811.1 Pretreatment. Chemical or liquid industrial wastes
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
that are likely to damage or increase maintenance costs on the sanitary sewer system, detrimentally affect sewage treatment or contaminate surface or subsurface waters shall be pretreated to render them innocuous before discharge into a drainage system. Detailed construction documents of the pretreatment facilities shall be required by the Authority Having Jurisdiction.
Piping conveying industrial, chemical, or process wastes from their point of origin to sewer-connected pretreatment facilities shall be of such material and design as to adequately perform its intended function to the satisfaction of the Authority Having Jurisdiction. Drainage discharge piping from pre
treatment facilities or interceptors shall be in accordance with standard drainage installation procedures.
Copper or copper alloy tube shall not be used for chemical or industrial wastes as defined in this section.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
▸Chapter 8 — INDIRECT WASTES
Overview- 801.1 Applicability. This chapter shall govern the materials,
- 801.2 Air Gap or Air Break Required. Indirect waste piping sha…
- 801.3 Food and Beverage Handling Establishments.
- 801.4 Bar and Fountain Sink Traps. Where the sink in a
- 801.5 Connections from Water Distribution System.
- 801.6 Sterilizers. Lines, devices, or apparatus such as stills,
- 801.7 Drip or Drainage Outlets. Appliances, devices, or
- 802.1 General. No plumbing fixtures served by indirect
- 803.1 Materials. Pipe, tube, and fittings conveying indirect
- 803.2 Copper and Copper Alloys. Joints and connections in copp…
- 803.3 Pipe Size and Length. Except as hereinafter provided, th…
- 804.1 Standpipe Receptors. Plumbing fixtures or other
- 805.1 General. Indirect waste connections shall be provided
- 806.1 General. Appliances, devices, or apparatus such as
- 807.1 Non-Classed Apparatus. Commercial dishwashing
- 807.2 Undiluted Condensate Waste. Where undiluted
- 807.3 Domestic Dishwashing Machine. No domestic
- 808.1 General. Where permitted by the Authority Having
- 809.1 General. Drinking fountains shall be permitted to be
- 810.1 High-Temperature Discharge. No steam pipe shall
- 810.2 Sumps, Condensers, and Intercepting Tanks.
- 810.3 Cleaning. Sumps and condensers shall be provided
- 810.4 Strainers. An indirect waste interceptor is receiving
- 811.1 Pretreatment. Chemical or liquid industrial wastes
- 811.2 Waste and Vent Pipes. Each waste pipe receiving or
- 811.3 Joining Materials. Joining materials shall be of
- 811.4 Access. Where practicable, the piping shall be readily a…
- 811.5 Permanent Record. The owner shall make and keep
- 811.6 Chemical Vent. No chemical vent shall intersect
- 811.7 Discharge. Chemical wastes shall be discharged in a
- 811.8 Diluted Chemicals. The provisions of this section
- 812.1 General. Water lifts, expansion tanks, cooling jackets, …
- 813.1 General. Pipes carrying wastewater from swimming
- 814.1 Condensate Disposal. Condensate from air washers, air-co…
- 814.2 Condensate Control. Where any equipment or
- 814.3 Condensate Waste Pipe Material and Sizing.
- 814.4 Appliance Condensate Drains. Condensate drain
- 814.5 Point of Discharge. Air-conditioning condensate
- 814.6 Condensate Waste from Air-Conditioning
- 814.7 Plastic Fittings. Female plastic screwed fittings shall
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS