407.1 General.

California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

407.1.1 All supply-air, return air, and exhaust-air sys- tems shall be mechanically operated and such systems for areas listed in Table 4-A shall be operated continu- ously. Natural ventilation through windows or other openings such as louvers will be considered as supple- mental to the required mechanical ventilation systems.

Exceptions: (1) Natural ventilation shall not be used in airborne

infection isolation rooms and protective environment rooms. (2) The number of air changes may be reduced to 25

percent of the indicated value in Table 4-A, when the room is unoccupied, if provisions are made to ensure the following: (1) The number of air changes per hour indicated

is reestablished whenever the space is occupied. (2) The pressure relationship with the surrounding

rooms is maintained when the air changes per hour are reduced. In areas requiring no contin- uous directional control as identified in accor-

68 2022 CALIFORNIA MECHANICAL CODE

dance with Table 4-A, ventilation systems may be shut down when the space is unoccupied and ventilation is not otherwise required. Ventilation shall not be reduced in rooms specifically used for airborne infection control, such as waiting rooms, triage rooms, corridors, reception areas, areas adjacent to waiting areas, airborne infec- tion isolation rooms, negative pressure exam room, negative pressure x-ray treatment rooms, and protective environment rooms. All operat- ing and delivery rooms shall maintain a mini- mum of six air changes per hour of total air when not in use. 407.1.2 Fans serving exhaust systems shall be located at the discharge end of the system. The ventilation rates shown in Table 4-A shall be considered as minimum acceptable rates and shall not be construed as precluding the use of higher ventilation rates if they are required to meet design conditions. 407.1.3 Services/Systems and Utilities. (Refer to Sec- tion 1224.4.1 of the California Building Code).

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
    Overview
    1. 402.2 Natural Ventilation. [Not permitted for OSHPD
    2. 401.1 Applicability. This chapter contains requirements for
    3. 401.2 Filters. [BSC-CG], [DSA-SS & DSA-SS/CC] In
    4. 402.1 Occupiable Spaces. Occupiable spaces listed in
    5. 402.3 Mechanical Ventilation. [Not permitted for
    6. 402.4 Outdoor Air Intake Protection. Required outdoorair intak…
    7. 403.1 General. The design outdoor air intake flow rate for
    8. 403.2 Zone Calculations. Ventilation zone parameters
    9. 403.6 Design for Varying Operating Conditions. Ventilation sys…
    10. 403.3 Single-Zone Systems. For ventilation systems
    11. 403.4 One Hundred Percent Outdoor Air Systems.
    12. 403.5 Multiple-Zone Recirculating Systems. For ventilation sys…
    13. 403.7 Exhaust Ventilation. Exhaust airflow shall be provided i…
    14. 403.8 Dynamic Reset. The system shall be permitted to
    15. 403.9 Air Classification and Recirculation. Air shall
    16. 404.1 General. This section presents an alternative procedure …
    17. 404.2 Average Outdoor Air Fraction. The average outdoor air fr…
    18. 404.3 Zone Ventilation Efficiency. The zone ventilation
    19. 405.1 General. Rooms or occupied spaces within residential occ…
    20. 405.2 Ventilation Air Rate. The required mechanical ventilatio…
    21. 405.3 Bathroom Exhaust. A mechanical exhaust directly
    22. 405.4 Kitchen Exhaust. A mechanical exhaust directly to
    23. 405.5 Ventilation Openings. Occupiable spaces shall be
    24. 406.0 Evaporative Cooling System for Health Care
    25. 407.1 General.
    26. 407.2 Outdoor Air Intakes and Exhaust Outlets.
    27. 407.3 Air Balance.
    28. 407.4 Air Circulation.
    29. 407.5 Variable Air Volume.
    30. 407.6 Economizers. Systems with economizers shall include
    31. 408.1 General. Filter efficiencies shall be certified by the
    32. 408.2 Filters for Hospitals.
    33. 408.3 Filters for Skilled Nursing Facilities, Intermedi-
    34. 408.4 Filters for Outpatient Facilities.
    35. 409.1 Ducts which penetrate construction, intended for X-
    36. 409.2 Duct linings and their use shall meet the requirements
    37. 409.3 Insulation of Ducts. Cold air ducts shall be insu-
    38. 409.4 The anchorage and supporting structural elements for
    39. 410.1 Laboratory Ventilating Systems. Laboratory ven-
    40. 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
    41. 410.3 Laboratory Fume Hoods. Laboratory fume hoods
    42. 411.1 The air from dining areas may be used to ventilate the
    43. 412.1 Boiler, heater and electrical equipment rooms shall be
    44. 412.2 Floor surfaces in occupied spaces above such rooms
    45. 413.1 Rooms in areas where excessive heat or moisture is
    46. 413.2 Kitchen, morgues and laundries located inside a hos-
    47. 414.1 Exhaust Systems. A separate, dedicated exhaust
    48. 414.2 Air Distribution. The supply outlets and exhaust
    49. 415.1 Air Distribution. The supply outlets and exhaust and
    50. 416.1 An alarm system which is based on static pressure con-
    51. 416.2 Other acceptable alarm systems will be allowed when
    52. 416.3 [For OSHPD 4] For correctional treatment centers,
    53. 416.4 Prior to acceptance of the rooms, the alarm system
    54. 417.0 Testing and Balancing Airborne Infection Isola-
    55. 418.1 Air Changes. The ETO sterilization equipment room
    56. 418.2 Exhaust Requirements.
    57. 418.3 Ventilation Requirements.
    58. 418.4 Gas Valves. Installation of gas line hand valves at the
    59. 418.5 Alarm Systems. An Audible and visual alarm system
    60. 419.1 Formula Preparation Area. Air shall be supplied
    61. 419.2 Treatment Area/Room. Air shall be supplied over
    62. 420.0 Air Distribution Devices. [OSHPD 1, 2, 3, 4 & 5]
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — GEOTHERMAL ENERGY SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  25. Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.