Section 110.2
California Energy Code (Title 24, Part 6) · 2022 edition · updated 2026-09-12 · California
MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
Certification by manufacturers. Any space-conditioning equipment listed in this section may be installed only if the manufacturer has certified to the Commission that the equipment complies with all the applicable requirements of this section.
(a) Efficiency. Equipment shall meet the applicable efficiency requirements in Tables 110.2-A through 110.2-N, subject to the following:
If more than one efficiency standard is listed for any equipment in Tables 110.2-A through 110.2-N, the equipment shall meet all the applicable standards that are listed; and
If more than one test method is listed in Tables 110.2-A through 110.2-N, the equipment shall comply with the applicable efficiency standard when tested with each listed test method; and
Where equipment serves more than one function, it shall comply with the efficiency standards applicable to each function; and
Where a requirement is for equipment rated at its “maximum rated capacity” or “minimum rated capacity,” the capacity shall be as provided for and allowed by the controls, during steady-state operation.
Exception 1 to Section 110.2(a): Water-cooled centrifugal water-chilling packages that are not designed for operation at ANSI/AHRI Standard 550/ 590 test conditions of 44°F leaving chilled water temperature and 85°F entering condenser water temperature with 3 gallons per minute per ton condenser water flow shall have a maximum full load kW/ton and NPLV ratings adjusted using the following equation:
Adjusted maximum full-load kW/ton rating = (fullload kW/ton from Table 110.2-D)/ K adj
Adjusted maximum NPLV rating = (IPLV from Table 110.2-D)/ K adj
Where:
K adj = (A) × (B)
A = 0.00000014592 × (LIFT) 4 0.0000346496 × (LIFT) 3 + 0.00314196 × (LIFT) 2 - 0.147199 × (LIFT) + 3.9302 LIFT = Lvg Cond – Lvg Evap (°F)
Lvg Cond = Full-load leaving condenser fluid temperature (°F) Lvg Evap = Full-load leaving evaporator fluid temperature (°F) B = (0.0015 × Lvg Evap) + 0.934 The adjusted full-load and NPLV values are only applicable for centrifugal chillers meeting all of the following full-load design ranges:
Minimum Leaving Evaporator Fluid Temperature: 36°F
Maximum Leaving Condenser Fluid Temperature: 115°F
LIFT ≥ 20°F and ≤ 80°F
Centrifugal chillers designed to operate outside of these ranges are not covered by this exception. Exception 2 to Section 110.2(a): Positive displacement (air-cooled and water-cooled) chillers with a leaving evaporator fluid temperature higher than 32°F shall show compliance with Table 110.2-D when tested or certified with water at standard rating conditions, per the referenced test procedure. Exception 3 to Section 110.2(a): Equipment pri - marily serving refrigerated warehouses or commercial refrigeration. (b) Controls for heat pumps with supplementary elec- tric resistance heaters. Heat pumps with supplementary electric resistance heaters shall have controls:
- That prevent supplementary heater operation when the heating load can be met by the heat pump alone; and
- In which the cut-on temperature for compression heating is higher than the cut-on temperature for supplementary heating, and the cut-off temperature for compression heating is higher than the cut-off temperature for supplementary heating.
Exception 1 to Section 110.2(b): The controls may allow supplementary heater operation during:
A. Defrost; and B. Transient periods such as start-ups and follow ing room thermostat setpoint advance, if the controls provide preferential rate control, intelligent recovery, staging, ramping or another control mechanism designed to preclude the unnecessary operation of supplementary heating. Exception 2 to Section 110.2(b): Room air-conditioner heat pumps.
38 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS,
EQUIPMENT AND BUILDING COMPONENTS
- Documentation of maximum achievable cycles of concentration. Building owners shall document the maximum cycles of concentration based on local water supply as reported annually by the local water supplier, and using the calculator approved by the Energy Commission. The calculator is intended to determine maximum cycles based on a Langelier Saturation Index (LSI) of 2.5 or less. Building owner shall document maximum cycles of concentration on the mechanical compliance form which shall be reviewed and signed by the Professional Engineer (P.E.) of Record.
- Be equipped with a flow meter with an analog output for flow either hardwired or available through a gateway on the makeup water line.
- Be equipped with an overflow alarm to prevent overflow of the sump in case of makeup water valve failure. Overflow alarm shall send an audible signal or provide an alert via the energy management control system to the tower operator in case of sump overflow.
- Be equipped with efficient drift eliminators that achieve drift reduction to 0.002 percent of the circulated water volume for counter-flow towers and 0.005 percent for cross-flow towers.
Exception to Section 110.2(e): Open and closed-circuit cooling towers with rated capacity < 150 tons. (f) Low leakage air-handling units. To qualify as a low leakage air-handling unit for use for meeting the requirements for applicable low leakage air-handling unit compliance credit(s) available in the performance standards set forth in Sections 150.1(b) and 140.1, the manufacturer shall certify to the Energy Commission that the air-handling unit meets the specifications in Reference Joint Appendix JA9.
(c) Thermostats. All heating or cooling systems not controlled by a central energy management control system (EMCS) shall have a setback thermostat.
- Setback capabilities. All thermostats shall have a clock mechanism that allows the building occupant to program the temperature setpoints for at least four periods within 24 hours. Thermostats for heat pumps shall meet the requirements of Section 110.2(b).
Exception to Section 110.2(c): Gravity gas wall heaters, gravity floor heaters, gravity room heaters, noncentral electric heaters, fireplaces or decorative gas appliances, wood stoves, room air conditioners and room air-conditioner heat pumps. (d) Gas-fired and oil-fired furnace standby loss con- trols. Gas-fired and oil-fired forced-air furnaces with input ratings ≥ 225,000 Btu/hr shall also have an intermittent ignition or interrupted device (IID), and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for furnaces where combustion air is drawn from the conditioned space. All furnaces with input ratings ≥ 225,000 Btu/hr, including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75 percent of the input rating.
(e) Open and closed-circuit cooling towers. All open and closed cooling tower installations shall comply with the following:
- Be equipped with conductivity or flow-based controls that maximize cycles of concentration based on local water quality conditions. Controls shall automate system bleed and chemical feed based on conductivity, or in proportion to metered makeup volume, metered bleed volume, recirculating pump run time, or bleed time. Conductivity controllers shall be installed in accordance with manufacturer’s specifications in order to maximize accuracy.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-A¶
AIR CONDITIONERS AND CONDENSING UNITS – MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | SIZE CATEGORY | EFFICIENCYa | TEST PROCEDUREb |
|---|---|---|---|
| Air conditioners, air cooled both split system and single package |
≥ 65,000 Btu/ < 135,000 Btu/ |
11.2 EERa 14.8 IEERa |
ANSI/ |
| Air conditioners, air cooled both split system and single package |
≥ 135,000 Btu/ < 240,000 Btu/ |
11.0 EERa 14.2 IEERa |
ANSI/ |
| Air conditioners, air cooled both split system and single package |
≥ 240,000 Btu/ < 760,000 Btu/ |
10.0 EERa 13.2 IEERa |
10.0 EERa 13.2 IEERa |
| Air conditioners, air cooled both split system and single package |
≥ 760,000 Btu/ |
9.7 EERa 12.5 IEERa |
9.7 EERa 12.5 IEERa |
| Air conditioners, water cooled |
≥ 65,000 Btu/ < 135,000 Btu/ |
12.1 EERa 13.9 IEERa |
ANSI/ |
| Air conditioners, water cooled |
≥ 135,000 Btu/ < 240,000 Btu/ |
12.5 EERa 13.9 IEERa |
ANSI/ |
| Air conditioners, water cooled |
≥ 240,000 Btu/ < 760,000 Btu/ |
12.4 EERa 13.6 IEERa |
ANSI/ |
| Air conditioners, water cooled |
≥ 760,000 Btu/ |
12.2 EERa 13.5 IEERa |
ANSI/ |
| Air conditioners, evaporatively cooled |
≥ 65,000 Btu/ < 135,000 Btu/ |
12.1 EERa 12.3 IEERa |
ANSI/ |
| Air conditioners, evaporatively cooled |
≥ 135,000 Btu/ < 240,000 Btu/ |
12.0 EERa 12.2 IEERa |
ANSI/ |
| Air conditioners, evaporatively cooled |
≥ 240,000 Btu/ < 760,000 Btu/ |
11.9 EERa 12.1 IEERa |
ANSI/ |
| Air conditioners, evaporatively cooled |
≥ 760,000 Btu/ |
11.7 EERa 11.9 IEERa |
ANSI/ |
| Condensing units, air cooled |
≥ 135,000 Btu/ |
10.5 EER 11.8 IEER |
ANSI/AHRI 365 |
| Condensing units, water cooled |
≥ 135,000 Btu/ |
13.5 EER 14.0 IEER |
13.5 EER 14.0 IEER |
| Condensing units, evapora- tively cooled |
≥ 135,000 Btu/ |
13.5 EER 14.0 IEER |
13.5 EER 14.0 IEER |
b. Applicable test procedure and reference year are provided under the definitions.
