814.1 Condensate Disposal.
California Plumbing Code (Title 24, Part 5) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Condensate from air washers, air-cooling coils, condensing appliances, and the overflow from evaporative coolers and similar water-supplied equipment or similar air-conditioning equipment shall be collected and discharged to an approved plumbing fixture or disposal area. Where discharged into the drainage system,
2022 CALIFORNIA PLUMBING CODE 183
INDIRECT WASTES
equipment shall drain using an indirect waste pipe. The waste pipe shall have a slope of not less than 1 ⁄ 8 inch per foot (10.4 mm/m) or 1 percent slope and shall be of an approved corrosion-resistant material not smaller than the outlet size in accordance with Section 814.3 or Section 814.4 for air-cooling coils or condensing appliances, respectively. Condensate or wastewater shall not drain over a public way.
814.1.1 Condensate Pumps. Where approved by the Authority Having Jurisdiction, condensate pumps shall be installed in accordance with the manufacturer’s installation instructions. Pump discharge shall rise vertically to a point where it is possible to connect to a gravity condensate drain and discharged to an approved disposal point. Each condensing unit shall be provided with a separate sump and interlocked with the equipment to prevent the equipment from operating during a failure. Separate pumps shall be permitted to connect to a single gravity indirect waste where equipped with check valves and approved by the Authority Having Jurisdiction.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
▸Chapter 8 — INDIRECT WASTES
Overview- 801.1 Applicability. This chapter shall govern the materials,
- 801.2 Air Gap or Air Break Required. Indirect waste piping sha…
- 801.3 Food and Beverage Handling Establishments.
- 801.4 Bar and Fountain Sink Traps. Where the sink in a
- 801.5 Connections from Water Distribution System.
- 801.6 Sterilizers. Lines, devices, or apparatus such as stills,
- 801.7 Drip or Drainage Outlets. Appliances, devices, or
- 802.1 General. No plumbing fixtures served by indirect
- 803.1 Materials. Pipe, tube, and fittings conveying indirect
- 803.2 Copper and Copper Alloys. Joints and connections in copp…
- 803.3 Pipe Size and Length. Except as hereinafter provided, th…
- 804.1 Standpipe Receptors. Plumbing fixtures or other
- 805.1 General. Indirect waste connections shall be provided
- 806.1 General. Appliances, devices, or apparatus such as
- 807.1 Non-Classed Apparatus. Commercial dishwashing
- 807.2 Undiluted Condensate Waste. Where undiluted
- 807.3 Domestic Dishwashing Machine. No domestic
- 808.1 General. Where permitted by the Authority Having
- 809.1 General. Drinking fountains shall be permitted to be
- 810.1 High-Temperature Discharge. No steam pipe shall
- 810.2 Sumps, Condensers, and Intercepting Tanks.
- 810.3 Cleaning. Sumps and condensers shall be provided
- 810.4 Strainers. An indirect waste interceptor is receiving
- 811.1 Pretreatment. Chemical or liquid industrial wastes
- 811.2 Waste and Vent Pipes. Each waste pipe receiving or
- 811.3 Joining Materials. Joining materials shall be of
- 811.4 Access. Where practicable, the piping shall be readily a…
- 811.5 Permanent Record. The owner shall make and keep
- 811.6 Chemical Vent. No chemical vent shall intersect
- 811.7 Discharge. Chemical wastes shall be discharged in a
- 811.8 Diluted Chemicals. The provisions of this section
- 812.1 General. Water lifts, expansion tanks, cooling jackets, …
- 813.1 General. Pipes carrying wastewater from swimming
- 814.1 Condensate Disposal. Condensate from air washers, air-co…
- 814.2 Condensate Control. Where any equipment or
- 814.3 Condensate Waste Pipe Material and Sizing.
- 814.4 Appliance Condensate Drains. Condensate drain
- 814.5 Point of Discharge. Air-conditioning condensate
- 814.6 Condensate Waste from Air-Conditioning
- 814.7 Plastic Fittings. Female plastic screwed fittings shall
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …