Section 160.3
California Energy Code (Title 24, Part 6) · 2022 edition · updated 2026-09-12 · California
MANDATORY REQUIREMENTS FOR SPACE-
CONDITIONING SYSTEMS IN MULTIFAMILY
BUILDINGS Space-conditioning systems serving multifamily dwelling units and common use areas shall comply with the applicable requirements of Sections 160.3(a) through 160.3(c).
(a) Controls. Space-conditioning systems serving dwelling units and common use areas in multifamily buildings shall comply with applicable requirements of Section 160.3(a)1 or 160.3(a)2.
Dwelling unit thermostats. All heating or cooling systems, including heat pumps, not controlled by a central energy management control system (EMCS) shall have a setback thermostat, as specified in Section 110.2(c).
Common use area controls . Heating or cooling systems serving common use areas of multifamily buildings shall comply with application requirements of Sections 160.3(a)2A through 160.3(a)2J.
Exception to Section 160.3(a)2: Heating or cooling systems exclusively serving dwelling units and common use areas providing shared provisions for living, eating, cooking or sanitation to dwelling units that would otherwise lack these provisions may instead comply with Section 160.3(a)1. A. Thermostatic controls for each zone. The supply
of heating and cooling energy to each space-conditioning zone shall be controlled by an individual thermostatic control that responds to temperature within the zone and that meets the applicable requirements of Section 160.3(a)2B. An energy management control system (EMCS) may be installed to comply with the requirements of one or
thermostat located in one of the zones served by the system. B. Criteria for zonal thermostatic controls. The indi
vidual thermostatic controls required by Section 160.3(a)2A shall meet the following requirements as applicable:
i. Where used to control comfort heating, the ther mostatic controls shall be capable of being set, locally or remotely, down to 55°F or lower.
i. Where used to control comfort heating, the ther
ii. Where used to control comfort cooling, the ther mostatic controls shall be capable of being set, locally or remotely, up to 85°F or higher.
iii.Where used to control both comfort heating and
comfort cooling, the thermostatic controls shall meet Items i and ii and shall be capable of providing a temperature range or deadband of at least 5°F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.
Exception to Section 160.3(a)2Biii: Systems with thermostats that require manual changeover between heating and cooling modes. iv. Thermostatic controls for all single zone air con ditioners and heat pumps shall comply with the requirements of Sections 110.2(c) and 110.12(a) and, if equipped with DDC to the zone level, with the automatic demand shed controls of Section 110.12(b).
Exception to Section 160.3(a)2Biv: Package terminal air conditioners, package terminal heat pumps, room air conditioners and room air-conditioner heat pumps. C. Heat pump controls. All heat pumps with supple mentary electric resistance heaters shall be installed with controls that comply with Section 110.2(b).
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
TABLE 160.2-A¶
INFILTRATION EFFECTIVENESS WEATHER AND SHIELDING FACTORS [ASHRAE 62.2:Table B1]
| TMY3 | wsf | WEATHER STATION | LATITUDE | LONGITUDE | STATE |
|---|---|---|---|---|---|
| 690150 | 0.50 | Twentynine Palms | 34.30 | –116.17 | California |
| 722860 | 0.43 | March AFB | 33.90 | –117.25 | California |
| 722868 | 0.45 | Palm Springs Intl | 33.83 | –116.50 | California |
| 722869 | 0.42 | Riverside Muni | 33.95 | –117.45 | California |
| 722880 | 0.39 | Burbank–Glendale–Pasadena AP | 34.20 | –118.35 | California |
| 722885 | 0.39 | Santa Monica Muni | 34.02 | –118.45 | California |
| 722886 | 0.39 | Van Nuys Airport | 34.22 | –118.48 | California |
| 722895 | 0.55 | Lompoc (AWOS) | 34.67 | –120.47 | California |
| 722897 | 0.51 | San Luis Co Rgnl | 35.23 | –120.63 | California |
| 722899 | 0.45 | Chino Airport | 33.97 | –117.63 | California |
| 722900 | 0.38 | San Diego Lindbergh Field | 32.73 | –117.17 | California |
| 722903 | 0.39 | San Diego/ |
32.82 | –117.13 | California |
| 722904 | 0.40 | Chula Vista Brown Field NAAS | 32.58 | –116.98 | California |
| 722906 | 0.39 | San Diego North Island NAS | 32.70 | –117.20 | California |
| 722926 | 0.40 | Camp Pendleton MCAS | 33.30 | –117.35 | California |
| 722927 | 0.38 | Carlsbad/ |
33.13 | –117.28 | California |
| 722930 | 0.39 | San Diego Miramar NAS | 32.87 | –117.13 | California |
| 722950 | 0.42 | Los Angeles Intl Arpt | 33.93 | –118.40 | California |
| 722956 | 0.38 | Jack Northrop Fld H | 33.92 | –118.33 | California |
| 722970 | 0.38 | Long Beach Daugherty Fld | 33.83 | –118.17 | California |
| 722976 | 0.34 | Fullerton Municipal | 33.87 | –117.98 | California |
| 722977 | 0.36 | Santa Ana John Wayne AP | 33.68 | –117.87 | California |
| 723805 | 0.51 | Needles Airport | 34.77 | –114.62 | California |
| 723810 | 0.59 | Edwards AFB | 34.90 | –117.87 | California |
| 723815 | 0.58 | Daggett Barstow–Daggett AP | 34.85 | –116.80 | California |
| 723816 | 0.62 | Lancaster Gen Wm Fox Field | 34.73 | –118.22 | California |
| 723820 | 0.57 | Palmdale Airport | 34.63 | –118.08 | California |
| 723830 | 0.68 | Sandberg | 34.75 | –118.72 | California |
| 723840 | 0.43 | Bakersfield Meadows Field | 35.43 | –119.05 | California |
| 723890 | 0.45 | Fresno Yosemite Intl AP | 36.78 | –119.72 | California |
| 723895 | 0.42 | Porterville (AWOS) | 36.03 | –119.07 | California |
| 723896 | 0.43 | Visalia Muni (AWOS) | 36.32 | –119.40 | California |
| 723910 | 0.45 | Point Mugu Nf | 34.12 | –119.12 | California |
| 723925 | 0.44 | Santa Barbara Municipal AP | 34.43 | –119.85 | California |
| 723926 | 0.43 | Camarillo (AWOS) | 34.22 | –119.08 | California |
| 723927 | 0.45 | Oxnard Airport | 34.20 | –119.20 | California |
| 723940 | 0.52 | Santa Maria Public Arpt | 34.92 | –120.47 | California |
continued
212 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
TABLE 160.2-A INFILTRATION EFFECTIVENESS WEATHER AND SHIELDING FACTORS [ASHRAE 62.2:Table B1] (continued)
| TMY3 | wsf | WEATHER STATION | LATITUDE | LONGITUDE | STATE |
|---|---|---|---|---|---|
| 723965 | 0.53 | Paso Robles Municipal Arpt | 35.67 | –120.63 | California |
| 724800 | 0.55 | Bishop Airport | 37.37 | –118.35 | California |
| 724815 | 0.46 | Merced/ |
37.28 | –120.52 | California |
| 724830 | 0.51 | Sacramento Executive Arpt | 38.50 | –121.50 | California |
| 724837 | 0.45 | Beale AFB | 39.13 | –121.43 | California |
| 724838 | 0.50 | Yuba Co | 39.10 | –121.57 | California |
| 724839 | 0.51 | Sacramento Metropolitan AP | 38.70 | –121.58 | California |
| 724915 | 0.49 | Monterey Naf | 36.60 | –121.87 | California |
| 724917 | 0.54 | Salinas Municipal AP | 36.67 | –121.60 | California |
| 724920 | 0.50 | Stockton Metropolitan Arpt | 37.90 | –121.23 | California |
| 724926 | 0.47 | Modesto City–County AP | 37.63 | –120.95 | California |
| 724927 | 0.53 | Livermore Municipal | 37.70 | –121.82 | California |
| 724930 | 0.54 | Oakland Metropolitan Arpt | 37.72 | –122.22 | California |
| 724935 | 0.47 | Hayward Air Term | 37.67 | –122.12 | California |
| 724936 | 0.53 | Concord–Buchanan Field | 38.00 | –122.05 | California |
| 724940 | 0.60 | San Francisco Intl AP | 37.62 | –122.40 | California |
| 724945 | 0.48 | San Jose Intl AP | 37.37 | –121.93 | California |
| 724955 | 0.55 | Napa Co. Airport | 38.22 | –122.28 | California |
| 724957 | 0.49 | Santa Rosa (AWOS) | 38.52 | –122.82 | California |
| 725845 | 0.44 | Blue Canyon AP | 39.30 | –120.72 | California |
| 725846 | 0.66 | Truckee–Tahoe | 39.32 | –120.13 | California |
| 725847 | 0.64 | South Lake Tahoe | 38.90 | –120.00 | California |
| 725905 | 0.47 | Ukiah Municipal AP | 39.13 | –123.20 | California |
| 725910 | 0.50 | Red Bluff Municipal Arpt | 40.15 | –122.25 | California |
| 725920 | 0.47 | Redding Municipal Arpt | 40.52 | –122.32 | California |
| 725945 | 0.56 | Arcata Airport | 40.98 | –124.10 | California |
| 725946 | 0.60 | Crescent City Faa Ai | 41.78 | –124.23 | California |
| 725955 | 0.55 | Montague Siskiyou County AP | 41.78 | –122.47 | California |
| 725958 | 0.59 | Alturas | 41.50 | –120.53 | California |
| 745090 | 0.45 | Mountain View Moffett Fld NAS | 37.40 | –122.05 | California |
| 745160 | 0.67 | Travis Field AFB | 38.27 | –121.93 | California |
| 746120 | 0.52 | China Lake Naf | 35.68 | –117.68 | California |
| 747020 | 0.50 | Lemoore Reeves NAS | 36.33 | –119.95 | California |
| 747185 | 0.46 | Imperial | 32.83 | –115.58 | California |
| 747187 | 0.46 | Palm Springs Thermal AP | 33.63 | –116.17 | California |
| 747188 | 0.48 | Blythe Riverside Co Arpt | 33.62 | –114.72 | California |
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
TABLE 160.2-B¶
MINIMUM VENTILATION RATES FOR MULTIFAMILY COMMON USE AREAS
| OCCUPANCY CATEGORY3 | AREA OUTDOOR AIR RATE1 R a cfm/ |
MIN AIR RATE FOR DC cfm/ |
AIR CLASS | NOTES |
|---|---|---|---|---|
| Daycare (through age 4) | 0.21 | 0.15 | 2 | — |
| Multiuse assembly | 0.50 | 0.15 | 1 | F |
| Dining rooms | 0.50 | 0.15 | 2 | — |
| Bars, cocktail lounges | 0.50 | 0.20 | 2 | — |
| Kitchen (cooking) | 0.15 | — | 2 | — |
| Break rooms | 0.50 | 0.15 | 1 | F |
| Coffee stations | 0.50 | 0.15 | 1 | F |
| Conference/ |
0.50 | 0.15 | 1 | F |
| Corridors | 0.15 | — | 1 | F |
| Occupiable storage rooms for liquids or gels | 0.15 | — | 2 | B |
| Laundry rooms, central | 0.15 | — | 2 | — |
| Lobbies/ |
0.50 | 0.15 | 1 | F |
| Breakrooms | 0.50 | 0.15 | — | — |
| Occupiable storage rooms for dry materials | 0.15 | — | — | — |
| Office space | 0.15 | — | 1 | — |
| Reception areas | 0.15 | — | 1 | F |
| Telephone/ |
0.15 | — | 1 | F |
| Computer (not printing) | 0.15 | — | — | — |
| Freezer and refrigerated spaces (<50°F) | — | — | 1 | F |
| Shipping/ |
0.15 | — | — | — |
| Gym, sports arena (play area) | 0.50 | 0.15 | 2 | E |
| Swimming (pool) | 0.15 | — | 2 | C |
| Swimming (deck) | 0.50 | 0.15 | 2 | C |
| Disco/ |
1.50 | 0.15 | 2 | F |
| Health club/ |
0.15 | — | 2 | — |
| Game arcades | 0.68 | 0.15 | 1 | — |
| All others | 0.15 | — | — | — |
A - RESERVED. B - Rate may not be sufficient where stored materials include those having potentially harmful emissions. C - Rate does not allow for humidity control. “Deck area” refers to the area surrounding the pool that is capable of being wetted during pool use or when the pool is occupied. Deck area that is not expected to be wetted shall be designated as an occupancy category. D - RESERVED. E - Where combustion equipment is intended to be used on the playing surface or in the space, additional dilution ventilation, source control or both shall be provided. F - Ventilation air for this occupancy category shall be permitted to be reduced to zero when the space is in occupied-standby mode.
Notes:
- Ra was determined as being the larger of the area method and the default per person method. The occupant density used in the per person method was assumed to be one-half of the maximum occupant load assumed for egress purposes in the CBC.
- If this column specifies a minimum cfm/ft 2 then it shall be used to comply with Section 160.2(c)5E.
- For spaces not included in this table, the spaces in Table 120.1-A shall apply.
214 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
TABLE 160.2-C¶
MINIMUM EXHAUST RATES
[ASHRAE 62.1: TABLE 6.5]
| OCCUPANCY CATEGORY1 | EXHAUST RATE, cfm/ |
EXHAUST RATE, cfm/ |
AIR CLASS | NOTES |
|---|---|---|---|---|
| Copy, printing rooms | — | 0.50 | 2 | — |
| Janitor closets, trash rooms, recycling | — | 1.00 | 3 | — |
| Kitchenettes | — | 0.30 | 2 | — |
| Kitchens – commercial | — | 0.70 | 2 | — |
| Locker rooms for athletic or industrial facilities | — | 0.50 | 2 | — |
| All other locker rooms | — | 0.25 | 2 | — |
| Shower rooms | 20/50 | — | 2 | G, H |
| Parking garages | — | 0.75 | 2 | C |
| Pet shops (animal areas) | — | 0.90 | 2 | — |
| Soiled laundry storage rooms | — | 1.00 | 3 | F |
| Storage rooms, chemical | — | 1.50 | 4 | F |
| Toilets – private | 25/50 | — | 2 | E |
| Toilets – public | 50/70 | — | 2 | D |
A - RESERVED. B - RESERVED. C - Exhaust shall not be required where two or more sides comprise walls that are at least 50 percent open to the outside. D - Rate is per water closet, urinal or both. Provide the higher rate where periods of heavy use are expected to occur. The lower rate shall be permitted to be used otherwise. E - Rate is for a toilet room intended to be occupied by one person at a time. For continuous systems operation during hours of use, the lower rate shall be permitted to be used. Otherwise the higher rate shall be used. F - See other applicable standards for exhaust rate. G - For continuous system operation, the lower rate shall be permitted to be used. Otherwise the higher rate shall be used. H - Rate is per showerhead.
Notes:
- For spaces not included in this table, the spaces in Table 120.1-B shall apply.
TABLE 160.2-D¶
AIRSTREAMS OR SOURCES
[ASHRAE 62.1: TABLE 5.16.1]
| DESCRIPTION | AIR CLASS |
|---|---|
| Commercial kitchen grease hoods | 4 |
| Commercial kitchen hoods other than grease | 3 |
| Hydraulic elevator machine room | 2 |
TABLE 160.2-E DEMAND-CONTROLLED LOCAL VENTILATION EXHAUST AIRFLOW RATES AND CAPTURE EFFICIENCY
| APPLICATION | COMPLIANCE CRITERIA |
|---|---|
| Enclosed kitchen or nonenclosed kitchen | Vented range hood, including appliance-range hood combinations, shall meet either the capture efficiency (CE) or the airflow rate specified in Table 160.2-G as applicable. |
| Enclosed kitchen | Other kitchen exhaust fans, including downdraft: 300 cfm (150 L/ |
| Nonenclosed kitchen | Other kitchen exhaust fans, including downdraft: 300 cfm (150 L/ |
| Bathroom | 50 cfm (25 L/ |
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
TABLE 160.2-F¶
CONTINUOUS LOCAL VENTILATION EXHAUST AIRFLOW RATES
| APPLICATION | AIRFLOW |
|---|---|
| Enclosed kitchen | 5 ach, based on kitchen volume |
| Bathroom | 20 cfm (10 L/ |
TABLE 160.2-G KITCHEN RANGE HOOD AIRFLOW RATES (cfm) AND ASTM E3087 CAPTURE EFFICIENCY (CE) RATINGS
According to Dwelling Unit Floor Area and Kitchen Range Fuel Type
| DWELLING UNIT FLOOR AREA (FT2) | HOOD OVER ELECTRIC RANGE | HOOD OVER NATURAL GAS RANGE |
|---|---|---|
| >1500 | 50% CE or 110 cfm | 70% CE or 180 cfm |
| >1000–1500 | 50% CE or 110 cfm | 80% CE or 250 cfm |
| 750–1000 | 55% CE or 130 cfm | 85% CE or 280 cfm |
| <750 | 65% CE or 160 cfm | 85% CE or 280 cfm |
TABLE 160.2-H¶
PRESCRIPTIVE VENTILATION SYSTEM DUCT SIZING [ASHRAE 62.2:TABLE 5-3]
| Fan airflow rating, cfm at minimum static pressuref 0.25 in. water (L/ |
≤50 (25) |
≤80 (40) |
≤100 (50) |
≤125 (60) |
≤150 (70) |
≤175 (85) |
≤200 (95) |
≤250 (120) |
≤350 (165) |
≤400 (190) |
≤450 (210) |
≤700 (330) |
≤800 (380) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Minimum duct diameter, in. (mm) a,b for rigid duct |
4 e (100) |
5 (125) |
5 (125) |
6 (150) |
6 (150) |
7 (180) |
7 (180) |
8 (205) |
9 (230) |
10 (255) |
10 (255) |
12 (305) |
12d (305) |
| Minimum duct diameter, in. (mm) a,b for flex ductc |
4 (100) |
5 (125) |
6 (150) |
6 (150) |
7 (150) |
7 (180) |
8 (205) |
8 (205) |
9 (230) |
10 (255) |
NP | NP | NP |
a. For noncircular ducts, calculate the diameter as four times the cross-sectional area divided by the perimeter. b. NP = application of the prescriptive table is not permitted for this scenario. c. Use of this table for verification of flex duct systems requires flex duct to be fully extended and any flex duct elbows to have a minimum bend radius to duct
diameter ratio of 1.0. d. For this scenario, use of elbows is not permitted. e. For this scenario, 4 in. (100 mm) oval duct shall be permitted, provided the minor axis of the oval is greater than or equal to 3 in. (75 mm). f. When a vented range hood utilizes a capture efficiency rating to demonstrate compliance with Section 160.2(b)2Avic2, a static pressure greater than or equal
to 0.25 in. of water at the rating point shall not be required, and the airflow listed in the approved directory corresponding to the compliant capture efficiency rating point shall be applied to Table 160.2-H for determining compliance.
NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8 and 25943, Public Resources Code .
216 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
D. Shut-off and reset controls for space-condition-
ing systems. Each space-conditioning system shall be installed with controls that comply with the following:
i. The control shall be capable of automatically
shutting off the system during periods of nonuse and shall have:
a. An automatic time switch control device com plying with Section 110.9, with an accessible manual override that allows operation of the system for up to 4 hours; or
b. An occupancy sensor; or
c. A 4-hour timer that can be manually operated.
ii. The control shall automatically restart and tempo rarily operate the system as required to maintain:
a. A setback heating thermostat setpoint if the
system provides mechanical heating; and
Exception to Section 160.3(a)2Diia: Thermostat setback controls are not required in multifamily buildings in areas where the Winter Median of Extremes outdoor air temperature determined in accordance with Section 170.2(c)1C is greater than 32°F.
b. A setup cooling thermostat setpoint if the sys tem provides mechanical cooling.
Exception to Section 160.3(a)2Diib: Thermostat setup controls are not required in multifamily buildings in areas where the summer design dry-bulb 0.5-percent temperature determined in accordance with Section 170.2(c)1C is less than 100°F.
iii. Occupant sensing zone controls . Where the sys tem providing space conditioning also provides the ventilation required by Section 160.2(c)3 and includes occupant sensor ventilation control as specified in Section 160.2(c)5E, the occupant sensing zone controls shall additionally comply with the following:
a. Occupant sensing zone controls shall comply
with the occupant sensor ventilation control device requirements of Section 160.3(c)5E and allow preoccupancy ventilation requirements of Section 160.3(c)5B; and
b. In 5 minutes or less after entering occupied standby mode as described in Section 160.2(c)5:
I. Automatically set up the operating cooling
temperature setpoint by 2°F or more and set back the operating heating temperature setpoint by 2°F or more; or
II. For multiple zone systems with direct digi tal controls (DDC) to the zone level, set up the operating cooling temperature setpoint by 0.5°F or more and set back the operating heating temperature setpoint by 0.5°F or more.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
c. In 5 minutes or less after entering occupied standby mode, mechanical ventilation to the zone shall remain off whenever the space temperature is between the active heating and cooling setpoints.
Exception to Section 160.3(a)2Diii : Zones that are only ventilated by a natural ventilation system in accordance with Section 120.1(c)2.
Exception 1 to Sections 160.3(a)2Di, ii and iii: Where it can be demonstrated to the satisfaction of the enforcing agency that the system serves an area that must operate continuously.
Exception 2 to Sections 160.3(a)2Di, ii and iii: Systems with full load demands of 2 kW or less, if they have a readily accessible manual shut-off switch.
E. Dampers for air supply and exhaust equipment.
Outdoor air supply and exhaust equipment shall be installed with dampers that automatically close upon fan shutdown.
Exception 1 to Section 160.3(a)2E: Equipment that serves an area that must operate continuously.
Exception 2 to Section 160.3(a)2E: Gravity and other nonelectrical equipment that has readily accessible manual damper controls.
Exception 3 to Section 160.3(a)2E: At combustion air intakes and shaft vents.
Exception 4 to Section 160.3(a)2E: Where prohibited by other provisions of law.
F. Isolation area devices . Each space-conditioning
system serving multiple zones with a combined conditioned floor area of more than 25,000 square feet shall be designed, installed and controlled to serve isolation areas.
i. Each zone, or any combination of zones not
exceeding 25,000 square feet, shall be a separate isolation area.
ii. Each isolation area shall be provided with isola tion devices, such as valves or dampers that allow the supply of heating or cooling to be reduced or shut off independently of other isolation areas.
iii.Each isolation area shall be controlled by a
device meeting the requirements of Section 160.3(a)2Di.
Exception to Section 160.3(a)2F: Zones designed to be conditioned continuously.
G. Automatic demand shed controls. See Section
110.12 for requirements for automatic demand shed controls.
H. Economizer fault detection and diagnostics
(FDD). All newly installed air handlers with a mechanical cooling capacity over 33,000 Btu/hr and an installed air economizer shall include a standalone or integrated fault detection and diagnostics
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
(FDD) system in accordance with Subsections 160.3(a)2Hi through 160.3(a)2Hviii.
i. The following temperature sensors shall be per manently installed to monitor system operation: outside air, supply air and, when required for differential economizer operation, a return air sensor; and
ii. Temperature sensors shall have an accuracy of
±2°F over the range of 40°F to 80°F; and
iii.The controller shall have the capability of dis playing the value of each sensor; and
iv. The controller shall provide system status by
indicating the following conditions:
a. Free cooling available;
b. Economizer enabled;
c. Compressor enabled;
d. Heating enabled, if the system is capable of
heating; and
e. Mixed air low limit cycle active.
v. The unit controller shall allow manual initiation
of each operating mode so that the operation of cooling systems, economizers, fans and heating systems can be independently tested and verified; and
vi. Faults shall be reported in one of the following
ways:
a. Reported to an energy management control
system regularly monitored by facility personnel.
b. Annunciated locally on one or more zone ther mostats, or a device within 5 feet of zone thermostat(s), clearly visible, at eye level and meeting the following requirements:
I. On the thermostat, the device or an adja cent written sign, display instructions to contact appropriate building personnel or an HVAC technician; and
II. In buildings with multiple tenants, the
annunciation shall either be within property management offices or in a common space accessible by the property or building manager.
c. Reported to a fault management application
that automatically provides notification of the fault to remote HVAC service provider.
vii. The FDD system shall detect the following faults:
a. Air temperature sensor failure/fault;
b. Not economizing when it should;
c. Economizing when it should not;
d. Damper not modulating; and
e. Excess outdoor air.
Exception to Section 160.3(a)2J: Systems that must operate continuously. (b) Dwelling unit space-conditioning and air distribu- tion systems.
- Building cooling and heating loads. Building heating and cooling loads shall be determined using a method based on any one of the following, using cooling and heating loads as two of the criteria for equipment sizing and selection: A. The ASHRAE Handbook, Equipment Volume,
Applications Volume and Fundamentals Volume; or
B. The SMACNA Residential Comfort System Instal lation Standards Manual; or
viii. The FDD system shall be certified by the Energy
Commission as meeting the requirements of Sections 160.3(a)2Hi through 160.3(a)2Hvii in accordance with Section 110.0 and JA6.3.
Exception to Section 160.3(a)2Hviii: FDD algorithms based in direct digital control systems are not required to be certified to the Energy Commission. I. Direct digital controls (DDC). Direct digital con trols to the zone shall be provided as specified by Table 160.3-C.
i. The provided DDC system shall meet the control
logic requirements of Sections 160.3(a)2E and 160.3(a)2G, and be capable of the following:
ii. Monitoring zone and system demand for fan
pressure, pump pressure, heating and cooling;
iii.Transferring zone and system demand informa tion from zones to air distribution system controllers and from air distribution systems to heating and cooling plant controllers;
iv. Automatically detecting the zones and systems
that may be excessively driving the reset logic and generate an alarm or other indication to the system operator;
v. Readily allow operator removal of zone(s) from
the reset algorithm;
vi. For new buildings, trending and graphically dis playing input and output points; and
vii. Resetting heating and cooling setpoints in all
noncritical zones upon receipt of a signal from a centralized contact or software point as described in Section 160.3(a)2G. J. Optimum start/stop controls. Space-conditioning
systems with DDC to the zone level shall have optimum start/stop controls. The control algorithm shall, as a minimum, be a function of the difference between space temperature and occupied setpoint, the outdoor air temperature, and the amount of time prior to scheduled occupancy. Mass radiant floor slab systems shall incorporate floor temperature onto the optimum start algorithm.
218 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
C. The ACCA Manual J.
NOTE: Heating systems are required to have a minimum heating capacity adequate to meet the minimum requirements of the CBC.
- Design conditions . Design conditions shall be determined in accordance with the following: A. For the purpose of sizing the space-conditioning
(HVAC) system, the indoor design temperatures shall be 68°F for heating and 75°F for cooling.
B. Outdoor design conditions shall be selected from
Reference Joint Appendix JA2, which is based on data from the ASHRAE Climatic Data for Region X.
C. The outdoor design temperatures for heating shall be
no lower than the Heating Winter Median of Extremes values.
D. The outdoor design temperatures for cooling shall
be no greater than the 1.0 percent Cooling Dry Bulb and Mean Coincident Wet Bulb values.
- Outdoor condensing units . A. Clearances. Installed air conditioner and heat pump
outdoor condensing units shall have a clearance of at least 5 feet (1.5 meters) from the outlet of any dryer vent.
B. Liquid line drier. Installed air conditioner and heat
pump systems shall be equipped with liquid line filter driers if required, as specified by manufacturer’s instructions.
Central forced-air heating furnaces . A. Temperature rise . Central forced-air heating fur nace installations shall be configured to operate in conformance with the furnace manufacturer's maximum inlet-to-outlet temperature rise specifications.
Air-distribution and ventilation system ducts, ple- nums and fans. A. CMC compliance.
i. All air-distribution system ducts and plenums,
including, but not limited to, mechanical closets and air-handler boxes, shall meet the requirements of the CMC Sections 601.0, 602.0, 603.0, 604.0 and 605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition, incorporated herein by reference.
ii. Portions of supply-air and return-air ducts and
plenums of a space heating or cooling system shall be insulated in accordance with either Subsection a or b below:
a. Ducts shall have a minimum installed level of
R-6.0, or
Exception to Section 160.3(b)5Aiia : Portions of the duct system located in conditioned space below the ceiling separating the occupiable space from the attic are not required to be insulated if all of the following conditions are met:
i. The noninsulated portion of the duct sys tem is located entirely inside the building’s thermal envelope as confirmed by visual inspection.
ii. At all locations where noninsulated por tions of the duct system penetrate into unconditioned space, the penetration shall be draft stopped compliant with CFC Sections 703.1 and 704.1 and air-sealed to the construction materials that are penetrated, using materials compliant with CMC Section E502.4.2 to prevent air infiltration into the cavity. All connections in unconditioned space are insulated to a minimum of R-6.0 as confirmed by visual inspection.
b. Ducts do not require insulation when the duct
system is located entirely in conditioned space. For buildings with three or fewer habitable stories, duct systems located entirely in conditioned space shall be confirmed through field verification and diagnostic testing in accordance with the requirements of Reference Residential Appendix RA3.1.4.3.8.
iii.Connections of metal ducts and the inner core of
flexible ducts shall be mechanically fastened.
iv. Openings shall be sealed with mastic, tape or
other duct-closure system that meets the applicable requirements of UL 181, UL 181A or UL 181B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than 1 /4 inch, the combination of mastic and either mesh or tape shall be used.
v. Building cavities, support platforms for air han dlers, and plenums designed or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts.
Exception to Section 160.3(b)5A: Ducts and fans integral to a wood heater or fireplace.
B. Factory-fabricated duct systems .
i. All factory-fabricated duct systems shall comply
with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director.
ii. All pressure-sensitive tapes, heat-activated tapes
and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
iii. All pressure-sensitive tapes and mastics used
with flexible ducts shall comply with UL 181 and UL 181B.
iv. Joints and seams of duct systems and their com ponents shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands. C. Field-fabricated duct systems.
i. Factory-made rigid fiberglass and flexible ducts
for field-fabricated duct systems shall comply with UL 181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.
ii. Mastic sealants and mesh.
a. Sealants shall comply with the applicable
requirements of UL 181, UL 181A and UL 181B, and be nontoxic and water resistant.
b. Sealants for interior applications shall be
tested in accordance with ASTM C731 and D2202, incorporated herein by reference.
c. Sealants for exterior applications shall be
tested in accordance with ASTM C731, C732 and D2202, incorporated herein by reference.
d. Sealants and meshes shall be rated for exterior
use.
iii.Pressure-sensitive tape. Pressure-sensitive tapes
shall comply with the applicable requirements of UL 181, UL 181A and UL 181B.
iv. Joints and seams of duct systems and their com ponents shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
v. Drawbands used with flexible duct.
a. Drawbands shall be either stainless-steel
worm-drive hose clamps or UV-resistant nylon duct ties.
b. Drawbands shall have a minimum tensile
strength rating of 150 pounds.
c. Drawbands shall be tightened as recom mended by the manufacturer with an adjustable tensioning tool.
vi. Aerosol-sealant closures.
temperature at the installed thickness, in accordance with ASTM C518 or ASTM C177, incorporated herein by reference, and certified pursuant to Section 110.8.
E. Duct insulation thickness. The installed thickness
of duct insulation used to determine its R- value shall be determined as follows:
i. For duct board, duct liner and factory-made rigid
ducts not normally subjected to compression, the nominal insulation thickness shall be used .
ii. For duct wrap, installed thickness shall be
assumed to be 75 percent (25 percent compression) of nominal thickness.
iii.For factory-made flexible air ducts, the installed
thickness shall be determined by dividing the difference between the actual outside diameter and nominal inside diameter by two. F. Duct labeling. Insulated flexible duct products
installed to meet this requirement shall include labels, in maximum intervals of 3 feet, showing the thermal performance R- value for the duct insulation itself (excluding air films, vapor retarder or other duct components), based on the tests in Section 160.3(b)5D and the installed thickness determined by Section 160.3(b)5Eiii.
G. Backdraft dampers. All fan systems, regardless of
volumetric capacity, that exchange air between the building conditioned space and the outside of the building shall be provided with backdraft or automatic dampers to prevent unintended air leakage through the fan system when the fan system is not operating.
H. Gravity ventilation dampers. All gravity ventilat ing systems that serve conditioned space shall be provided with either automatic or readily accessible, manually operated dampers in all openings to the outside except combustion inlet and outlet air openings and elevator shaft vents.
a. Aerosol sealants shall meet the requirements
of UL 723 and be applied according to manufacturer specifications.
b. Tapes or mastics used in combination with
I. Protection of insulation. Insulation shall be pro tected from damage, including that due to sunlight, moisture, equipment maintenance and wind but not limited to the following: Insulation exposed to weather shall be suitable for outdoor service (e.g., protected by aluminum, sheet metal, painted canvas or plastic cover).
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material.
J. Porous inner core flex duct. Flexible ducts having
porous inner cores shall have a nonporous layer or air barrier between the inner core and the outer vapor barrier.
K. Duct system sealing and leakage testing. When
space-conditioning systems utilize forced air duct systems to supply conditioned air to an individual
aerosol sealing shall meet the requirements of this section. D. Duct insulation R- value ratings. All duct insula
tion product R- values shall be based on insulation only (excluding air films, vapor retarder or other duct components) and tested C-values at 75°F mean
220 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
dwelling unit, the ducts shall be sealed, as confirmed through field verification and diagnostic testing, in accordance with all applicable procedures specified in Reference Residential Appendix RA3.1. Air handler airflow for calculation of duct leakage rate compliance targets shall be determined according to methods specified in Reference Residential Appendix RA3.1.4.2.
For multifamily dwellings with the air-handling unit installed and the ducts connected directly to the air handler, regardless of duct system location:
i. The total leakage of the duct system shall not
exceed 12 percent of the air handler airflow as determined utilizing the procedures in Reference Residential Appendix Section RA3.1.4.3.1; or
ii. The duct system leakage to outside shall not
exceed 6 percent of the air handler airflow as determined utilizing the procedures in Reference Residential Appendix Section RA3.1.4.3.4.
Exception 1 to Section 160.3(b)5K: The HERS Rater field verification and HERS Provider data registry requirements of Reference Residential Appendix RA2 and RA3 are not required for multifamily dwelling units in buildings four habitable stories and greater. The installer shall certify that diagnostic testing was performed in accordance with the applicable procedures.
Exception 2 to Section 160.3(b)5K: Multifamily dwelling units in buildings four habitable stories and greater in Climate Zones 1, 3, 5 and 7.
L. System airflow rate and fan efficacy. Space-condi tioning systems that utilize forced air ducts to supply cooling to an individual dwelling unit shall:
i. Static pressure probe. Have a hole for the place ment of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum downstream of the air conditioning evaporator coil. The size, location and labeling of the HSPP or PSPP shall conform to the requirements specified in Reference Residential Appendix RA3.3.1.1 as confirmed by field verification and diagnostic testing; and
Exception to Section 160.3(b)5Li: Systems that cannot conform to the specifications for hole location in Reference Residential Appendix Figure RA3.3-1 shall not be required to provide holes as described in Figure RA3.3-1.
ii. Single zone central forced air systems. Demon strate, in every control mode, airflow greater than or equal to 350 cfm per ton of nominal cooling capacity through the return grilles, and an airhandling unit fan efficacy less than or equal to the maximum W/cfm specified in Subsection a or b below. The airflow rate and fan efficacy requirements in this section shall be confirmed by field verification and diagnostic testing in accordance with the procedures given in Reference Residential Appendix RA3.3.
a. 0.45 W/cfm for gas furnace air-handling units.
b. 0.58 W/cfm for air-handling units that are not
gas furnaces.
Exception 1 to Section 160.3(b)5Lii: Standard ducted systems without zoning dampers may comply by meeting the applicable requirements in Table 160.3-A or 160.3-B as confirmed by field verification and diagnostic testing in accordance with the procedures in Reference Residential Appendix Sections RA3.1.4.4 and RA3.1.4.5. The design cleanfilter pressure drop requirements specified by Section 160.2(b)1Div for the system air filter(s) shall conform to the requirements given in Table 160.3-A or 160.3-B.
Exception 2 to Section 160.3(b)5Lii: Multispeed compressor systems or variable speed compressor systems shall verify airflow (cfm/ ton) and fan efficacy (watt/cfm) for system operation at the maximum compressor speed and the maximum air handler fan speed.
Exception 3 to Section 160.3(b)5Lii: Gas furnace air-handling units manufactured prior to July 3, 2019 shall comply with a fan efficacy value less than or equal to 0.58 w/cfm as confirmed by field verification and diagnostic testing in accordance with the procedures given in Reference Residential Appendix RA3.3.
iii. Zonally controlled central forced air systems.
Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode, an airflow from the dwelling, through the air handler fan and delivered to the dwelling, of greater than or equal to 350 cfm per ton of nominal cooling capacity, and operating at an air-handling unit fan efficacy of less than or equal to the maximum W/cfm specified in Subsection a or b below. The airflow rate and fan efficacy requirements in this section shall be confirmed by field verification and diagnostic testing in accordance with the applicable procedures specified in Reference Residential Appendix RA3.3.
a. 0.45 W/cfm for gas furnace air-handling units.
b. 0.58 W/cfm for air-handling units that are not
gas furnaces.
Exception 1 to Section 160.3(b)5Liii: Multispeed or variable speed compressor systems, or single speed compressor systems that utilize the performance compliance approach, shall demonstrate compliance with the airflow (cfm/ton) and fan efficacy (watt/cfm) requirements of Section 160.3(b)5Liii by operating the system at maximum compressor capacity
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
and system fan speed with all zones calling for conditioning, rather than in every zonal control mode.
Exception 2 to Section 160.3(b)5Liii: Gas furnace air-handling units manufactured prior to July 3, 2019 shall comply with a fan efficacy value less than or equal to 0.58 w/cfm as confirmed by field verification and diagnostic testing in accordance with the procedures given in Reference Residential Appendix RA3.3.
iv. Small duct high velocity forced air systems.
Demonstrate, in every control mode, airflow greater than or equal to 250 cfm per ton of nominal cooling capacity through the return grilles, and an air-handling unit fan efficacy less than or equal to 0.62 W/cfm as confirmed by field verification and diagnostic testing in accordance with the procedures given in Reference Residential Appendix RA3.3.
Exception 1 to Section 160.3(b)5Liv: Standard ducted systems without zoning dampers may comply by meeting the applicable requirements in Table 160.3-A or 160.3-B as confirmed by field verification and diagnostic testing in accordance with the procedures in Reference Residential Appendix Sections RA3.1.4.4 and RA3.1.4.5. The design cleanfilter pressure drop requirements specified by Section 160.2(b)1Div for the system air filter(s) shall conform to the requirements given in Table 160.3-A or 160.3-B.
Exception 2 to Section 160.3(b)5Liv: Multispeed compressor systems or variable speed compressor systems shall verify airflow (cfm/ ton) and fan efficacy (watt/cfm) for system operation at the maximum compressor speed and the maximum air handler fan speed.
Exception 1 to Section 160.3(b)5L: The HERS Rater field verification and HERS Provider data registry requirements of Reference Residential Appendix RA2 and RA3 are not required for multifamily dwelling units in buildings four habitable stories and greater. The installer shall certify that diagnostic testing was performed in accordance with the applicable procedures.
Exception 2 to Section 160.3(b)5L: Multifamily dwelling units in buildings four habitable stories and greater in Climate Zone 1.
- Piping for space-conditioning systems, solar waterheating system collector loop, and distribution piping for steam and hydronic heating system shall meet the requirements of Section 160.3(c)1. (c) Fluid distribution systems; common area space- conditioning systems. Multifamily buildings shall comply
with the applicable requirements of Section 160.3(a)1. Multifamily common areas shall comply with the applicable requirements of Sections 160.3(a)2A through 160.3(a)2J.
- Pipe insulation . Multifamily buildings shall comply with the applicable requirements of Sections 160.3(c)1A through 160.3(c)1D. A. General requirements. The piping conditions listed
below for space-conditioning systems with fluid normal operating temperatures listed in Table 160.3D shall have at least the amount of insulation specified in Section 160.3(c)1C:
i. Space cooling systems. All refrigerant suction,
chilled water and brine fluid distribution systems.
ii. Space heating systems. All refrigerant, steam,
steam condensate and hot water fluid distribution systems. B. Insulation conductivity shall be determined in accor
dance with ASTM C335 at the mean temperature listed in Table 160.3-D, and shall be rounded to the nearest 1 /100 Btu-inch per hour per square foot per °F. Fluid distribution systems include all elements that are in series with the fluid flow, such as pipes, pumps, valves, strainers, coil u-bends and air separators, but not including elements that are not in series with the fluid flow, such as expansion tanks, fill lines, chemical feeders and drains.
C. Insulation protection. Pipe insulation shall be pro tected from damage due to sunlight, moisture, equipment maintenance and wind. Protection shall, at minimum, include the following:
i. Pipe insulation exposed to weather shall be pro tected by a cover suitable for outdoor service. The cover shall be water retardant and provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be used to provide this protection.
ii. Pipe insulation covering chilled water piping and
refrigerant suction piping located outside the conditioned space shall include, or be protected by, a Class I or Class II vapor retarder. All penetrations and joints shall be sealed. iii.Pipe insulation buried below grade must be
installed in a waterproof and noncrushable casing or sleeve. D. Insulation thickness.
i. For insulation with a conductivity in the range
shown in Table 160.3-D for the applicable fluid temperature range, the insulation shall have the applicable minimum thickness or R- value shown in Table 160.3-D.
ii. For insulation with a conductivity outside the
range shown in Table 160.3-D for the applicable fluid temperature range, the insulation shall have
222 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
a minimum R- value shown in Table 160.3-D or thickness as calculated with Equation 160.3-A:
T = PR 1 + ------- t PR
K
-- k -
= PR 1 + ------- - 1
(Equation 160.3-A)
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
is used to seal openings greater than 1 /4 inch, the combination of mastic and either mesh or tape shall be used.
B. Portions of supply-air and return-air ducts convey ing heated or cooled air located in one or more of the following spaces shall be insulated to a minimum installed level of R-8:
i. Outdoors; or
ii. In a space between the roof and an insulated ceil ing; or
iii.In a space directly under a roof with fixed vents
or openings to the outside or unconditioned spaces; or
iv. In an unconditioned crawl space; or
v. In other unconditioned spaces.
Portions of supply-air ducts that are not in one of these spaces, including ducts buried in concrete slab, shall be insulated to a minimum installed level of R4.2 or be enclosed in directly conditioned space. C. Duct and plenum materials.
i. Factory-fabricated duct systems.
a. All factory-fabricated duct systems shall com ply with UL 181 for ducts and closure systems, including collars, connections and splices, and be labeled as complying with UL 181. UL 181 testing may be performed by UL laboratories or a laboratory approved by the Executive Director.
b. All pressure-sensitive tapes, heat-activated
tapes and mastics used in the manufacture of rigid fiberglass ducts shall comply with UL 181 and UL 181A.
c. All pressure-sensitive tapes and mastics used
with flexible ducts shall comply with UL 181 and UL 181B.
d. Ductwork and plenums with pressure class
ratings shall be constructed to Seal Class A. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
Exception to Section 160.3(c)2Cid: Ductwork located in occupied space and exposed to view.
ii. Field-fabricated duct systems.
a. Factory-made rigid fiberglass and flexible
ducts for field-fabricated duct systems shall comply with UL 181. All pressure-sensitive tapes, mastics, aerosol sealants or other closure systems used for installing field-fabricated duct systems shall meet the applicable requirements of UL 181, UL 181A and UL 181B.
where: T = Minimum insulation thickness for material with conductivity K, inches. PR = Pipe actual outside radius, inches. t = Insulation thickness from 160.3-D, inches. K = Conductivity of alternate material at the
mean rating temperature indicated in Table 160.3-D for the applicable fluid temperature range, in Btu-inch per hour per square foot per °F. k = The lower value of the conductivity range
listed in Table 160.3-D for the applicable fluid temperature range, Btu-inch per hour per square foot per °F.
Exception 1 to Section 160.3(c)1: Factoryinstalled piping within space-conditioning equipment certified under Section 110.1 or 110.2.
Exception 2 to Section 160.3(c)1: Piping that conveys fluids with a design operating temperature range between 60°F and 105°F.
Exception 3 to Section 160.3(c)1: Where the heat gain or heat loss to or from piping without insulation will not increase building source energy use.
Exception 4 to Section 160.3(c)1: Piping that penetrates framing members shall not be required to have pipe insulation for the distance of the framing penetration. Metal piping that penetrates metal framing shall use grommets, plugs, wrapping or other insulating material to ensure that no contact is made with the metal framing.
- Requirements for air distribution system, ducts and plenum. Multifamily common areas shall comply with the applicable requirements of Sections 160.3(c)2A through 160.3(c)2F. A. CMC compliance. All air distribution system
ducts and plenums, including, but not limited to, building cavities, mechanical closets, air-handler boxes and support platforms used as ducts or plenums shall meet the requirements of CMC Sections 601.0, 602.0, 603.0, 604.0 and 605.0, and ANSI/ SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition, incorporated herein by reference. Connections of metal ducts and the inner core of flexible ducts shall be mechanically fastened. Openings shall be sealed with mastic, tape, aerosol sealant or other duct-closure system that meets the applicable requirements of UL 181, UL 181A or UL 181B. If mastic or tape
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
b. Mastic sealants and mesh.
I. Sealants shall comply with the applicable
requirements of UL 181, UL 181A and UL 181B, and be nontoxic and water resistant.
II. Sealants for interior applications shall pass
ASTM C731 (extrudability after aging) and D2202 (slump test on vertical surfaces), incorporated herein by reference.
III. Sealants for exterior applications shall pass
ASTM C731, C732 (artificial weathering test) and D2202, incorporated herein by reference.
IV.Sealants and meshes shall be rated for exte rior use.
c. Pressure-sensitive tape. Pressure-sensitive tapes shall comply with the applicable requirements of UL 181, UL 181A and UL 181B.
d. Ductwork and plenums with pressure class
ratings shall be constructed to Seal Class A. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands.
e. Drawbands used with flexible duct.
I. Drawbands shall be either stainless-steel
worm-drive hose clamps or UV-resistant nylon duct ties.
II. Drawbands shall have a minimum tensile
strength rating of 150 pounds.
III. Drawbands shall be tightened as recom mended by the manufacturer with an adjustable tensioning tool.
f. Aerosol-sealant closures.
I. Aerosol sealants shall meet the require ments of UL 723 and be applied according to manufacturer specifications.
II. Tapes or mastics used in combination with
aerosol sealing shall meet the requirements of this section.
D. All duct insulation product R- values shall be based
on insulation only (excluding air films, vapor retarders or other duct components) and tested C-values at 75°F mean temperature at the installed thickness, in accordance with ASTM C518 or ASTM C177, incorporated herein by reference, and certified pursuant to Section 110.8.
E. The installed thickness of duct insulation used to
determine its R- value shall be determined as follows:
i. For duct board, duct liner and factory-made rigid
ducts not normally subjected to compression, the nominal insulation thickness shall be used.
ii. For duct wrap, installed thickness shall be
assumed to be 75 percent (25 percent compression) of nominal thickness.
iii.For factory-made flexible air ducts, the installed
thickness shall be determined by dividing the difference between the actual outside diameter and nominal inside diameter by two. F. Insulated flexible duct products installed to meet
this requirement must include labels, in maximum intervals of 3 feet, showing the thermal performance R- value for the duct insulation itself (excluding air films, vapor retarder or other duct components), based on the tests in Section 160.3(c)2D and the installed thickness determined by Section 160.3(c)2Eiii.
G. Insulation shall be protected from damage, including
that due to sunlight, moisture, equipment maintenance and wind but not limited to the following: Insulation exposed to weather shall be suitable for outdoor service; e.g., protected by aluminum, sheet metal, painted canvas or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material.
H. Duct systems shall be tested in accordance with i or
ii below:
i. New duct systems that meet the criteria in Sub sections a, b and c below or ductwork that is part of a system that meets the criteria of Section 180.2(b)2B shall be sealed to a leakage rate not to exceed 6 percent of the nominal air handler airflow rate as confirmed through field verification and diagnostic testing, in accordance with the applicable procedures in Reference Nonresidential Appendices NA1 and NA2.
a. The duct system provides conditioned air to an
occupiable space for a constant volume, single zone, space-conditioning system; and
b. The space-conditioning system serves less
than 5,000 square feet of conditioned floor area; and
c. The combined surface area of the ducts
located in the following spaces is more than 25 percent of the total surface area of the entire duct system:
I. Outdoors; or
II. In a space directly under a roof that has a
U- factor greater than the U- factor of the ceiling, or if the roof does not meet the requirements of Section 170.2(a)1; or
III.In a space directly under a roof that has
fixed vents or openings to the outside or unconditioned spaces; or
IV.In an unconditioned crawl space; or
V. In other unconditioned spaces.
224 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ii. All duct systems that do not meet the criteria in
Section 160.3(c)2H shall meet the duct leakage testing requirements of CMC Section 603.9.2. (d) Mechanical acceptance testing.
- Common areas. Before an occupancy permit is granted, the following systems and equipment serving multifamily common areas shall be certified as meeting the Acceptance Requirements for Code Compliance, as specified by Reference Nonresidential Appendix NA7. These systems and equipment shall also comply with the applicable requirements of Section 160.3(d)3. A Certificate of Acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements: A. Outdoor air ventilation systems shall be tested in
accordance with NA7.5.1.
B. Constant volume, single zone air conditioning and
heat pump unit controls shall be tested in accordance with NA7.5.2.
C. Duct systems shall be tested in accordance with
NA7.5.3 where either:
a. They are new duct systems; or
b. They are part of an altered system. D. Air economizers shall be tested in accordance with
NA7.5.4.
Exception to Section 160.3(d)1D: Air economizers installed by the HVAC system manufacturer and certified to the Commission as being factory calibrated and tested are exempt from the Functional Testing section of the Air Economizer Controls acceptance test as described in NA7.5.4.2. E. Demand control ventilation systems required by
Section 160.2(c)3 shall be tested in accordance with NA7.5.5.
F. Supply fan variable flow controls shall be tested in
accordance with NA7.5.6.
G. Hydronic system variable flow controls shall be
tested in accordance with NA7.5.7 and NA7.5.9.
H. Boilers or chillers that require isolation controls as
specified by Section 170.2(c)4Iii or 170.2(c)4Iiii shall be tested in accordance with NA7.5.7.
I. Hydronic systems with supply water temperature
reset controls shall be tested in accordance with NA7.5.8.
J. Automatic demand shed controls shall be tested in
accordance with NA7.5.10.
K. Fault detection and diagnostics (FDD) for packaged
direct expansion units shall be tested in accordance with NA7.5.11.
L. Automatic fault detection and diagnostics (FDD) for
air handling units and zone terminal units shall be tested in accordance with NA7.5.12.
M.Distributed energy storage DX AC systems shall be
tested in accordance with NA7.5.13.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
N. Thermal energy storage (TES) systems shall be
tested in accordance with NA7.5.14.
O. Supply air temperature reset controls shall be tested
in accordance with NA7.5.15.
P. Water-cooled chillers served by cooling towers with
condenser water reset controls shall be tested in accordance with NA7.5.16.
Q. When an energy management control system is
installed, it shall functionally meet all of the applicable requirements of Part 6.
R. Occupant sensing zone controls shall be tested in
accordance with NA7.5.17.
- Multifamily dwelling units. Before an occupancy permit is granted, the following systems and equipment serving multifamily dwelling units shall be certified as meeting the acceptance requirements for code compliance, as specified by the Reference Nonresidential Appendix NA7. These systems and equipment shall also comply with the applicable requirements of Section 160.3(d)3. A Certificate of Acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements:
A. In multifamily buildings with four or more habitable
stories, dwelling unit ventilation systems shall be tested in accordance with NA7.18.1.
B. In multifamily buildings with four or more habitable
stories, dwelling unit enclosure leakage shall be tested in accordance with NA7.18.2 when exhaust or supply ventilation systems are used for compliance with whole-dwelling unit ventilation requirements as specified in Section 160.2(b)2Aivb2.
C. Multifamily building central ventilation ducts in
multifamily buildings with four or more habitable stories shall be leak tested in accordance with NA7.18.3.
D. Multifamily building central ventilation system heat
recovery or energy recovery systems in multifamily buildings with four or more habitable stories shall be tested in accordance with NA7.18.4.
- When certification is required by Title 24, Part 1, Section 10-103.2, the acceptance testing specified by Section 160.3(d)1 and 2 shall be performed by a Certified Mechanical Acceptance Test Technician (CMATT). If the CMATT is operating as an employee, the CMATT shall be employed by a Certified Mechanical Acceptance Test Employer. The CMATT shall disclose on the Certificate of Acceptance a valid CMATT certification identification number issued by an approved Acceptance Test Technician Certification Provider. The CMATT shall complete all Certificate of Acceptance documentation in accordance with the applicable requirements in Section 10-103(a)4.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
TABLE 160.3-A¶
RETURN DUCT SIZING FOR SINGLE RETURN DUCT SYSTEMS
| SYSTEM NOMINAL COOLING CAPACITY (TON)* |
RETURN DUCT MINIMUM NOMINAL DIAMETER (INCH) |
MINIMUM TOTAL RETURN FILTER GRILLE NOMINAL AREA (INCH2) |
|---|---|---|
| 1.5 | 16 | 500 |
| 2.0 | 18 | 600 |
| 2.5 | 20 | 800 |
***** Not applicable to systems with nominal cooling capacity greater than 2.5 tons or less than 1.5 ton.
| TABLE 160.3-B RETURN DUCT SIZING FOR MULTIPLE RETURN DUCT SYSTEMS | |||
|---|---|---|---|
| Each return duct length shall not exceed 30 feet and shall contain no more than 180 degrees of bend. If the total bending exceeds 90 degrees, one bend shall be a metal elbow. Return grille devices shall be labeled in accordance with the requirements in Section 160.2(b)1Biv to disclose the grille's design airflow rate and a maximum allowable clean-filter pressure drop of 25 Pa (0.1 inches water) for the air filter when tested using ASHRAE Standard 52.2, or as rated in accordance with AHRI Standard 680 for the design airflow rate for the return grille. |
|||
| SYSTEM NOMINAL COOLING CAPACITY (TON)* |
RETURN DUCT 1 MINIMUM NOMINAL DIAMETER (INCH) |
RETURN DUCT 2 MINIMUM NOMINAL DIAMETER (INCH) |
MINIMUM TOTAL RETURN FILTER GRILLE NOMINAL AREA **(INCH2) ** |
| 1.5 | 12 | 10 | 500 |
| 2.0 | 14 | 12 | 600 |
| 2.5 | 14 | 14 | 800 |
| 3.0 | 16 | 14 | 900 |
| 3.5 | 16 | 16 | 1000 |
| 4.0 | 18 | 18 | 1200 |
| 5.0 | 20 | 20 | 1500 |
***** Not applicable to systems with nominal cooling capacity greater than 2.5 tons or less than 1.5 ton.
226 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
TABLE 160.3-C¶
DDC APPLICATIONS AND QUALIFICATIONS
| BUILDING STATUS | APPLICATIONS | QUALIFICATIONS |
|---|---|---|
| Newly Constructed Buildings | Air handling system and all zones served by the system |
Individual systems supplying more than three zones and with design heating or cooling capacity of 300 kBtu/ |
| Newly Constructed Buildings | Chilled water plant and all coils and terminal units served by the system |
Individual plants supplying more than three zones and with design cooling capacity of 300 kBtu/ |
| Newly Constructed Buildings | Hot water plant and all coils and terminal units served by the system |
Individual plants supplying more than three zones and with design heating capacity of 300 kBtu/ |
| Additions or Alterations | Zone terminal unit such as VAV box | Where existing zones served by the same air handling, chilled water or hot water systems that have DDC |
| Additions or Alterations | Air handling system or fan coil | Where existing air handling system(s) and fan coil(s) served by the same chilled or hot water plant have DDC |
| Additions or Alterations | New air handling system and all new zones served by the system |
Individual systems with design heating or cooling capacity of 300 kBtu/ more than 75 percent of zones are new |
| Additions or Alterations | New or upgraded chilled water plant | Where all chillers are new and plant design cooling capacity is 300 kBtu/ |
| Additions or Alterations | New or upgraded hot water plant | Where all boilers are new and plant design heating capacity is 300 kBtu/ |
TABLE 160.3-D¶
PIPE INSULATION THICKNESS
| FLUID OPERATING TEMPERATURE RANGE (°F) |
INSULATION CONDUCTIVITY | NOMINAL PIPE DIAMETER (in inches) | ||||||
|---|---|---|---|---|---|---|---|---|
| FLUID OPERATING TEMPERATURE RANGE (°F) |
Conductivity (in Btu·in/ °F) |
Mean Rating Temperature (°F) |
Mean Rating Temperature (°F) |
< 1 | 1 to <1.5 | 1.5 to < 4 | 4 to < 8 | 8 and larger |
| Space heating (Steam, Steam Condensate, Refrigerant, Space Heating) |
Space heating (Steam, Steam Condensate, Refrigerant, Space Heating) |
Space heating (Steam, Steam Condensate, Refrigerant, Space Heating) |
Space heating (Steam, Steam Condensate, Refrigerant, Space Heating) |
Minimum Pipe Insulation Required (Thickness in inches or_R-_value) |
Minimum Pipe Insulation Required (Thickness in inches or_R-_value) |
Minimum Pipe Insulation Required (Thickness in inches or_R-_value) |
Minimum Pipe Insulation Required (Thickness in inches or_R-_value) |
Minimum Pipe Insulation Required (Thickness in inches or_R-_value) |
| Above 350 | 0.32–0.34 | 250 | Inches | 4.5 | 5.0 | 5.0 | 5.0 | 5.0 |
| Above 350 | 0.32–0.34 | 250 | _R-_value |
R37 |
R41 |
R37 |
R27 |
R23 |
| 251–350 | 0.29–0.32 | 200 | Inches |
3.0 |
4.0 |
4.5 |
4.5 |
4.5 |
| 251–350 | 0.29–0.32 | 200 | _R-_value | R24 | R34 | R35 | R26 | R22 |
| 201–250 | 0.27–0.30 | 150 | Inches | 2.5 | 2.5 | 2.5 | 3.0 | 3.0 |
| 201–250 | 0.27–0.30 | 150 | _R-_value |
R21 |
R20 |
R17.5 |
R17 |
R14.5 |
| 141–200 | 0.25–0.29 | 125 | Inches |
1.5 |
1.5 |
2.0 |
2.0 |
2.0 |
| 141–200 | 0.25–0.29 | 125 | _R-_value | R11.5 | R11 | R14 | R11 | R10 |
| 105–140 | 0.22–0.28 | 100 | Inches |
1.0 |
1.5 |
1.5 |
1.5 |
1.5 |
| 105–140 | 0.22–0.28 | 100 | _R-_value | R7.7 | R12.5 | R11 | R9 | R8 |
| FLUID OPERATING TEMPERATURE RANGE (°F) |
INSULATION CONDUCTIVITY | INSULATION CONDUCTIVITY | NOMINAL PIPE DIAMETER (in inches) | NOMINAL PIPE DIAMETER (in inches) | NOMINAL PIPE DIAMETER (in inches) | NOMINAL PIPE DIAMETER (in inches) | NOMINAL PIPE DIAMETER (in inches) | |
| FLUID OPERATING TEMPERATURE RANGE (°F) |
Conductivity (in Btu·in/ °F) |
Mean Rating Temperature (°F) |
Mean Rating Temperature (°F) |
< 1 | 1 to <1.5 | 1.5 to < 4 | 4 to < 8 | 8 and larger |
| Space cooling systems (chilled water, refrigerant and brine) |
Space cooling systems (chilled water, refrigerant and brine) |
Space cooling systems (chilled water, refrigerant and brine) |
Space cooling systems (chilled water, refrigerant and brine) |
Minimum Pipe Insulation Required (Thickness in inches or_R-_value) |
Minimum Pipe Insulation Required (Thickness in inches or_R-_value) |
Minimum Pipe Insulation Required (Thickness in inches or_R-_value) |
Minimum Pipe Insulation Required (Thickness in inches or_R-_value) |
Minimum Pipe Insulation Required (Thickness in inches or_R-_value) |
| 40–60 | 0.21–0.27 | 75 | Inches | 0.75 | 0.75 | 1.0 | 1.0 | 1.0 |
| 40–60 | 0.21–0.27 | 75 | _R-_value |
R6 |
R5 |
R7 |
R6 |
R5 |
| Below 40 | 0.20–0.26 | 50 | Inches |
1.0 |
1.5 |
1.5 |
1.5 |
1.5 |
| Below 40 | 0.20–0.26 | 50 | _R-_value | R8.5 | R14 | R12 | R10 | R9 |
- These thicknesses are based on energy efficiency considerations only. Issues such as water vapor permeability or surface condensation sometimes require vapor retarders or additional insulation.
NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8 and 25943, Public Resources Code .
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
Get a plain-English answer with a citation back to this text.
Ask AI about this code