Chapter 6 — DUCT SYSTEMS

605.1 General — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 605.1 · Effective January 1, 2026 · Official source: Building Standards Commission

Air ducts conveying air at temperatures exceeding 140°F (60°C) shall be insulated to maintain an insulation surface temperature of not more than 140°F (60°C). Insulation material on the exterior of ducts shall be legibly printed with the name of the manufacturer, the thermal resistance (R) value at installed thickness, flame-spread index, and smoke developed index of the composite material. Internal duct liners and insulation shall be installed in accordance with

SMACNA HVAC Duct Construction Standards – Metal and Flexible. [OSHPD 1, 1R, 2, 3, 4 & 5] Cold air ducts shall be insulated wherever necessary or to prevent condensation.

Exceptions:

(1) Factory-installed plenums, casings, or ductwork furnished as a part of HVAC equipment tested and rated in accordance with approved energy efficiency standards.

(2) Ducts or plenums located in conditioned spaces where heat gain or heat loss will not increase energy use.

(3) For runouts less than 10 feet (3048 mm) in length to air terminals or air outlets, the rated R-value of insulation need not exceed R-3.5.

(4) Backs of air outlets and outlet plenums exposed to unconditioned or indirectly conditioned spaces with face areas exceeding 5 square feet (0.5 m [2] ) need not exceed R2; those 5 square feet (0.5 m [2] ) or smaller need not be insulated.

(5) Ducts and plenums used exclusively for evaporative cooling systems.

605.1.1 Within Ducts or Plenums. Materials installed

within ducts and plenums for insulating, sound deadening, or other purposes shall have a mold, humidity, and erosion-resistant surface where tested in accordance with

UL 181. Duct liners in systems operating with air velocities exceeding 2000 feet per minute (10.16 m/s) shall be fastened with both adhesive and mechanical fasteners, and exposed edges shall have approved treatment to withstand the operating velocity. Where the internal insulation is capable of being in contact with condensates or other liquids, the material shall be water-resistant. Pipe and duct insulation shall not be used to reduce the maxi mum flame and smoke requirements in Section 602.2 unless listed for application in plenums and tested in accordance with ASTM E84 or UL 723 as a composite assembly of the duct or pipe and its associated insulation, coatings and adhesives.

605.1.2 Duct Coverings and Linings. Insulation applied to the interior or exterior surface of ducts located in buildings, including duct coverings, linings, tapes, and adhesives, shall have a flame-spread index not to exceed 25 and a smoke-developed index not to exceed 50, where tested in accordance with ASTM E84 or UL 723. The

specimen preparation and mounting procedures of ASTM E2231 shall be used. Air duct coverings and linings shall not flame, glow, smolder, or smoke where tested in accordance with ASTM C411 at the temperature to which they are exposed in service. In no case shall the test temperature be less than 250°F (121°C). Coverings shall not penetrate a fire-resistance-rated assembly. The duct coverings and linings shall be listed and labeled.