40 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS,
EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-B¶
HEAT PUMPS, MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | SIZE CATEGORY | SUBCATEGORY OR RATING CONDITION |
EFFICIENCYa | TEST PROCEDUREb |
|---|---|---|---|---|
| Air cooled (cooling mode), both split system and single package |
≥ 65,000 Btu/ < 135,000 Btu/ |
11.0 EER 14.1 IEER |
AHRI 340/360 | |
| Air cooled (cooling mode), both split system and single package |
≥ 135,000 Btu/ < 240,000 Btu/ |
10.6 EER 13.5 IEER |
10.6 EER 13.5 IEER |
|
| Air cooled (cooling mode), both split system and single package |
≥ 240,000 Btu/ |
9.5 EER 12.5 IEER |
9.5 EER 12.5 IEER |
|
| Water source (cooling mode) |
≥ 65,000 Btu/ < 135,000 Btu/ |
86ºF entering water | 13.0 EER | ISO-13256-1 |
| Groundwater source (cooling mode) |
< 135,000 Btu/ |
59ºF entering water | 18.0 EER | ISO-13256-1 |
| Ground source (cooling mode) |
< 135,000 Btu/ |
77ºF entering water | 14.1 EER | ISO-13256-1 |
| Water source water-to-water (cooling mode) |
< 135,000 Btu/ |
86ºF entering water | 10.6 EER | ISO-13256-2 |
| Groundwater source water-to-water (cooling mode) |
< 135,000 Btu/ |
59ºF entering water | 16.3 EER | ISO-13256-2 |
| Ground source brine-to-water (cooling mode) |
< 135,000 Btu/ |
77ºF entering water | 12.1 EER | ISO-13256-2 |
| Air cooled (heating mode) Split system and single pack- age |
≥ 65,000 Btu/ < 135,000 Btu/ (cooling capacity) |
47°F db/43°F wb outdoor air |
3.4 COP | AHRI 340/360 |
| Air cooled (heating mode) Split system and single pack- age |
≥ 65,000 Btu/ < 135,000 Btu/ (cooling capacity) |
17°F db/15°F wb outdoor air |
2.25 COP | 2.25 COP |
| Air cooled (heating mode) Split system and single pack- age |
≥ 135,000 Btu/ (cooling capacity) |
47°F db/43°F wb outdoor air |
3.3 COP | 3.3 COP |
| Air cooled (heating mode) Split system and single pack- age |
≥ 135,000 Btu/ (cooling capacity) |
17°F db/15°F wb outdoor air |
2.05 COP | 2.05 COP |
| Water source (heating mode) |
< 135,000 Btu/ (cooling capacity) |
68ºF entering water | 4.3 COP | ISO-13256-1 |
| Water source (heating mode) |
≥ 135,000 Btu/ < 240,000 Btu/ |
68ºF entering water | 2.90 COP | ISO-13256-1 |
| Groundwater source (heating mode) |
< 135,000 Btu/ (cooling capacity) |
50ºF entering water | 3.7 COP | ISO-13256-1 |
| Ground source (heating mode) |
< 135,000 Btu/ (cooling capacity) |
32ºF entering water | 3.2 COP | ISO-13256-1 |
| Water source water-to-water (heating mode) |
< 135,000 Btu/ (cooling capacity) |
68ºF entering water | 3.7 COP | ISO-13256-2 |
| Groundwater source water-to-water (heating mode) |
< 135,000 Btu/ (cooling capacity) |
50ºF entering water | 3.1 COP | ISO-13256-2 |
| Ground source brine-to-water (heating mode) |
< 135,000 Btu/ (cooling capacity) |
32ºF entering water | 2.5 COP | ISO-13256-2 |
a. Deduct 0.2 from the required EERs and IEERs for units with a heating section other than electric resistance heat. b. Applicable test procedure and reference year are provided under the definitions.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-C¶
AIR-COOLED GAS-ENGINE HEAT PUMPS
| EQUIPMENT TYPE | SIZE CATEGORY | SUBCATEGORY OR RATING CONDITION |
EFFICIENCY | TEST PROCEDUREa |
|---|---|---|---|---|
| Air-cooled gas-engine heat pump (cooling mode) |
All capacities | 95°F db outdoor air | 0.60 COP | ANSI Z21.40.4A |
| Air-cooled gas-engine heat pump (heating mode) |
All capacities | 47°F db/43°F wb outdoor air | 0.72 COP | ANSI Z21.40.4A |
a. Applicable test procedure and reference year are provided under the definitions.
TABLE 110.2-D WATER CHILLING PACKAGES—MINIMUM EFFICIENCY REQUIREMENTS a, b
| EQUIPMENT TYPE | SIZE CATEGORY | PATH A EFFICIENCYa, b |
PATH B EFFICIENCYa, b |
TEST PROCEDUREc |
|---|---|---|---|---|
| Air cooled, with condenser electrically operated |
< 150 tons | ≥ 10.100 EER ≥ 13.700 IPLV |
≥ 9.700 EER ≥ 15.800 IPLV |
AHRI 550/590 |
| Air cooled, with condenser electrically operated |
≥ 150 tons | ≥ 10.100 EER ≥ 14.000 IPLV |
≥ 9.700 EER ≥ 16.100 IPLV |
≥ 9.700 EER ≥ 16.100 IPLV |
| Air cooled, without condenser electrically operated |
All capacities | Air-cooled chillers without condensers must be rated with matching condensers and comply with the air-cooled chiller efficiency requirements. |
Air-cooled chillers without condensers must be rated with matching condensers and comply with the air-cooled chiller efficiency requirements. |
AHRI 550/590 |
| Water cooled, electrically operated reciprocating |
All capacities | Reciprocating units must comply with the water- cooled positive displacement efficiency requirements. |
Reciprocating units must comply with the water- cooled positive displacement efficiency requirements. |
AHRI 550/590 |
| Water cooled, electrically operated, positive displacement |
< 75 tons | ≤ 0.750 kW/ ≤ 0.600 IPLV |
≤ 0.780 kW/ ≤ 0.500 IPLV |
AHRI 550/590 |
| Water cooled, electrically operated, positive displacement |
≥ 75 tons and < 150 tons |
≤ 0.720 kW/ ≤ 0.560 IPLV |
≤ 0.750 kW/ ≤ 0.490 IPLV |
≤ 0.750 kW/ ≤ 0.490 IPLV |
| Water cooled, electrically operated, positive displacement |
≥ 150 tons and < 300 tons |
≤ 0.660 kW/ ≤ 0.540 IPLV |
≤ 0.680 kW/ ≤ 0.440 IPLV |
≤ 0.680 kW/ ≤ 0.440 IPLV |
| Water cooled, electrically operated, positive displacement |
≥ 300 tons and < 300 tons |
≤ 0.610 kW/ ≤ 0.520 IPLV |
≤ 0.625 kW/ ≤ 0.410 IPLV |
≤ 0.625 kW/ ≤ 0.410 IPLV |
| Water cooled, electrically operated, positive displacement |
≥ 600 tons | ≤ 0.560 kW/ ≤ 0.500 IPLV |
≤ 0.585 kW/ ≤ 0.380 IPLV |
≤ 0.585 kW/ ≤ 0.380 IPLV |
| Water cooled, electrically operated, centrifugal |
> 150 ton | ≤ 0.610 kW/ ≤ 0.550 IPLV |
≤ 0.695 kW/ ≤ 0.440 IPLV |
≤ 0.695 kW/ ≤ 0.440 IPLV |
| Water cooled, electrically operated, centrifugal |
≥ 150 tons and < 300 tons |
≤ 0.610 kW/ ≤ 0.550 IPLV |
≤ 0.635 kW/ ≤ 0.400 IPLV |
≤ 0.635 kW/ ≤ 0.400 IPLV |
| Water cooled, electrically operated, centrifugal |
≥ 300 tons and < 400 tons |
≤ 0.560 kW/ ≤ 0.520 IPLV |
≤ 0.595 kW/ ≤ 0.390 IPLV |
≤ 0.595 kW/ ≤ 0.390 IPLV |
| Water cooled, electrically operated, centrifugal |
≥ 400 tons and < 600 tons |
≤ 0.560 kW/ ≤ 0.500 IPLV |
≤ 0.585 kW/ ≤ 0.380 IPLV |
≤ 0.585 kW/ ≤ 0.380 IPLV |
| Water cooled, electrically operated, centrifugal |
≥ 600 tons | ≤ 0.560 kW/ ≤ 0.500 IPLV |
≤ 0.585 kW/ ≤ 0.380 IPLV |
≤ 0.585 kW/ ≤ 0.380 IPLV |
| Air cooled absorption single effect | All capacities | ≥ 0.600 COP | N.A.d |
AHRI 560 |
| Water cooled absorption single effect | All capacities | ≥ 0.700 COP | N.A.d | N.A.d |
| Absorption double effect, indirect-fired |
All capacities | ≥ 1.000 COP ≥ 1.050 IPLV |
N.A.d | N.A.d |
| Absorption double effect, direct-fired |
All capacities | ≥ 1.000 COP ≥ 1.000 IPLV |
N.A.d | N.A.d |
| Water cooled gas engine driven chiller |
All capacities | ≥ 1.2 COP ≥ 2.0 IPLV |
N.A.d | ANSI Z21.40.4 |
a. No requirements for:
Centrifugal chillers with design leaving evaporator temperature < 36°F; or
Positive displacement chillers with design leaving fluid temperature ≤ 32°F; or
Absorption chillers with design leaving fluid temperature < 40°F.
b. Must meet the minimum requirements of Path A or Path B. However, both the full load (COP) and IPLV must be met to fulfill the requirements of the
applicable path. c. See Section 100.1 for definitions. d. N.A. means not applicable.
42 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS,
EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-E¶
PACKAGED TERMINAL AIR CONDITIONERS AND PACKAGED TERMINAL HEAT PUMPS— MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | SIZE CATEGORY (Input) | SUBCATEGORY OR RATING CONDITION |
EFFICIENCY | TEST PROCEDUREc |
|---|---|---|---|---|
| PTAC (cooling mode) Newly constructed or newly conditioned buildings or additions |
All capacities | 95°F db outdoor air | 14.0 - (0.300 × Cap/ 1000)a EER |
ANSI/ CSA 310/380 |
| PTAC (cooling mode) Replacementsb | All capacities | 95°F db outdoor air | 10.9 - (0.213 × Cap/ 1000)a EER |
10.9 - (0.213 × Cap/ 1000)a EER |
| PTHP (cooling mode) Newly constructed or newly conditioned buildings or additions |
All capacities | 95°F db outdoor air | 14.0 - (0.300 × Cap/ 1000)a EER |
14.0 - (0.300 × Cap/ 1000)a EER |
| PTHP (cooling mode) Replacementsb | All capacities | 95°F db outdoor air | 10.8 - (0.213 × Cap/ 1000)a EER |
10.8 - (0.213 × Cap/ 1000)a EER |
| PTHP (heating mode) Newly constructed or newly conditioned buildings or additions |
All capacities | — | 3.7 - (0.052 × Cap/1000)a COP |
3.7 - (0.052 × Cap/1000)a COP |
| PTHP (heating mode) Replacementsb | All capacities | — | 2.9 - (0.026 × Cap/1000)a COP |
2.9 - (0.026 × Cap/1000)a COP |
| SPVAC (cooling mode) | < 65,000 Btu/h | 95°F db/75°F wb outdoor air |
11.0 EER | ANSI/AHRI 390 |
| SPVAC (cooling mode) | ≥ 65,000 Btu/ < 135,000 Btu/ |
95°F db/75°F wb outdoor air |
10.0 EER | 10.0 EER |
| SPVAC (cooling mode) | ≥ 135,000 Btu/ < 240,000 Btu/ |
95°F db/75°F wb outdoor air |
10.0 EER | 10.0 EER |
| SPVHP (cooling mode) | < 65,000 Btu/h | 95°F db/75°F wb outdoor air |
11.0 EER | 11.0 EER |
| SPVHP (cooling mode) | ≥ 65,000 Btu/ < 135,000 Btu/ |
95°F db/75°F wb outdoor air |
10.0 EER | 10.0 EER |
| SPVHP (cooling mode) | ≥ 135,000 Btu/ < 240,000 Btu/ |
95°F db/75°F wb outdoor air |
10.0 EER | 10.0 EER |
| SPVHP (heating mode) | < 65,000 Btu/h | 47°F db/43°F wb outdoor air |
3.3 COP | 3.3 COP |
| SPVHP (heating mode) | ≥ 65,000 Btu/ < 135,000 Btu/ |
47°F db/43°F wb outdoor air |
3.0 COP | 3.0 COP |
| SPVHP (heating mode) | ≥ 135,000 Btu/ < 240,000 Btu/ |
47°F db/43°F wb outdoor air |
3.0 COP | 3.0 COP |
a. Cap means the rated cooling capacity of the product in Btu/h. If the unit’s capacity is less than 7,000 Btu/h, use 7,000 Btu/h in the calculation. If the unit’s
capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculation. b. Replacement units must be factory labeled as follows: “MANUFACTURED FOR REPLACEMENT APPLICATIONS ONLY; NOT TO BE INSTALLED
IN NEWLY CONSTRUCTED BUILDINGS.” Replacement efficiencies apply only to units with existing sleeves less than 16 inches high or less than 42 inch wide and having a cross-sectional area less than 670 square inches. c. Applicable test procedure and reference year are provided under the definitions.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-F¶
PERFORMANCE REQUIREMENTS FOR HEAT REJECTION EQUIPMENT
| EQUIPMENT TYPE | TOTAL SYSTEM HEAT REJECTION CAPACITY AT RATED CONDITIONS |
SUBCATEGORY OR RATING CONDITION |
PERFORMANCE REQUIREDa, b, c, d |
TEST PROCEDUREe |
|---|---|---|---|---|
| Propeller or axial fan open- circuit cooling towers |
All | 95°F entering water 85°F leaving water 75°F entering air wb |
≥ 42.1 gpm/hp | CTI ATC-105 and CTI STD-201 RS |
| Centrifugal fan open-circuit cooling towers |
All | 95°F entering water 85°F leaving water 75°F entering air wb |
≥ 20.0 gpm/hp | ≥ 20.0 gpm/hp |
| Propeller or axial fan closed- circuit cooling towers |
All | 102°F entering water 90°F leaving water 75°F entering air wb |
≥ 16.1 gpm/hp | CTI ATC-105S and CTI STD-201 RS |
| Centrifugal fan closed-circuit cooling towers |
All | 102°F entering water 90°F leaving water 75°F entering air wb |
≥ 7.0 gpm/hp | ≥ 7.0 gpm/hp |
| Propeller or axial fan evaporative condensers |
All | R-448A test fluid 165°F entering gas temp 105°F condensing temp 75°F entering air wb |
≥ 157,000 Btu/ |
CTI ATC-106 |
| Propeller or axial fan evaporative condensers |
All | Ammonia test fluid 140°F entering gas temp 96.3°F condensing temp 75°F entering air wb |
≥ 134,000 Btu/ |
≥ 134,000 Btu/ |
| Centrifugal fan evaporative condensers |
All | R-448A test fluid 165°F entering gas temp 105°F condensing temp 75°F entering air wb |
≥ 135,000 Btu/ |
≥ 135,000 Btu/ |
| Centrifugal fan evaporative condensers |
All | Ammonia test fluid 140°F entering gas temp 96.3°F condensing temp 75°F entering air wb |
≥ 110,000 Btu/ |
≥ 110,000 Btu/ |
| Air cooled condensers | All | 125°F condensing temperature 190°F entering gas temperature 15°F subcooling 95°F entering dry-bulb |
≥ 176,000 Btu/ |
AHRI 460 |
| Propeller or axial fan dry coolers (air-cooled fluid coolers) |
All | 115°F entering water 105°F leaving water 95°F entering air db |
≥ 4.5 gpm/hp | CTI ATC-105DS |
a. For purposes of this table, open-circuit cooling tower performance is defined as the water flow rating of the tower at the given rated conditions divided by the
fan motor nameplate power. b. For purposes of this table, closed-circuit cooling tower performance is defined as the process water flow rating of the tower at the given rated conditions
divided by the sum of the fan motor nameplate rated power and the integral spray pump motor nameplate power. c. For purposes of this table, dry cooler performance is defined as the process water flow rating of the unit at the given thermal rating condition divided by the
total fan motor nameplate power of the unit and air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the fan motor nameplate power of the unit. d. Open cooling towers shall be tested using the test procedures in CTI ATC-105. Performance of factory-assembled open cooling towers shall be either
certified as base models as specified in CTI STD-201 or verified by testing in the field by a CTI approved testing agency. Open factory assembled cooling towers with custom options added to a CTI certified base model for the purpose of safe maintenance or to reduce environmental or noise impact shall be rated at 90 percent of the CTI certified performance of the associated base model or at the manufacturer’s stated performance, whichever is less. Base models of open factory-assembled cooling towers are open cooling towers configured in exact accordance with the Data of Record submitted to CTI as specified by CTI STD-201. There are no certification requirements for field-erected cooling towers. e. Applicable test procedure and reference year are provided under the definitions. For refrigerated warehouses or commercial refrigeration applications,
condensers shall comply with requirements specified by Section 120.6(a) or Section 120.6(b).
44 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS,
EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-G¶
ELECTRICALLY OPERATED VARIABLE REFRIGERANT FLOW (VRF) AIR CONDITIONERS MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | SIZE CATEGORY | HEATING SECTION TYPE |
SUBCATEGORY OR RATING CONDITION |
MINIMUM EFFICIENCY |
TEST PROCEDUREa |
|---|---|---|---|---|---|
| VRF Air conditioners, Air cooled |
< 65,000 Btu/h | All | VRF multisplit system | 13.0 SEER | AHRI 1230 |
| VRF Air conditioners, Air cooled |
≥ 65,000 Btu/ < 135,000 Btu/ |
Electric resistance (or none) |
VRF multisplit system | 11.2 EER 15.5 IEERb |
11.2 EER 15.5 IEERb |
| VRF Air conditioners, Air cooled |
≥ 135,000 Btu/ < 240,000 Btu/ |
Electric resistance (or none) |
VRF multisplit system | 11.0 EER 14.9 IEERb |
11.0 EER 14.9 IEERb |
| VRF Air conditioners, Air cooled |
≥ 240,000 Btu/ |
Electric resistance (or none) |
VRF multisplit system | 10.0 EER 13.9 IEERb |
10.0 EER 13.9 IEERb |
a. Applicable test procedure and reference year are provided under the definitions. b. IEERs are only applicable to equipment with capacity control as specified in ANSI/AHRI 1230 test procedures.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-H¶
ELECTRICALLY OPERATED VARIABLE REFRIGERANT FLOW AIR-TO-AIR AND APPLIED HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | SIZE CATEGORY | HEATING SECTION TYPE |
SUBCATEGORY OR RATING CONDITION |
MINIMUM EFFICIENCY |
TEST PROCEDUREa, b |
|---|---|---|---|---|---|
| VRF Air cooled (cooling mode) |
< 65,000 Btu/ |
All | VRF multisplit system | 13.0 SEER |
AHRI 1230 |
| VRF Air cooled (cooling mode) |
≥ 65,000 Btu/ < 135,000 Btu/ |
Electric resistance (or none) |
VRF multisplit systema | 11.0 EER 14.6 IEERc |
11.0 EER 14.6 IEERc |
| VRF Air cooled (cooling mode) |
≥ 135,000 Btu/ < 240,000 Btu/ |
Electric resistance (or none) |
VRF multisplit systema | 10.6 EER 13.9 IEERc |
10.6 EER 13.9 IEERc |
| VRF Air cooled (cooling mode) |
≥ 240,000 Btu/ |
Electric resistance (or none) |
VRF multisplit systema |
9.5 EER 12.7 IEERc |
9.5 EER 12.7 IEERc |
| VRF Water source (cooling mode) |
< 65,000 Btu/ |
All | VRF multisplit systema 86ºF entering water |
12.0 EER 16.0 IEERc |
AHRI 1230 |
| VRF Water source (cooling mode) |
≥ 65,000 Btu/ < 135,000 Btu/ |
All | VRF multisplit systema 86ºF entering water |
12.0 EER 16.0 IEERc |
12.0 EER 16.0 IEERc |
| VRF Water source (cooling mode) |
≥ 135,000 Btu/ < 240,000 Btu/ |
All | VRF multisplit systema 86ºF entering water |
10.0 EER 14.0 IEERc |
10.0 EER 14.0 IEERc |
| VRF Water source (cooling mode) |
≥ 240,000 Btu/ |
All | VRF multisplit systema 86ºF entering water |
10.0 EER 12.0 IEER |
10.0 EER 12.0 IEER |
| VRF Groundwater source (cooling mode) |
< 135,000 Btu/ |
All | VRF multisplit systema 59ºF entering water |
16.2 EER | AHRI 1230 |
| VRF Groundwater source (cooling mode) |
≥ 135,000 Btu/ |
All | VRF multisplit systema 59ºF entering water |
13.8 EER | 13.8 EER |
| VRF Ground source (cooling mode) |
< 135,000 Btu/ |
All | VRF multisplit systema 77ºF entering water |
13.4 EER | AHRI 1230 |
| VRF Ground source (cooling mode) |
≥ 135,000 Btu/ |
All | VRF multisplit systema 77ºF entering water |
11.0 EER | 11.0 EER |
| VRF Air cooled (heating mode) |
< 65,000 Btu/ (cooling capacity) |
— | VRF multisplit system |
7.7 HSPF | AHRI 1230 |
| VRF Air cooled (heating mode) |
≥ 65,000 Btu/ < 135,000 Btu/ (cooling capacity) |
— | VRF multisplit system 47ºF db/43ºF wb outdoor air |
3.3 COP | 3.3 COP |
| VRF Air cooled (heating mode) |
≥ 65,000 Btu/ < 135,000 Btu/ (cooling capacity) |
— | VRF multisplit system 17ºF db/15ºF wb outdoor air |
2.25 COP | 2.25 COP |
| VRF Air cooled (heating mode) |
≥ 135,000 Btu/ (cooling capacity) |
— | VRF multisplit system 47ºF db/43ºF wb outdoor air |
3.2 COP | 3.2 COP |
| VRF Air cooled (heating mode) |
≥ 135,000 Btu/ (cooling capacity) |
— | VRF multisplit system 17ºF db/15ºF wb outdoor air |
2.05 COP | 2.05 COP |
| VRF Water source (heating mode) |
< 65,000 Btu/ (cooling capacity) |
— | VRF multisplit system 68ºF entering water |
4.3 COP | AHRI 1230 |
| VRF Water source (heating mode) |
≥ 65,000 Btu/ < 135,000 Btu/ (cooling capacity) |
— | VRF multisplit system 68ºF entering water |
4.3 COP | 4.3 COP |
| VRF Water source (heating mode) |
≥ 135,000 Btu/ < 240,000 Btu/ (cooling capacity) |
— | VRF multisplit system 68ºF entering water |
4.0 COP | 4.0 COP |
| VRF Water source (heating mode) |
≥ 240,000 Btu/ (cooling capacity) |
— | VRF multisplit system 68ºF entering water |
3.9 COP | 3.9 COP |
| VRF Groundwater source (heating mode) |
< 135,000 Btu/ (cooling capacity) |
— | VRF multisplit system 50ºF entering water |
3.6 COP | AHRI 1230 |
| VRF Groundwater source (heating mode) |
≥ 135,000 Btu/ (cooling capacity) |
— | VRF multisplit system 50ºF entering water |
3.3 COP | 3.3 COP |
| VRF Ground source (heating mode) |
< 135,000 Btu/ (cooling capacity) |
— | VRF multisplit system 32ºF entering water |
3.1 COP | AHRI 1230 |
| VRF Ground source (heating mode) |
≥ 135,000 Btu/ (cooling capacity) |
— | VRF multisplit system 32ºF entering water |
2.8 COP | 2.8 COP |
a. Deduct 0.2 from the required EERs and IEERs for variable refrigerant flow (VRF) multisplit system units with a heating recovery section. b. Applicable test procedure and reference year are provided under the definitions. c. IEERs are only applicable to equipment with capacity control as specified in ANSI/AHRI 1230 test procedures.
46 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS,
EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-I¶
WARM-AIR FURNACES AND COMBINATION WARM-AIR FURNACES/AIR-CONDITIONING UNITS, WARM-AIR DUCT FURNACES AND UNIT HEATERS c, f
| EQUIPMENT TYPE |
SIZE CATEGORY (Input) |
SUBCATEGORY OR RATING CONDITIONb |
MINIMUM EFFICIENCYd, e |
TEST PROCEDUREa |
|---|---|---|---|---|
| Warm-Air furnace, gas-fired | ≥ 225,000 Btu/ |
Maximum capacity | 81%Et | Section 2.39, Thermal Efficiency, ANSI Z21.47 |
| Warm-Air furnace, oil-fired | ≥ 225,000 Btu/ |
Maximum capacity | 82%Et | Section 42, Combustion, UL 727 |
| Warm-Air duct furnaces, gas-fired | All capacities | Maximum capacity | 80%Ec | Section 2.10, Efficiency, ANSI Z83.8 |
| Warm-Air unit heaters, gas-fired | All capacities | Maximum capacity | 80%Ec | Section 2.10, Efficiency, ANSI Z83.8 |
| Warm-Air unit heaters, oil-fired | All capacities | Maximum capacity | 80%Ec | Section 40, Combustion, UL 731 |
a. Applicable test procedure and reference year are provided under the definitions. b. Compliance of multiple firing rate units shall be at maximum firing rate. c. Combustion units not covered by the U.S. Department of Energy Code of Federal Regulations 10 CFR 430 (3-phase power or cooling capacity greater than or
equal to 19 kW) may comply with either rating. d. Et = thermal efficiency. Units must also include an interrupted or intermittent ignition device (IID), have jacket losses not exceeding 0.75% of the input rating,
and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space. e. Ec = combustion efficiency (100% less flue losses). See test procedure for detailed discussion. f. As of August 8, 2008, according to the Energy Policy Act of 2005, units must also include an interrupted or intermittent ignition device (IID) and have either
power venting or an automatic flue damper.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-J¶
GAS- AND OIL-FIRED BOILERS, MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE |
SUBCATEGORY | SIZE CATEGORY (Input) |
MINIMUM EFFICIENCYb, c | TEST PROCEDUREa |
|
|---|---|---|---|---|---|
| EQUIPMENT TYPE |
SUBCATEGORY | SIZE CATEGORY (Input) |
Before 1/10/2023 | On or After 1/10/2023f | On or After 1/10/2023f |
| Boiler, hot water | Gas-Fired | < 300,000 Btu/ |
82% AFUE | 82% AFUE | DOE 10 CFR Part 430 |
| Boiler, hot water | Gas-Fired | ≥ 300,000 Btu/ ≤ 2,500,000 Btu/ |
80%Et | 80%Et | DOE 10 CFR Part 431 |
| Boiler, hot water | Gas-Fired | > 2,500,000 Btu/ ≤ 10,000,000 Btu/ |
82%Ec | 85%Ec | 85%Ec |
| Boiler, hot water | Gas-Fired | > 10,000,000 Btu/ |
82%Ec | 82%Ec | 82%Ec |
| Boiler, hot water | Oil-Firede | < 300,000 Btu/ |
84% AFUE | 84% AFUE | DOE 10 CFR Part 430 |
| Boiler, hot water | Oil-Firede | ≥ 300,000 Btu/ ≤ 2,500,000 Btu/ |
82%Et | 87%Et | DOE 10 CFR Part 431 |
| Boiler, hot water | Oil-Firede | > 2,500,000 Btu/ ≤ 10,000,000 Btu/ |
84%Ec | 88%Ec | 88%Ec |
| Boiler, hot water | Oil-Firede | > 10,000,000 Btu/ |
84%Ec | 84%Ec | 84%Ec |
| Boiler, steam | Gas-Fired | < 300,000 Btu/ |
80% AFUE | 80% AFUE | DOE 10 CFR Part 430 |
| Boiler, steam | Gas-Fired | ≥ 300,000 Btu/ ≤ 2,500,000 Btu/ |
81%Et | DOE 10 CFR Part 431 | |
| Boiler, steam | Gas-Fired | > 2,500,000 Btu/ ≤ 10,000,000 Btu/ |
82%Et | 82%Et | |
| Boiler, steam | Gas-Fired | > 10,000,000 Btu/ |
79%Et | 79%Et | |
| Boiler, steam | Gas-Fired all, except natural draftf |
≥ 300,000 Btu/ ≤ 2,500,000 Btu/ |
79%Et | 81%Et | 81%Et |
| Boiler, steam | Gas-Fired all, except natural draftf |
> 2,500,000 Btu/ ≤ 10,000,000 Btu/ |
79%Et | 82%Et | 82%Et |
| Boiler, steam | Gas-Fired all, except natural draftf |
> 10,000,000 Btu/ |
79%Et | 79%Et | 79%Et |
| Boiler, steam | Gas-Fired, natural draftf |
≥ 300,000 Btu/ ≤ 2,500,000 Btu/ |
77%Et | 81%Et | 81%Et |
| Boiler, steam | Gas-Fired, natural draftf |
> 2,500,000 Btu/ ≤ 10,000,000 Btu/ |
77%Et | 82%Et | 82%Et |
| Boiler, steam | Gas-Fired, natural draftf |
> 10,000,000 Btu/ |
77%Et | 79%Et | 79%Et |
| Boiler, steam | Oil-Firede | < 300,000 Btu/ |
82% AFUE | 82% AFUE | 82% AFUE |
| Boiler, steam | Oil-Firede | ≥ 300,000 Btu/ ≤ 2,500,000 Btu/ |
81%Et | 84%Et | 84%Et |
| Boiler, steam | Oil-Firede | > 2,500,000 Btu/ ≤ 10,000,000 Btu/ |
81%Et | 85%Et | 85%Et |
| Boiler, steam | Oil-Firede | > 10,000,000 Btu/ |
81%Et | 81%Et | 81%Et |
a. Applicable test procedure and reference year are provided under the definitions. b. Ec = combustion efficiency (100% less flue losses). See test procedure for detailed information. c. Et = thermal efficiency. See test procedure for detailed information. d. Maximum capacity—maximum rating per the certified unit capacity. e. Included oil-fired (residual). f. Federal efficiency standards do not distinguish between natural draft gas-fired steam boilers and other gas-fired steam boilers on or after January 10, 2023.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code .
48 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS,
EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-K¶
DX-DOAS UNITS, SINGLE-PACKAGE AND REMOTE CONDENSER—MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE |
ENERGY RECOVERY | SUBCATEGORY OR RATING CONDITION |
MINIMUM EFFICIENCY |
TEST PROCEDUREa |
|---|---|---|---|---|
| Air cooled (dehumidification mode) |
Without energy recovery | 4.0 ISMRE | AHRI 920 | |
| Air source heat pumps (dehumidification mode) |
Without energy recovery | 4.0 ISMRE | AHRI 920 | |
| Water cooled (dehumidification mode) |
Without energy recovery | Cooling tower condenser water | 4.9 ISMRE | AHRI 920 |
| Water cooled (dehumidification mode) |
Without energy recovery | Chilled water | 6.0 ISMRE | AHRI 920 |
| Water source heat pump (dehumidification mode) |
Without energy recovery | Ground source, closed loop | 4.8 ISMRE | AHRI 920 |
| Water source heat pump (dehumidification mode) |
Without energy recovery | Ground-water source | 5.0 ISMRE | AHRI 920 |
| Water source heat pump (dehumidification mode) |
Without energy recovery | Water source | 4.0 ISMRE | AHRI 920 |
| Air source heat pumps (heating mode) |
Without energy recovery | 2.7 ISCOP | AHRI 920 | |
| Water source heat pump (heating mode) |
Without energy recovery | Ground source, closed loop | 2.0 ISCOP | AHRI 920 |
| Water source heat pump (heating mode) |
Without energy recovery | Ground-water source | 3.2 ISCOP | AHRI 920 |
| Water source heat pump (heating mode) |
Without energy recovery | Water source | 3.5 ISCOP | AHRI 920 |
| Air cooled (dehumidification mode) |
With energy recovery | 5.2 ISMRE | AHRI 920 | |
| Air source heat pumps (dehumidification mode) |
With energy recovery | 5.2 ISMRE | AHRI 920 | |
| Water cooled (dehumidification mode) |
With energy recovery | Cooling tower condenser water | 5.3 ISMRE | AHRI 920 |
| Water cooled (dehumidification mode) |
With energy recovery | Chilled water | 6.6 ISMRE | AHRI 920 |
| Water source heat pump (dehumidification mode) |
With energy recovery | Ground source, closed loop | 5.2 ISMRE | AHRI 920 |
| Water source heat pump (dehumidification mode) |
With energy recovery | Ground-water source | 5.8 ISMRE | AHRI 920 |
| Water source heat pump (dehumidification mode) |
With energy recovery | Water source | 4.8 ISMRE | AHRI 920 |
| Air source heat pumps (heating mode) |
With energy recovery | 3.3 ISCOP | AHRI 920 | |
| Water source heat pump (heating mode) |
With energy recovery | Ground source, closed loop | 3.8 ISCOP | AHRI 920 |
| Water source heat pump (heating mode) |
With energy recovery | Ground-water source | 4.0 ISCOP | AHRI 920 |
| Water source heat pump (heating mode) |
With energy recovery | Water source | 4.8 ISCOP | AHRI 920 |
a. Applicable test procedure and reference year are provided under the definitions.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-L¶
FLOOR-MOUNTED AIR CONDITIONERS AND CONDENSING UNITS SERVING
COMPUTER ROOMS—MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | STANDARD MODEL | NET SENSIBLE COOLING CAPACITY |
MINIMUM NET SENSIBLE COP |
RATING CONDITIONS RETURN AIR (dry bulb/ |
TEST PROCEDUREa |
|---|---|---|---|---|---|
| Air cooled | Downflow | < 80,000 Btu/ |
2.70 | 85°F/52°F (Class 2) | AHRI 1360 |
| Air cooled | Downflow | ≥ 80,000 Btu/ < 295,000 Btu/ |
2.58 |
2.58 |
2.58 |
| Air cooled | Downflow | ≥ 295,000 Btu/ |
2.36 | 2.36 | 2.36 |
| Air cooled | Upflow—ducted | < 80,000 Btu/ |
2.67 | 2.67 | 2.67 |
| Air cooled | Upflow—ducted | ≥ 80,000 Btu/ < 295,000 Btu/ |
2.55 |
2.55 |
2.55 |
| Air cooled | Upflow—ducted | ≥ 295,000 Btu/ |
2.33 |
2.33 |
2.33 |
| Air cooled | Upflow—nonducted | < 65,000 Btu/h | 2.16 | 75°F/52°F (Class 1) | 75°F/52°F (Class 1) |
| Air cooled | Upflow—nonducted | ≥ 65,000 Btu/ < 240,000 Btu/ |
2.04 | 2.04 | 2.04 |
| Air cooled | Upflow—nonducted | ≥ 240,000 Btu/ |
1.89 |
1.89 |
1.89 |
| Air cooled | Horizontal | < 65,000 Btu/ |
2.65 | 95°F/52°F (Class 3) | 95°F/52°F (Class 3) |
| Air cooled | Horizontal | ≥ 65,000 Btu/ < 240,000 Btu/ |
2.55 | 2.55 | 2.55 |
| Air cooled | Horizontal | ≥ 240,000 Btu/ |
2.47 |
2.47 |
2.47 |
| Air cooled with fluid economizer |
Downflow | < 80,000 Btu/ |
2.70 | 85°F/52°F (Class 2) | AHRI 1360 |
| Air cooled with fluid economizer |
Downflow | ≥ 80,000 Btu/ < 295,000 Btu/ |
2.58 |
2.58 |
2.58 |
| Air cooled with fluid economizer |
Downflow | ≥ 295,000 Btu/ |
2.36 | 2.36 | 2.36 |
| Air cooled with fluid economizer |
Upflow—ducted | < 80,000 Btu/ |
2.67 | 2.67 | 2.67 |
| Air cooled with fluid economizer |
Upflow—ducted | ≥ 80,000 Btu/ < 295,000 Btu/ |
2.55 |
2.55 |
2.55 |
| Air cooled with fluid economizer |
Upflow—ducted | ≥ 295,000 Btu/ |
2.33 |
2.33 |
2.33 |
| Air cooled with fluid economizer |
Upflow—nonducted | < 65,000 Btu/h | 2.09 | 75°F/52°F (Class 1) | 75°F/52°F (Class 1) |
| Air cooled with fluid economizer |
Upflow—nonducted | ≥ 65,000 Btu/ < 240,000 Btu/ |
1.99 | 1.99 | 1.99 |
| Air cooled with fluid economizer |
Upflow—nonducted | ≥ 240,000 Btu/ |
1.81 |
1.81 |
1.81 |
| Air cooled with fluid economizer |
Horizontal | < 65,000 Btu/ |
2.65 | 95°F/52°F (Class 3) | 95°F/52°F (Class 3) |
| Air cooled with fluid economizer |
Horizontal | ≥ 65,000 Btu/ < 240,000 Btu/ |
2.55 |
2.55 |
2.55 |
| Air cooled with fluid economizer |
Horizontal | ≥ 240,000 Btu/ |
2.47 | 2.47 | 2.47 |
| Water cooled | Downflow | < 80,000 Btu/ |
2.82 | 85°F/52°F (Class 2) | AHRI 1360 |
| Water cooled | Downflow | ≥ 80,000 Btu/ < 295,000 Btu/ |
2.73 |
2.73 |
2.73 |
| Water cooled | Downflow | ≥ 295,000 Btu/ |
2.67 |
2.67 |
2.67 |
| Water cooled | Upflow—ducted | < 80,000 Btu/h | 2.79 | 2.79 | 2.79 |
| Water cooled | Upflow—ducted | ≥ 80,000 Btu/ < 295,000 Btu/ |
2.70 | 2.70 | 2.70 |
| Water cooled | Upflow—ducted | ≥ 295,000 Btu/ |
2.64 |
2.64 |
2.64 |
| Water cooled | Upflow—nonducted | < 65,000 Btu/ |
2.43 | 75°F/52°F (Class 1) | 75°F/52°F (Class 1) |
| Water cooled | Upflow—nonducted | ≥ 65,000 Btu/ < 240,000 Btu/ |
2.32 |
2.32 |
2.32 |
| Water cooled | Upflow—nonducted | ≥ 240,000 Btu/ |
2.20 | 2.20 | 2.20 |
| Water cooled | Horizontal | < 65,000 Btu/ |
2.79 | 95°F/52°F (Class 3) | 95°F/52°F (Class 3) |
| Water cooled | Horizontal | ≥ 65,000 Btu/ < 240,000 Btu/ |
2.68 |
2.68 |
2.68 |
| Water cooled | Horizontal | ≥ 240,000 Btu/ |
2.60 | 2.60 | 2.60 |
(continued)
50 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS,
EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-L—continued FLOOR-MOUNTED AIR CONDITIONERS AND CONDENSING UNITS SERVING
COMPUTER ROOMS—MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | STANDARD MODEL | NET SENSIBLE COOLING CAPACITY |
MINIMUM NET SENSIBLE COP |
RATING CONDITIONS RETURN AIR (dry bulb/ |
TEST PROCEDUREa |
|---|---|---|---|---|---|
| Water cooled with fluid economizer |
Downflow | < 80,000 Btu/h | 2.77 | 85°F/52°F (Class 2) | AHRI 1360 |
| Water cooled with fluid economizer |
Downflow | ≥ 80,000 Btu/ < 295,000 Btu/ |
2.68 | 2.68 | 2.68 |
| Water cooled with fluid economizer |
Downflow | ≥ 295,000 Btu/ |
2.61 |
2.61 |
2.61 |
| Water cooled with fluid economizer |
Upflow—ducted | < 80,000 Btu/h | 2.74 | 2.74 | 2.74 |
| Water cooled with fluid economizer |
Upflow—ducted | ≥ 80,000 Btu/ < 295,000 Btu/ |
2.65 | 2.65 | 2.65 |
| Water cooled with fluid economizer |
Upflow—ducted | ≥ 295,000 Btu/ |
2.58 |
2.58 |
2.58 |
| Water cooled with fluid economizer |
Upflow—nonducted | < 65,000 Btu/ |
2.35 | 75°F/52°F (Class 1) | 75°F/52°F (Class 1) |
| Water cooled with fluid economizer |
Upflow—nonducted | ≥ 65,000 Btu/ < 240,000 Btu/ |
2.24 |
2.24 |
2.24 |
| Water cooled with fluid economizer |
Upflow—nonducted | ≥ 240,000 Btu/ |
2.12 | 2.12 | 2.12 |
| Water cooled with fluid economizer |
Horizontal | < 65,000 Btu/ |
2.71 | 95°F/52°F (Class 3) | 95°F/52°F (Class 3) |
| Water cooled with fluid economizer |
Horizontal | ≥ 65,000 Btu/ < 240,000 Btu/ |
2.60 |
2.60 |
2.60 |
| Water cooled with fluid economizer |
Horizontal | ≥ 240,000 Btu/ |
2.54 |
2.54 |
2.54 |
| Glycol cooled | Downflow | < 80,000 Btu/h | 2.56 | 85°F/52°F (Class 2) | AHRI 1360 |
| Glycol cooled | Downflow | ≥ 80,000 Btu/ < 295,000 Btu/ |
2.24 | 2.24 | 2.24 |
| Glycol cooled | Downflow | ≥ 295,000 Btu/ |
2.21 |
2.21 |
2.21 |
| Glycol cooled | Upflow—ducted | < 80,000 Btu/ |
2.53 | 2.53 | 2.53 |
| Glycol cooled | Upflow—ducted | ≥ 80,000 Btu/ < 295,000 Btu/ |
2.21 |
2.21 |
2.21 |
| Glycol cooled | Upflow—ducted | ≥ 295,000 Btu/ |
2.18 | 2.18 | 2.18 |
| Glycol cooled | Upflow—nonducted | < 65,000 Btu/ |
2.08 | 75°F/52°F (Class 1) | 75°F/52°F (Class 1) |
| Glycol cooled | Upflow—nonducted | ≥ 65,000 Btu/ < 240,000 Btu/ |
1.90 |
1.90 |
1.90 |
| Glycol cooled | Upflow—nonducted | ≥ 240,000 Btu/ |
1.81 |
1.81 |
1.81 |
| Glycol cooled with fluid economizer |
Horizontal | < 65,000 Btu/h | 2.48 | 95°F/52°F (Class 3) | AHRI 1360 |
| Glycol cooled with fluid economizer |
Horizontal | ≥ 65,000 Btu/ < 240,000 Btu/ |
2.18 | 2.18 | 2.18 |
| Glycol cooled with fluid economizer |
Horizontal | ≥ 240,000 Btu/ |
2.18 |
2.18 |
2.18 |
| Glycol cooled with fluid economizer |
Downflow | < 80,000 Btu/ |
2.51 | 85°F/52°F (Class 2) | 85°F/52°F (Class 2) |
| Glycol cooled with fluid economizer |
Downflow | ≥ 80,000 Btu/ < 295,000 Btu/ |
2.19 |
2.19 |
2.19 |
| Glycol cooled with fluid economizer |
Downflow | ≥ 295,000 Btu/ |
2.15 | 2.15 | 2.15 |
| Glycol cooled with fluid economizer |
Upflow—ducted | < 80,000 Btu/ |
2.48 | 2.48 | 2.48 |
| Glycol cooled with fluid economizer |
Upflow—ducted | ≥ 80,000 Btu/ < 295,000 Btu/ |
2.16 |
2.16 |
2.16 |
| Glycol cooled with fluid economizer |
Upflow—ducted | ≥ 295,000 Btu/ |
2.12 |
2.12 |
2.12 |
| Glycol cooled with fluid economizer |
Upflow—nonducted | < 65,000 Btu/h | 2.00 | 75°F/52°F (Class 1) | 75°F/52°F (Class 1) |
| Glycol cooled with fluid economizer |
Upflow—nonducted | ≥ 65,000 Btu/ < 240,000 Btu/ |
