608.8 Noncombustible Receptacle — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 608.8 · Effective January 1, 2026 · Official source: Building Standards Commission

A noncombustible receptacle shall be placed below each floor opening into the air chamber, and such receptacle shall comply with Section 608.8.1 through Section 608.8.3.

608.8.1 Location. The receptacle shall be securely suspended from the floor members and shall be not more than 18 inches (457 mm) below the floor opening.

608.8.2 Area. The area of the receptacle shall extend 3 inches (76 mm) beyond the opening on all sides.

608.8.3 Perimeter. The perimeter of the receptacle shall have a vertical lip not less than 1 inch (25.4 mm) high at the open sides where it is at the level of the bottom of the joists, or 3 inches (76 mm) high where the receptacle is suspended.