Chapter 6 — WATER SUPPLY AND DISTRIBUTION
603.3 Backflow Prevention Devices, Assemblies, and Methods.
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Methods. Backflow prevention devices, assemblies, and methods shall comply with Section 603.3.1 through Section 603.3.12.
603.3.1 Air Gap. The minimum air gap to afford backflow protection shall be in accordance with Table 603.3.1. 603.3.2 Atmospheric Vacuum Breaker (AVB). An atmospheric vacuum breaker consists of a body, a checking member, and an atmospheric port.
603.3.3 Hose Connection Backflow Preventer. A hose connection backflow preventer consists of two independent check valves with an independent atmospheric vent between and a means of field testing and draining.
603.3.4 Double Check Valve Backflow Prevention Assembly (DC). A double check valve backflow prevention assembly consists of two independently acting internally loaded check valves, four properly located test cocks, and two isolation valves.
603.3.5 Pressure Vacuum Breaker Backflow Pre- vention Assembly (PVB). A pressure vacuum breaker backflow prevention assembly consists of a loaded air inlet valve, an internally loaded check valve, two properly located test cocks, and two isolation valves. This device shall be permitted to be installed indoors where provisions for spillage are provided. 603.3.6 Spill-Resistant Pressure Vacuum Breaker (SVB). A pressure-type vacuum breaker backflow prevention assembly consists of one check valve force loaded closed and an air inlet vent valve force loaded open to atmosphere, positioned downstream of the check valve and located between and including two tightly closing shutoff valves and test cocks. 603.3.7 Reduced-Pressure Principle Backflow Prevention Assembly (RP). A reduced-pressure principle backflow prevention assembly consists of two independently acting internally loaded check valves, a differential pressure relief valve, four properly located test cocks, and two isolation valves.
603.3.8 Double Check Detector Fire Protection Backflow Prevention Assembly. A double check valve backflow prevention assembly with a parallel
detector assembly consisting of a water meter and a double check valve backflow prevention assembly (DC).
603.3.9 Reduced Pressure Detector Fire Protec- tion Backflow Prevention Assembly. A reducedpressure principle backflow prevention assembly with a parallel detector assembly consisting of a water meter and a reduced-pressure principle backflow prevention assembly (RP).
603.3.10 Dual Check Backflow Preventer. A dual check backflow preventer consists of two independently acting check valves, force loaded to a normally closed position.
603.3.11 Laboratory Faucet Backflow Preven- ters. Laboratory faucet backflow preventers shall comply with ASSE 1035.
603.3.12 Backflow Preventer with Intermediate Atmospheric Vent. A backflow preventer with intermediate atmospheric vent consists of two independently acting check valves, force loaded to a normally closed position, and an intermediate chamber with a means for automatically venting to atmosphere, force loaded to a normally open position.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
▸Chapter 6 — WATER SUPPLY AND DISTRIBUTION
Overview- 601.1 Applicability.
- 601.2 Water Supply and Flushing.
- 601.3 Identification of a Potable and Nonpotable Water System.
- 601.4 Schools of Cosmetology and Cosmetological
- 601.5 Meat and Poultry Processing Plants.
- 601.6 Collection Centers and Facilities. [AGR]
- 601.7 Renderers. [AGR]
- 601.8 Horse Meat and Pet Food Establishments. [AGR]
- 602.1 Prohibited Installation.
- 602.2 Cross-Contamination.
- 602.3 Backflow Prevention.
- 602.4 Approval by Authority.
- 603.1 General.
- 603.2 Approval of Devices or Assemblies.
- 603.3 Backflow Prevention Devices, Assemblies, and Methods.
- 603.4 General Requirements.
- 603.5 Specific Requirements.
- 604.1 Pipe, Tube, and Fittings.
- 604.2 Lead Content.
- 604.3 Copper or Copper Alloy Tube.
- 604.4 Hard-Drawn Copper or Copper Alloy Tubing.
- 604.5 Flexible Connectors.
- 604.6 Cast-Iron Fittings.
- 604.7 Malleable Iron Fittings.
- 604.8 Previously Used Piping and Tubing.
- 604.9 Epoxy Coating.
- 604.10 Plastic Materials.
- 604.11 Solder.
- 604.12 Flexible Corrugated Connectors.
- 604.13 Water Heater Connectors.
- 605.1 Copper or Copper Alloy Pipe, Tubing,
- 605.2 CPVC Plastic Pipe and Joints.
