CALGreen · California Green Building Standards Code (CALGreen)

Where in CALGreen do I find the standard identifiers (ANSI/ASTM/ISO/etc.) and their cross-reference sections?

CALGreen puts the list of standard identifiers and the CALGreen sections that reference them in Chapter 6, **§ 601.1** — use that table to find which code section cites a given ANSI/ASTM/ISO standard, then read the cited CALGreen section for how the standard is applied.

Last reviewed: July 6, 2026

What the code requires — 2–4 sentences

The California Green Building Standards Code lists the referenced standards (the standard identifiers such as ANSI, ASTM, ISO, etc.) and the CALGreen sections that cite them in Chapter 6 — Referenced Organizations and Standards, specifically § 601.1. § 601.1 organizes the standards by the promulgating agency and shows the CALGreen cross‑reference (the CALGreen section where that standard is used) in a table format .

The single practical rule: look in Chapter 6, Section 601.1 — it is the table that maps each standard identifier to the CALGreen section(s) that reference it.

Requirements in detail

Where to look

  • Open CALGreen, Chapter 6 — Referenced Organizations and Standards. The Chapter header and Section 601 — General introduce the list. § 601.1 contains the table that shows each STANDARD ACRONYM or NUMBER, the STANDARD NAME or TITLE, and the REFERENCED SECTION (the CALGreen section(s) that cite the standard) .
  • The table is organized by the promulgating agency (for example, ANSI/ACCA, ACI, etc.) so you can look up standards by organization or by identifier in that table .

How the identifiers and cross‑references are shown

  • Each table row shows:
    • Standard identifier (for example ANSI/ACCA 1 Manual D–2016),
    • Short title (for example “Residential Duct Systems”),
    • Code Reference — the CALGreen section where that standard is referenced (for example § 4.507.2).
  • The table therefore provides a direct map: Standard identifier → CALGreen section(s) that require or cite it .

Quick reference table (decision‑relevant examples)

Standard identifier (example) Short title (example) Code Reference
ANSI/ACCA 1 Manual D–2016 Residential Duct Systems § 4.507.2
ANSI/ACCA 2 Manual J–2016 Residential Load Calculations § 4.507.2
ANSI/ACCA 3 Manual S–2014 Residential Equipment Selection § 4.507.2
ACI CT‑21 Concrete Terminology § A5.405.5.2.1.1

(These rows are taken directly from the Section § 601.1 table; consult that table for the full list of agencies, standards and the referenced CALGreen sections.)

How to use the cross‑reference

  1. Find the standard identifier in the § 601.1 table.
  2. Read the Code Reference column to get the CALGreen section number (for example § 4.507.2).
  3. Go to that CALGreen section to see how the standard is applied or required in the code text (the table in § 601.1 does not reproduce the standard text; it only points you to the CALGreen location that cites it) .

Exceptions & special cases

  • What § 601.1 contains: § 601.1 lists the organizations and standards and shows the CALGreen sections that reference them; the table is organized by promulgating agency. It does not include the full standards text — it is a cross‑reference table only .
  • Edition / “current edition” language: The retrieved text of § 601.1 shows identifiers and referenced sections but does not itself state an explicit rule in that paragraph about which edition of a referenced standard is required (e.g., “latest edition” vs. a specific year). The snippet in § 601.1 lists standards including edition years in many rows, but § 601.1 itself does not include a general adoption‑of‑edition clause in the retrieved snippet; if you need the legal adoption/edition rule, check the code’s administrative/adoption language (often in Chapter 1) or the specific referencing section cited in the table for clarifying language — that step is necessary because § 601.1 only provides the identifiers and cross‑references .
  • Standards vs. CALGreen text: The table indicates where CALGreen relies on a standard; it does not make the entire referenced standard automatically enforceable beyond the portion CALGreen cites. To understand the enforceable requirement, read the CALGreen section that references the standard (the code text in that CALGreen section determines how the standard is used) .

Common mistakes

  • Mistaking the § 601.1 table for the normative text of a standard — the table only points you to the CALGreen section(s) that reference the standard, it does not replace or reproduce the standard itself .
  • Assuming any standard listed is adopted in full and verbatim without checking the specific CALGreen section that references it — always read the CALGreen section (the Code Reference) to see how the standard is applied. The table shows where the code cites the standard, but the usage context is in the cited section .
  • Overlooking the promulgating agency grouping — searching by organization (e.g., “ACI”, “ANSI/ACCA”) in § 601.1 can be faster than scanning long lists of identifiers .

Worked example — step‑by‑step

Scenario: You need to confirm which CALGreen section requires the ANSI/ACCA Manual D sizing method for residential ductwork.

  1. Open CALGreen Chapter 6 and go to § 601.1 (Referenced Organizations and Standards). That table lists ANSI/ACCA 1 Manual D–2016 and shows the Code Reference § 4.507.2 for that standard .
  2. Go to § 4.507.2 in CALGreen to read how the code requires duct design/sizing and how it cites ANSI/ACCA Manual D. The table in § 601.1 gave you the cross‑reference; the enforceable requirement appears in § 4.507.2 (not in the table itself) .
  3. If you need the exact methodology from Manual D, obtain the ANSI/ACCA 1 Manual D–2016 standard (publisher text) and apply it to the scope that § 4.507.2 specifies. (Note: § 601.1 tells you which standard to consult and where the code points to it; the standard itself is purchased/searched separately.)

Related provisions

  • § 601.1 — Section that contains the referenced organizations and standards table (the controlling table discussed above).
  • Section 601 — Chapter 6 header: “Referenced Organizations and Standards” (see chapter introduction and table) .
  • § 4.507.2 — Example CALGreen section that is listed in the § 601.1 table for ANSI/ACCA standards (use the table to find such cross‑references) .
  • § 5.410.2 — Commissioning-related section that is mentioned elsewhere in CALGreen and is shown in cross‑references tied to standards; check the specific CALGreen section named in the table for the standard’s application. .
  • § A5.405.5.2.1.1 — Example appendix reference shown in the § 601.1 table (e.g., ACI CT‑21 maps to this CALGreen reference) .

Code references

Grounded in the retrieved California Green Building Standards Code (CALGreen) — click a citation to read the verbatim passage:

  • CALGreen § 5.1.1 Medium relevance — show source text

    5.1.1, 705.5.1.3| |ASTM F2735-2021|Standard Specification for Plastic Insert Fittings for SDR9
    Cross-linked Polyethylene (PEX) and Polyethylene of Raised
    Temperature (PE-RT) Tubing|Fittings|Table 604.1| |ASTM F2769-2018|Standard Specification for Polyethylene of Raised Temperature
    (PE-RT) Plastic Hot and Cold-Water Tubing and Distribution
    Systems|Piping, Fittings|Table 604.1| |ASTM F2831-2019|Standard Practice for Internal Non Structural Epoxy Barrier
    Coating Material Used in Rehabilitation of Metallic Pressur-
    ized Piping Systems|Miscellaneous|320.1| |ASTM F2855-2019|Standard Specification for Chlorinated Poly (Vinyl
    Chloride)/Aluminum/Chlorinated Poly (Vinyl Chloride) (CPVC-
    AL-CPVC) Composite Pressure Tubing|Piping|Table 604.1, 605.3.1| |ASTM F2945-2018|Standard Specification for Polyamide 11 Gas Pressure Pipe,
    Tubing, and Fittings|Piping|1208.5.4,
    1208.5.10.2| |ASTM F3226/F3226M-
    2019|Standard Specification for Metallic Press-Connect Fittings for
    Piping and Tubing Systems|Fittings|Table 604.1| |ASTM F3240-2019e1|Standard Practice for Installation of Seamless Molded
    Hydrophilic Gaskets (SMHG) for Long-Term Watertightness
    of Cured-in-Place Rehabilitation of Main and Lateral Pipelines|Piping|715.3.1| |ASTM F3347-2021|Metal Press Insert Fittings with Factory Assembled Stainless
    Steel Press Sleeve for SDR9 Cross-linked Polyethylene (PEX)
    Tubing and SDR9 Polyethylene of Raised Temperature (PE-RT)
    Tubing|Fittings|Table 604.1| |ASTM F3348-2021a|Plastic Press Insert Fittings with Factory Assembled Stainless
    Steel Press Sleeve for SDR9 Cross-linked Polyethylene (PEX)
    Tubing and SDR9 Polyethylene of Raised Temperature (PE-RT)
    Tubing|Fittings|Table 604.1| |AWS|AWS|AWS|AWS| |AWS A5.8M/A5.8-2019|Filler Metals for Brazing and Braze Welding|Joints|605.1.1, 705.3.1,
    1321.3| |AWS A5.9/A5.9M-2017
    (ISO 14343:2009 MOD)|Welding Consumables—Wire Electrodes, Strip Electrodes,
    Wires, and Rods for Arc Welding of Stainless and Heat Resisting
    Steels—Classification|Joints|605.13.2| |AWS B2.2/B2.2M-2016|Brazing Procedure and Performance Qualification|Certification|1323.11| |AWWA|AWWA|AWWA|AWWA| |AWWA C110-2012|Ductile-Iron and Gray-Iron Fittings|Fittings|Table 604.1| |AWWA C111-2017|Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings|Joints|605.4.1,

  • CALGreen § 301.1 Medium relevance — show source text
    Adopting Agency BSC BSC-
    CG
    SFM Col5 HCD Col7 Col8 DSA Col10 OSHPD Col12 Col13 Col14 Col15 Col16 BSCC DPH AGR DWR CEC CA SL SLC
    Adopting Agency BSC BSC-
    CG
    T-24 T-19* 1 2 1/AC AC SS 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
    Adopt Entire Chapter
    Adopt Entire Chapter as
    amended (amended sections
    listed below)
    X
    Adopt only those sections that
    are listed below
    [California Code of Regulations,
    Title 19, Division 1]
    Chapter / Section
    301.1 X
    301.2 X
    302.1 X
    302.2 X
    • The California Code of Regulations (CCR), Title 19, Division 1 provisions that are found in the California Wildland-Urban Interface Code are a reprint from the current CCR, Title 19, Division 1 text for the code user’s convenience only. The scope, applicability and appeals procedures of CCR, Title 19, Division I remain the same. The state agency does not adopt sections identified by the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

