603.4 Flexible Air Ducts. Flexible air ducts shall comply
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
with UL 181, and shall be installed in accordance with the manufacturer’s installation instructions and SMACNA
HVAC Duct Construction Standards – Metal and Flexible.
Flexible air duct installations shall comply with the following:
(1) Ducts shall be installed using the minimum required length to make the connection.
(2) Horizontal duct runs shall be supported at not more than 4 feet (1219 mm) intervals.
(3) Vertical risers shall be supported at not more than 6 feet (1829 mm) intervals.
(4) Sag between support hangers shall not exceed [1] ⁄ 2 inch (12.7 mm) per foot (305 mm) of support spacing.
(5) Supports shall be rigid and shall be not less than 1 [1] ⁄ 2 inches (38 mm) wide at point of contact with the duct surface.
(6) Duct bends shall be not less than one duct diameter bend radius.
(7) Screws shall not penetrate the inner liner of non-metallic flexible ducts unless permitted in accordance with the manufacturer’s installation instructions.
(8) Fittings for attaching non-metallic ducts shall be beaded and have a collar length of not less than 2 inches (51 mm) for attaching the duct. Metal worm-gear clamps shall be used.
«
138 2025 CALIFORNIA MECHANICAL CODE
DUCT SYSTEMS
Exception: Where attaching metallic ducts using screws in accordance with the manufacturer’s installation
instructions.
(9) Duct inner liner shall be installed at not less than 1 inch (25.4 mm) on the collar and past the bead prior to the application of the tape and mechanical fastener. Where mastic is used instead of tape, the mastic shall be applied in accordance the mastic manufacturer’s instructions.
(10)Duct outer vapor barriers shall be secured using two wraps of approved tape. A mechanical fastener shall be permitted to be used in place of, or in combination with, the tape.
(11)Flexible air ducts shall not penetrate a fire-resistancerated assembly or construction.
(12)The temperature of the air to be conveyed in a flexible air duct shall not exceed 250°F (121°C).
(13)Flexible air ducts shall be sealed in accordance with Section 603.9.
603.4.1 Length Limitation. [Not permitted for OSHPD 1, 2, 3, 4 & 5] Flexible air ducts shall be not more than 5 feet (1524 mm) in length and shall not be used in lieu of rigid elbows or fittings. Flexible air ducts shall be permitted to be used as an elbow at a terminal device.
Exception: Residential occupancies.
603.4.1.1 Flexible Ducts. [OSHPD 1, 2, 3, 4 & 5] In hospital building projects and all other health- care facilities, including clinics and correctional treatment centers, flexible ducts of not more than 10 feet (3048 mm) in length may be used to connect supply, return or exhaust-air terminal devices to rigid duct systems. Where constant volume, variable volume or mixing boxes are utilized, flexible duct of not more than 5 feet (1524 mm), may be used on the inlet side for alignment. An internal impervious liner shall be provided to isolate insulation material from conditioned air. Flexible duct is not permitted in cor- ridors where fire or smoke dampers are omitted per CBC 717.5.4 and the duct is required to be con- structed of steel not less than 0.019 inch (0.483 mm) in thickness.
603.4.2 Flexible Air Connectors. Flexible air connectors shall not be permitted.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
▸Chapter 6 — DUCT SYSTEMS
Overview- 601.1 Applicability. Ducts and plenums that are portions of
- 601.2 Sizing Requirements. Duct systems shall be sized
- 602.1 General. Materials used for duct systems shall comply wi…
- 602.2 Combustibles Within Ducts or Plenums. Materials exposed …
- 602.3 Tall Wood (Mass Timber) Buildings. Duct systems installe…
- 602.4 Metallic. Ducts, plenums, or fittings of metal shall
- 602.5 Nonmetallic Ducts. Nonmetallic ducts shall comply
- 602.6 Vibration Isolators. Vibration isolation connectors
- 602.7 Corridors. Corridors shall not be used to convey air to
- 603.1 General. Air ducts shall be installed in accordance
- 603.2 Under-Floor or Crawl Space. Air ducts installed
- 603.3 Metal Ducts. Ducts shall be supported at each change
- 603.4 Flexible Air Ducts. Flexible air ducts shall comply
- 603.5 Plastic Ducts. Plastic air ducts and fittings shall be
- 603.6 Protection of Ducts. Ducts installed in locations
- 603.7 Support of Ducts. Ducts shall be supported in
- 603.8 Protection Against Flood Damage. In flood hazard areas, …
- 603.9 Joints and Seams of Ducts. Joints and seams for
- 603.10 Cross Contamination. Exhaust ducts that convey
- 603.11 Underground Installation. Ducts installed underground s…
- 603.12 Air Dispersion Systems. Where installed, air dispersion…
- 603.13 Clearances. Duct clearances shall be in accordance
- 604.1 Furnace Plenums and Air Ducts. Furnace plenums
- 604.2 Supplied as a Part of Furnace. A furnace plenum
- 604.3 Not Supplied with the Furnace. Where a furnace
- 604.4 Return Air. Where a furnace is installed so supply
- 605.1 General. Air ducts conveying air at temperatures
- 605.2 [OSHPD 1, 3 (Surgical Clinics), 4 & 5] Thermal
- 605.3 [OSHPD 1, 2, 4 & 5] Thermal or acoustical lining
- 606.1 Smoke Dampers. Smoke dampers shall comply
- 606.2 Fire Dampers. Fire dampers shall comply with UL
- 606.3 Ceiling Radiation Dampers. Ceiling radiation
- 606.4 Combination Fire/Smoke Dampers. Combination fire/smoke d…
- 606.5 Corridor Dampers. Corridor dampers shall comply
- 606.6 Periodic Testing and Inspection. Testing and
- 606.7 Multiple Arrangements. Where size requires the
- 606.8 Access and Identification. Fire and smoke
- 606.9 Freedom from Interference. Dampers shall be
- 606.10 Temperature Classification of Operating Ele-
- 607.1 General. Perforated ceilings shall be permitted to be
- 607.2 Requirements. Ventilating ceilings shall comply
- 608.1 General. An under-floor space shall be permitted to
- 608.2 Dwelling Units. The use of under-floor space shall
- 608.3 Enclosed. Such spaces shall be cleaned of all loose
- 608.4 Flammable Materials. The enclosing material of
- 608.5 Access. Access shall be through an opening in the
- 608.6 Automatic Control. A furnace supplying warm air
- 608.7 Temperature Limit. A furnace supplying warm air to
- 608.8 Noncombustible Receptacle. A noncombustible
- 608.9 Floor Registers. Floor registers shall be designed
- 608.10 Exterior Wall and Interior Stud Partitions.
- 608.11 Wall Register. Each wall register shall be connected
- 608.12 Distance from Combustible. A duct complying
- 608.13 Vapor Barrier. The entire ground surface of the
- 608.14 Prohibited. Fuel gas lines and plumbing waste
- 609.1 Air-Moving Systems and Smoke Detectors.
- 609.2 Air-Moving Systems and Smoke Detectors in
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
- Chapter 18 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
- Appendix H — PROFESSIONAL QUALIFICATIONS
- Appendix I — INDOOR HORTICULTURAL FACILITIES
- Appendix J — CLEAN AIR DELIVERY