Chapter 4 — VENTILATION AIR

407.4 Air Circulation.

California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

407.4.1 Design of the ventilation system shall provide air movement that is generally from clean to less clean areas.

407.4.1.1 Air supplied to operating rooms, cesarean operating rooms, cardiac catheterization labs, cys- toscopy rooms, delivery rooms, and nurseries shall be delivered at or near the ceiling of the area served. In these areas and in morgues and autopsy rooms all air removed from the area shall be removed near floor level. Exhaust or recirculation inlets shall be located not less than 3 inches (76 mm) nor more than 8 inches (203 mm) above the finished floor, except in morgues and autopsy rooms where all of the exhaust air is removed through an autopsy table designed for this purpose. At least two exhaust or recirculation air inlets of equal capacity shall be used in all cardiac catheterization labs, cystoscopy rooms, operating rooms, and delivery rooms and shall be located not less than 3 inches (76 mm) nor more than 8 inches (203 mm) above the finished floor. Exception: For airborne infection isolation rooms and protective environment rooms, see Sections 414.0 and 415.0. 407.4.1.2 Room supply air outlets and room recir- culation and exhaust air inlets installed in nonsensi- tive areas shall be located not less than 3 inches (76 mm) above the floor. Exception: For airborne infection isolation rooms and protective environment rooms, see Sections 414.0 and 415.0. 407.4.1.3 Corridors shall not be used to convey sup- ply, return, transfer or exhaust air to or from any room if the corridor is required to be fire resistive construction per the California Building Code. Exceptions: (1) Mechanically exhausted toilet rooms of 50

square feet (4.7 m 2 ) or less and small rooms of 30 square feet (2.79 m 2 ) or less such as janitor closets, housekeeping rooms, and electrical or telephone closets opening directly onto corridor. (2) Air transfer caused by pressure differentials in

rooms required to have a positive or negative air balance by Table 4-A. 407.4.1.4 No space above a ceiling may be utilized as an outside-air, relief-air, supply-air, exhaust-air, or return-air plenum. Exception: Designs specifically approved by the enforcing agency. 407.4.1.5 Air from a patient room, exam room, treat- ment room shall not be transferred to another simi- lar room without first having passed through air filters as required by Table 4-B or Table 4-C.

2022 CALIFORNIA MECHANICAL CODE 69

VENTILATION AIR

407.4.1.6 Supply outlets and return and exhaust air inlets shall be located to prevent short-circuiting. 407.4.1.7 Recirculating Room Units. For spaces where Table 4-A permits air to be recirculated by room units, the portion of the minimum total air changes per hour required for a space that is greater than the minimum outdoor air changes per hour required component may be provided by recirculat- ing room HVAC units. Such recirculating room HVAC units shall: (1) not receive nonfiltered, nonconditioned outdoor

air; (2) serve only a single space; and (3) provide filtration per Section 408.2 and Section

408.3 for airflow passing over any surface that is designed to condense water. This filter shall be located upstream of any such cold surface, so that all of the air passing over the cold surface is fil- tered.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
    Overview
    1. 402.2 Natural Ventilation. [Not permitted for OSHPD
    2. 401.1 Applicability. This chapter contains requirements for
    3. 401.2 Filters. [BSC-CG], [DSA-SS & DSA-SS/CC] In
    4. 402.1 Occupiable Spaces. Occupiable spaces listed in
    5. 402.3 Mechanical Ventilation. [Not permitted for
    6. 402.4 Outdoor Air Intake Protection. Required outdoorair intak…
    7. 403.1 General. The design outdoor air intake flow rate for
    8. 403.2 Zone Calculations. Ventilation zone parameters
    9. 403.6 Design for Varying Operating Conditions. Ventilation sys…
    10. 403.3 Single-Zone Systems. For ventilation systems
    11. 403.4 One Hundred Percent Outdoor Air Systems.
    12. 403.5 Multiple-Zone Recirculating Systems. For ventilation sys…
    13. 403.7 Exhaust Ventilation. Exhaust airflow shall be provided i…
    14. 403.8 Dynamic Reset. The system shall be permitted to
    15. 403.9 Air Classification and Recirculation. Air shall
    16. 404.1 General. This section presents an alternative procedure …
    17. 404.2 Average Outdoor Air Fraction. The average outdoor air fr…
    18. 404.3 Zone Ventilation Efficiency. The zone ventilation
    19. 405.1 General. Rooms or occupied spaces within residential occ…
    20. 405.2 Ventilation Air Rate. The required mechanical ventilatio…
    21. 405.3 Bathroom Exhaust. A mechanical exhaust directly
    22. 405.4 Kitchen Exhaust. A mechanical exhaust directly to
    23. 405.5 Ventilation Openings. Occupiable spaces shall be
    24. 406.0 Evaporative Cooling System for Health Care
    25. 407.1 General.
    26. 407.2 Outdoor Air Intakes and Exhaust Outlets.
    27. 407.3 Air Balance.
    28. 407.4 Air Circulation.
    29. 407.5 Variable Air Volume.
    30. 407.6 Economizers. Systems with economizers shall include
    31. 408.1 General. Filter efficiencies shall be certified by the
    32. 408.2 Filters for Hospitals.
    33. 408.3 Filters for Skilled Nursing Facilities, Intermedi-
    34. 408.4 Filters for Outpatient Facilities.
    35. 409.1 Ducts which penetrate construction, intended for X-
    36. 409.2 Duct linings and their use shall meet the requirements
    37. 409.3 Insulation of Ducts. Cold air ducts shall be insu-
    38. 409.4 The anchorage and supporting structural elements for
    39. 410.1 Laboratory Ventilating Systems. Laboratory ven-
    40. 410.2 Exhaust Hoods and Safety Cabinets. Hoods and
    41. 410.3 Laboratory Fume Hoods. Laboratory fume hoods
    42. 411.1 The air from dining areas may be used to ventilate the
    43. 412.1 Boiler, heater and electrical equipment rooms shall be
    44. 412.2 Floor surfaces in occupied spaces above such rooms
    45. 413.1 Rooms in areas where excessive heat or moisture is
    46. 413.2 Kitchen, morgues and laundries located inside a hos-
    47. 414.1 Exhaust Systems. A separate, dedicated exhaust
    48. 414.2 Air Distribution. The supply outlets and exhaust
    49. 415.1 Air Distribution. The supply outlets and exhaust and
    50. 416.1 An alarm system which is based on static pressure con-
    51. 416.2 Other acceptable alarm systems will be allowed when
    52. 416.3 [For OSHPD 4] For correctional treatment centers,
    53. 416.4 Prior to acceptance of the rooms, the alarm system
    54. 417.0 Testing and Balancing Airborne Infection Isola-
    55. 418.1 Air Changes. The ETO sterilization equipment room
    56. 418.2 Exhaust Requirements.
    57. 418.3 Ventilation Requirements.
    58. 418.4 Gas Valves. Installation of gas line hand valves at the
    59. 418.5 Alarm Systems. An Audible and visual alarm system
    60. 419.1 Formula Preparation Area. Air shall be supplied
    61. 419.2 Treatment Area/Room. Air shall be supplied over
    62. 420.0 Air Distribution Devices. [OSHPD 1, 2, 3, 4 & 5]
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — GEOTHERMAL ENERGY SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  25. Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.