810.1 High-Temperature Discharge. No steam pipe shall

California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

be directly connected to plumbing or drainage system, nor shall water having a temperature above 140°F (60°C) be discharged under pressure directly into a drainage system. Pipes from boilers shall discharge by means of indirect waste piping as determined by the Authority Having Jurisdiction or the boiler manufacturer’s recommendations. Such pipes shall be permitted to be indirectly connected by discharging into an open or closed condenser or an intercepting sump of an approved type that will prevent the entrance of steam or such water under pressure into the drainage system. Closed condensers or sumps shall be provided with a vent that shall be taken off the top and extended separately, full size above the roof. Condensers and sumps shall be properly trapped at the outlet with a deep seal trap extending to within 6 inches (152 mm) of the bottom of the tank. The top of the deep seal trap shall have a 3 ⁄ 4 of an inch (19.1 mm) opening located at the highest point of the trap to serve as a siphon breaker. Outlets shall be taken off from the side in such a manner as to allow a waterline to be maintained that will permanently occupy not less than one-half the capacity of the condenser or sump. Inlets shall enter above the waterline. Wearing plates or baffles shall be installed in the tank to protect the shell. The sizes

182 2022 CALIFORNIA PLUMBING CODE

of the blowoff line inlet, the water outlets, and the vent shall be as shown in Table 810.1. The contents of condensers receiving steam or hot water under pressure shall pass through an open sump before entering the drainage system.

TABLE 810.1
PIPE CONNECTIONS IN BLOWOFF
CONDENSERS AND SUMPS
(inches)

BOILER BLOWOFF
WATER OUTLET
VENT
3⁄4*
3⁄4*
2
1
1
21⁄2
11⁄4
11⁄4
3
11⁄2
11⁄2
4
2
2
5
21⁄2
21⁄2
6

For SI units: 1 inch = 25 mm

  • To be used only with boilers of 100 square feet (9.29 m 2 ) of heating surface or less.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
    Overview
    1. 801.1 Applicability. This chapter shall govern the materials,
    2. 801.2 Air Gap or Air Break Required. Indirect waste piping sha…
    3. 801.3 Food and Beverage Handling Establishments.
    4. 801.4 Bar and Fountain Sink Traps. Where the sink in a
    5. 801.5 Connections from Water Distribution System.
    6. 801.6 Sterilizers. Lines, devices, or apparatus such as stills,
    7. 801.7 Drip or Drainage Outlets. Appliances, devices, or
    8. 802.1 General. No plumbing fixtures served by indirect
    9. 803.1 Materials. Pipe, tube, and fittings conveying indirect
    10. 803.2 Copper and Copper Alloys. Joints and connections in copp…
    11. 803.3 Pipe Size and Length. Except as hereinafter provided, th…
    12. 804.1 Standpipe Receptors. Plumbing fixtures or other
    13. 805.1 General. Indirect waste connections shall be provided
    14. 806.1 General. Appliances, devices, or apparatus such as
    15. 807.1 Non-Classed Apparatus. Commercial dishwashing
    16. 807.2 Undiluted Condensate Waste. Where undiluted
    17. 807.3 Domestic Dishwashing Machine. No domestic
    18. 808.1 General. Where permitted by the Authority Having
    19. 809.1 General. Drinking fountains shall be permitted to be
    20. 810.1 High-Temperature Discharge. No steam pipe shall
    21. 810.2 Sumps, Condensers, and Intercepting Tanks.
    22. 810.3 Cleaning. Sumps and condensers shall be provided
    23. 810.4 Strainers. An indirect waste interceptor is receiving
    24. 811.1 Pretreatment. Chemical or liquid industrial wastes
    25. 811.2 Waste and Vent Pipes. Each waste pipe receiving or
    26. 811.3 Joining Materials. Joining materials shall be of
    27. 811.4 Access. Where practicable, the piping shall be readily a…
    28. 811.5 Permanent Record. The owner shall make and keep
    29. 811.6 Chemical Vent. No chemical vent shall intersect
    30. 811.7 Discharge. Chemical wastes shall be discharged in a
    31. 811.8 Diluted Chemicals. The provisions of this section
    32. 812.1 General. Water lifts, expansion tanks, cooling jackets, …
    33. 813.1 General. Pipes carrying wastewater from swimming
    34. 814.1 Condensate Disposal. Condensate from air washers, air-co…
    35. 814.2 Condensate Control. Where any equipment or
    36. 814.3 Condensate Waste Pipe Material and Sizing.
    37. 814.4 Appliance Condensate Drains. Condensate drain
    38. 814.5 Point of Discharge. Air-conditioning condensate
    39. 814.6 Condensate Waste from Air-Conditioning
    40. 814.7 Plastic Fittings. Female plastic screwed fittings shall
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARDS
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR
  31. Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.