Chapter 6 — DUCT SYSTEMS

608.2 Dwelling Units — 2025 California Mechanical Code

California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-25 · California

CBSC: official editions, supplements and errata

Italicized text is a California amendment to the model code, as printed in the official publication.

Cite as: 2025 California Mechanical Code (Title 24, Part 4) § 608.2 · Effective January 1, 2026 · Official source: Building Standards Commission

The use of under-floor space shall be limited to dwelling units not more than two stories in height. Except for the floor immediately above the underfloor plenum, supply ducts shall be provided extending from the plenum to registers on other floor levels.

Exception: In flood hazard areas, under-floor spaces shall not be used as supply plenums unless the flood opening requirements in the building code are met.