Section 130.5
California Energy Code (Title 24, Part 6) · 2022 edition · updated 2026-09-12 · California
ELECTRICAL POWER DISTRIBUTION SYSTEMS
Nonresidential and hotel/motel buildings shall comply with the applicable requirements of Sections 130.5(a) through 130.5(e).
(a) Service electrical metering. Each electrical service or feeder shall have a permanently installed metering system
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS
- For hotel and motel guest rooms, install controlled receptacles for at least one-half of the 120-volt receptacles in each guestroom. Electric circuits serving controlled receptacles in guestrooms shall have captive card key controls, occupant sensing controls, or automatic controls so the power is switched OFF no longer than 30 minutes after the guestroom has been vacated. NOTE: A hardwired power strip controlled by an occupant sensing control may be used to comply with Section 130.5(d). Plug-in strips and other plug-in devices shall not be used to comply with the requirements of Section 130.5(d).
Exception 1 to Section 130.5(d): Receptacles that are only for the following purposes:
i. Receptacles specifically for refrigerators and
water dispensers in kitchen area.
ii. Receptacles located a minimum of six feet above
the floor that are specifically for clocks.
iii.Receptacles for network copiers, fax machines,
A/V and data equipment other than personal computers in copy rooms.
iv. Receptacles on circuits rated more than 20
amperes.
TABLE 130.5-A MINIMUM REQUIREMENTS FOR METERING OF ELECTRICAL LOAD
| METERING FUNCTIONALITY | ELECTRICAL SERVICES RATED 50 kVA OR LESS |
ELECTRICAL SERVICES RATED MORE THAN 50 kVA AND LESS THAN OR EQUAL TO 250 kVA |
ELECTRICAL SERVICES RATED MORE THAN 250 kVA AND LESS THAN OR EQUAL TO 1000 kVA |
ELECTRICAL SERVICES RATED MORE THAN 1000 kVA |
|---|---|---|---|---|
| Instantaneous (at the time) kW demand |
Required | Required | Required | Required |
| Historical peak demand (kW) | Not required | Not required | Required | Required |
| Tracking kWh for a user- definable period |
Required | Required | Required | Required |
| kWh per rate period | Not required | Not required | Not required | Required |
TABLE 130.5-B MINIMUM REQUIREMENTS FOR SEPARATION OF ELECTRICAL LOAD
| ELECTRICAL LOAD TYPE | ELECTRICAL SERVICES RATED 50 kVA OR LESS |
ELECTRICAL SERVICES RATED MORE THAN 50 kVA AND LESS THAN OR EQUAL TO 250 kVA |
ELECTRICAL SERVICES RATED MORE THAN 250 kVA AND LESS THAN OR EQUAL TO 1000 kVA |
ELECTRICAL SERVICES RATED MORE THAN 1000 kVA |
|---|---|---|---|---|
| Lighting including exit and egress lighting and exterior lighting |
Not required | All lighting in aggregate | All lighting disaggregated by floor, type or area |
All lighting disaggregated by floor, type or area |
| HVAC systems and components including chillers, fans, heaters, furnaces, package units, cooling towers and circulation pumps associated with HVAC |
Not required | All HVAC in aggregate | All HVAC in aggregate and each HVAC load rated at least 50 kVA |
All HVAC in aggregate and each HVAC load rated at least 50 kVA |
| Domestic and service water system pumps and related systems and components |
Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Plug load including appliances rated less than 25 kVA |
Not required | All plug load in aggregate Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf |
All plug load separated by floor, type or area Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf |
All plug load separated by floor, type or area All groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf |
| Elevators, escalators, moving walks and transit systems |
Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Other individual non-HVAC loads or appliances rated 25 kVA or greater |
Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Industrial and commercial load centers 25 kVA or greater, including theatrical lighting installations and commercial kitchens |
Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Renewable power source (net or total) | Each group | Each group | Each group | Each group |
| Loads associated with renewable power source |
Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Charging stations for electric vehicles | All loads in aggregate |
All loads in aggregate | All loads in aggregate | All loads in aggregate |
104 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS
v. Receptacles connected to an uninterruptible
power supply (UPS) that are intended to be in continuous use, 24 hours per day/365 days per year, and are marked to differentiate them from other uncontrolled receptacles or circuits.
Exception 2 to Section 130.5(d): Receptacles in healthcare facilities. (e) Demand responsive controls and equipment. See Section 110.12 for requirements for demand responsive controls and equipment, including demand responsive controls for controlled receptacles.
NOTE: Definitions of terms and phrases in Section 130.5 are determined as specified in Section 100.1(b). Terms and phrases not found in Section 100.1(b) shall be defined as specified in Title 24, Part 3, Article 100 of the California Electrical Code.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
106 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
SUBCHAPTER 5
NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—
PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY
space-conditioning, indoor lighting, mechanical ventilation, photovoltaic (PV) and battery storage systems, and service water heating and covered process loads.
Exception to Section 140.1(b). A community shared solar electric generation system, or other renewable electric generation system, and/or community shared battery storage system, that provides dedicated power, utility energy reduction credits or payments for energy bill reductions to the permitted building and is approved by the Energy Commission as specified in Title 24, Part 1, Section 10115, may offset part or all of the solar electric generation system or battery storage system TDV energy required to comply with the standards, as calculated according to methods established by the Commission in the Nonresidential ACM Reference Manual.
(c) Calculation of energy budget. The TDV energy for both the standard design building and the proposed design building shall be computed by compliance software certified for this use by the Commission. The processes for compliance software approval by the Commission are documented in the ACM Approval Manual.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.