- 605.3 CPVC/AL/CPVC Plastic Pipe and Joints.
- 605.4 Ductile Iron Pipe and Joints.
- 605.5 Galvanized Steel Pipe and Joints.
- 605.6 PE
- 605.7 PE-AL-PE Plastic
- 605.8 PE-RT.
- 605.9 PEX
- 605.10 PEX-AL-PEX Plastic Tubing and Joints.
- 605.11 Polypropylene (PP) Piping and Joints.
- 605.12 PVC
- 605.13 Stainless Steel Pipe
- 605.14 Slip Joints.
- 605.15 Dielectric Unions.
- 605.16 Joints Between Various Materials.
- 606.1 General.
- 606.2 Fullway Valve.
- 606.3 Multidwelling Units.
- 606.4 Multiple Openings.
- 606.5 Control Valve.
- 606.6 Accessible.
- 606.7 Multiple Fixtures.
- 606.8 [OSHPD 1, 1R, 2, 3, 4 & 5]
- 606.9 Check Valve Required.
- 606.10 Leak Detection Devices.
- 607.1 General.
- 607.2 Private Well Water Tanks.
- 607.3 Potable Water Tanks.
- 607.4 Venting.
- 607.5 Overflow.
- 607.6 Valves.
- 608.1 Inadequate Water Pressure.
- 608.2 Excessive Water Pressure.
- 608.3 Expansion Tanks, and Combination Tempera-ture and Pressu…
- 608.4 Pressure Relief Valves.
- 608.5 Discharge Piping.
- 608.6 Water-Heating Devices.
- 608.7 Vacuum Relief Valves.
- 609.1 Installation.
- 609.2 Trenches.
- 609.3 Under Concrete Slab.
- 609.4 Testing.
- 609.5 Unions.
- 609.6 Location.
- 609.7 Abutting Lot.
- 609.8 Pumps.
- 609.9 Low-Pressure Cutoff Required on Booster Pumps for Water …
- 609.10 Disinfection of Potable Water System.
- 609.11 Water Hammer.
- 609.12 Pipe Insulation.
- 610.1 Size.
- 610.2 Pressure Loss.
- 610.3 Quantity of Water.
- 610.4 Sizing Water Supply and Distribution Systems.
- 610.5 Sizing per Appendices A, C,
- 610.6 Friction and Pressure Loss.
- 610.7 Conditions for Using Table 610.4.
- 610.8 Size of Meter and Building Supply Pipe Using Table 610.4.
- 610.9 Size of Branches.
- 610.10 Sizing for Flushometer Valves.
- 610.11 Sizing Systems for Flushometer Tanks.
- 610.12 Sizing for Velocity.
- 610.13 Exceptions.
- 611.1 Application.
- 611.2 Air Gap Discharge.
- 611.3 Connection Tubing.
- 611.4 Sizing of Residential Softeners.
- 612.1 Installation.
- 613.1 The domestic water-heating equipment and distribu-
- 613.2 At least two pieces of hot-water-heating equipment shall
- 613.3 Instantaneous heaters are permitted for supplying hot
- 613.4 Water storage tanks shall be fabricated of corrosion-
- 613.5 Temperature control valves shall be provided to auto-
- 613.6 Hot-water distribution system serving patient care areas
- 613.7 At fixtures where water exceeding 125°F (52°C) is acces-
- 613.8 Sectionalizing valves shall be provided as required by S…
- 613.9 Hot water distribution shall include test ports and valved
- 614.1 Dialysis water feedlines shall be CPVC (chlorinated
- 614.2 All piping for multistation or central dialysis units sh…
- 614.3 All valves shall be located in accessible locations.
- 614.4 Piping and valves shall be identified according to their…
- 614.5 A means of preventing backwashing or flushing of the
- 614.6 A continuous audible alarm shall sound at the nurses’
- 614.7 Water treatment equipment and water used for dialysis
- 614.8 A diagram of all piping as installed shall be posted at …
- 615.1 Uses Not Permitted.
- 615.2 [OSHPD 1, 1R, 2, 3, 4 & 5]
- 615.3 [OSHPD 1, 1R, 2, 3, 4 & 5]
- 616.1 For new acute care hospital buildings submitted after
- 616.2 The emergency supply of water shall be provided at ade-
- 616.3 Storage tank connections and circulation shall be
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS