810.1 High-Temperature Discharge. No steam pipe shall
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
be directly connected to plumbing or drainage system, nor shall water having a temperature above 140°F (60°C) be discharged under pressure directly into a drainage system. Pipes from boilers shall discharge by means of indirect waste piping as determined by the Authority Having Jurisdiction or the boiler manufacturer’s recommendations. Such pipes shall be permitted to be indirectly connected by discharging into an open or closed condenser or an intercepting sump of an approved type that will prevent the entrance of steam or such water under pressure into the drainage system. Closed condensers or sumps shall be provided with a vent that shall be taken off the top and extended separately, full size above the roof. Condensers and sumps shall be properly trapped at the outlet with a deep seal trap extending to within 6 inches (152 mm) of the bottom of the tank. The top of the deep seal trap shall have a [3] ⁄ 4 of an inch (19.1 mm) opening located at the highest point of the trap to serve as a siphon breaker. Outlets shall be taken off from the side in such a manner as to allow
a waterline to be maintained that will permanently occupy not
182 2025 CALIFORNIA PLUMBING CODE
INDIRECT WASTES
less than one-half the capacity of the condenser or sump. Inlets shall enter above the waterline. Wearing plates or baffles shall be installed in the tank to protect the shell. The sizes of the blowoff line inlet, the water outlets, and the vent shall be as shown in Table 810.1. The contents of condensers
receiving steam or hot water under pressure shall pass through an open sump before entering the drainage system.
TABLE 810.1
PIPE CONNECTIONS IN BLOWOFF
CONDENSERS AND SUMPS (inches)
| BOILER BLOWOFF | WATER OUTLET | VENT |
|---|---|---|
| 3⁄4* | 3⁄4* | 2 |
1 |
1 | 21⁄2 |
11⁄4 |
11⁄4 | 3 |
11⁄2 |
11⁄2 | 4 |
2 |
2 | 5 |
21⁄2 |
21⁄2 | 6 |
For SI units: 1 inch = 25 mm
- To be used only with boilers of 100 square feet (9.29 m [2] ) of heating surface or less.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
▸Chapter 8 — INDIRECT WASTES
Overview- 801.1 Applicability. This chapter shall govern the materials,
- 801.2 Air Gap or Air Break Required. Indirect waste piping sha…
- 801.3 Food and Beverage Handling Establishments.
- 801.4 Bar and Fountain Sink Traps. Where the sink in a
- 801.5 Connections from Water Distribution System.
- 801.6 Sterilizers. Lines, devices, or apparatus such as stills,
- 801.7 Drip or Drainage Outlets. Appliances, devices, or
- 802.1 General. No plumbing fixtures served by indirect
- 803.1 Materials. Pipe, tube, and fittings conveying indirect
- 803.2 Copper and Copper Alloys. Joints and connections in copp…
- 803.3 Pipe Size and Length. Except as hereinafter provided, th…
- 804.1 Standpipe Receptors. Plumbing fixtures or other
- 805.1 General. Indirect waste connections shall be provided
- 806.1 General. Appliances, devices, or apparatus such as
- 807.1 Non-Classed Apparatus. Commercial dishwashing
- 807.2 Undiluted Condensate Waste. Where undiluted
- 807.3 Domestic Dishwashing Machine. No domestic
- 808.1 General. Where permitted by the Authority Having
- 809.1 General. Drinking fountains shall be permitted to be
- 810.1 High-Temperature Discharge. No steam pipe shall
- 810.2 Sumps, Condensers, and Intercepting Tanks.
- 810.3 Cleaning. Sumps and condensers shall be provided
- 810.4 Strainers. An indirect waste interceptor is receiving
- 811.1 Pretreatment. Chemical or liquid industrial wastes
- 811.2 Waste and Vent Pipes. Each waste pipe receiving or
- 811.3 Joining Materials. Joining materials shall be of
- 811.4 Access. Where practicable, the piping shall be readily a…
- 811.5 Permanent Record. The owner shall make and keep
- 811.6 Chemical Vent. No chemical vent shall intersect
- 811.7 Discharge. Chemical wastes shall be discharged in a
- 811.8 Diluted Chemicals. The provisions of this section
- 812.1 General. Water lifts, expansion tanks, cooling jackets, …
- 813.1 General. Pipes carrying wastewater from swimming
- 814.1 Condensate Disposal. Condensate from air washers, air-co…
- 814.2 Condensate Control. Where any equipment or
- 814.3 Condensate Waste Pipe Material and Sizing.
- 814.4 Appliance Condensate Drains. Condensate drain
- 814.5 Point of Discharge. Air-conditioning condensate
- 814.6 Condensate Waste from Air-Conditioning
- 814.7 Plastic Fittings. Female plastic screwed fittings shall
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS