PRESCRIPTIVE REQUIREMENTS FOR SERVICE WATER-HEATING SYSTEMS (a) Nonresidential occupancies. Service water-heating systems in nonresidential buildings shall meet the requirements of 1 or 2 below, or meet the performance compliance requirements of Section 140.1:
- School buildings less than 25,000 square feet and less than 4 stories in Climate Zones 2 through 15. A
heat pump water-heating system that meets the applicable requirements of Sections 110.1, 110.3 and 120.3.
- All other occupancies. A service water-heating system that meets the applicable requirements of Sections 110.1, 110.3, 120.3 and 140.5(c).
Exception to Section 140.5(a)1: A water-heating system serving an individual bathroom space may be an instantaneous electric water heater. (b) Hotel/motel occupancies. A service water-heating system installed in hotel/motel buildings shall meet the requirements of Section 170.2(d).
(c) High-capacity service water-heating systems . Gas service water-heating systems with a total installed gas waterheating input capacity of 1 MMBtu/h or greater shall have gas service water-heating equipment with a minimum thermal efficiency of 90 percent. Multiple units can meet this requirement if the water-heating input provided by equipment with thermal efficiencies above and below 90 percent aver
TABLE 140.4-J: ENERGY RECOVERY REQUIREMENTS BY CLIMATE ZONE AND PERCENT
OUTDOOR AIR AT FULL DESIGN AIRFLOW (<8,000 HOURS/YEAR)
| % OUTDOOR AIR AT FULL DESIGN AIRFLOW |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ≥10% and <20% | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
| ≥20% and <30% | ≥15,000 | ≥20,000 | NR | NR | NR | NR | NR | NR | NR | NR | ≥18,500 | ≥18,500 | ≥18,500 | ≥18,500 | ≥18,500 | ≥18,500 |
| ≥30% and <40% | ≥13,000 | ≥15,000 | NR | NR | NR | NR | NR | NR | NR | NR | ≥15,000 | ≥15,000 | ≥15,000 | ≥15,000 | ≥15,000 | ≥15,000 |
| ≥40% and <50% | ≥10,000 | ≥12,000 | NR | NR | NR | NR | NR | NR | NR | ≥22,000 | ≥10,000 | ≥10,000 | ≥10,000 | ≥10,000 | ≥10,000 | ≥10,000 |
| ≥50% and <60% | ≥9,000 | ≥10,000 | NR | ≥18,500 | NR | NR | NR | NR | NR | ≥17,000 | ≥8,000 | ≥8,000 | ≥8,000 | ≥8,000 | ≥8,000 | ≥8,000 |
| ≥60% and <70% | ≥7,000 | ≥7,500 | NR | ≥16,500 | NR | NR | NR | NR | ≥20,000 | ≥15,000 | ≥7,000 | ≥7,000 | ≥7,000 | ≥7,000 | ≥7,000 | ≥7,000 |
| ≥70% and <80% | ≥6,500 | ≥7,000 | NR | ≥15,000 | NR | NR | NR | NR | ≥17,000 | ≥14,000 | ≥5,000 | ≥5,000 | ≥5,000 | ≥5,000 | ≥5,000 | ≥5,000 |
| ≥80% | ≥4,500 | ≥6,500 | NR | ≥14,000 | NR | NR | NR | NR | ≥15,000 | ≥13,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
- Flow rates in Table 140.4-J represent the design supply fan airflow rate in cfm.
- For a DOAS unit providing outdoor air to another space-conditioning system, the full design supply fan airflow rate shall be the total airflow of only the DOAS unit.
TABLE 140.4-K: ENERGY RECOVERY REQUIREMENTS BY CLIMATE ZONE AND PERCENT
OUTDOOR AIR AT FULL DESIGN AIRFLOW (≥8,000 HOURS/YEAR)
| % OUTDOOR AIR AT FULL DESIGN AIRFLOW |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ≥10% and <20% | ≥10,000 | ≥10,000 | NR | NR | NR | NR | NR | NR | NR | ≥40,000 | ≥40,000 | ≥20,000 | ≥10,000 | ≥10,000 | ≥10,000 | ≥10,000 |
| ≥20% and <30% | ≥2,000 | ≥5,000 | ≥13,000 | ≥9,000 | ≥9,000 | NR | NR | NR | NR | ≥15,000 | ≥15,000 | ≥5,000 | ≥5,000 | ≥5,000 | ≥5,000 | ≥5,000 |
| ≥30% and <40% | ≥2,000 | ≥3,000 | ≥10,000 | ≥6,500 | ≥6,500 | NR | NR | NR | ≥15,000 | ≥7,500 | ≥7,500 | ≥3,000 | ≥3,000 | ≥3,000 | ≥3,000 | ≥3,000 |
| ≥40% and <50% | ≥2,000 | ≥2,000 | ≥8,000 | ≥6,000 | ≥6,000 | NR | NR | NR | ≥12,000 | ≥6,000 | ≥6,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
| ≥50% and <60% | ≥2,000 | ≥2,000 | ≥7,000 | ≥6,000 | ≥6,000 | NR | NR | ≥20,000 | ≥10,000 | ≥5,000 | ≥5,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
| ≥60% and <70% | ≥2,000 | ≥2,000 | ≥6,000 | ≥6,000 | ≥6,000 | NR | NR | ≥18,000 | ≥9,000 | ≥4,000 | ≥4,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
| ≥70% and <80% | ≥2,000 | ≥2,000 | ≥6,000 | ≥5,000 | ≥5,000 | NR | NR | ≥15,000 | ≥8,000 | ≥3,000 | ≥3,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
| ≥80% | ≥2,000 | ≥2,000 | ≥6,000 | ≥5,000 | ≥5,000 | NR | NR | ≥12,000 | ≥7,000 | ≥3,000 | ≥3,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
- Flow rates in Table 140.4-K represent the design supply fan airflow rate in cfm.
- For a DOAS unit providing outdoor air to another space-conditioning system, the full design supply fan airflow rate shall be the total airflow of only the DOAS unit.
128 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES FOR
ACHIEVING ENERGY EFFICIENCY
C. The two lighting systems are interlocked with a
nonprogrammable double-throw switch to prevent simultaneous operation of both systems.
For compliance with Part 6 a nonprogrammable double-throw switch is an electrical switch commonly called a “single pole double throw” or “three-way” switch that is wired as a selector switch allowing one of two loads to be enabled. It can be a line voltage switch or a low voltage switch selecting between two relays. It cannot be overridden or changed in any manner that would permit both loads to operate simultaneously. 2. Reduction of wattage through controls. In calculating adjusted indoor lighting power, the installed watts of a luminaire providing general lighting in an area listed in Table 140.6-A may be reduced by the product of (i) the number of watts controlled as described in Table 140.6-A, times (ii) the applicable power adjustment factor (PAF), if all of the following conditions are met:
A. An installation certificate is submitted in accor dance with Section 130.4(b), and
B. Luminaires and controls meet the applicable
requirements of Section 110.9, and Sections 130.0 through 130.5; and
C. The controlled lighting is permanently installed
general lighting systems and the controls are permanently installed nonresidential-rated lighting controls.
When used for determining PAFs for general lighting in offices, furniture mounted luminaires that comply with all of the following conditions shall qualify as permanently installed general lighting systems:
i. The furniture mounted luminaires shall be
permanently installed no later than the time of building permit inspection; and
ii. The furniture mounted luminaires shall be
permanently hardwired; and
iii. The furniture mounted lighting system
shall be designed to provide indirect general lighting; and
iv. Before multiplying the installed watts of
the furniture mounted luminaire by the applicable PAF, 0.2 watts per square foot of the area illuminated by the furniture mounted luminaires shall be subtracted from installed watts of the furniture mounted luminaires; and
v. The lighting control for the furniture
mounted luminaire complies with all other applicable requirements in Section 140.6(a)2.
D. At least 50 percent of the light output of the con trolled luminaire is within the applicable area listed in Table 140.6-A. Luminaires on lighting
ages out to an input capacity-weighted average of at least 90 percent.
Exception 1 to Section 140.5(c): If 25 percent of the annual service water-heating requirement is provided by site-solar energy or site-recovered energy.
Exception 2 to Section 140.5(c): Water heaters installed in individual dwelling units.
Exception 3 to Section 140.5(c): Individual gas water heaters with input capacity at or below 100,000 Btu/h shall not be included in the calculations of the total system input or total system efficiency.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.