    The California Code of Regulations (CCR), Title 14, Division 1.5 provisions that are found in the California Wildland-Urban Interface Code are not listed in the Matrix Adoption Tables as they are not within the State Fire Marshal’s authority to adopt. These provisions are a reprint from the current CCR, Title 14, Division 1.5 text for the code user’s convenience only and are identified in the body of the code by square brackets containing references to applicable Title 14 sections.

    2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE 3-1

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    3-2 2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    3 WILDLAND-URBAN INTERFACE AREAS

    User notes:

    About this chapter: Chapter 3 provides for the fundamental aspect of applying the code—the legal declaration and establishment of wildlandurban interface areas within the adopting jurisdiction, mapping of the area, periodic review and updates.

    SECTION 301—GENERAL

  • CALGreen § 12.7.3.4 Medium relevance — show source text

    12.7.3.4 – At least two No. 5 bars in diaphragms having two layers of reinforcement in both directions and one No. 5 bar in diaphragms having a single layer of reinforcement in both directions shall be provided around openings larger than 12 inches in any dimension in addition to the minimum reinforcement required by Section 12.6.

    1910.3.2 ACI 318, Section 18.12.6. Add Section 18.12.6.2 to ACI 318 as follows:

    Collector and boundary elements in topping slabs placed over precast floor and roof elements shall not be less than 3 inches (76 mm) or 6 d b thick, where d b is the diameter of the largest reinforcement in the topping slab.

    1910.3.3 ACI 318, Table 19.2.1.1. Modify ACI 318 Table 19.2.1.1 as follows: For concrete designed and constructed in accordance with this chapter, fc, , shall not be less than 3,000 psi (20.7 MPa). Reinforced normal weight concrete with specified compressive strength higher than 8,000 psi (55 MPa) shall require prior approval of struc- tural design method and acceptance criteria by the enforcement agency.

    1910.3.4 ACI 318, Section 26.11.1.2. Modify ACI 318 Section 26.11.1.2 by adding Item (e) as follows:

    (e) Forms for shotcrete shall be substantial and rigid. Forms shall be built and placed so as to permit the escape of air and rebound. Adequate ground wires, which are to be used as screeds, shall be placed to establish the thickness, surface planes and form of the shotcrete work. All surfaces shall be rodded to these wires.

    SECTION 1911—EXISTING CONCRETE STRUCTURES [OSHPD 1R, 2 & 5]

    1911.1 Concrete Core Sampling. Where concrete cores are required to be taken for material property determination, cores shall be at least 4 inches (102 mm) in diameter. Cores as small as 2.75 inches (70 mm) in diameter may be allowed by the enforcement agency when reinforcement is closely spaced and the coarse aggregate does not exceed [3] / 4 inch (19 mm).

    1911.2 Crack repair by epoxy injection. Crack Repair of concrete and masonry member by epoxy injection shall conform to all require- ments of ACI 548.15.

    1911.3 Concrete strengthening by externally bonded fiber reinforced polymer (FRP). Design and construction of externally bonded FRP systems for strengthening concrete structures shall be in accordance with ACI 440.2R.

    Exceptions: 1. Near-Surface Mounted (NSM) FRP bars shall not be permitted. 2. Strengthening of shear walls and diaphragms (including chords and collectors) shall be considered as an alternative system.

    Design capacities, reliability and serviceability of FRP materials shall be permitted to be established in accordance with ICC-ES AC 125. Minimum inspection requirements of FRP composite systems shall be in accordance with ICC-ES AC 178.

    2025 CALIFORNIA BUILDING CODE 19-13

  • CALGreen § 19-12 Medium relevance — show source text

    The following samples of materials and tendons selected by the engineer or the designated testing laboratory from the prestress- ing steel at the plant or job site shall be furnished by the contractor and tested by an approved independent testing agency: 1. For wire, strand or bars, 7-foot-long (2134 mm) samples shall be taken of the coil of wire or strand reel or rods. A minimum of one random sample per 5,000 pounds (2270 kg) of each heat or lot used on the job shall be selected. 2. For prefabricated prestressing tendons other than bars, one completely fabricated tendon 10 feet (3048 mm) in length between grips with the anchorage assembly at one end shall be furnished for each size and type of tendon and anchorage assembly.

    Variations of the bearing plate size need not be considered.

    The anchorages of unbonded tendons shall develop at least 95 percent of the minimum specified ultimate strength of the prestressing steel. The total elongation of the tendon under ultimate load shall not be less than 2 percent measured in a minimum gage length of 10 feet (3048 mm).

    Anchorages of bonded tendons shall develop at least 90 percent of the minimum specified strength of the prestressing steel tested in an unbonded state. All couplings shall develop at least 95 percent of the minimum specified strength of the

    19-12 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CONCRETE

    prestressing steel and shall not reduce the elongation at rupture below the requirements of the tendon itself. 3. If the prestressing tendon is a bar, one 7-foot (2134 mm) length complete with one end anchorage shall be furnished and, in addition, if couplers are to be used with the bar, two 4-foot (1219 mm) lengths of bar fabricated to fit and equipped with one coupler shall be furnished. 4. Mill tests of materials used for end anchorages shall be furnished. In addition, at least one Brinnell hardness test shall be made of each thickness of bearing plate.

    1910.2.4 Composite construction cores. Cores of the completed composite concrete construction shall be taken to demonstrate the shear strength along the contact surfaces. The cores shall be tested when the cast-in-place concrete is approximately 28 days old and shall be tested by a shear loading parallel to the joint between the precast concrete and the cast-in-place concrete. The minimum unit shear strength of the contact surface area of the core shall not be less than 100 psi (689 kPa). At least one core shall be taken from each building for each 5,000 square feet (465 m [2] ) of area of composite concrete construction and not fewer than three cores shall be taken from each project. The architect or structural engineer in responsible charge of the proj- ect or his or her representative shall designate the location for sampling.

    1910.3 Modifications to ACI 318.

    1910.3.1 ACI 318, Section 12.7.3. Add Section 12.7.3.4 to ACI 318 as follows:

  • CALGreen § 3-83 Medium relevance — show source text

    Exceptions:

    1. Exhaust ventilation shall not be required in areas with an approved engineered ventilation system, which maintains a hydrogen gas concentration at less than 25 percent of the lower flammability limit. 2. Mechanical exhaust ventilation for hydrogen shall not be required where the charging equipment utilized is installed and listed for indoor charging of electric vehicles without ventilation.

    2025 CALIFORNIA RESIDENTIAL CODE 3-83

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    BUILDING PLANNING

    SECTION 339—RESERVED

    SECTION R340—POLLUTANT CONTROL

    R340.1 Finish material pollutant control. Finish materials including adhesives, sealants, caulks, paints and coatings, aerosol paints and coatings, carpet systems, carpet cushion, carpet adhesive, resilient flooring systems and composite wood products shall meet the volatile organic compound (VOC) emission limits in accordance with the California Green Building Standards Code, Chapter 4, Division 4.5.

    3-84 2025 CALIFORNIA RESIDENTIAL CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA RESIDENTIAL CODE – MATRIX ADOPTION TABLE

    CHAPTER 4 – FOUNDATIONS

    (Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

    Adopting agency BSC BSC-
    CG
    SFM HCD Col6 Col7 DSA Col9 Col10 OSHPD Col12 Col13 Col14 Col15 Col16 BSCC DPH AGR DWR CEC CA SL SLC
    Adopting agency BSC BSC-
    CG
    SFM 1 2 1/AC AC SS SS/CC 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
    Adopt entire chapter
    Adopt entire chapter as
    amended (amended
    sections listed below)
    X
    Adopt only those sections
    that are listed below
    X
    Chapter / Section
    R401.2 X
    R401.4.1.1 through
    R401.4.1.1.5
    X
    R404.5.1 X
    R408.3 X
    R408.4 X
    R408.8 X

    The state agency does not adopt sections identified with the following symbol: †

    2025 CALIFORNIA RESIDENTIAL CODE 4-1

  • CALGreen § 5.410.2.1 Medium relevance — show source text

    Independent Third-Party Commissioning Professional— A commissioning consultant contracted directly by the owner who is not responsible to, or affiliated with, any other member of the design and construction team.

    Operation and Maintenance (O&M) Manuals— Documents that provide information necessary for operating and maintaining installed equipment and systems.

    Owner Representative— An individual or entity assigned by the owner to act and sign on the owner’s behalf.

    Process Equipment— Energy-using equipment and components that are not used for HVAC, electrical, plumbing and irrigation operations. Such devices would include but are not limited to heat transfer, water purifying, air cleaning, air vacuum and air compressing.

    Sequence of Operation— A written description of the intended performance and operation of each control element and feature of the equipment and systems.

    Selecting Trained Personnel (for Commissioning)

    This code requires that “Commissioning shall be performed in accordance with this section by trained personnel with experience on projects of comparable size and complexity.” The trained personnel manage and facilitate the commissioning process. The trained personnel develop and implement the commissioning tasks and documentation identified in Sections 5.410.2.1 through 5.410.2.6. Trained personnel may include appropriate members of owner staff, contractor and design team as well as independent commissioning professionals.

    It is essential that there is a single person designated to lead and manage the commissioning activities. In practice, this individual has been referenced by various identifiers such as commissioning authority, agent, provider, coordinator, lead, etc. In this guide the term “commissioning coordinator” is used.

    The designated commissioning coordinator may be an independent, third-party commissioning professional, a project design team member (e.g., engineer or architect), an owner’s engineer or facility staff, contractor or specialty subcontractor. Methods of evaluating the designated commissioning coordinator and trained personnel include review of the following:

    1. Technical knowledge;
    2. Relevant experience;
    3. Potential conflict of interest concerns;
    4. Professional certifications and training;
    5. Communication and organizational skills; and
    6. Reference and sample work products.

    8-14 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL

    Selection of “trained,” qualified personnel is required by this code. In order to meet this requirement, the commissioning provider should be evaluated via the methods discussed above. In addition, various organizations have training and certification programs that may be a source for identification of qualified commissioning providers.

    For information about enforcement and compliance of each commissioning element see Sections 5.410.2.1 through 5.410.2.6.

    For compliance forms and templates see Part 2 following this standard.

    Reference: 1 Owner’s Project Requirements

    CALGreen Section 5.410.2.1, Owner’s or Owner representative’s Project Requirements (OPR).

    1.1 Intent:

    The Owner’s Project Requirements (OPR) documents the functional requirements of a project and expectations of the building use and operation as it relates to systems being commissioned. The document describes the physical and functional building characteristics desired by the owner and establishes performance and acceptance criteria. The OPR is most effective when developed during predesign and used to develop the Basis of Design (BOD) during the design process. The level of detail and complexity of the OPR will vary according to building use, type and systems.

    1.2 Compliance Method:

  • CALGreen § 4.1 Medium relevance — show source text

    This Standard refers to the following publications, and where such reference is made, it shall be to the current edition of those publications, including all amendments published thereto.

    ASTM International

    ASTM F876 Standard Specification for Crosslinked Polyethylene (PEX) Tubing

    ASTM F877 Standard Specification for Crosslinked Polyethylene (PEX) Hot- and Cold-Water Distribution Systems

    ASTM F1807 Standard Specification for Metal Insert Fittings Utilizing a Copper Crimp Ring, or Alternate Stainless Steel Clamps, for SDR9 Crosslinked Polyethylene (PEX) Tubing and SDR9 Polyethylene of Raised Temperature (PE-RT) Tubing

    ASTM F1960 Standard Specification for Cold Expansion Fittings with PEX Reinforcing Rings for Use with Cross-linked Polyethylene (PEX) Polyethylene of Raised Temperature (PE-RT) Tubing

    2025 CALIFORNIA PLUMBING CODE 455

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    IS 31

    ASTM F2080 Standard Specification for ColdExpansion Fittings with Metal Compression-Sleeves for CrossLinked Polyethylene (PEX) Pipe and SDR9 Polyethylene of Raised Temperature (PE-RT) Pipe

    ASTM F2159 Standard Specification for Plastic Insert Fittings Utilizing a Copper Crimp Ring, or Alternate Stainless Steel Clamps for SDR9 Cross-linked Polyethylene (PEX) Tubing and SDR9 Polyethylene of Raised Temperature (PE-RT) Tubing

    ASTM F2657 Standard Test Method for Out door Weathering Exposure of Crosslinked Polyethylene (PEX) Tubing

    AWWA (American Water Works Association)

    AWWA C904 Cross-Linked Polyethylene (PEX) Pressure Tubing, ½ In. (13 mm) Through 3 In. (76 mm), for Water Service

    IAPMO (International Association of Plumb- ing and Mechanical Officials)

    IAPMO/ANSI

    UPC-1 Uniform Plumbing Code

    PPI (Plastics Pipe Institute)

    PPI TR-3 Policies and Procedures for

    Developing Hydrostatic Design Basis (HDB), Hydrostatic Design Stresses (HDS), Pressure Design Basis (PDB), Strength Design Basis (SDB), Minimum Required Strength (MRS) Ratings, and Categorized Required Strength (CRS) for Thermoplastic Piping Materials or Pipe

    3 Abbreviations

    The following abbreviations apply in this Standard:

    CTS — copper tube size

    HDPE — high density polyethylene

    IC — insulation contact

    NTS — nominal tubing size

    PEX — crosslinked polyethylene

    SDR — standard dimension ratio

    UV — ultraviolet light

    4 General

    4.1 Tubing

    4.1.1 PEX tubing can be

    (a) pigmented throughout (i.e., with color); (b) non-pigmented (e.g., translucent or natural); or (c) coated with a pigmented layer. 4.1.2 PEX tubing is typically available in NTS-1/4 to NTS-3.

    4.1.3 Before installation, the installer shall review the tubing markings and verify that

  • CALGreen § 1.1.1 Medium relevance — show source text

    Note: See Section R301.1.1.1 for limited-density owner- built rural dwellings.

    R502.1.1.1 Preservative-treated lumber. Preservative treated dimension lumber shall be identified as required by Section R304.2.

    R502.1.1.2 End-jointed lumber. Approved end-jointed lumber identified by a grade mark conforming to Section R502.1.1 shall be permitted to be used interchangeably with solid-sawn members of the same species and grade. End-jointed lumber used in an assembly required elsewhere in this code to have a fire-resistance rating shall have the designation “Heat-Resistant Adhesive” or “HRA” included in its grade mark.

    R502.1.2 Prefabricated wood I-joists. Structural capacities and design provisions for prefabricated wood I-joists shall be established and monitored in accordance with ASTM D5055.

    R502.1.3 Structural glued-laminated timbers. Glued-laminated timbers shall be manufactured and identified as required in ANSI A190.1, ANSI 117 and ASTM D3737.

    R502.1.4 Structural log members. Structural log members shall comply with the provisions of ICC 400.

    R502.1.5 Structural composite lumber. Structural capacities for structural composite lumber shall be established and monitored in accordance with ASTM D5456.

    R502.1.6 Cross-laminated timber. Cross-laminated timber shall be manufactured and identified as required by ANSI/APA PRG 320.

    R502.1.7 Engineered wood rim board. Engineered wood rim boards shall conform to ANSI/APA PRR 410 or shall be evaluated in accordance with ASTM D7672. Structural capacities shall be in accordance with ANSI/APA PRR 410 or established in accordance with ASTM D7672. Rim boards conforming to ANSI/APA PRR 410 shall be marked in accordance with that standard.

    R502.2 Design and construction. Floors shall be designed and constructed in accordance with the provisions of this chapter, Figure R502.2 and Sections R304 and R305 or in accordance with ANSI AWC NDS.

    2025 CALIFORNIA RESIDENTIAL CODE 5-3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FLOORS

    FIGURE R502.2—FLOOR CONSTRUCTION

    SILL PLATE

    BAND, RIM OR HEADER JOIST

    BOTTOM WALL STUDS

    PLATE

    OPTIONAL FINISH

    FLOOR

    SUBFLOOR OR FLOOR SHEATHING– JOISTS–SEE TABLES SEE SECTION R503 R502.3.1(1) AND R502.3.1(2)

    Col1 Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10 Col11 Col12 Col13 Col14 Col15

    2 IN. CLEARANCE

    SEE SECTION

    R1001.11

    FIREPLACE

    SOLID

    BLOCKING–SEE

    SECTION R502.7

    SILL PLATE

    FOUNDATION

  • CALGreen § 18-22 Medium relevance — show source text

    18-22 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    SOILS AND FOUNDATIONS

    1810.3.2.6 Allowable stresses. The allowable stresses for materials used in deep foundation elements shall not exceed those specified in Table 1810.3.2.6.

    TABLE 1810.3.2.6—ALLOWABLE STRESSES FOR MATERIALS USED IN DEEP FOUNDATION ELEMENTS Col2
    MATERIAL TYPE AND CONDITION MAXIMUM ALLOWABLE STRESSa
    1. Concrete or grout in compressionb
    Cast-in-place with a permanent casing in accordance with Section 1810.3.2.7
    or Section 1810.3.5.3.4
    Cast-in-place in other permanent casing or rock
    Cast-in-place without a permanent casing
    Precast nonprestressed
    Precast prestressed
    0.4_f ′c_
    0.33_f ′c_
    0.3_f ′c_
    0.33_f ′c_
    0.33_f ′c_ - 0.27_fpc_
    2. Nonprestressed reinforcement in compression 0.4_fy_ ≤ 30,000 psi
    3. Steel in compression
    Cores within concrete-filled pipes or tubes
    Pipes, tubes or H-piles, where justified in accordance with Section 1810.3.2.8
    Pipes or tubes for micropiles
    Other pipes, tubes or H-piles
    Helical piles
    0.5_Fy_ ≤ 32,000 psi
    0.5_Fy ≤ 32,000 psi
    0.4_Fy
    ≤ 32,000 psi
    0.35_Fy_ ≤ 24,000 psi
    0.6_Fy_ ≤ 0.5_Fu_
    4. Nonprestressed reinforcement in tension
    Within micropiles
    Other conditions
    For load combinations that do not include wind or seismic loads
    For load combinations that include wind or seismic loads
    0.6_fy_
    0.5_fy_ ≤ 30,000 psi
    0.5_fy_ ≤ 40,000 psi
    5. Steel in tension
    Pipes, tubes or H-piles, where justified in accordance with Section 1810.3.2.8
    Other pipes, tubes or H-piles
    Helical piles
    0.5_Fy_ ≤ 32,000 psi
    0.35_Fy_ ≤ 24,000 psi
    0.6_Fy_ ≤ 0.5_Fu_
    6. Timber In accordance with the ANSI/AWC NDS
    a.f ′c is the specified compressive strength of the concrete or grout;fpc is the compressive stress on the gross concrete section due to effective prestress forces only;fy is the spec-
    ified yield strength of reinforcement;Fy is the specified minimum yield stress of steel;Fu is the specified minimum tensile stress of structural steel.
    b. The stresses specified apply to the gross cross-sectional area of the concrete for precast prestressed piles and to the net cross-sectional area for all other piles.
  • CALGreen § 02-3.8. Medium relevance — show source text
    • When glass tile is used, specify mortar designated by tile and mortar manufacturers. Bond coat color will impact the final appearance of translucent glass tile. Specifier shall confirm bond coat color is acceptable.

    • Epoxy bond coat, when used—ANSI A118.3 or ISO R1 or better.

    • When glass tile is used, specify epoxy bond coat designated by tile and bond coat manufacturers. Bond coat color will impact the final appearance of translucent glass tile. Specifier shall confirm bond coat color is acceptable.

    • Vapor retarder membrane—ANSI A108.02-3.8.

    • Waterproof membrane, when used—ANSI A118.10.

    • Mortar bed, metal lath, and cleavage membrane— ANSI A108.1A.

    • Flexible mildew-resistant sealant—ASTM C920.

    • Shower pan membrane—local building code.

    • Metal studs—ASTM C645.

    Materials for Green/Sustainable Design

    • See “Green Building Standards and Green Product Selection Guide” and consult manufacturers and suppliers for product sustainability and contribution to green building design.

    • Consider specifying tile and installation materials that meet ANSI A138.1, the American National Standard Specifica- tions for Sustainable Ceramic Tiles, Glass Tiles, and Tile Installation Materials .

    Preparation by Other Trades

    • Wall framing shall meet the general framing requirements of ANSI A108.11-4.0–4.3.

    • Apply blocking between the studs to support the shower pan membrane.

    Movement Joint (architect must specify type of joint and show location and details on drawings)

    • Movement joints—mandatory according to EJ171.

    • When glass tile is used, adhere to more frequent placement recommendations within the ranges listed in EJ171.

    Installation Specifications

    • Shower pan membrane—ANSI A108.01-3.6.

    • Tile—ANSI A108.1A, .1B, or .1C. A108.1B required if waterproof membrane or epoxy bond coat to be used.

    • Glass tile—ANSI A108.14, .15, .16, or manufacturer’s directions.

    • Cementitious grout—ANSI A108.10.

    • Epoxy mortar/grout—ANSI A108.6.

    • Waterproof membrane—ANSI A108.13.

    • Movement Joints—EJ171 and ASTM C1193.

    Notes

    • Test shower pan membrane and drainage fitting for leaks before commencing tilework.

    • Materials adversely affected by moisture in areas immediately adjacent to showers, tubs, and roman tubs should be properly protected.

    • A sloped portland cement mortar fill or approved preformed slope may be used under shower pan membrane when subfloor is not sloped to drain.

    • All horizontal surfaces, for example shower seats, sills, curbs, etc., must slope towards drain or other surface sloped toward drain. Where present, waterproofing also must be sloped.

    • When glass tile is used, see “Glass Tile Selection and Installation Guide,” and consult manufacturer for recommendations and requirements.

    • For curbless shower receptor, see B421C and B422C.

    474 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    TILE TUBS AND FOUNTAINS TCNA HANDBOOK

    Requirements

  • California Green Building Standards Code Medium relevance — show source text
    • Cementitious grout—ANSI A118.6 or better or ISO CG1 or better. When glass tile is used, specify grout designated by tile and grout manufacturers.

    • Epoxy grout, when used—ANSI A118.3 or ISO RG.

    • Cementitious bond coat:

    • ANSI A118.4 or better or ISO C2S1 or better unless ANSI A118.1 or ISO C1 is recommended by membrane manufacturer.

    • When glass tile is used, specify mortar designated by tile and mortar manufacturers. Bond coat color will impact the final appearance of translucent glass tile. Specifier shall confirm bond coat color is acceptable.

    • Waterproof membrane—ANSI A118.10 and recommended by manufacturer of membrane for use over backing type in intended application.

    • Flexible mildew-resistant sealant—ASTM C920.

    Materials for Green/Sustainable Design

    • See “Green Building Standards and Green Product Selection Guide” and consult manufacturers and suppliers for product sustainability and contribution to green building design.

    • Consider specifying tile and installation materials that meet ANSI A138.1, the American National Standard Specifica- tions for Sustainable Ceramic Tiles, Glass Tiles, and Tile Installation Materials .

    Preparation by Other Trades/Backer Board Installers

    • Depressed slab by others. Depressed area must extend beyond shower area to facilitate a finished floor installation that effectively evacuates shower water and splash water, which are often difficult to contain within a curbless

    shower.

    • Refer to appropriate wall method for applicable preparations by other trades and backer board installers.

    • Maximum allowable variation in the tile substrate—for tiles with all edges shorter than 15", maximum allowable variation is [1] ⁄ 4 " in 10' from the required plane, with no more than 1 ⁄ 16 " variation in 12" when measured from the high points in

    the surface. For tiles with at least one edge 15" in length, maximum allowable variation is [1] ⁄ 8 " in 10' from the required plane, with no more than [1] ⁄ 16 " variation in 24" when measured from the high points in the surface.

    • Center backer board end or edge joints on framing and stagger joints in adjacent rows so four corners do not come together within the same plane. Space panel ends and edges in accordance with manufacturer’s recommendations.

    Movement Joint (architect must specify type of joint and show location and details on drawings)

    • Movement joints—mandatory according to EJ171.

    • When glass tile is used, adhere to more frequent placement recommendations within the ranges listed in EJ171. Installation Specifications

    • Waterproof membrane—ANSI A108.13.

    • Tile—ANSI A108.5.

    • Glass tile—manufacturer’s directions.

    • Cementitious grout—ANSI A108.10.

    • Epoxy grout—ANSI A108.6.

    • Movement Joints—EJ171 and ASTM C1193.

    Notes

    • Test shower pan membrane/waterproof membrane and drainage fitting for leaks before commencing tilework.

    • Materials adversely affected by moisture in areas immediately adjacent to showers, tubs, and roman tubs should be properly protected.

    • All horizontal surfaces, for example shower seats, sills, curbs, etc., must slope towards drain or other surface sloped toward drain. Where present, waterproofing also must be sloped.

    • When glass tile is used, see “Glass Tile Selection and Installation Guide,” and consult manufacturer for recommendations and requirements.

  • CALGreen § 909.21.1.1 Medium relevance — show source text

    909.21.1.1 Use of ventilation systems. Ventilation systems, other than hoistway supply air systems, are permitted to be used to exhaust air from adjacent spaces on the fire floor, two floors immediately below and one floor immediately above the fire floor to the building’s exterior where necessary to maintain positive pressure relationships as required in Section 909.21.1 during operation of the elevator shaft pressurization system.

    909.21.2 Rational analysis. A rational analysis complying with Section 909.4 shall be submitted with the construction documents.

    909.21.3 Ducts for system. Any duct system that is part of the pressurization system shall be protected with the same fire-resistance rating as required for the elevator shaft enclosure.

    909.21.4 Fan system. The fan system provided for the pressurization system shall be as required by Sections 909.21.4.1 through 909.21.4.4.

    909.21.4.1 Fire resistance. Where located within the building, the fan system that provides the pressurization shall be protected with the same fire-resistance rating required for the elevator shaft enclosure.

    909.21.4.2 Smoke detection. The fan system shall be equipped with a smoke detector that will automatically shut down the fan system when smoke is detected within the system.

    909.21.4.3 Separate systems. A separate fan system shall be used for each elevator hoistway.

    909.21.4.4 Fan capacity. The supply fan shall be either adjustable with a capacity of not less than 1,000 cubic feet per minute (0.4719 m [3] /s) per door, or that specified by a registered design professional to meet the requirements of a designed pressurization system.

    909.21.5 Standby power. The pressurization system shall be provided with standby power in accordance with Section 2702.

    909.21.6 Activation of pressurization system. The elevator pressurization system shall be activated upon activation of the elevator lobby smoke detectors.

    909.21.7 Testing. Testing for performance shall be required in accordance with Section 909.18.8. System acceptance shall be in accordance with Section 909.19.

    909.21.8 Marking and identification. Detection and control systems shall be marked in accordance with Section 909.14.

    909.21.9 Control diagrams. Control diagrams shall be provided in accordance with Section 909.15.

    909.21.10 Control panel. A control panel complying with Section 909.16 shall be provided.

    909.21.11 System response time. Hoistway pressurization systems shall comply with the requirements for smoke control system response time in Section 909.17.

    SECTION 910—SMOKE AND HEAT REMOVAL

    [F] 910.1 General. Where required by this code, smoke and heat vents or mechanical smoke removal systems shall conform to the requirements of this section.

    2025 CALIFORNIA BUILDING CODE 9-51

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE PROTECTION AND LIFE SAFETY SYSTEMS

    [F] 910.2 Where required. Smoke and heat vents or a mechanical smoke removal system shall be installed as required by Sections 910.2.1 and 910.2.2.

Frequently asked questions

Where exactly in the code is the list of standard identifiers?

The list is in Chapter 6 — Referenced Organizations and Standards, specifically § 601.1, which contains the table mapping identifiers to CALGreen sections.

Does the § 601.1 table include the full text of the standards?

No. § 601.1 is a cross‑reference table; it lists the identifiers and the CALGreen sections that cite them. You must consult the referenced CALGreen section and the original standard for full requirements.

How do I find which CALGreen section uses a particular ASTM or ANSI standard?

Search § 601.1’s table by the promulgating agency or the standard identifier; the table’s “Referenced Section” column shows the CALGreen section number (for example § 4.507.2).

If a standard in the table has a year (e.g., 2016), is that the required edition?

§ 601.1 lists specific identifiers (many include years), but the snippet in § 601.1 does not, by itself, state the code’s general edition‑adoption rule. To determine which edition is enforceable, check the specific CALGreen section that cites the standard or the code’s administrative/adoption language (often in Chapter 1).

Are the standards grouped in any particular order?

Yes — § 601.1 organizes standards by the promulgating agency (e.g., ANSI/ACCA, ACI, etc.) so you can locate standards by organization or by identifier.

More in California Green Building Standards Code (CALGreen)

Ask about the CALGreen

Get cited, plain-English answers on the California Green Building Standards Code (CALGreen) for your project — any code section, any scenario.

Start Free Trial

Related in the CALGreen