Skip to content

Chapter 6 — DUCT SYSTEMS

605.1 General. Air ducts conveying air at temperatures

California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

exceeding 140°F (60°C) shall be insulated to maintain an insulation surface temperature of not more than 140°F (60°C). Insulation material on the exterior of ducts shall be legibly printed with the name of the manufacturer, the thermal resistance (R) value at installed thickness, flame-spread index, and smoke developed index of the composite material. Internal duct liners and insulation shall be installed in accordance with SMACNA HVAC Duct Construction Standards – Metal and Flexible. [OSHPD 1, 1R, 2, 3, 4 & 5] Cold air ducts shall be insulated wherever necessary or to prevent condensation. Exceptions: (1) Factory-installed plenums, casings, or ductwork fur nished as a part of HVAC equipment tested and rated in accordance with approved energy efficiency standards. (2) Ducts or plenums located in conditioned spaces where

heat gain or heat loss will not increase energy use. (3) For runouts less than 10 feet (3048 mm) in length to air

terminals or air outlets, the rated R-value of insulation need not exceed R-3.5. (4) Backs of air outlets and outlet plenums exposed to

unconditioned or indirectly conditioned spaces with face areas exceeding 5 square feet (0.5 m 2 ) need not exceed R2; those 5 square feet (0.5 m 2 ) or smaller need not be insulated. (5) Ducts and plenums used exclusively for evaporative

cooling systems. 605.1.1 Within Ducts or Plenums. Materials installed within ducts and plenums for insulating, sound deadening, or other purposes shall have a mold, humidity, and erosion-resistant surface where tested in accordance with UL 181. Duct liners in systems operating with air velocities exceeding 2000 feet per minute (10.16 m/s) shall be fastened with both adhesive and mechanical fasteners, and exposed edges shall have approved treatment to withstand the operating velocity. Where the internal insulation is capable of being in contact with condensates or other liquids, the material shall be water-resistant. Pipe and duct insulation shall not be used to reduce the maximum flame and smoke requirements in Section 602.2 unless listed for application in plenums and tested in accordance with ASTM E84 or UL 723 as a composite assembly of the duct or pipe and its associated insulation, coatings and adhesives. 605.1.2 Duct Coverings and Linings. Insulation applied to the surface of ducts, including duct coverings, linings, tapes, and adhesives, located in buildings shall have a flame-spread index not to exceed 25 and a smokedeveloped index not to exceed 50, where tested in accordance with ASTM E84 or UL 723. The specimen

« « « « « «

DUCT SYSTEMS

preparation and mounting procedures of ASTM E2231 shall be used. Air duct coverings and linings shall not flame, glow, smolder, or smoke where tested in accordance with ASTM C411 at the temperature to which they are exposed in service. In no case shall the test temperature be less than 250°F (121°C). Coverings shall not penetrate a fire-resistance-rated assembly.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
    Overview
    1. 602.3 Metallic. Ducts, plenums, or fittings of metal shall com…
    2. 602.4 Nonmetallic Ducts. Nonmetallic ducts shall comply
    3. 601.1 Applicability. Ducts and plenums that are portions of
    4. 601.2 Sizing Requirements. Duct systems shall be sized
    5. 602.1 General. Materials used for duct systems shall comply wi…
    6. 602.2 Combustibles Within Ducts or Plenums. Materials exposed …
    7. 603.4 Flexible Air Ducts. Flexible air ducts shall comply
    8. 602.5 Vibration Isolators. Vibration isolation connectors
    9. 602.6 Corridors. Corridors shall not be used to convey air
    10. 603.1 General. Air ducts shall be installed in accordance
    11. 603.2 Under Floor or Crawl Space. Air ducts installed
    12. 603.3 Metal Ducts. Ducts shall be supported at each change
    13. 603.8 Protection Against Flood Damage. In flood hazard areas, …
    14. 603.9 Joints and Seams of Ducts. Joints and seams for
    15. 603.5 Plastic Ducts. Plastic air ducts and fittings shall be
    16. 603.6 Protection of Ducts. Ducts installed in locations
    17. 603.7 Support of Ducts. Ducts shall be supported in
    18. 603.12 Air Dispersion Systems. Where installed, air dispersion…
    19. 603.13 Clearances. Duct clearances shall be in accordance
    20. 604.1 Furnace Plenums and Air Ducts. Furnace plenums
    21. 604.2 Supplied as a Part of Furnace. A furnace plenum
    22. 604.3 Not Supplied with the Furnace. Where a furnace
    23. 603.10 Cross Contamination. Exhaust ducts that convey
    24. 603.11 Underground Installation. Ducts installed underground s…
    25. 604.4 Return Air. Where a furnace is installed so supply
    26. 605.1 General. Air ducts conveying air at temperatures
    27. 605.2 [OSHPD 1, 1R, 2, 3 (Surgical Clinics), 4 & 5] Ther-
    28. 605.3 [OSHPD 1, 1R, 2, 4 & 5] Thermal or acoustical lining
    29. 606.1 Smoke Dampers. Smoke dampers shall comply
    30. 606.2 Fire Dampers. Fire dampers shall comply with UL
    31. 606.3 Ceiling Radiation Dampers. Ceiling radiation
    32. 606.4 Multiple Arrangements. Where size requires the
    33. 606.5 Access and Identification. Fire and smoke
    34. 608.1 General. An under-floor space shall be permitted to
    35. 608.2 Dwelling Units. The use of under-floor space shall
    36. 608.3 Enclosed. Such spaces shall be cleaned of all loose
    37. 608.4 Flammable Materials. The enclosing material of
    38. 608.5 Access. Access shall be through an opening in the
    39. 608.6 Automatic Control. A furnace supplying warm air
    40. 608.7 Temperature Limit. A furnace supplying warm air to
    41. 608.8 Noncombustible Receptacle. A noncombustible
    42. 608.9 Floor Registers. Floor registers shall be designed
    43. 608.10 Exterior Wall and Interior Stud Partitions.
    44. 606.6 Freedom from Interference. Dampers shall be
    45. 606.7 Temperature Classification of Operating Ele-
    46. 606.8 When the automatic activation of a smoke damper or a
    47. 607.1 General. Perforated ceilings shall be permitted to be
    48. 607.2 Requirements. Ventilating ceilings shall comply
    49. 608.11 Wall Register. Each wall register shall be connected
    50. 608.12 Distance from Combustible. A duct complying
    51. 608.13 Vapor Barrier. The entire ground surface of the
    52. 608.14 Prohibited. Fuel gas lines and plumbing waste
    53. 609.1 Air-Moving Systems and Smoke Detectors.
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — GEOTHERMAL ENERGY SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  25. Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.