heat or moisture is
- 413.2 Kitchen, morgues and laundries located inside a hos-
- 414.1 Exhaust Systems. A separate, dedicated exhaust
- 414.2 Air Distribution. The supply outlets and exhaust
- 415.1 Air Distribution. The supply outlets and exhaust and
- 416.1 An alarm system which is based on static pressure con-
- 416.2 Other acceptable alarm systems will be allowed when
- 416.3 [For OSHPD 4] For correctional treatment centers,
- 416.4 Prior to acceptance of the rooms, the alarm system
- 417.0 Testing and Balancing Airborne Infection Isola-
- 418.1 Air Changes. The ETO sterilization equipment room
- 418.2 Exhaust Requirements.
- 418.3 Ventilation Requirements.
- 418.4 Gas Valves. Installation of gas line hand valves at the
- 418.5 Alarm Systems. An Audible and visual alarm system
- 419.1 Formula Preparation Area. Air shall be supplied
- 419.2 Treatment Area/Room. Air shall be supplied over
- 420.0 Air Distribution Devices. [OSHPD 1, 2, 3, 4 & 5]
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — GEOTHERMAL ENERGY SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE