605.6 PE

California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-12 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

Plastic Pipe/Tubing and Joints. PE plastic pipe or tubing and fitting joining methods shall be installed in accordance with the manufacturer’s installation instructions and shall comply with Section 605.6.1 or Section 605.6.2.

605.6.1 Heat-Fusion Joints. Heat-fusion joints between PE pipe or tubing and fittings shall be assembled in accordance with Section 605.6.1.1 through Section 605.6.1.3 using butt, socket, or electro-fusion heat methods.

605.6.1.1 Butt-Fusion Joints. Butt-fusion joints shall be made in accordance with ASTM F2620. Joints shall be made by heating the squared ends of two pipes, pipe and fitting, or two fittings by holding ends against a heated element. The heated element shall be removed where the proper melt is obtained and joined ends shall be placed together with applied force.

605.6.1.2 Electro-Fusion Joints. Electro-fusion joints shall be heated internally by a conductor at the interface of the joint. Align and restrain fitting to pipe to prevent movement and apply electric current to the fitting. Turn off the current when the proper time has elapsed to heat the joint. The joint shall fuse together and remain undisturbed until cool.

605.6.1.3 Socket-Fusion Joints. Socket-fusion joints shall be made in accordance with ASTM F2620. Joints shall be made by simultaneously heating the outside surface of a pipe end and the inside of a fitting socket. Where the proper melt is obtained, the pipe and fitting shall be joined by inserting one into the other with applied force. The joint shall fuse together and remain undisturbed until cool.

605.6.2 Mechanical Joints. Mechanical joints between PE pipe or tubing and fittings shall include insert and mechanical compression fittings that provide a pressure seal resistance to pullout. Joints for insert fittings shall be made by cutting the pipe square, using a cutter designed for plastic piping, and removal of sharp edges. Two stainless steel clamps shall be placed over the end of the pipe. Fittings shall be checked for proper size based on the diameter of the pipe. The end of pipe shall be placed over the barbed insert fitting, making contact with the fitting shoulder. Clamps shall be positioned equal to 180 degrees (3.14 rad) apart and shall be tightened to provide a leak tight joint. Compression type couplings and fittings shall be permitted for use in joining PE piping and tubing. Stiffeners that extend beyond the

clamp or nut shall be prohibited. Bends shall be not less than 30 pipe diameters, or the coil radius where bending with the coil. Bends shall not be permitted closer than 10 pipe diameters of a fitting or valve. Mechanical joints shall be designed for their intended use.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
    Overview
    1. 601.1 Applicability.
    2. 601.2 Water Supply and Flushing.
    3. 601.3 Identification of a Potable and Nonpotable Water System.
    4. 601.4 Schools of Cosmetology and Cosmetological
    5. 601.5 Meat and Poultry Processing Plants.
    6. 601.6 Collection Centers and Facilities. [AGR]
    7. 601.7 Renderers. [AGR]
    8. 601.8 Horse Meat and Pet Food Establishments. [AGR]
    9. 602.1 Prohibited Installation.
    10. 602.2 Cross-Contamination.
    11. 602.3 Backflow Prevention.
    12. 602.4 Approval by Authority.
    13. 603.1 General.
    14. 603.2 Approval of Devices or Assemblies.
    15. 603.3 Backflow Prevention Devices, Assemblies, and Methods.
    16. 603.4 General Requirements.
    17. 603.5 Specific Requirements.
    18. 604.1 Pipe, Tube, and Fittings.
    19. 604.2 Lead Content.
    20. 604.3 Copper or Copper Alloy Tube.
    21. 604.4 Hard-Drawn Copper or Copper Alloy Tubing.
    22. 604.5 Flexible Connectors.
    23. 604.6 Cast-Iron Fittings.
    24. 604.7 Malleable Iron Fittings.
    25. 604.8 Previously Used Piping and Tubing.
    26. 604.9 Epoxy Coating.
    27. 604.10 Plastic Materials.
    28. 604.11 Solder.
    29. 604.12 Flexible Corrugated Connectors.
    30. 604.13 Water Heater Connectors.
    31. 605.1 Copper or Copper Alloy Pipe, Tubing,
    32. 605.2 CPVC Plastic Pipe and Joints.
    33. 605.3 CPVC/AL/CPVC Plastic Pipe and Joints.
    34. 605.4 Ductile Iron Pipe and Joints.
    35. 605.5 Galvanized Steel Pipe and Joints.
    36. 605.6 PE
    37. 605.7 PE-AL-PE Plastic
    38. 605.8 PE-RT.
    39. 605.9 PEX
    40. 605.10 PEX-AL-PEX Plastic Tubing and Joints.
    41. 605.11 Polypropylene (PP) Piping and Joints.
    42. 605.12 PVC
    43. 605.13 Stainless Steel Pipe
    44. 605.14 Slip Joints.
    45. 605.15 Dielectric Unions.
    46. 605.16 Joints Between Various Materials.
    47. 606.1 General.
    48. 606.2 Fullway Valve.
    49. 606.3 Multidwelling Units.
    50. 606.4 Multiple Openings.
    51. 606.5 Control Valve.
    52. 606.6 Accessible.
    53. 606.7 Multiple Fixtures.
    54. 606.8 [OSHPD 1, 1R, 2, 3, 4 & 5]
    55. 606.9 Check Valve Required.
    56. 606.10 Leak Detection Devices.
    57. 607.1 General.
    58. 607.2 Private Well Water Tanks.
    59. 607.3 Potable Water Tanks.
    60. 607.4 Venting.
    61. 607.5 Overflow.
    62. 607.6 Valves.
    63. 608.1 Inadequate Water Pressure.
    64. 608.2 Excessive Water Pressure.
    65. 608.3 Expansion Tanks, and Combination Tempera-ture and Pressu…
    66. 608.4 Pressure Relief Valves.
    67. 608.5 Discharge Piping.
    68. 608.6 Water-Heating Devices.
    69. 608.7 Vacuum Relief Valves.
    70. 609.1 Installation.
    71. 609.2 Trenches.
    72. 609.3 Under Concrete Slab.
    73. 609.4 Testing.
    74. 609.5 Unions.
    75. 609.6 Location.
    76. 609.7 Abutting Lot.
    77. 609.8 Pumps.
    78. 609.9 Low-Pressure Cutoff Required on Booster Pumps for Water …
    79. 609.10 Disinfection of Potable Water System.
    80. 609.11 Water Hammer.
    81. 609.12 Pipe Insulation.
    82. 610.1 Size.
    83. 610.2 Pressure Loss.
    84. 610.3 Quantity of Water.
    85. 610.4 Sizing Water Supply and Distribution Systems.
    86. 610.5 Sizing per Appendices A, C,
    87. 610.6 Friction and Pressure Loss.
    88. 610.7 Conditions for Using Table 610.4.
    89. 610.8 Size of Meter and Building Supply Pipe Using Table 610.4.
    90. 610.9 Size of Branches.
    91. 610.10 Sizing for Flushometer Valves.
    92. 610.11 Sizing Systems for Flushometer Tanks.
    93. 610.12 Sizing for Velocity.
    94. 610.13 Exceptions.
    95. 611.1 Application.
    96. 611.2 Air Gap Discharge.
    97. 611.3 Connection Tubing.
    98. 611.4 Sizing of Residential Softeners.
    99. 612.1 Installation.
    100. 613.1 The domestic water-heating equipment and distribu-
    101. 613.2 At least two pieces of hot-water-heating equipment shall
    102. 613.3 Instantaneous heaters are permitted for supplying hot
    103. 613.4 Water storage tanks shall be fabricated of corrosion-
    104. 613.5 Temperature control valves shall be provided to auto-
    105. 613.6 Hot-water distribution system serving patient care areas
    106. 613.7 At fixtures where water exceeding 125°F (52°C) is acces-
    107. 613.8 Sectionalizing valves shall be provided as required by S…
    108. 613.9 Hot water distribution shall include test ports and valved
    109. 614.1 Dialysis water feedlines shall be CPVC (chlorinated
    110. 614.2 All piping for multistation or central dialysis units sh…
    111. 614.3 All valves shall be located in accessible locations.
    112. 614.4 Piping and valves shall be identified according to their…
    113. 614.5 A means of preventing backwashing or flushing of the
    114. 614.6 A continuous audible alarm shall sound at the nurses’
    115. 614.7 Water treatment equipment and water used for dialysis
    116. 614.8 A diagram of all piping as installed shall be posted at …
    117. 615.1 Uses Not Permitted.
    118. 615.2 [OSHPD 1, 1R, 2, 3, 4 & 5]
    119. 615.3 [OSHPD 1, 1R, 2, 3, 4 & 5]
    120. 616.1 For new acute care hospital buildings submitted after
    121. 616.2 The emergency supply of water shall be provided at ade-
    122. 616.3 Storage tank connections and circulation shall be
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARDS
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR
  31. Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
  32. Appendix O — NON-SEWERED SANITATION SYSTEMS
  33. Appendix P — PROFESSIONAL QUALIFICATIONS
  34. Appendix Q — INDOOR HORTICULTURAL FACILITIES
  35. Appendix R — TINY HOUSES
  36. Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.