814.3 Condensate Waste Pipe Material and Sizing.
California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Condensate waste pipes from air-cooling coils shall be sized in accordance with the equipment capacity as specified in Table 814.3. The material of the piping shall comply with the pressure and temperature rating of the appliance or equipment and shall be approved for use with the liquid being discharged.
TABLE 814.3 MINIMUM CONDENSATE PIPE SIZE
| EQUIPMENT CAPACITY IN TONS OF REFRIGERATION |
MINIMUM CONDENSATE PIPE DIAMETER (inches) |
|---|---|
Up to 20 |
3⁄4 |
21 – 40 |
1 |
41 – 90 |
11⁄4 |
91 – 125 |
11⁄2 |
126 – 250 |
2 |
For SI units: 1 ton of refrigerant = 3.52 kW, 1 inch = 25 mm
The size of condensate waste pipes is for one unit or a combination of units, or as recommended by the manufacturer. The capacity of waste pipes assumes a 1 ⁄ 8 inch per foot (10.4 mm/m) or 1 percent slope, with the pipe running threequarters full at the following pipe conditions:
| Outside Air – 20% | Room Air – 80% | ||
|---|---|---|---|
DB |
WB |
DB |
WB |
90°F |
73°F |
75°F | 62.5°F |
Condensate drain sizing for other slopes or other conditions shall be approved by the Authority Having Jurisdiction.
Air-conditioning waste pipes shall be constructed of materials specified in Chapter 7.
814.3.1 Cleanouts. Condensate drain lines shall be configured or provided with a cleanout to permit the clearing of blockages and for maintenance without requiring the drain line to be cut.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
▸Chapter 8 — INDIRECT WASTES
Overview- 801.1 Applicability. This chapter shall govern the materials,
- 801.2 Air Gap or Air Break Required. Indirect waste piping sha…
- 801.3 Food and Beverage Handling Establishments.
- 801.4 Bar and Fountain Sink Traps. Where the sink in a
- 801.5 Connections from Water Distribution System.
- 801.6 Sterilizers. Lines, devices, or apparatus such as stills,
- 801.7 Drip or Drainage Outlets. Appliances, devices, or
- 802.1 General. No plumbing fixtures served by indirect
- 803.1 Materials. Pipe, tube, and fittings conveying indirect
- 803.2 Copper and Copper Alloys. Joints and connections in copp…
- 803.3 Pipe Size and Length. Except as hereinafter provided, th…
- 804.1 Standpipe Receptors. Plumbing fixtures or other
- 805.1 General. Indirect waste connections shall be provided
- 806.1 General. Appliances, devices, or apparatus such as
- 807.1 Non-Classed Apparatus. Commercial dishwashing
- 807.2 Undiluted Condensate Waste. Where undiluted
- 807.3 Domestic Dishwashing Machine. No domestic
- 808.1 General. Where permitted by the Authority Having
- 809.1 General. Drinking fountains shall be permitted to be
- 810.1 High-Temperature Discharge. No steam pipe shall
- 810.2 Sumps, Condensers, and Intercepting Tanks.
- 810.3 Cleaning. Sumps and condensers shall be provided
- 810.4 Strainers. An indirect waste interceptor is receiving
- 811.1 Pretreatment. Chemical or liquid industrial wastes
- 811.2 Waste and Vent Pipes. Each waste pipe receiving or
- 811.3 Joining Materials. Joining materials shall be of
- 811.4 Access. Where practicable, the piping shall be readily a…
- 811.5 Permanent Record. The owner shall make and keep
- 811.6 Chemical Vent. No chemical vent shall intersect
- 811.7 Discharge. Chemical wastes shall be discharged in a
- 811.8 Diluted Chemicals. The provisions of this section
- 812.1 General. Water lifts, expansion tanks, cooling jackets, …
- 813.1 General. Pipes carrying wastewater from swimming
- 814.1 Condensate Disposal. Condensate from air washers, air-co…
- 814.2 Condensate Control. Where any equipment or
- 814.3 Condensate Waste Pipe Material and Sizing.
- 814.4 Appliance Condensate Drains. Condensate drain
- 814.5 Point of Discharge. Air-conditioning condensate
- 814.6 Condensate Waste from Air-Conditioning
- 814.7 Plastic Fittings. Female plastic screwed fittings shall
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …