Section 100.0
California Energy Code (Title 24, Part 6) · 2022 edition · updated 2026-09-12 · California
SCOPE (a) Buildings covered. The provisions of Part 6 apply to all buildings:
- That are of Occupancy Group A, B, E, F, H, I, M, R, S or U; and
- For which an application for a building permit or renewal of an existing permit is filed (or is required by law to be filed) on or after the effective date of the provisions, or which are constructed by a governmental agency; and
- That are: A. Unconditioned; or B. Indirectly or directly conditioned, or process spaces.
Exception 1 to Section 100.0(a): Qualified historic buildings as regulated by the California His- toric Building Code (Title 24, Part 8). Lighting in qualified historic buildings shall comply with the applicable requirements in Section 140.6(a)3Q. Exception 2 to Section 100.0(a): Building departments, at their discretion, may exempt temporary buildings, temporary outdoor lighting or temporary lighting in an unconditioned building, or structures erected in response to a natural disaster. Temporary buildings or structures shall be completely removed upon the expiration of the time limit stated in the permit. Exception 3 to Section 100.0(a): Buildings in Occupancy Group I-3 and I-4. (b) Parts of buildings regulated. The provisions of Part 6 apply to the building envelope, space-conditioning systems, water-heating systems, pool and spas, solar ready buildings, indoor lighting systems of buildings, outdoor lighting systems, electrical power distribution systems, and signs located either indoors or outdoors, in buildings that are:
Covered by Section 100.0(a); and
Set forth in Table 100.0-A. (c) Habitable stories.
All conditioned space in a story shall comply with Part 6, whether or not the story is a habitable space.
All unconditioned space in a story shall comply with the lighting requirements of Part 6, whether or not the story is a habitable space. (d) Outdoor lighting and indoor and outdoor signs. The provisions of Part 6 apply to outdoor lighting systems and to signs located either indoors or outdoors as set forth in Table 100.0-A. (e) Sections applicable to particular buildings. Table 100.0-A and this subsection list the provisions of Part 6 that are applicable to different types of buildings covered by Section 100.0(a).
All buildings. Sections 100.0 through 110.12 apply to all buildings.
(i) Performance approach: Section
150.1(a) and (b); or (ii) Prescriptive approach: Sections
150.1(a) and (c). Exception to Section 100.0(e)2Diib: Seasonally occupied agricultural housing limited by state or federal agency contract to occupancy not more than 180 days in any calendar year.
Exception to Section 100.0(e)1: Spaces or requirements not listed in Table 100.0-A. 2. Newly constructed buildings. A. All newly constructed buildings. Sections 110.0
through 110.12 apply to all newly constructed buildings within the scope of Section 100.0(a). In addition, newly constructed buildings shall meet the requirements of Subsections B, C, D or E, as applicable. B. Nonresidential and hotel/motel buildings that are
mechanically heated or mechanically cooled.
i. Sections applicable. Sections 120.0 through
140.8 apply to newly constructed nonresidential buildings and hotels/motels that are mechanically heated or mechanically cooled. ii. Compliance approaches. In order to comply
with Part 6, newly constructed nonresidential buildings and hotels/motels that are mechanically heated or mechanically cooled must meet the requirements of:
a. Mandatory measures: The applicable
provisions of Sections 120.0 through 130.5; and b. Either:
(i) Performance approach: Section
140.1; or (ii) Prescriptive approach: Sections
140.2 through 140.8. C. Unconditioned nonresidential buildings and pro-
cess space. Sections 110.9, 110.10, 130.0 through 130.5, 140.3(c), 140.6, 140.7 and 140.9 apply to all newly constructed unconditioned buildings and 140.1, and 140.3(c), for process spaces within the scope of Section 100.0(a). D. Single-family buildings.
i. Sections applicable. Sections 150.0 through
150.1 apply to newly constructed single-family buildings. ii. Compliance approaches. In order to comply
with Part 6, newly constructed single-family buildings must meet the requirements of:
a. Mandatory measures: The applicable
provisions of Sections 110.0 through 110.10 and 150.0; and b. Either:
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
| OCCUPANCIES | APPLICATION | MANDATORY | PRESCRIPTIVE | PERFORMANCE | ADDITIONS/ ALTERATIONS |
|---|---|---|---|---|---|
| All Buildings | General | 100.0, 100.1, 100.2, 110.0 | 100.0, 100.1, 100.2, 110.0 |
100.0, 100.1, 100.2, 110.0 |
100.0, 100.1, 100.2, 110.0 |
| Nonresidential and Hotels/ Motels |
General | 120.0 | 140.0, 140.2 | 140.0, 140.1 |
141.0 |
| Nonresidential and Hotels/ Motels |
Envelope (conditioned) | 110.6, 110.7, 110.8, 120.7 | 140.3 | 140.3 | 140.3 |
| Nonresidential and Hotels/ Motels |
Envelope (unconditioned, process spaces) |
N.A. |
140.3(c) | 140.3(c) | 140.3(c) |
| Nonresidential and Hotels/ Motels |
HVAC (conditioned) |
110.2, 110.5, 120.1, 120.2, 120.3, 120.4, 120.5, 120.8 |
140.4 |
140.4 |
140.4 |
| Nonresidential and Hotels/ Motels |
Water Heating |
110.3, 120.3, 120.8, 120.9 |
140.5 | 140.5 | 140.5 |
| Nonresidential and Hotels/ Motels |
Indoor Lighting (conditioned, process spaces) |
110.9, 120.8, 130.0, 130.1, 130.4 |
140.3(c), 140.6 | 140.3(c), 140.6 | 140.3(c), 140.6 |
| Nonresidential and Hotels/ Motels |
Indoor Lighting (unconditioned and parking garages) |
110.9, 120.8, 130.0, 130.1, 130.4 |
140.3(c), 140.6 |
N.A. |
N.A. |
| Nonresidential and Hotels/ Motels |
Outdoor Lighting |
110.9, 130.0, 130.2, 130.4 |
140.7 | 140.7 | 140.7 |
| Nonresidential and Hotels/ Motels |
Electrical Power Distribution |
110.11, 130.5 |
N.A. | N.A. | N.A. |
| Nonresidential and Hotels/ Motels |
Pool and Spa Systems |
110.4, 110.5, 150.0(p) |
110.4, 110.5, 150.0(p) |
110.4, 110.5, 150.0(p) |
110.4, 110.5, 150.0(p) |
| Nonresidential and Hotels/ Motels |
Solar Ready Buildings | 110.10 | 110.10 | 110.10 | 141.0(a) |
| Nonresidential and Hotels/ Motels |
Solar PV and Battery Storage Systems | N.A. | 141.10 | 140.0, 140.1 |
N.A. |
| Covered Processes1 |
Envelope, Ventilation, Process Loads | 110.2, 120.6 | 140.9 | 140.1 | 120.6, 140.9, 141.1 |
| Signs | Indoor and Outdoor | 110.9, 130.0, 130.3 | 140.8 | N.A. | 141.0, 141.0(b)2H |
| Single-family | General | 150.0 | 150.1(a), (c) |
150.1(a), (b) |
150.2(a), (b) |
| Single-family | Envelope (conditioned) | 110.6, 110.7, 110.8, 150(a), 150.0(b), 150.0(c), 150.0(d), 150.0(e), 150.0(g), 150.0(q) |
110.6, 110.7, 110.8, 150(a), 150.0(b), 150.0(c), 150.0(d), 150.0(e), 150.0(g), 150.0(q) |
110.6, 110.7, 110.8, 150(a), 150.0(b), 150.0(c), 150.0(d), 150.0(e), 150.0(g), 150.0(q) |
110.6, 110.7, 110.8, 150(a), 150.0(b), 150.0(c), 150.0(d), 150.0(e), 150.0(g), 150.0(q) |
| Single-family | HVAC (conditioned) |
110.2, 110.5, 150.0(h), 150.0(i), 150.0(j), 150.0(m), 150.0(o) |
110.2, 110.5, 150.0(h), 150.0(i), 150.0(j), 150.0(m), 150.0(o) |