1.82 | 1.82 | 1.82 |
| Glycol cooled with fluid economizer |
Upflow—nonducted | ≥ 240,000 Btu/ |
1.73 |
1.73 |
1.73 |
| Glycol cooled with fluid economizer |
Horizontal | < 65,000 Btu/h | 2.44 | 95°F/52°F (Class 3) | 95°F/52°F (Class 3) |
| Glycol cooled with fluid economizer |
Horizontal | ≥ 65,000 Btu/ < 240,000 Btu/ |
2.10 | 2.10 | 2.10 |
| Glycol cooled with fluid economizer |
Horizontal | ≥ 240,000 Btu/ |
2.10 | 2.10 | 2.10 |
For SI: 1 British thermal unit per hour = 0.2931 W, °C = [(°F) – 32]/1.8, COP = (Btu/h × hp)/(2,550.7). a. Applicable test procedure and reference year are provided under the definitions.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-M¶
CEILING-MOUNTED AIR CONDITIONERS AND CONDENSING UNITS SERVING COMPUTER ROOMS—MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | STANDARD MODEL | NET SENSIBLE COOLING CAPACITY |
MINIMUM NET SENSIBLE COP |
RATING CONDITIONS RETURN AIR (dry bulb/ |
TEST PROCEDUREa |
|---|---|---|---|---|---|
| Air cooled with free air discharge condenser |
Ducted | < 29,000 Btu/h | 2.05 | 75°F/52°F (Class 1) | AHRI 1360 |
| Air cooled with free air discharge condenser |
Ducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
2.02 | 2.02 | 2.02 |
| Air cooled with free air discharge condenser |
Ducted | ≥ 65,000 Btu/h | 1.92 | 1.92 | 1.92 |
| Air cooled with free air discharge condenser |
Nonducted | < 29,000 Btu/h | 2.08 | 2.08 | 2.08 |
| Air cooled with free air discharge condenser |
Nonducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
2.05 | 2.05 | 2.05 |
| Air cooled with free air discharge condenser |
Nonducted | ≥ 65,000 Btu/h | 1.94 | 1.94 | 1.94 |
| Air cooled with free air discharge condenser with fluid economizer |
Ducted | < 29,000 Btu/h | 2.01 | 75°F/52°F (Class 1) | AHRI 1360 |
| Air cooled with free air discharge condenser with fluid economizer |
Ducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
1.97 | 1.97 | 1.97 |
| Air cooled with free air discharge condenser with fluid economizer |
Ducted | ≥ 65,000 Btu/h | 1.87 | 1.87 | 1.87 |
| Air cooled with free air discharge condenser with fluid economizer |
Nonducted | < 29,000 Btu/h | 2.04 | 2.04 | 2.04 |
| Air cooled with free air discharge condenser with fluid economizer |
Nonducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
2.00 | 2.00 | 2.00 |
| Air cooled with free air discharge condenser with fluid economizer |
Nonducted | ≥ 65,000 Btu/h | 1.89 | 1.89 | 1.89 |
| Air cooled with ducted condenser |
Ducted | < 29,000 Btu/h | 1.86 | 75°F/52°F (Class 1) | AHRI 1360 |
| Air cooled with ducted condenser |
Ducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
1.83 | 1.83 | 1.83 |
| Air cooled with ducted condenser |
Ducted | ≥ 65,000 Btu/h | 1.73 | 1.73 | 1.73 |
| Air cooled with ducted condenser |
Nonducted | < 29,000 Btu/h | 1.89 | 1.89 | 1.89 |
| Air cooled with ducted condenser |
Nonducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
1.86 | 1.86 | 1.86 |
| Air cooled with ducted condenser |
Nonducted | ≥ 65,000 Btu/h | 1.75 | 1.75 | 1.75 |
| Air cooled with fluid economizer and ducted condenser |
Ducted | < 29,000 Btu/h | 1.82 | 75°F/52°F (Class 1) | AHRI 1360 |
| Air cooled with fluid economizer and ducted condenser |
Ducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
1.78 | 1.78 | 1.78 |
| Air cooled with fluid economizer and ducted condenser |
Ducted | ≥ 65,000 Btu/h | 1.68 | 1.68 | 1.68 |
| Air cooled with fluid economizer and ducted condenser |
Nonducted | < 29,000 Btu/h | 1.85 | 1.85 | 1.85 |
| Air cooled with fluid economizer and ducted condenser |
Nonducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
1.81 | 1.81 | 1.81 |
| Air cooled with fluid economizer and ducted condenser |
Nonducted | ≥ 65,000 Btu/h | 1.70 | 1.70 | 1.70 |
| Water cooled | Ducted | < 29,000 Btu/h | 2.38 | 75°F/52°F (Class 1) | AHRI 1360 |
| Water cooled | Ducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
2.38 | 2.38 | 2.38 |
| Water cooled | Ducted | ≥ 65,000 Btu/h | 2.18 | 2.18 | 2.18 |
| Water cooled | Nonducted | < 29,000 Btu/h | 2.41 | 2.41 | 2.41 |
| Water cooled | Nonducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
2.31 | 2.31 | 2.31 |
| Water cooled | Nonducted | ≥ 65,000 Btu/h | 2.20 | 2.20 | 2.20 |
(continued)
52 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS,
EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-M—continued CEILING-MOUNTED AIR CONDITIONERS AND CONDENSING UNITS SERVING COMPUTER ROOMS—MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | STANDARD MODEL | NET SENSIBLE COOLING CAPACITY |
MINIMUM NET SENSIBLE COP |
RATING CONDITIONS RETURN AIR (dry bulb/ |
TEST PROCEDUREa |
|---|---|---|---|---|---|
| Water cooled with fluid economizer |
Ducted | < 29,000 Btu/h | 2.33 | 75°F/52°F (Class 1) | AHRI 1360 |
| Water cooled with fluid economizer |
Ducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
2.23 | 2.23 | 2.23 |
| Water cooled with fluid economizer |
Ducted | ≥ 65,000 Btu/h | 2.13 | 2.13 | 2.13 |
| Water cooled with fluid economizer |
Nonducted | < 29,000 Btu/h | 2.36 | 2.36 | 2.36 |
| Water cooled with fluid economizer |
Nonducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
2.26 | 2.26 | 2.26 |
| Water cooled with fluid economizer |
Nonducted | ≥ 65,000 Btu/h | 2.16 | 2.16 | 2.16 |
| Glycol cooled | Ducted | < 29,000 Btu/h | 1.97 | 75°F/52°F (Class 1) | AHRI 1360 |
| Glycol cooled | Ducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
1.93 | 1.93 | 1.93 |
| Glycol cooled | Ducted | ≥ 65,000 Btu/h | 1.78 | 1.78 | 1.78 |
| Glycol cooled | Nonducted | < 29,000 Btu/h | 2.00 | 2.00 | 2.00 |
| Glycol cooled | Nonducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
1.98 | 1.98 | 1.98 |
| Glycol cooled | Nonducted | ≥ 65,000 Btu/h | 1.81 | 1.81 | 1.81 |
| Glycol cooled with fluid economizer |
Ducted | < 29,000 Btu/h | 1.92 | 75°F/52°F (Class 1) | AHRI 1360 |
| Glycol cooled with fluid economizer |
Ducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
1.88 | 1.88 | 1.88 |
| Glycol cooled with fluid economizer |
Ducted | ≥ 65,000 Btu/h | 1.73 | 1.73 | 1.73 |
| Glycol cooled with fluid economizer |
Nonducted | < 29,000 Btu/h | 1.95 | 1.95 | 1.95 |
| Glycol cooled with fluid economizer |
Nonducted | ≥ 29,000 Btu/ < 65,000 Btu/ |
1.93 | 1.93 | 1.93 |
| Glycol cooled with fluid economizer |
Nonducted | ≥ 65,000 Btu/h | 1.76 | 1.76 | 1.76 |
For SI: 1 British thermal unit per hour = 0.2931 W, °C = [(°F) – 32]/1.8, COP = (Btu/h × hp)/(2,550.7). a. Applicable test procedure and reference year are provided under the definitions.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
| HEATING OPERATION | Test Procedure | AHRI 550/ 590 | AHRI 550/ 590 | AHRI 550/ 590 | ||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| HEATING OPERATION | HEAT RECOVERY CHILLER FULL-LOAD EFFICIENCY (COPHR)b, c SIMULTANEOUS COOLING AND HEATING FULL-LOAD EFFICIENCY (COPSHC)b |
Leaving Heating Water Temperature | Boost | 140°F | NA | NA | NA | ≥ 6.150 | NA | ≥ 6.150 | NA | ≥ 6.150 | NA | ≥ 6.850 | NA | ≥ 6.850 | NA | ≥ 6.150 | NA | ≥ 6.150 | NA | ≥ 6.150 | NA | ≥ 6.850 | NA | ≥ 6.850 |
| HEATING OPERATION | HEAT RECOVERY CHILLER FULL-LOAD EFFICIENCY (COPHR)b, c SIMULTANEOUS COOLING AND HEATING FULL-LOAD EFFICIENCY (COPSHC)b |
Leaving Heating Water Temperature | High | 140°F | NA | NA | ≥ 4.420 | NA | ≥ 4.420 | NA | ≥ 4.420 | NA | ≥ 5.000 | NA | ≥ 5.000 | NA | ≥ 4.420 | NA | ≥ 4.420 | NA | ≥ 4.420 | NA | ≥ 5.000 | NA | ≥ 5.000 | NA |
| HEATING OPERATION | HEAT RECOVERY CHILLER FULL-LOAD EFFICIENCY (COPHR)b, c SIMULTANEOUS COOLING AND HEATING FULL-LOAD EFFICIENCY (COPSHC)b |
Leaving Heating Water Temperature | Medium | 120°F | NA | NA | ≥ 6.410 | NA | ≥ 6.410 | NA | ≥ 6.410 | NA | ≥ 6.980 | NA | ≥ 6.980 | NA | ≥ 6.410 | NA | ≥ 6.410 | NA | ≥ 6.410 | NA | ≥ 6.980 | NA | ≥ 6.980 | NA |
| HEATING OPERATION | HEAT RECOVERY CHILLER FULL-LOAD EFFICIENCY (COPHR)b, c SIMULTANEOUS COOLING AND HEATING FULL-LOAD EFFICIENCY (COPSHC)b |
Leaving Heating Water Temperature | Low | 105°F | NA | NA | ≥ 8.330 | NA | ≥ 8.330 | NA | ≥ 8.330 | NA | ≥ 8.900 | NA | ≥ 8.900 | NA | ≥ 8.330 | NA | ≥ 8.330 | NA | ≥ 8.330 | NA | ≥ 8.900 | NA | ≥ 8.900 | NA |
| HEATING OPERATION | HEAT-PUMP HEATING FULL-LOAD EFFICIENCY (COPH)b |
Leaving Heating Water Temperature | Boost | 140°F | NA | NA | NA | ≥ 3.550 | NA | ≥ 3.550 | NA | ≥ 3.550 | NA | ≥ 3.900 | NA | ≥ 3.900 | NA | ≥ 3.550 | NA | ≥ 3.550 | NA | ≥ 3.550 | NA | ≥ 3.900 | NA | ≥ 3.900 |
| HEATING OPERATION | HEAT-PUMP HEATING FULL-LOAD EFFICIENCY (COPH)b |
Leaving Heating Water Temperature | High | 140°F | ≥ 2.310 | ≥ 1.630 | ≥ 2.680 | NA | ≥ 2.680 | NA | ≥ 2.680 | NA | ≥ 2.970 | NA | ≥ 2.970 | NA | ≥ 2.680 | NA | ≥ 2.680 | NA | ≥ 2.680 | NA | ≥ 2.970 | NA | ≥ 2.970 | NA |
| HEATING OPERATION | HEAT-PUMP HEATING FULL-LOAD EFFICIENCY (COPH)b |
Leaving Heating Water Temperature | Medium | 120°F | ≥ 2.770 | ≥ 1.950 | ≥ 3.680 | NA | ≥ 3.680 | NA | ≥ 3.680 | NA | ≥ 3.960 | NA | ≥ 3.960 | NA | ≥ 3.680 | NA | ≥ 3.680 | NA | ≥ 3.680 | NA | ≥ 3.960 | NA | ≥ 3.960 | NA |
| HEATING OPERATION | HEAT-PUMP HEATING FULL-LOAD EFFICIENCY (COPH)b |
Leaving Heating Water Temperature | Low | 105°F | ≥ 3.290 | ≥ 2.230 | ≥ 4.640 | NA | ≥ 4.640 | NA | ≥ 4.640 | NA | ≥ 4.930 | NA | ≥ 4.930 | NA | ≥ 4.640 | NA | ≥ 4.640 | NA | ≥ 4.640 | NA | ≥ 4.930 | NA | ≥ 4.930 | NA |
| HEATING OPERATION | HEATING SOURCE CONDITIONSd, e |
HEATING SOURCE CONDITIONSd, e |
HEATING SOURCE CONDITIONSd, e |
HEATING SOURCE CONDITIONSd, e |
47 db 43 wbe |
17 db 15 wbe |
54/44f | 75/65f | 54/44f | 75/65f | 54/44f | 75/65f | 54/44f | 75/65f | 54/44f | 75/65f | 54/44f | 75/65f | 54/44f | 75/65f | 54/44f | 75/65f | 54/44f | 75/65f | 54/44f | 75/65f |
| COOLING-ONLY OPERATION COOLING EFFICIENCYa FULL LOAD EFFICIENCY (EER OR kW/ IPLV (EER OR kW/ |
COOLING-ONLY OPERATION COOLING EFFICIENCYa FULL LOAD EFFICIENCY (EER OR kW/ IPLV (EER OR kW/ |
COOLING-ONLY OPERATION COOLING EFFICIENCYa FULL LOAD EFFICIENCY (EER OR kW/ IPLV (EER OR kW/ |
COOLING-ONLY OPERATION COOLING EFFICIENCYa FULL LOAD EFFICIENCY (EER OR kW/ IPLV (EER OR kW/ |
Path B | ≥ 9.215 EER ≥ 15.01 IPLV |
≥ 9.215 EER ≥ 15.30 IPLV |
≤ 0.7875 kW/ ≤ 0.5145 IPLV |
≤ 0.7875 kW/ ≤ 0.5145 IPLV |
≤ 0.7140 kW/ ≤ 0.4620 IPLV |
≤ 0.7140 kW/ ≤ 0.4620 IPLV |
≤ 0.7140 kW/ ≤ 0.4620 IPLV |
≤ 0.7140 kW/ ≤ 0.4620 IPLV |
≤ 0.6563 kW/ ≤ 0.4305 IPLV |
≤ 0.6563 kW/ ≤ 0.4305 IPLV |
≤ 0.6143 kW/ ≤ 0.3990 IPLV |
≤ 0.6143 kW/ ≤ 0.3990 IPLV |
≤ 0.7316 kW/ ≤ 0.4632 IPLV |
≤ 0.7316 kW/ ≤ 0.4632 IPLV |
≤ 0.6684 kW/ ≤ 0.4211 IPLV |
≤ 0.6684 kW/ ≤ 0.4211 IPLV |
≤ 0.6263 kW/ ≤ 0.4105 IPLV |
≤ 0.6263 kW/ ≤ 0.4105 IPLV |
≤ 0.6158 kW/ ≤ 0.4000 IPLV |
≤ 0.6158 kW/ ≤ 0.4000 IPLV |
≤ 0.6158 kW/ ≤ 0.4000 IPLV |
≤ 0.6158 kW/ ≤ 0.4000 IPLV |
| COOLING-ONLY OPERATION COOLING EFFICIENCYa FULL LOAD EFFICIENCY (EER OR kW/ IPLV (EER OR kW/ |
COOLING-ONLY OPERATION COOLING EFFICIENCYa FULL LOAD EFFICIENCY (EER OR kW/ IPLV (EER OR kW/ |
COOLING-ONLY OPERATION COOLING EFFICIENCYa FULL LOAD EFFICIENCY (EER OR kW/ IPLV (EER OR kW/ |
COOLING-ONLY OPERATION COOLING EFFICIENCYa FULL LOAD EFFICIENCY (EER OR kW/ IPLV (EER OR kW/ |
Path A | ≥ 9.595 EER ≥ 13.02 IPLV |
≥ 9.595 EER ≥ 13.30 IPLV |
≤ 0.7885 kW/ ≤ 0.6316 IPLV |
≤ 0.7885 kW/ ≤ 0.6316 IPLV |
≤ 0.7579 kW/ ≤ 0.5895 IPLV |
≤ 0.7579 kW/ ≤ 0.5895 IPLV |
≤ 0.6947 kW/ ≤ 0.5684 IPLV |
≤ 0.6947 kW/ ≤ 0.5684 IPLV |
≤ 0.6421 kW/ ≤ 0.5474 IPLV |
≤ 0.6421 kW/ ≤ 0.5474 IPLV |
≤ 0.5895 kW/ ≤ 0.5263 IPLV |
≤ 0.5895 kW/ ≤ 0.5263 IPLV |
≤ 0.6421 kW/ ≤ 0.5789 IPLV |
≤ 0.6421 kW/ ≤ 0.5789 IPLV |
≤ 0.5895 kW/ ≤ 0.5474 IPLV |
≤ 0.5895 kW/ ≤ 0.5474 IPLV |
≤ 0.5895 kW/ ≤ 0.5263 IPLV |
≤ 0.5895 kW/ ≤ 0.5263 IPLV |
≤ 0.5895 kW/ ≤ 0.5263 IPLV |
≤ 0.5895 kW/ ≤ 0.5263 IPLV |
≤ 0.5895 kW/ ≤ 0.5263 IPLV |
≤ 0.5895 kW/ ≤ 0.5263 IPLV |
| SIZE CATEGORY, tons |
SIZE CATEGORY, tons |
SIZE CATEGORY, tons |
SIZE CATEGORY, tons |
SIZE CATEGORY, tons |
All sizes | All sizes | < 75 | < 75 | ≥ 75 and < 150 |
≥ 75 and < 150 |
≥ 150 and < 300 |
≥ 150 and < 300 |
≥ 300 and < 600 |
≥ 300 and < 600 |
≥ 600 | ≥ 600 | < 75 | < 75 | ≥ 75 and < 150 |
≥ 75 and < 150 |
≥ 150 and < 300 |
≥ 150 and < 300 |
≥ 300 and < 600 |
≥ 300 and < 600 |
≥ 600 | ≥ 600 |
| EQUIPMENT TYPE | EQUIPMENT TYPE | EQUIPMENT TYPE | EQUIPMENT TYPE | EQUIPMENT TYPE | Air source | Air source | Water-source electrically operated positive displacement |
Water-source electrically operated positive displacement |
Water-source electrically operated positive displacement |
Water-source electrically operated positive displacement |
Water-source electrically operated positive displacement |
Water-source electrically operated positive displacement |
Water-source electrically operated positive displacement |
Water-source electrically operated positive displacement |
Water-source electrically operated positive displacement |
Water-source electrically operated positive displacement |
Water-source electrically operated centrifugal |
Water-source electrically operated centrifugal |
Water-source electrically operated centrifugal |
Water-source electrically operated centrifugal |
Water-source electrically operated centrifugal |
Water-source electrically operated centrifugal |
Water-source electrically operated centrifugal |
Water-source electrically operated centrifugal |
Water-source electrically operated centrifugal |
Water-source electrically operated centrifugal |
54 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS,
EQUIPMENT AND BUILDING COMPONENTS