CALGreen · California Green Building Standards Code (CALGreen)
What does Section 601.1 list and how do I use the Chapter 6 table of referenced standards?
Chapter 6 is a lookup table: it lists the standards and the agency that publishes them, and shows which CALGreen sections reference each standard (see **§ 601.1**). Use Chapter 6 to identify the standard name/number and the CALGreen provision that uses it, then read that provision to see the actual requirement. Some appendix lists are provided only for convenience and are enforceable only if your local jurisdiction has adopted them.
Last reviewed: July 6, 2026
What the code requires — 2-4 sentences
§ 601.1 says the Chapter 6 tables list the organizations and the standards that are referenced elsewhere in CALGreen and that the standards are grouped by the promulgating agency. Use Chapter 6 as a lookup to find the standard acronym/number, the standard name/title, and the section(s) of CALGreen that reference that standard. § 601.1 is the controlling rule for what Chapter 6 contains.
Use Chapter 6 as a lookup table: it tells you who issued a standard, the standard identifier/title entered in CALGreen, and where CALGreen refers to it.
Requirements in detail
What Chapter 6 actually contains (plain list)
- A list of organizations (promulgating agencies) and the standards they publish. § 601.1 calls out that the chapter “lists the organizations and standards that are referenced in various sections of this document.”
- The table rows show at least these columns: STANDARD ACRONYM or NUMBER, STANDARD NAME or TITLE, and REFERENCED SECTION (the CALGreen section(s) that cite the standard). The table header in the text shows those three columns.
- Some referenced standards appear elsewhere in CALGreen (for example in the appendices or in Chapter 8 commissioning reference lists); some of those appendix reference lists are included only “as a convenience” and are not part of the mandatory code unless specifically adopted by a jurisdiction.
How to use the table — decision checklist (quick)
| Decision / question | What you do in Chapter 6 | Code Reference |
|---|---|---|
| Do I need the exact standard CALGreen cites for a provision? | Find the standard acronym/number or title in Chapter 6, then go to the REFERENCED SECTION column to see the CALGreen section(s) that rely on that standard. | § 601.1 |
| How are standards grouped? | Look under the promulgating agency heading (tables are organized by agency acronym). Chapter 6 groups standards by the publishing organization (promulgating agency). | § 601.1 |
| Is a standard listed in an Appendix binding? | No — some Appendix/Chapter 8 referenced standards are included “as a convenience” and are not part of the code unless adopted locally. Confirm adoption status with the authority having jurisdiction. | Appendix/Chapter 8 notes |
| What if the table doesn't show edition/effective date? | The Chapter 6 header in CALGreen shows the columns and agency grouping. If edition/effective date is not shown in the CALGreen entry, obtain the correct edition from the promulgating agency or ask your authority having jurisdiction — CALGreen’s Chapter 6 lists the identifier and where it’s referenced, but the file text does not guarantee every entry includes edition information. | § 601.1 (table header) |
Practical reading tips
- Always note the REFERENCED SECTION column value and open that CALGreen section first — the code text there tells you how the standard is being used. Chapter 6 is a cross‑reference tool, not the primary regulatory language.
- If a referenced standard is needed to satisfy a requirement in CALGreen, you must comply with the CALGreen provision that cites it (the standard is used to define methods, test procedures, or performance requirements where CALGreen references it). The table shows where to find those provisions.
Exceptions & special cases
- Appendix/commissioning referenced standards may be provided for user convenience and are not automatically part of the mandatory code unless adopted by the local jurisdiction; verify adoptive status before relying on an appendix standard as a compliance path.
- Some voluntary measures and appendices are intended for optional local adoption (CALGreen notes that voluntary measures “may be mandatory if adopted by a city, county, or city and county as specified in Section 101.7”). If you rely on a voluntary appendix, check whether your jurisdiction has adopted it.
- The Chapter 6 table gives the cross‑reference but not always the administrative rule about how a standard applies (if CALGreen has a separate “application” clause elsewhere, that clause controls). The materials retrieved for § 601.1 do not include a standalone CALGreen phrase that tells you “the application of the referenced standards shall be as specified in …” (other California codes use that language with a section reference). If you need an application rule, confirm in the applicable CALGreen section or ask the authority having jurisdiction.
Common mistakes
- Assuming every standard listed in an appendix or in Chapter 6 is automatically mandatory — some appendix lists are convenience documents and require local adoption to be enforceable.
- Citing the wrong edition of a standard because Chapter 6 entry lacks the edition field — always confirm edition/effective date from the promulgating agency or the AHJ when the CALGreen table does not show it.
- Treating Chapter 6 as the normative text for a requirement — Chapter 6 cross‑references standards; the actual legal requirement (and any exceptions) appear in the CALGreen section(s) that cite the standard. Start at the referenced CALGreen section, not only the Chapter 6 entry.
Worked example — lookup and use (concrete)
Scenario: Your project’s HVAC balancing work references an industry standard named “Total System Balance” that you’ve heard is required.
- Open CALGreen Chapter 6 and search the table for the standard (look up the promulgating agency or the title). The Chapter 6 table lists Total System Balance under the appropriate agency/entry and shows the CALGreen section(s) that reference it (for example, the table shows a “Total System Balance” entry with 5.410.4.3.1 and related cross references).
- Go to CALGreen § 5.410.4.3.1 (the referenced CALGreen provision). Read that section to see how CALGreen uses the standard — it will state whether the standard defines test method, acceptance criteria, or an installer responsibility. The Chapter 6 entry only told you where to look; the actual requirement is in § 5.410.4.3.1.
- Confirm the edition or effective date of “Total System Balance.” If Chapter 6 does not list the edition, obtain the edition from the promulgating agency or confirm with the building official (the Chapter 6 table provides the identifier and the referenced section but may not contain the edition field in every case).
- If the standard you found is listed in an appendix or in Chapter 8 commissioning reference lists that are “convenience” documents, verify whether your jurisdiction has adopted that appendix as mandatory before assuming it’s an enforceable compliance path.
Related provisions
- § 601.1 — Chapter 6 general statement: lists organizations and standards; grouped by promulgating agency.
- § 5.410.2 — Commissioning (referenced by Chapter 8 sample/commissioning materials). See Appendix/Chapter 8 cross‑references for commissioning reference lists.
- Chapter 8 / Appendix — Compliance forms, worksheets and reference material; some reference lists here are provided “as a convenience” and may not be mandatory unless adopted locally.
- § 101.7 — (See note in CALGreen about local adoption of voluntary measures and appendices — voluntary measures may become mandatory if adopted by a local jurisdiction.)
Code references
Grounded in the retrieved California Green Building Standards Code (CALGreen) — click a citation to read the verbatim passage:
CALGreen § 6-1 High relevance — show source text
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 6-1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
6-2 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
6 REFERENCED ORGANIZATIONS AND STANDARDS
SECTION 601—GENERAL
601.1 This chapter lists the organizations and standards that are referenced in various sections of this document. The standards are listed according the promulgating agency of the standard.
STANDARD ACRONYM or
NUMBERSTANDARD NAME or TITLE REFERENCED
SECTION~~**AABC **~~Associated Air Balance Council, 1518 K St NW, Washington, DC
20005www.aabc.com~~**AABC **~~Associated Air Balance Council, 1518 K St NW, Washington, DC
20005www.aabc.com~~**AABC **~~Associated Air Balance Council, 1518 K St NW, Washington, DC
20005www.aabc.comNational Standards, 1989 Total System Balance 5.410.4.3.1, A5.410.5.3.1 ACCAAir Conditioning Contractors of America, 2800 Shirlington Road, Suite 300, Arlington, VA 22206
www.acca.orgACCAAir Conditioning Contractors of America, 2800 Shirlington Road, Suite 300, Arlington, VA 22206
www.acca.orgACCAAir Conditioning Contractors of America, 2800 Shirlington Road, Suite 300, Arlington, VA 22206
www.acca.orgANSI/ACCA 1 Manual D–2016 Residential Duct Systems 4.507.2 ANSI/ACCA 2 Manual J–2016 Residential Load Calculations 4.507.2 ANSI/ACCA 3 Manual S–2014 Residential Equipment Selection 4.507.2 ACI American Concrete Institute, 38800 Country Club Drive, Farmington Hills, MI 48331-3439
www.concrete.orgACI American Concrete Institute, 38800 Country Club Drive, Farmington Hills, MI 48331-3439
www.concrete.orgACI American Concrete Institute, 38800 Country Club Drive, Farmington Hills, MI 48331-3439
www.concrete.orgACI CT-21 Concrete Terminology A5.405.5.2.1.1 ~~**AHAM **~~Association of Home Appliance Manufacturers, 1119 19th Street NW, Suite 402, Washington, D.C. 20026-3627
http://www.aham.org~~**AHAM **~~Association of Home Appliance Manufacturers, 1119 19th Street NW, Suite 402, Washington, D.C. 20026-3627
http://www.aham.org~~**AHAM **~~Association of Home Appliance Manufacturers, 1119 19th Street NW, Suite 402, Washington, D.C. CALGreen § 5.1 High relevance — show source text
5.1 Planning and Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-3 5.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15 5.3 Water Efficiency and Conservation . . . . . . . . . . . . . . . 5-19 5.4 Material Conservation and Resource Efficiency . . . . 5-23 5.5 Environmental Quality . . . . . . . . . . . . . . . . . . . . . . . . . . 5-31
CHAPTER 6 REFERENCED ORGANIZATIONS
AND STANDARDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
601 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-3
CHAPTER 7 INSTALLER AND SPECIAL
INSPECTOR QUALIFICATIONS . . . . . . . . . . . . . . . . . . . . . . 7-3 701 General (Reserved) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-3 702 Qualifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-3
703 Verifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-3
CHAPTER 8 COMPLIANCE FORMS, WORKSHEETS AND
REFERENCE MATERIAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
Worksheet (WS-1) Baseline Water Use: Baseline Water Use Calculation Table . . . . . . . . . . .8-3
Worksheet (WS-2) Water Use Reduction: 12-, 20- or 25-Percent Reduction Water Use Calculation Table . . . . . . . . . . . . . . . . . . .8-4
Worksheet (WS-3) 5.105.2 Building Reuse . . . . . . . . . . . . . . . .8-4 Worksheet (WS-4) 5.409.2 Whole Building Life Cycle Assessment:. . . . . . . . . . . . . . . . . . . . . . . . .8-5 Worksheet (WS-5) 5.409.3 Product GWP Compliance—Prescriptive Path: . . . . . . . . . . . . . . . .8-5
Worksheet (WS-6) A5.105.2 Building Reuse Tier 1 and Tier 2:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
Worksheet (WS-7) A5.409.2 Whole Building Life Cycle Assessment: . . . . . . . . . . . . . .
CALGreen § 44-2 High relevance — show source text
44-2 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
Part IX— Referenced Standards
44 REFERENCED STANDARDS
Notwithstanding California laws and regulations, these referenced standards shall be applicable only to those California Residential Code sections that are adopted.
User notes:
About this chapter: The one- and two-family dwelling code contains numerous references to standards promulgated by other organizations that are used to provide requirements for materials, products and methods of construction. Chapter 44 contains a comprehensive list of all standards that are referenced in this code. These standards, in essence, are part of this code to the extent of the reference to the standard.
This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this document that reference the standard. The application of the referenced standards shall be as specified in Section R102.4.
ABTG Applied Building Technology Group LLC6300 Enterprise Lane Madison, WI 53719
ANSI/ABTG FS 100—2012 (R2018): Standard Requirements for Wind Pressure Resistance of Foam Plastic Insulation Sheathing Used in Exterior Wall Covering Assemblies
R303.8
ACCA Air Conditioning Contractors of America 1330 Braddock Place, Suite 350 Alexandria, VA 22314
ANSI/ACCA 2 Manual J—2016: Residential Load Calculation
Table R301.2
ACI American Concrete Institute 38800 Country Club Drive Farmington Hills, MI 48331
318—19: Building Code Requirements for Structural Concrete R402.2, R404.1.3, R404.1.3.1, Table R404.1.3.2(2), Table R404.1.3.2(5), Table R404.1.3.2(6), Table R404.1.3.2(7), Table R404.1.3.2(8), R404.1.3.3, R404.1.3.4, R404.1.4.2, R404.5.1, R608.1, R608.1.1, R608.1.2, R608.2, R608.5.1, R608.6.1, R608.8.2, R608.9.2, R608.9.3
332—20: Residential Code Requirements for Structural Concrete
R402.2, R403.1, R404.1.3, R404.1.3.4, R404.1.4.2, R506.1
AISI American Iron and Steel Institute 25 Massachusetts Avenue, NW Suite 800 Washington, DC 20001
AISI S100—16 (2020) w/S2—20: North American Specification for the Design of Cold-Formed Steel Structural Members, 2016 Edition (Reaffirmed 2020), with Supplement 2, 2020 Edition
R608.9.2, R608.9.3
AISI S220—20: North American Standard for Cold-Formed Steel Nonstructural Framing, 2020 Edition
R702.3.3
AISI S230—19: North American Standard for Cold-Formed Steel Framing—Prescriptive Method for One and Two Family Dwellings, 2019 Edition
CALGreen § 5-3 Medium relevance — show source text
502 Reserved . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-3
503 Ignition-Resistant Construction and Material. . . . . .5-3
504 Ignition-Resistant Construction. . . . . . . . . . . . . . . . . .5-4
505 Reserved . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-9
506 Reserved . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-9
507 Replacement or Repair of Roof Coverings. . . . . . . . .5-9
CHAPTER 6 FIRE PROTECTION REQUIREMENTS. . . . . . .6-3
601 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
602 Fire Protection Plans . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
603 Vegetation Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
604 Maintenance of Defensible Space . . . . . . . . . . . . . . . 6-5
605 Spark Arrestors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
606 Liquefied Petroleum Gas Installations . . . . . . . . . . . 6-5
607 Storage of Firewood and Combustible Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
608 Building Siting and Setbacks . . . . . . . . . . . . . . . . . . . . 6-5
609 Ridgelines, Fuel Breaks and Greenbelts . . . . . . . . . . . 6-6
610 Fire Safe Development Regulations . . . . . . . . . . . . . . 6-7
611 Subdivision Review Survey . . . . . . . . . . . . . . . . . . . . . . 6-7
612 General Plan Safety Element . . . . . . . . . . . . . . . . . . . . 6-7
CHAPTER 7 REFERENCED STANDARDS . . . . . . . . . . . . . .7-3
APPENDIX A GENERAL REQUIREMENTS . . . . APPENDIX A-3
A101 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A-3
A102 Vegetation Control. . . . . . . . . . . . . . . . . . . APPENDIX A-3
CALGreen § 1616.2.2.1 Medium relevance — show source text
Demolition 3303 Design Flood 1612 Design Strength Column splice 1616.2.2.1 Conformance to standards 1706.1
New materials 1706.2 Designated Seismic System 1704.3.2, 1704.4, 1704.5 Seismic certification 1705.14.3
Special inspection 1705.13.4 Detached Single-family Dwelling 202 Detectable Warning 202 Diaphragms 202 Analysis 1604.4 Ceilings 2508.6
Penetrations 714
Permit application 105.1 Relocation 107.2.8
Retention 107.5
Review 107.3
Roof assemblies 1503
Roof live load 1603.1.2
Roof rain load data 1603.1.9
Roof snow load 1603.1.3
Seismic 1603.1.5, 1705.14.2, 1705.14.3 Site plan 107.2.6 Special loads 1603.1.8 Temporary structures 3103.2 Wind data 1603.1.4 Construction Types 202, Chapter 6 Aircraft-related occupancies 412.2.1, Table 412.3.6, 412.5.2 Classification 602 Combustible material in Type I and Type II construction 603, 805 Covered and open mall buildings 402.4.1 Fire district D102.2.3
Fire resistance Table 601, Table 705.5 High-rise 403.2 Type I Table 601, 602.2, 603 Type II Table 601, 602.2, 603 Type III Table 601, 602.3 Type IV Table 601, 602.4 Type V Table 601, 602.5 Underground buildings 405.2 Continuity Head-Of-Wall System 202 Continuous Insulation (ci) 202 Contractor’s Responsibilities 901.5, 1704.4 Control Area 414.2, 707.3.8 Construction 414.2.1
Fire-resistance rating 414.2.4 Maximum allowed quantities 414.2.2 Number 414.2.3 Conventional Light-frame Construction 2302.1, 2308 Additional seismic requirements 2308 Braced wall lines 2308.10 Design of elements 2308.8 Floor joists 2308.8.2 Foundation plates or sills 2308.7 Girders 2308.8.1 Roof and ceiling framing 2308.11 Wall framing 2308.9 Conveying System S3004 Cornices
Definition 202 Draftstopping 718.2.6 Live load Table 1607.1
Masonry 2104.1.2 Projection 705.2, 705.2.3.1 Public right-of-way encroachments 3202.3.2, 3202.3.3 Correctional Treatment Centers
[OSHPD 4] 1227 Application 1227.2 Ceiling heights 1227.8 Corridors 1227.5
CALGreen § 6.1507 Medium relevance — show source text
LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
where× = Condenser DT + LIFT
COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
where× = Condenser DT + LIFT
COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
where× = Condenser DT + LIFT
COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
where× = Condenser DT + LIFT
COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
where× = Condenser DT + LIFT
COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
where× = Condenser DT + LIFT
COPadj = Kadj * COPstd|A6.207.1.2 Controls for heat pumps with supplementary electric resistance heaters. Heat pumps with supplementary electric resistance heaters shall have controls:
A6.207.1.2.1 That prevent supplementary heater operation when the heating load can be met by the heat pump alone; and
CALGreen § 1801.1 Medium relevance — show source text
Chapter 16 Stationary Power Plants. This chapter provides minimum requirements for stationary fuel cell power plants. A fuel cell is a device that produces electricity by a chemical reaction. Fuel cells have been used mostly for satellites. However, the costs of fuel cells have decreased to a point where they are now economically attainable. With the increase in electricity costs, fuel cells are being considered as an alternative for producing electricity.
xvi 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FORMAT OF THE UNIFORM MECHANICAL CODE
Chapter 17 Geothermal Energy Systems and Ambient Temperature Loops. Chapter 17 regulates the design, installation, construction, and location of geothermal energy systems and ambient temperature loops (ATLs). This chapter provides the minimum safety requirements for various types of geothermal systems, including building systems coupled with a ground-heat exchangers, submerged heat exchangers using water-based fluid as a heat transfer medium, and groundwater (well). For ease of use and clarification on the applicability of geothermal provisions, Chapter 17 is divided into five parts pertaining to general provisions for all types of geothermal systems, closed-loop systems, open-loop systems, direct-exchange (DX) systems, and ambient temperature loops. For district ambient temperature loops, including those utilizing multiple hybrid systems, Part I through Part V are applicable.
In order to properly design a geothermal system, it is important to know the seasonal variation in the soil temperature, as well as the soil’s inherent capability to store and transmit heat, namely its heat capacity and thermal conductivity. In addition, a properly designed heat pump distribution system is essential for the distribution of geothermal energy.
Materials for piping and tubing must meet the working temperature and pressure of the system. Furthermore, materials must be compatible with the transfer medium to prevent deformation, bursting, or any chemical action between the material and the transfer medium. Approved materials for indoor piping, fittings, and accessories that are a part of a groundwater system as well as the allowable joining methods for piping or tubing are provided for application and enforcement purposes.
Chapter 18 Referenced Standards. Chapter 18 provides two comprehensive tables with referenced standards. The standards listed in Table 1801.1 are applied as indicated in the applicable reference section(s). A list of additional approved standards, publications, practices, and guides that are not referenced in specific sections appear in Table 1801.2.
Referenced standards set forth specific details of accepted practices, materials specifications, or test methods in many specialized applications. Standards provide an efficient method of conveying complex information and specifications on the performance requirements for materials, products, systems, application, and installation. The manner and purpose for a standard’s use and, in turn, code compliance, must be definitive in all references to the standard. If the standard is intended to be a requirement for judging code compliance, the code must state its intent for use. The standard should adequately address a defined need and at the same time specify the minimum performance requirements, technical characteristics and methods of testing, and required test results.
The referenced standards tables are organized in a manner that makes it easy to find specific standards in alphabetical order, and by acronym of the publishing agency of the standard. The tables list the title of the standard, the edition, and any addenda. Contact information for each publishing agency is provided at the end of the chapter.
CMC § 2025 Medium relevance — show source text
Systems that carry nonabrasive exhaust, such as smoke, moderate abrasives such as sawdust, and high abrasives such as manganese or acid vapors use product-conveying ducts. Part II provides the minimum fire safety requirements related to the design, installation, inspection, and maintenance of grease-type operations, such as cooking, for both fuel-gas and solid fuel. Cooking produces a significant amount of smoke, fumes, vapors, heat, and other pollutants. Therefore, acceptable kitchen ventilation is necessary to prevent fires from the build-up of grease and to provide the occupants protection from smoke, unpleasant odors, pollutants, and dangerous gases. There are two types of exhaust hoods (Type I and Type II) used in commercial kitchen applications.
xiv 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FORMAT OF THE UNIFORM MECHANICAL CODE
Type I hoods are intended to be installed above equipment or appliances that generate grease or smoke. Type II hoods are intended to be installed above equipment or appliances that generate steam, vapor, heat, or odors and do not generate grease or smoke.
Chapter 6 Duct Systems. Chapter 6 regulates requirements for ducts and plenums that are portions of a heating, cooling, ventilation, or exhaust system. This chapter contains material and installation requirements for metal, gypsum, factory-made, flexible, and plastic ducts. It also contains provisions for duct insulation, dampers, fire protection, and automatic shutoff for the building’s air distribution system. It is worth noting that exhaust ducts are regulated by Chapter 5, and combustion air ducts are regulated by Chapter 7.
Chapter 7 Combustion Air. Chapter 7 regulates combustion air requirements for ventilation and dilution of flue gases for appliances installed in buildings. Fuel-gas appliances not regulated by chapter include direct vent appliances and Type I clothes dryers. Makeup air requirements for Type I clothes dryers are located in Chapter 5. Chapter 7 provides acceptable methods for supplying satisfactory combustion air to ensure proper combustion. Combustion air can be supplied by using indoor combustion air or by introducing the air from the outdoors.
Combustion is the rapid oxidation of fuel to release energy. The oxygen required to release the energy from the fuel normally comes from the air. Incomplete combustion of fuel occurs when inadequate oxygen is provided to the appliance. Combustion is needed to provide ventilation cooling for the casing and internal controls. When a lack of oxygen occurs, some of the carbon is not oxidized, and carbon monoxide forms.
Chapter 8 Chimneys and Vents. Chapter 8 regulates the installation, design, and construction of venting systems for fuel-burning appliances. The provisions addressed within this chapter follow procedures an installer would use to design or evaluate a venting system. Many requirements apply to the design and construction of venting systems, chimneys, installation of gas vents, and the sizing of venting system for a Category I appliance. Sizing venting systems require rigorous engineering calculations. However, the venting sizing requirements and sizing tables in this chapter already perform the calculations for the benefit of the end user.
Combustion appliances produce products of incomplete combustion, including potentially harmful carbon monoxide (CO). It is desirable to vent these products to the outdoors. Although the gas is clean-burning fuel, the products of combustion must not be allowed to collect within a building.
CALGreen § 1974-17 Medium relevance — show source text
E108-2020a|||X||||||||||||||||||||| |CSA||||X|||||||||||||||||||| |DASMA||||X|||||||||||||||||||| |ICC|||X|X|||||||||||||||||||| |IFC-18||||X|||||||||||||||||||| |ISO||||X|||||||||||||||||||| |NFPA|||X|X|||||||||||||||||||| |NFPA 68-13|||X||||||||||||||||||||| |SFM|||X||||||||||||||||||||| |UBC|||X||||||||||||||||||||| |UL||||X|||||||||||||||||||| |UL 790 Edition 9 2022|||X||||||||||||||||||||| |UL 1974-17|||X||||||||||||||||||||| |UL 9540-20|||X||||||||||||||||||||| |UL 9540 Edition 4 2019|||X||||||||||||||||||||| |WDMA||||X||||||||||||||||||||
The state agency does not adopt sections identified with the following symbol: †
2025 CALIFORNIA RESIDENTIAL CODE 44-1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
44-2 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
Part IX— Referenced Standards
44 REFERENCED STANDARDS
Notwithstanding California laws and regulations, these referenced standards shall be applicable only to those California Residential Code sections that are adopted.
User notes:
About this chapter: The one- and two-family dwelling code contains numerous references to standards promulgated by other organizations that are used to provide requirements for materials, products and methods of construction. Chapter 44 contains a comprehensive list of all standards that are referenced in this code. These standards, in essence, are part of this code to the extent of the reference to the standard.
This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this document that reference the standard. The application of the referenced standards shall be as specified in Section R102.4.
ABTG Applied Building Technology Group LLC6300 Enterprise Lane Madison, WI 53719
ANSI/ABTG FS 100—2012 (R2018): Standard Requirements for Wind Pressure Resistance of Foam Plastic Insulation Sheathing Used in Exterior Wall Covering Assemblies
R303.8
ACCA Air Conditioning Contractors of America 1330 Braddock Place, Suite 350 Alexandria, VA 22314
ANSI/ACCA 2 Manual J—2016: Residential Load Calculation
Table R301.2
ACI American Concrete Institute 38800 Country Club Drive Farmington Hills, MI 48331
CALGreen § 408.3 Medium relevance — show source text
2025 CALIFORNIA MECHANICAL CODE 79
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
VENTILATION AIR
408.3 Filters for Skilled Nursing Facilities, Intermedi- ate Care Facilities, and Correctional Treatment Centers.
408.3.1 The air ventilation systems for skilled nursing facilities, intermediate care facilities and correctional treatment centers shall have filter bank efficiencies as listed in Table 4-C.
408.3.2 Airborne infection isolation rooms, protective environment rooms, and sensitive areas in correctional treatment centers shall comply with Section 408.2. 408.4 Filters for Outpatient Facilities.
408.4.1 The air ventilation systems for outpatient facil- ities shall have filter bank efficiencies as listed in Table 4-B.
408.5 Filters for Recirculating Room Units.
408.5.1 Filters for recirculating room units shall comply with Section 407.4.5. Where Table 4-A does not permit air recirculated by means of room units, room units with filtration per Table 4-B are permitted.
409.0 Ducts. [OSHPD 1, 1R, 2, 3, 4 & 5]
409.1 Ducts which penetrate construction, intended for X- ray or other radiation protection, shall not impair the effec- tiveness of the protection.
409.2 Duct linings and their use shall meet the requirements of Chapter 6, California Mechanical Code.
409.3 The anchorage and supporting structural elements for airducts shall be designed to withstand the lateral forces as required by the California Building Code, Title 24, Part 2.
410.0 Laboratory Ventilating Systems and Hoods.
[OSHPD 1, 1R, 2, 3, 4 & 5]
410.1 Laboratory Ventilating Systems. Laboratory ven- tilating systems shall comply with NFPA 99, as required by Section 1224.4.6.4 of the California Building Code.
410.2 Exhaust Hoods and Safety Cabinets. Hoods and safety cabinets may be used for normal exhaust of a space pro- vided minimum air change rates are maintained. If air change standards in Table 4-A do not provide sufficient air for proper operation of exhaust hoods and safety cabinets (when in use), supplementary makeup air (filtered and preheated) shall be provided around these units to maintain the required airflow direction and exhaust velocity. Makeup systems for hoods shall be arranged to minimize “short circuiting” of air and to avoid reduction in air velocity at the point of contaminant capture.
410.3 Laboratory Fume Hoods. Laboratory fume hoods shall meet the following standards:
CALGreen § 1801.1 Medium relevance — show source text
Materials for piping and tubing must meet the working temperature and pressure of the system. Furthermore, materials must be compatible with the transfer medium to prevent deformation, bursting, or any chemical action between the material and the transfer medium. Approved materials for indoor piping, fittings, and accessories that are a part of a groundwater system as well as the allowable joining methods for piping or tubing are provided for application and enforcement purposes.
Chapter 18 Referenced Standards. Chapter 18 provides two comprehensive tables with referenced standards. The standards listed in Table 1801.1 are applied as indicated in the applicable reference section(s). A list of additional approved standards, publications, practices, and guides that are not referenced in specific sections appear in Table 1801.2.
Referenced standards set forth specific details of accepted practices, materials specifications, or test methods in many specialized applications. Standards provide an efficient method of conveying complex information and specifications on the performance requirements for materials, products, systems, application, and installation. The manner and purpose for a standard’s use and, in turn, code compliance, must be definitive in all references to the standard. If the standard is intended to be a requirement for judging code compliance, the code must state its intent for use. The standard should adequately address a defined need and at the same time specify the minimum performance requirements, technical characteristics and methods of testing, and required test results.
The referenced standards tables are organized in a manner that makes it easy to find specific standards in alphabetical order, and by acronym of the publishing agency of the standard. The tables list the title of the standard, the edition, and any addenda. Contact information for each publishing agency is provided at the end of the chapter.
Appendix A Residential Plans Examiner Review Form for HVAC System Design. A residential plans examiner review form is located in this appendix as an example to assist users in identifying whether the HVAC system has followed the approved procedures for system design (loads, equipment, and ducts).
Appendix B Procedures to be Followed to Place Gas Equipment in Operation. Appendix B provides requirements for the procedures that apply after an appliance is installed in place, piped, and connected to its venting system. The requirements include adjusting the burner input, air adjustments, verifying operation of safety shutoffs, automatic ignition, and protective devices, checking draft for vent-connected appliances, and operating instructions.
Appendix C Installation and Testing of Oil (Liquid) Fuel-Fired Equipment. Appendix C governs the installation, testing, or repair of oil or liquid fuel-burning equipment used in buildings or structures and equipment.
Appendix D Fuel Supply: Manufactured/Mobile Home Parks and Recreational Vehicle Parks. The provisions of this appendix apply to the fuel gas piping systems of mobile home and recreational vehicle parks. These provisions also apply to the use, maintenance, and installation for supplying fuel gas for accessory buildings or structures, and building components.
2025 CALIFORNIA MECHANICAL CODE xvii
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
FORMAT OF THE UNIFORM MECHANICAL CODE
Appendix E Sustainable Practices. This appendix provides a comprehensive set of technically sound provisions that encourage sustainable practices and works toward improving the design and construction of mechanical systems that result in a positive long-term environmental impact. Environmental sustainability is important because it involves natural resources that human beings need for economic or manufactured capital. Their sustainability is defined by their reliance
CALGreen § 1701.2 Medium relevance — show source text
1|X|X|X|X||||X||X|X|X|X|X|X|||||||||| |Table 1701.2||X||X|||||||||||||||||||||
This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
2025 CALIFORNIA PLUMBING CODE 333
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
334 2025 CALIFORNIA PLUMBING CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHAPTER 17
REFERENCED STANDARDS
1701.0 General.
1701.1 Standards. The standards listed in Table 1701.1 are
referenced in various sections of this code and shall be con sidered part of the requirements of this document. The standards are listed herein by the standard number and effective
date, the title, application and the section(s) of this code that references the standard. The application of the referenced standard(s) shall be as specified in Section 301.2.2. The promulgating agency acronyms referred to in Table 1701.1 are defined in a list found at the end of the tables.
TABLE 1701.1
Col1 REFERENCED STANDARDS Col3 Col4 STANDARD NUMBER STANDARD TITLE APPLICATION REFERENCED
SECTIONAAMI AAMI AAMI AAMI ANSI/AAMI/ISO 23500-2 Preparation and Quality Management of Fluids for
Haemodialysis and Related Therapies—Part 2: Water Treat-
ment Equipment for Hemodialysis ApplicationsMiscellaneous 614.7 ANSI/AAMI/ISO 23500-3 Preparation and Quality Management of Fluids for
Haemodialysis and Related Therapies—Part 3: Water for
Haemodialysis and Related Therapies.Miscellaneous 614.7 ARCSA ARCSA ARCSA ARCSA ARCSA/ASPE/ANSI 63-
2020Rainwater Catchment Systems Miscellaneous 1602.1 ASME ASME ASME ASME ASME A112.1.2-2012
(R2017)Air Gaps in Plumbing Systems (For Plumbing Fixtures and
Water-Connected Receptors)Fittings Table 603.2 ASME A112.1.3-2000
(R2019)Air Gap Fittings for Use with Plumbing Fixtures, Appliances,
and AppurtenancesFittings Table 603.2 ASME A112.3.1-2007
(R2017)Stainless Steel Drainage Systems for Sanitary DWV, Storm,
and Vacuum Applications,CALGreen § 15-2 Medium relevance — show source text
are listed below|||||||X|||||||||||||||||X| |Chapter / Section||||||||||||||||||||||||| |UBC 15-2|||X|||||||||||||||||||||| |UBC 15-3|||X|||||||||||||||||||||| |UBC 15-4|||X|||||||||||||||||||||| |UL 13-96|||X|||||||||||||||||||||| |UL 38-99|||X|||||||||||||||||||||| |UL 193-04|||X|||||||||||||||||||||| |UL 199-95|||X|||||||||||||||||||||| |UL 228-97|||X|||||||||||||||||||||| |UL 260-04|||X|||||||||||||||||||||| |UL 262-04|||X|||||||||||||||||||||| |UL 268A-09|||X|||||||||||||||||||||| |UL 312-04|||X|||||||||||||||||||||| |UL 346-05|||X|||||||||||||||||||||| |UL 464-03|||X|||||||||||||||||||||| |UL 497B-04|||X|||||||||||||||||||||| |UL 521-99|||X|||||||||||||||||||||| |UL 539-00|||X|||||||||||||||||||||| |UL 632-00|||X|||||||||||||||||||||| |UL 753-04|||X|||||||||||||||||||||| |UL 790_Edition 9-2022_|||X|||||||||||||||||||||| |UL 813-96|||X|||||||||||||||||||||| |UL 857-13||||||||†|†|X|X|X||X|X|||||||||| |UL 864-2014|||X||||||||||||||||||||||
The state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
35-4 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
35 REFERENCED STANDARDS
User notes:
About this chapter: The California Building Code contains numerous references to standards promulgated by other organizations that are used to provide requirements for materials and methods of construction. This chapter contains a comprehensive list of all standards that are referenced in this code. These standards, in essence, are part of this code to the extent of the reference to the standard.
[DSA-SS, DSA-SS/CC, OSHPD 1 & 4] Reference to other chapters. In addition to the code sections referenced, the standards listed in this chapter are applicable to the respective code sections in Chapters 16A, 17A, 18A, 19A, 21A and 22A.
This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this document that reference the standard. The application of the referenced standards shall be as specified in Section 102.4.
AA Aluminum Association, 1400 Crystal Drive, Suite 430, Arlington, VA 22202
CALGreen § 3-4 Medium relevance — show source text
302 Mixed Occupancy Buildings . . . . . . . . . . . . . . . . . . . . . . .3-4 303 Phased Projects. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4 304 Voluntary Tiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4 305 CALGreen Tier 1 and CALGreen Tier 2 . . . . . . . . . . . . . .3-4
306 Voluntary Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
CHAPTER 4 RESIDENTIAL MANDATORY MEASURES . . . . . . 4-3
4.1 Planning and Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-3 4.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-7 4.3 Water Efficiency and Conservation . . . . . . . . . . . . . . . . .4-9 4.4 Material Conservation and Resource Efficiency . . . . 4-11 4.5 Environmental Quality . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
CHAPTER 5 NONRESIDENTIAL MANDATORY MEASURES . . 5-3
5.1 Planning and Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-3 5.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15 5.3 Water Efficiency and Conservation . . . . . . . . . . . . . . . 5-19 5.4 Material Conservation and Resource Efficiency . . . . 5-23 5.5 Environmental Quality . . . . . . . . . . . . . . . . . . . . . . . . . . 5-31
CHAPTER 6 REFERENCED ORGANIZATIONS
AND STANDARDS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
601 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-3
CHAPTER 7 INSTALLER AND SPECIAL
INSPECTOR QUALIFICATIONS . . . . . . . . . . . . . . . . . . . . . . 7-3 701 General (Reserved) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-3 702 Qualifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-3
CALGreen § 12-8 Medium relevance — show source text
(b) Materials intended for application to a wood surface are to be applied to a substrate made of 1 inch by 4 inches (25 mm by 101 mm) nominal “C” and better VG Douglas fir flooring (FSC 70 to 90) or to other species for which the surface burning characteristic is to be measured.
2025 CALIFORNIA REFERENCED STANDARDS CODE 67
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
GUIDE TO MOUNTING TECHNIQUES FOR WALL AND CEILING INTERIOR FINISH MATERIAL
(c) Coating materials intended for application to particular combustible surfaces, but not wood, are to be applied to the specific surface for which they are intended. The coating material and combustible material are to be attached to the substrate board as specified in Section 12-8-1B.1 (d).
(d) Coating materials intended only for field applications to nonflammable surfaces are to be applied to 0.5 in calcium silicate board.
WALL COVERING MATERIAL
Sec. 12-8-1B.6. Wall coverings such as vinyl coatings, wallpaper, etc., of various types are to be mounted on 0.625-inch (16 mm) gypsum wallboard or on the actual substrate to which they are to be applied, using the adhesive and application technique specified by the manufacturer.
FIGURE 12-8-1B-1—TYPICAL STEEL FRAME SUPPORT SYSTEM
FIGURE 12-8-1B-2—MATERIAL FASTENING TECHNIQUE
68 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
GUIDE TO MOUNTING TECHNIQUES FOR WALL AND CEILING INTERIOR FINISH MATERIAL
FIGURE 12-8-1B-3—TYPICAL MOUNTING TECHNIQUE FOR RIGID WALL MATERIALS
Note: When required, additional fasteners may be used to hold up the specimen flush to the wall.
2025 CALIFORNIA REFERENCED STANDARDS CODE 69
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
GUIDE TO MOUNTING TECHNIQUES FOR WALL AND CEILING INTERIOR FINISH MATERIAL
FIGURE 12-8-1B-4—TYPICAL MOUNTING TECHNIQUE FOR FLEXIBLE WALL MATERIALS
70 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
GUIDE TO MOUNTING TECHNIQUES FOR WALL AND CEILING INTERIOR FINISH MATERIAL
FIGURE 12-8-1B-5—TYPICAL MOUNTING TECHNIQUE FOR CEILING MATERIALS
2025 CALIFORNIA REFERENCED STANDARDS CODE 71
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
72 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
POWER-OPERATED EXIT DOORS
STANDARD 12-10-1
STATE FIRE MARSHAL
SCOPE
Sec. 12-10-100.
California Green Building Standards Code (CALGreen) Medium relevance — show source text
K103 Structural Stability . . . . . . . . . . . . . . . . . . . . . APPENDIX K-2
K104 Evacuation Locations. . . . . . . . . . . . . . . . . . . APPENDIX K-3
K105 Space Within the Building . . . . . . . . . . . . . . . APPENDIX K-3
K106 Decks and Balconies That Are
Evacuation Locations. . . . . . . . . . . . . . . . . APPENDIX K-3
K107 Rooftop Evacuation Locations . . . . . . . . . . . APPENDIX K-3
K108 Attics That Are Evacuation Locations . . . . . APPENDIX K-4
K109 Alternate Means of Protection . . . . . . . . . . . APPENDIX K-4
APPENDIX L EARTHQUAKE RECORDING
INSTRUMENTATION . . . . . . . . . . . . . . . . . . . . . APPENDIX L-1
L101 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX L-2
L102 Referenced Standards . . . . . . . . . . . . . . . . APPENDIX L-2
APPENDIX M TSUNAMI-GENERATED
FLOOD HAZARDS. . . . . . . . . . . . . . . . . . . . . . . .APPENDIX M-1
M101 Refuge Structures for Vertical Evacuation from Tsunami-Generated Flood Hazards. . .APPENDIX M-2
M102 Referenced Standards . . . . . . . . . . . . . . . .APPENDIX M-2
APPENDIX N REPLICABLE BUILDINGS . . . . . . . APPENDIX N-1
N101 Administration . . . . . . . . . . . . . . . . . . . . . . . APPENDIX N-2
N102 Definitions. . . . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX N-2
N103 Replicable Design Requirements . . . . . . . APPENDIX N-2
N104 Replicable Design Submittal Requirements. . . . . . . . . . . . . . . . . . . . . . APPENDIX N-2
N105 Review and Approval of Replicable Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX N-3
N106 Site-Specific Application of Approved Replicable Design . . . . . . . . . . . . . . . . . . APPENDIX N-3
N107 Site-Specific Review and Approval of Replicable Design . . . . . . . . . . . . . . . . APPENDIX N-3
APPENDIX O PERFORMANCE-BASED
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX O-1
CALGreen § 602.1 Medium relevance — show source text
VOLUNTARY MEASURES. . . . . . . . . . . . . . . . . APPENDIX A5-3
A5.1 Planning and Design . . . . . . . . . . . . . . . . . APPENDIX A5-3 A5.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . APPENDIX A5-13 A5.3 Water Efficiency and Conservation . . . APPENDIX A5-19 A5.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-25 A5.5 Environmental Quality . . . . . . . . . . . . . . APPENDIX A5-35 A5.6 Voluntary Tiers . . . . . . . . . . . . . . . . . . . . . APPENDIX A5-41 A5.601 CALGren Tier 1 and Tier 2. . . . . . . . . . APPENDIX A5-41
A5.602 CALGreen Verification Guidelines Mandatory Measures Checklist . . . . . . . . . . . . . . . APPENDIX A5-44
A5.602.1 CALGreen Verification Guidelines
Tier 1 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-48
A5.602.2 CALGreen Verification Guidelines
Tier 2 Checklist . . . . . . . . . . . . . . . . . APPENDIX A5-55
APPENDIX A6 VOLUNTARY STANDARDS FOR HEALTH
FACILITIES [OSHPD 1, 2 & 4] . . . . . . . . . . . APPENDIX A6.1-3 A6.1 Site Planning and Design . . . . . . . . . . . APPENDIX A6.1-3 A6.2 Energy Efficiency . . . . . . . . . . . . . . . . . . APPENDIX A6.1-3 A6.4 Material Conservation and Resource Efficiency . . . . . . . . . . . . . APPENDIX A6.1-32 A6.5 Environmental Quality . . . . . . . . . . . . APPENDIX A6.1-33
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INDEX-1
HISTORY NOTE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . HIST-1
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE vii
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
viii 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CALIFORNIA GREEN BUILDING STANDARDS CODE – MATRIX ADOPTION TABLE
CHAPTER 1 – ADMINISTRATION
(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
|Adopting
CALGreen § 8-10 Medium relevance — show source text
8-10 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
Title 23, Waters, California Code of Regulations
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 8-11
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-12 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
Commissioning Referenced Standards for Non-Energy Systems
The following CALGreen Referenced Standards are included herein as a convenience for the users of the California Green Building Standards Code, but they are not considered to be part of the code unless they are officially adopted by a local jurisdiction.
Contents Page Part 1: Standards for Compliance with Building Commissioning 8-14 Part 2: Commissioning Sample Forms and Templates 8-23
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 8-13
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
PART 1 STANDARDS FOR COMPLIANCE WITH BUILDING COMMISSIONING
Reference: Section 5.410.2, Commissioning.
Introduction:
The purpose of this code is to improve public health, safety and general welfare by enhancing the design and construction of buildings through the use of concepts that reduce negative and increase positive environmental impacts. Commissioning is a vital element in this effort.
Definitions used in the CALGreen Cx Reference standard:
Acronyms
BOD Basis of Design
Cx Commissioning
FPT Functional Performance Test
HVAC Heating, Ventilating and Air-Conditioning
O&M Operations and Maintenance
OPR Owner’s Project Requirements
Glossary:
Acceptance Criteria— The conditions that must be met for systems or equipment to meet defined and expected outcomes.
Commissioning (Cx)— Building commissioning as required in this code involves a quality assurance process that begins during design and continues to occupancy. Commissioning verifies that the new building operates as the owner intended and that building staff are prepared to operate and maintain its systems and equipment. Exceptions are allowed for dry storage warehouses of any size and conditioned spaces under 10,000 square feet accessory to them; and for tenant improvements under 10,000 square feet within a larger space.
Owner— The individual or entity holding title to the property on which the building is constructed.
Commissioning Coordinator— The person who coordinates the commissioning process. This can be either a third-party commissioning provider or an experienced member of the design team or owner in-house staff member.
Commissioning Team— The key members of each party involved with the project designated to provide insight and carry out tasks necessary for a successful commissioning project. Team members may include the commissioning coordinator, owner or owner’s representative, building staff, design professionals, contractors or manufacturer’s representatives and testing specialists.
CALGreen § 101.7. Medium relevance — show source text
Green building measures listed in this table may be mandatory if adopted by a city, county, or city and county as specified in Section 101.7.
2. Required prerequisite for this Tier.
3. These measures are currently required elsewhere in statute or in regulation.|1. Green building measures listed in this table may be mandatory if adopted by a city, county, or city and county as specified in Section 101.7.
2. Required prerequisite for this Tier.
3. These measures are currently required elsewhere in statute or in regulation.|2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A4-29
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX A4-30 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
DIVISION A4.7 – RESIDENTIAL MODEL ORDINANCE
A4.701.1 General. The voluntary measures of this code are designed and promulgated to be adopted by reference and made mandatory by local ordinance pursuant to Section 101.7. Jurisdictions wishing to adopt the voluntary provisions of this code as an enforceable regulation governing structures and premises should ensure that certain factual information is included in the adopting ordinance and that the measures are appropriate and achievable and are considered to be suitable as mandatory by the city, county, or city and county. The following sample adoption ordinance addresses several key elements of a code adoption ordinance, including the information required for insertion into the code text.
This code does not limit the authority of city, county, or city and county government to make necessary changes to the provisions contained in this code.
SAMPLE RESOLUTION FOR ADOPTION OF THE TIER 1 OR TIER 2 PROVISIONS OF THE CALIFORNIA GREEN BUILDING STANDARDS CODE WITH OR WITHOUT ADDITIONAL ITEMS NECESSARY TO ADDRESS INNOVATIVE CONCEPTS OR LOCAL ENVIRONMENTAL CONDITIONS.
ATTACHMENT___.
SAMPLE RESOLUTION ADOPTING THE CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDICES AS A MANDATORY REFERENCE STANDARD
CITY OF ________________________
RESOLUTION # __________________
RESOLUTION ADOPTING ENHANCED GREEN BUILDING MEASURES FOR NEW AND EXISTING RESIDENTIAL CONSTRUCTION.
WHEREAS, the City/County of ______’s (City or County) General Plan sets forth goals for preserving and improving the natural and built environment of the City/County, protecting the health of its residents and visitors, and fostering its economy; and
WHEREAS, green building is a holistic approach to design, construction and demolition that minimizes the building’s impact on the environment, the occupants and the community; and
WHEREAS, green buildings benefit building industry professionals, residents and communities by improving construction quality; increasing building durability; reducing utility, maintenance, water and energy costs; creating healthier homes; and enhancing comfort and livability; and
WHEREAS, the California Green Building Standards Code appendices have included voluntary tiers to provide a city, county, or city and county, building professionals, and the general public with a range of voluntary green building measures for builders to choose from when constructing homes in California; and
CALGreen § 207.1.1 Medium relevance — show source text
**
A6.207.1.1 Efficiency.
A6.207.1.2 Controls for heat pumps with supplementary electric resistance heaters.
A6.207.1.3 Thermostats.
A6.207.1.4 Gas-and oil-fired furnace standby loss controls.||
|
|| |A6.207.2 Space conditioning systems.
A6.207.2.1 Supply air temperature reset controls.
A6.207.2.2 Electric resistance heating.
A6.207.2.3 Heat rejection systems.
A6.207.2.4 Hydronic system measures.
A6.207.2.5 Air distribution system duct leakage sealing.
A6.207.2.6 Variable air volume control for single zone systems.||
|
|| |A6.207.3 Service water-heating systems and equipment.
A6.207.3.1 Certification by manufacturers.
A6.207.3.2 Efficiency.
A6.207.3.3 Installation.||
|
|| |A6.207.4 Natural gas central furnaces, cooking equipment and pool and spa heaters.
Pilot lights prohibited.||||| |A6.207.5 Controls for space-conditioning systems.
A6.207.5.1 Thermostatic controls for each zone.
A6.207.5.2 Criteria for zonal thermostatic controls.
A6.207.5.3 Heat pump controls.
A6.207.5.4 Dampers for air supply and exhaust equipment.
A6.207.5.5 Automatic demand shed controls.||
|
|| |A6.207.6 Pipe insulation.||||| |SECTION A6.209 Lighting||||| |A6.209.1 Lighting control devices, ballasts and luminaires.
A6.209.1.1 All devices: Instructions and calibration.
A6.209.1.2 Indicator lights.
**A6.209.1.3 Automatic time switch control devices.CALGreen § 10.3 Medium relevance — show source text
Mixing of continuous sheathing methods CS-WSP, CS-G and CS-PF along a braced wall line shall be permitted. Intermittent methods ABW, PFH and PFG shall be permitted to be used along a braced wall line with continuous sheathed methods, provided that the length of required bracing for that braced wall line is determined in accordance with Table R602.10.3(1) or R602.10.3(3) using the highest value of the bracing methods used.
In Seismic Design Categories A and B, and for detached one- and two-family dwellings in Seismic Design Category C, mixing of intermittent bracing methods along the interior portion of a braced wall line with continuous sheathing methods CS-WSP, CS-G and CS-PF along the exterior portion of the same braced wall line shall be permitted. The length of required bracing shall be the highest value of all intermittent bracing methods used in accordance with Table R602.10.3(1) or R602.10.3(3) as adjusted by Tables R602.10.3(2) and R602.10.3(4), respectively. The requirements of Section R602.10.7 shall apply to each end of the continuously sheathed portion of the braced wall line. R602.10.4.2 Continuous sheathing methods. Continuous sheathing methods require structural panel sheathing to be used on all sheathable surfaces on one side of a braced wall line including areas above and below openings and gable end walls and shall meet the requirements of Section R602.10.7. R602.10.4.3 Braced wall panel interior finish material. Braced wall panels shall have gypsum wall board installed on the side of the wall opposite the bracing material. Gypsum wall board shall be not less than [1] / 2 inch (12.7 mm) in thickness and be fastened with nails or screws in accordance with Table R602.3(1) for exterior sheathing or Table R702.3.5 for interior gypsum wall board. Spacing of fasteners at panel edges for gypsum wall board opposite Method LIB bracing shall not exceed 8 inches (203 mm). Interior finish material shall not be glued in Seismic Design Categories D 0, D 1 and D 2 . Exceptions:
Interior finish material is not required opposite wall panels that are braced in accordance with Methods GB, BVWSP, ABW, PFH, PFG and CS-PF, unless otherwise required by Section R302.6.
An approved interior finish material with an in-plane shear resistance equivalent to gypsum board shall be permitted to be substituted, unless otherwise required by Section R302.6.
Except for Method LIB, gypsum wall board is permitted to be omitted provided that the required length of bracing in Tables R602.10.3(1) and R602.10.3(3) is multiplied by the appropriate adjustment factor in Tables R602.10.3(2) and R602.10.3(4), respectively, unless otherwise required by Section R302.6. R602.10.4.4 Panel joints. Vertical joints of panel sheathing shall occur over and be fastened to common studs. Horizontal joints of panel sheathing in braced wall panels shall occur over and be fastened to common blocking of a thickness of 1 [1] / 2 inches (38 mm) or greater.
CALGreen § 1.15 Medium relevance — show source text
Exception: The gap-to-side plate thickness ratio shall be permitted to be modified for moment connections with unequal beam sizes on opposite sides of the column or when orthogonal beams acting as drag connections frame into the side plate. 9. Demand Critical fillet welds {2}, {5}, {5a} and {8} shall have Magnetic Particle Testing (MT) in accordance with AWS D1.1 for procedure, technique and acceptance. Inspect the beginning and end of these welds for a 6-inch (152 mm) length, plus any location along the length of the weld where a start and restart is visually noted for a distance of 6 inches (152 mm) on either side of the start/stop location. 10. The connection specific factor to account for peak connection strength, C pr , shall be between 1.15 and 1.35. Calculations shall be submitted to OSHPD for review and approval. 11. For in-plane collectors transferring axial loads into the sideplate connection, coordination between sideplate and the regis- tered design professional in responsible charge will be required to confirm the collector connection is sufficient to transfer the load into the moment frame system. This requirement shall be satisfied by designing the sideplate connections in the first bay of a multi-bay sideplate moment frame or an end bay to have a minimum connection capacity, including combined shear (V u + V g ) and moment (M pr ) demands, of at least 1.2 times the M pr at the plastic hinge location when the axial load, as determined by ASCE 7, Section 12.10.2.1 without Ω o , exceeds 0.1 F y A g of the sideplate beam. 12. A complete frame analysis for gravity and design wind loading using LRFD load combinations in Section 1605A.1 shall be performed including Demand/Capacity Ratios. Frame beam member nominal moment strengths (M n ) used for gravity and design wind loading for the bolted sideplate connection using Class A or Class B faying surfaces shall be taken as 0.80 F y Z for frame beams up to 300 plf and 0.60 F y Z for frame beams greater than 300 plf. 13. For moment frame beams with maximum beam shear greater than 90 percent of the vertical bolt shear capacity, a second- ary check is to be provided to confirm the vertical bolt shear capacities are sufficient. 14. Bolted sideplate connections used on heavy-shallow frame beams for beams greater than 200 plf and shallower than 24 inches (610 mm) in depth shall be considered as an alternative system. 15. Skewed beams shall utilize the link-beam fabrication method with CJP welded splices for skew angles. The skew angle shall be less than 15 degrees. 16. For two-sided bolted sideplate connections sharing the same side plates at the same height and depth across the column, the vertical offset in the beams shall not exceed 10 inches (254 mm).
CALGreen § 416.0 Medium relevance — show source text
416.0 Emergency Eyewash and Shower Equipment. 416.1 Application. Emergency eyewash and shower equipment shall comply with ISEA Z358.1. 416.2 Water Supply. Emergency eyewash and shower equipment shall not be limited in the water supply flow rates. Where hot and cold water is supplied to an emergency shower or eyewash station, the temperature of the water supply shall be controlled by a temperature actuated mixing valve complying with ASSE 1071. Where water is supplied directly to an emergency shower or eyewash station from a water heater, the water heater shall comply with ASSE 1085. The flow rate, discharge pattern, and temperature of flushing fluids shall be provided in accordance with ISEA Z358.1. 416.3 Installation. Emergency eyewash and shower equipment shall be installed in accordance with the manufacturer’s
installation instructions.
416.4 Location. Emergency eyewash and shower equipment shall be located on the same level as the hazard and accessible for immediate use. The path of travel shall be free of obstructions and shall be clearly identified with signage. 416.5 Drain. A drain shall not be required for emergency eyewash or shower equipment. Where a drain is provided, the discharge shall be in accordance with Section 811.0.
417.0 Faucets and Fixture Fittings. 417.1 Application. Faucets and fixture fittings shall comply with ASME A112.18.1/CSA B125.1. Fixture fittings covered under the scope of NSF/ANSI/CAN 61 shall comply with the requirements of NSF/ANSI/CAN 61. 417.1.1 Wash Fountains. [BSC-CG & DSA-SS] Wash fountains shall have a maximum flow rate of not more than 1.8 gallons (6.81 L) per minute/20 [rim space (inches) at 60 psi] in compliance with Chapter 5, Divi- sion 5.3 of the California Green Building Standards Code (CALGreen). 417.1.2 Metering Faucets for Wash Fountains.
[BSC-CG & DSA-SS] Metering faucets for wash foun- tains shall have a maximum flow rate of not more than 0.20 gallons (0.76 L) per cycle/20 [rim space (inches) at 60 psi] in compliance with Chapter 5, Division 5.3 of the California Green Building Standards Code (CALGreen).
417.2 Deck Mounted Bath/Shower Valves. Deck mounted bath/shower transfer valves with integral backflow protection shall comply with ASME A112.18.1/CSA B125.1.
This shall include handheld showers, and other bathing appliances mounted on the deck of bathtubs or other bathing appliances that incorporate a hose or pull out feature. 417.3 Handheld Showers. Handheld showers shall comply with ASME A112.18.1/CSA B125.1. Handheld showers with integral backflow protection shall comply with ASME A112.18.1/CSA B125.1 or shall have a backflow prevention device that complies with ASME A112.18.3 or ASSE 1014. 417.4 Faucets and Fixture Fittings with Hose Con- **nected Outlets.
CALGreen § 15-11 Medium relevance — show source text
are listed below||||||||X||||||||||||||| |Chapter/Section||||||||||||||||||||||| |WS-3||||||||X||||||||||||||| |WS-4||||||||X||||||||||||||| |WS-5||||||||X||||||||||||||| |WS-9||||||||X||||||||||||||| |IES TM-15-11 Table A-1||||||||X||||||||||||||| |Table 130.2-A||||||||X||||||||||||||| |Table 1302.2-B||||||||X|||||||||||||||
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 8-1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-2 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8 COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
[BSC] Sample forms found in “A Guide to the California Green Building Standards Code (Nonresidential)” located at https://www.dgs.ca.gov/BSC/Resources/Page-Content/Building-Standards-Commission-Resources-List-Folder/CALGreen may be used to assist in documenting compliance with the waste management plan and other provisions of this code.
[HCD 1] Sample forms located at www.hcd.ca.gov/building-standards/calgreen/cal-green-forms.shtml may be used to assist in documenting compliance with CALGreen . WORKSHEET (WS-1) BASELINE WATER USE
BASELINE WATER USE CALCULATION TABLE Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10 FIXTURE TYPE FLOW RATE DURATION DAILY USES OCCUPANTS1 GALLONS PER DAY Showerheads 1.8 gpm @ 80 psi × 5 min. × 1 × Note 1a = Lavatory faucets nonresidential 0.5 gpm @ 60 psi × .25 min. × 3 × = Kitchen faucets 1.8 gpm @ 60 psi × 4 min. × 1 × Note 1b = Replacement aerators 2.2 gpm × × × = Wash fountains 1.8 gpm/20 [rim
space(in.)@ 60 psi]× × × = Metering faucets 0.20 gal/cycle × × 3 × = Metering faucets for wash
fountains0.20 gal/cycle/20 [rim
space(in.CALGreen § 8-10 Medium relevance — show source text
Construction Waste Management (CWM) Acknowledgment
Note: This sample form may be used to assist in documenting compliance with the waste management plan.
Project Name:
Job Number:_
Project Manager: ________________________________________________
Waste Hauling Company: _________________________________________Col2 Col3 Col4 CWM Plan Acknowledgment CWM Plan Acknowledgment CWM Plan Acknowledgment CWM Plan Acknowledgment The Foreman for each new Subcontractor that comes on site is to receive a copy of the Construction Waste Management Plan and
complete this Acknowledgment Form.
I have read the Waste Management Plan for the project; I understand the goals of this plan and agree to follow the procedures described in this
plan.The Foreman for each new Subcontractor that comes on site is to receive a copy of the Construction Waste Management Plan and
complete this Acknowledgment Form.
I have read the Waste Management Plan for the project; I understand the goals of this plan and agree to follow the procedures described in this
plan.The Foreman for each new Subcontractor that comes on site is to receive a copy of the Construction Waste Management Plan and
complete this Acknowledgment Form.
I have read the Waste Management Plan for the project; I understand the goals of this plan and agree to follow the procedures described in this
plan.The Foreman for each new Subcontractor that comes on site is to receive a copy of the Construction Waste Management Plan and
complete this Acknowledgment Form.
I have read the Waste Management Plan for the project; I understand the goals of this plan and agree to follow the procedures described in this
plan.DATE SUBCONTRACTOR COMPANY NAME FOREMAN NAME SIGNATURE 8-10 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
Title 23, Waters, California Code of Regulations
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 8-11
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
8-12 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
Commissioning Referenced Standards for Non-Energy Systems
The following CALGreen Referenced Standards are included herein as a convenience for the users of the California Green Building Standards Code, but they are not considered to be part of the code unless they are officially adopted by a local jurisdiction.
Contents Page Part 1: Standards for Compliance with Building Commissioning 8-14 Part 2: Commissioning Sample Forms and Templates 8-23
CALGreen § 1801.1 Medium relevance — show source text
REFERENCED STANDARDS
TABLE 1801.1 (continued) « REFERENCED STANDARDS
2025 CALIFORNIA MECHANICAL CODE 373
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFERENCED STANDARDS
» TABLE 1801.1 (continued) REFERENCED STANDARDS
374 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFERENCED STANDARDS
TABLE 1801.1 (continued) « REFERENCED STANDARDS
2025 CALIFORNIA MECHANICAL CODE 375
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFERENCED STANDARDS
» TABLE 1801.1 (continued) REFERENCED STANDARDS
376 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFERENCED STANDARDS
TABLE 1801.1 (continued) « REFERENCED STANDARDS
2025 CALIFORNIA MECHANICAL CODE 377
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
REFERENCED STANDARDS
» 1801.2 Standards, Publications, Practices, and Guides. and guides shall be as specified in Section 302.1.2. The prom The standards, publications, practices and guides listed in Table ulgating agency acronyms are found at the end of the table. 1801.2 are not referenced in other sections of this code. The application of the referenced standards, publications, practices
»
TABLE 1801.2
Col1 STANDARDS, PUBLICATIONS, PRACTICES, AND GUIDES Col3 DOCUMENT NUMBER DOCUMENT TITLE APPLICATION ACCA ACCA ACCA ACCA Manual N-2012 Commercial Load Calculations Ducts ACCA Manual Q-1990 Low Pressure, Low Velocity Duct System Design Ducts AHAM AHAM AHAM AHAM RAC-1-2020 Energy Measurement Test Procedure for Room Air Conditioners Air Conditioners AHRI AHRI AHRI AHRI 310/380-2017 Packaged Terminal Air Conditioners and Heat Pumps (Same as CSA C744) Air Conditioners AHRI 340/360-2019 Performance Rating of Commercial and Industrial Unitary Air-Conditioning
and Heat Pump EquipmentAir-Source Heat Pumps AHRI 390-2021 Performance Rating of Single Package Vertical Air-Conditioners and Heat
PumpsAir Conditioners AHRI 400-2015 Performance Rating of Liquid to Liquid Heat Exchangers Heat Exchangers AHRI 550/590-2020 Performance Rating of Water-Chilling and Heat Pump Water-Heating Pack-
ages Using the Vapor Compression CycleWater-Source Heat
Frequently asked questions
What if Chapter 6 lists a standard but no edition or date?
Confirm the correct edition with the promulgating agency or the authority having jurisdiction. The Chapter 6 table provides the identifier and cross‑reference but may not include full edition details in every entry.
Are standards in the appendices enforceable statewide?
Not automatically. CALGreen notes that some appendix referenced standards are included as a convenience and are not part of the code unless officially adopted by the local jurisdiction. Always check local adoption.
Do I ever need to read Chapter 6 instead of the cited section?
Use Chapter 6 to locate the standard and the CALGreen section(s) that rely on it; the substantive requirement is in the CALGreen section that cites the standard, so review that cited section next.
If a CALGreen section references a standard, must I obtain the standard document?
Yes — when a CALGreen provision delegates a method, test, or performance requirement to a standard, you need the standard text (and the correct edition) to perform or document compliance; Chapter 6 tells you which standard to obtain.
Where do I confirm whether a voluntary appendix measure was adopted locally?
Check your locality’s adoption ordinance or the adopting-agency matrix referenced in CALGreen (local resolutions or adoption tables indicate whether voluntary appendices were adopted). CALGreen notes voluntary measures may be adopted locally (see Section 101.7 context).
More in California Green Building Standards Code (CALGreen)
- Administration (Chapter 1)
- Nonresidential Voluntary Measures (Appendix A5 — divisions A5.1–A5.6, electives & verification)
- Residential Mandatory Measures — Planning & Design; Energy; Water; Materials; Environmental Quality (Chapter 4)
- Definitions (Chapter 2)
- Voluntary Standards for Health Facilities (Appendix A6 / OSHPD guidance)
- Green Building – scope, mixed occupancies, phased projects (Chapter 3)
- Residential Voluntary Measures (Appendix A4 — divisions A4.1–A4.6, tiers & model ordinance)
- Nonresidential Mandatory Measures — Planning & Design; Energy; Water; Materials; Environmental Quality (Chapter 5)
- Compliance verification, construction documents & checklists (Section 102, Chapter 7, Appendix checklists)
- Referenced Organizations and Standards (Chapter 6)
- Voluntary Tiers and CALGreen Tier 1 / Tier 2 (performance tiers, thresholds)
- Installer and Special Inspector Qualifications (Chapter 7)
Ask about the CALGreen
Get cited, plain-English answers on the California Green Building Standards Code (CALGreen) for your project — any code section, any scenario.
Start Free TrialRelated in the CALGreen
Where in CALGreen do I find the standard identifiers (ANSI/ASTM/ISO/etc.) and their cross-reference sections?
How does the Matrix Adoption Table affect which referenced standards apply to my project?
Chapter 6 — How to use the referenced standards list
California Green Building Standards Code (CALGreen)