110.2, 110.5, 150.0(h), 150.0(i), 150.0(j), 150.0(m), 150.0(o) |
110.2, 110.5, 150.0(h), 150.0(i), 150.0(j), 150.0(m), 150.0(o) |
| Single-family | Water Heating |
110.3, 150.0(j, n) | 110.3, 150.0(j, n) | 110.3, 150.0(j, n) | 110.3, 150.0(j, n) |
| Single-family | Indoor Lighting (conditioned, unconditioned and parking garages) |
110.9, 130.0, 150.0(k) |
110.9, 130.0, 150.0(k) |
110.9, 130.0, 150.0(k) |
110.9, 130.0, 150.0(k) |
| Single-family | Outdoor Lighting |
110.9, 130.0, 150.0(k) |
110.9, 130.0, 150.0(k) |
110.9, 130.0, 150.0(k) |
110.9, 130.0, 150.0(k) |
| Single-family | Pool and Spa Systems |
110.4, 150.0(p) |
N.A. |
N.A. |
N.A. |
| Single-family | Solar Ready Buildings | 110.10 |
N.A. | N.A. | N.A. |
| Single-family | Electric Ready | 150.0(s), 150.0(t), 150.0(u), 150.0(v) |
N.A. | N.A. | N.A. |
| Single-family | Solar PV Systems | N.A. | 150.0(c)14 | 150.1(a), (b) | N.A. |
| Multifamily | General | 160.0 | 170.2 | 170.1 | 180.0 |
| Multifamily | HVAC (conditioned) | 110.6, 110.7, 110.8, 160.1 | 170.1(a) | 170.1(a) | 170.1(a) |
| Multifamily | Ventilation and Indoor Air Quality | 160.2 | N.A. | N.A. | N.A. |
| Multifamily | HVAC (conditioned) | 110.2, 110.5, 160.3 | 170.2(c) | 170.2(c) | 170.2(c) |
| Multifamily | Water Heating | 110.3, 160.4 | 170.2(d) | 170.2(d) | 170.2(d) |
| Multifamily | Indoor Lighting | 110.9, 160.5 | 170.2(e) | 170.2(e) | 170.2(e) |
| Multifamily | Outdoor Lighting | 110.9, 160.5 | 170.2(e) | 170.2(e) | 170.2(e) |
| Multifamily | Electrical Power Distribution | 110.11, 160.6 | N.A. | N.A. | N.A. |
| Multifamily | Pool and Spa Systems | 110.4, 110.5, 160.7 | 110.4, 110.5, 160.7 | 110.4, 110.5, 160.7 | 110.4, 110.5, 160.7 |
| Multifamily | Solar Ready Buildings | 110.10, 160.8 | 110.10, 160.8 | 110.10, 160.8 | 110.10, 160.8 |
| Multifamily | Electric Ready | 160.9 | 160.9 | 160.9 | N.A. |
| Multifamily | Solar PV and Battery Storage Systems | N.A. | 170.2(f), (g), (h) | 170.1 | N.A. |
- Nonresidential and hotel/motel buildings that contain covered processes may conform to the applicable requirements of both occupancy types listed in this table. Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8 and 25943, Public Resources Code .
2 2022 CALIFORNIA ENERGY CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—GENERAL PROVISIONS
TABLE 100.0-A—APPLICATION OF STANDARDS
ALL OCCUPANCIES—GENERAL PROVISIONS
ified in Section 150.2 apply to the occupancy after the alterations.
C. Multifamily buildings. Section 180.0 applies to
new construction in existing multifamily buildings. New construction in existing buildings includes additions, alterations and repairs. Section 180.0 specifies requirements that uniquely apply to additions, alterations or repairs to existing buildings, and specifies which requirements in other sections also apply. For alterations that change the occupancy classification of the building, the requirements specified in Section 180.0 apply to the occupancy after the alterations.
Installation of insulation in existing buildings. Section 110.8(d) applies to buildings in which insulation is being installed in existing attics, or on existing water heaters or existing space conditioning ducts.
Outdoor lighting. Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 150.0 apply to newly constructed outdoor lighting systems, and Section 141.0 applies to outdoor lighting that is either added or altered.
Signs. Sections 130.0, 130.3 and 140.8 apply to newly constructed signs located either indoors or outdoors, and Section 141.0 applies to sign alterations located either indoors or outdoors. (f) Mixed occupancy. When a building is designed and constructed for more than one type of occupancy (residential and nonresidential), the space for each occupancy shall meet the provisions of Part 6, applicable to that occupancy.
Exception 1 to Section 100.0(f): If one occupancy constitutes at least 80 percent of the conditioned floor area of the building, the entire building envelope, HVAC and water heating may be designed to comply with the provisions of Part 6 applicable to that occupancy, provided that the applicable lighting requirements in Sections 140.6 through 140.8, 150.0(k), or 160.5 and 170.2(e) are met for each occupancy and space, and mandatory measures in Sections 110.0 through 130.5, 150.0, and 160.0 through 160.9 are met for each occupancy and space.
Exception 2 to Section 100.0(f): If one occupancy constitutes at least 90 percent of the combined conditioned plus unconditioned floor area of the building, the entire building indoor lighting may be designed to comply with only the lighting provisions of Part 6 applicable to that occupancy.
(g) Administrative requirements. Administrative requirements relating to permit requirements, enforcement by the Commission, locally adopted energy standards, interpretations, claims of exemption, approved calculation methods, rights of appeal, and certification and labeling requirements of fenestration products and roofing products are specified in California Code of Regulations, Title 24, Part 1, Sections 10101 to 10-114.
(h) Certification requirements for manufactured equip- ment, products and devices. Part 6 limits the installation of manufactured equipment, products and devices to those that have been certified as specified by Sections 110.0 and 110.1.
E. Multifamily Buildings .
i. Sections applicable. Sections 160.0 through
170.2 apply to newly constructed multifamily buildings.
ii. Compliance approaches. In order to comply
with Part 6, newly constructed multifamily buildings must meet the requirements of:
a. Mandatory measures: The applicable
provisions of Sections 110.0 through 110.10, and 160.0; and
b. Either:
(i) Performance approach: Section
170.1; or
(ii) Prescriptive approach: Section
170.2(a) through (f).
F. Covered processes.
i. Sections applicable. Sections 110.2, 120.6 and
140.9 apply to covered processes.
ii. Compliance approaches. In order to comply with
Part 6, covered processes must meet the requirements of:
a. The applicable mandatory measures in Sec tion 120.6; and
b. Either:
(i) The performance approach requirements
of Section 140.1; or
(ii) The prescriptive approach requirements
of Section 140.9.
Note: If covered processes do not have prescriptive requirements, then only the applicable mandatory measures in Section 120.6 must be met.
- New construction in existing buildings (additions, alterations and repairs).
A. Nonresidential and hotel/motel buildings. Section
141.0 applies to new construction in existing nonresidential, high-rise residential and hotel/motel buildings. New construction in existing buildings includes additions, alterations and repairs. Section 141.0 specifies requirements that uniquely apply to additions, alterations or repairs to existing buildings, and specify which requirements in other sections also apply. For alterations that change the occupancy classification of the building, the requirements specified in Section 141.0 apply to the occupancy after the alterations.
B. Single-family buildings. Section 150.2 applies to
new construction in existing single-family buildings. New construction in existing buildings includes additions, alterations and repairs. Section 150.2 specifies requirements that uniquely apply to additions, alterations or repairs to existing buildings, and specifies which requirements in other sections also apply. For alterations that change the occupancy classification of the building, the requirements spec
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ALL OCCUPANCIES—GENERAL PROVISIONS
Requirements for manufactured equipment, products, and devices, when not specified in Title 24 Part 6, are specified in California Code of Regulations, Title 20, Sections 1601– 1609.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code .