Chapter 6 — WATER SUPPLY AND DISTRIBUTION
601.3 Identification of a Potable and Nonpotable Water System.
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Water System. In buildings where potable water and nonpotable water systems are installed, each system shall be clearly identified in accordance with Section 601.3.1 through Section 601.3.5.
601.3.1 Potable Water. Green background with white lettering.
601.3.2 Color and Information. Each system shall be identified with a colored pipe or band and coded with paints, wraps, and materials compatible with the piping.
Except as required by Section 601.3.3, nonpotable water systems shall have a yellow background with black uppercase lettering, with the words “CAUTION: NONPOTABLE WATER, DO NOT DRINK.” Each nonpotable system shall be identified to designate the liquid being conveyed, and the direction of normal flow shall be clearly shown. The minimum size of the letters and length of the color field shall comply with Table 601.3.2.
[HCD 1 & HCD 2] An international symbol of a glass in a circle with a slash through it shall be provided sim- ilar to that shown in Figure 601 for all nonpotable water
systems.
WATER SUPPLY AND DISTRIBUTION
FIGURE 601
INTERNATIONAL SYMBOL
The background color and required information shall be indicated every 20 feet (6096 mm) but not less than once per room, and shall be visible from the floor level.
601.3.3 Alternate Water Sources. Alternate water source systems shall have a purple (Pantone color No. 512, 522C, or equivalent) background with uppercase lettering and shall be field or factory marked as follows:
(1) Gray water systems shall be marked in accordance with this section with the words “CAUTION: NONPOTABLE GRAY WATER, DO NOT DRINK” in black letters.
(2) Reclaimed (recycled) water systems for outdoor applications shall be marked in accordance with this section with the words: “CAUTION: NONPOTABLE RECLAIMED (RECYCLED) WATER, DO NOT DRINK” in black letters.
(3) On-site treated water systems shall be marked in accordance with this section with the words: “CAU TION: ON-SITE TREATED NONPOTABLE WATER, DO NOT DRINK” in black letters.
(4) Rainwater catchment systems shall be marked in accordance with this section with the words: “CAU TION: NONPOTABLE RAINWATER, DO NOT DRINK” in black letters.
Exception: [DWR] For recycled water supply systems that are within or a part of a building, the provisions of Section 1505.7 shall apply.
TABLE 601.3.2
MINIMUM LENGTH OF COLOR FIELD AND SIZE OF LETTERS
| OUTSIDE DIAMETER OF PIPE OR COVERING (inches) |
MINIMUM LENGTH OF COLOR FIELD (inches) |
MINIMUM SIZE OF LETTERS (inches) |
|---|---|---|
1⁄2 to 11⁄4 |
8 | 1⁄2 |
11⁄2 to 2 |
8 | 3⁄4 |
21⁄2 to 6 |
12 | 11⁄4 |
8 to 10 |
24 | 21⁄2 |
Over 10 |
32 |
31⁄2 |
For SI units: 1 inch = 25.4 mm
601.3.4 Fixtures. Where vacuum breakers or backflow preventers are installed with fixtures listed in Chapter 17, identification of the discharge side shall be permitted to be omitted.
601.3.5 Outlets. Each outlet on the nonpotable water line that is used for special purposes shall be posted with black uppercase lettering as follows: “CAUTION: NONPOTABLE WATER, DO NOT DRINK.”
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
▸Chapter 6 — WATER SUPPLY AND DISTRIBUTION
Overview- 601.1 Applicability.
- 601.2 Water Supply and Flushing.
- 601.3 Identification of a Potable and Nonpotable Water System.
- 601.4 Schools of Cosmetology and Cosmetological
- 601.5 Meat and Poultry Processing Plants.
- 601.6 Collection Centers and Facilities. [AGR]
- 601.7 Renderers. [AGR]
- 601.8 Horse Meat and Pet Food Establishments. [AGR]
- 602.1 Prohibited Installation.
- 602.2 Cross-Contamination.
- 602.3 Backflow Prevention.
- 602.4 Approval by Authority.
- 603.1 General.
- 603.2 Approval of Devices or Assemblies.
- 603.3 Backflow Prevention Devices, Assemblies, and Methods.
- 603.4 General Requirements.
- 603.5 Specific Requirements.
- 604.1 Pipe, Tube, and Fittings.
- 604.2 Lead Content.
- 604.3 Copper or Copper Alloy Tube.
- 604.4 Hard-Drawn Copper or Copper Alloy Tubing.
- 604.5 Flexible Connectors.
- 604.6 Cast-Iron Fittings.
- 604.7 Malleable Iron Fittings.
- 604.8 Previously Used Piping and Tubing.
- 604.9 Epoxy Coating.
- 604.10 Plastic Materials.
- 604.11 Solder.
- 604.12 Flexible Corrugated Connectors.
- 604.13 Water Heater Connectors.
- 605.1 Copper or Copper Alloy Pipe, Tubing,
- 605.2 CPVC Plastic Pipe and Joints.
- 605.3 CPVC/AL/CPVC Plastic Pipe and Joints.
- 605.4 Ductile Iron Pipe and Joints.
- 605.5 Galvanized Steel Pipe and Joints.
- 605.6 PE
- 605.7 PE-AL-PE Plastic
- 605.8 PE-RT.
- 605.9 PEX
- 605.10 PEX-AL-PEX Plastic Tubing and Joints.
- 605.11 Polypropylene (PP) Piping and Joints.
- 605.12 PVC
- 605.13 Stainless Steel Pipe
- 605.14 Slip Joints.
- 605.15 Dielectric Unions.
- 605.16 Joints Between Various Materials.
- 606.1 General.
- 606.2 Fullway Valve.
- 606.3 Multidwelling Units.
- 606.4 Multiple Openings.
- 606.5 Control Valve.
- 606.6 Accessible.
- 606.7 Multiple Fixtures.
- 606.8 [OSHPD 1, 1R, 2, 3, 4 & 5]
- 606.9 Check Valve Required.
- 606.10 Leak Detection Devices.
- 607.1 General.
- 607.2 Private Well Water Tanks.
- 607.3 Potable Water Tanks.
- 607.4 Venting.
- 607.5 Overflow.
- 607.6 Valves.
- 608.1 Inadequate Water Pressure.
- 608.2 Excessive Water Pressure.
- 608.3 Expansion Tanks, and Combination Tempera-ture and Pressu…
- 608.4 Pressure Relief Valves.
- 608.5 Discharge Piping.
- 608.6 Water-Heating Devices.
- 608.7 Vacuum Relief Valves.
- 609.1 Installation.
- 609.2 Trenches.
- 609.3 Under Concrete Slab.
- 609.4 Testing.
- 609.5 Unions.
- 609.6 Location.
- 609.7 Abutting Lot.
- 609.8 Pumps.
- 609.9 Low-Pressure Cutoff Required on Booster Pumps for Water …
- 609.10 Disinfection of Potable Water System.
- 609.11 Water Hammer.
- 609.12 Pipe Insulation.
- 610.1 Size.
- 610.2 Pressure Loss.
- 610.3 Quantity of Water.
- 610.4 Sizing Water Supply and Distribution Systems.
- 610.5 Sizing per Appendices A, C,
- 610.6 Friction and Pressure Loss.
- 610.7 Conditions for Using Table 610.4.
- 610.8 Size of Meter and Building Supply Pipe Using Table 610.4.
- 610.9 Size of Branches.
- 610.10 Sizing for Flushometer Valves.
- 610.11 Sizing Systems for Flushometer Tanks.
- 610.12 Sizing for Velocity.
- 610.13 Exceptions.
- 611.1 Application.
- 611.2 Air Gap Discharge.
- 611.3 Connection Tubing.
- 611.4 Sizing of Residential Softeners.
- 612.1 Installation.
- 613.1 The domestic water-heating equipment and distribu-
- 613.2 At least two pieces of hot-water-heating equipment shall
- 613.3 Instantaneous heaters are permitted for supplying hot
- 613.4 Water storage tanks shall be fabricated of corrosion-
- 613.5 Temperature control valves shall be provided to auto-
- 613.6 Hot-water distribution system serving patient care areas
- 613.7 At fixtures where water exceeding 125°F (52°C) is acces-
- 613.8 Sectionalizing valves shall be provided as required by S…
- 613.9 Hot water distribution shall include test ports and valved
- 614.1 Dialysis water feedlines shall be CPVC (chlorinated
- 614.2 All piping for multistation or central dialysis units sh…
- 614.3 All valves shall be located in accessible locations.
- 614.4 Piping and valves shall be identified according to their…
- 614.5 A means of preventing backwashing or flushing of the
- 614.6 A continuous audible alarm shall sound at the nurses’
- 614.7 Water treatment equipment and water used for dialysis
- 614.8 A diagram of all piping as installed shall be posted at …
- 615.1 Uses Not Permitted.
- 615.2 [OSHPD 1, 1R, 2, 3, 4 & 5]
- 615.3 [OSHPD 1, 1R, 2, 3, 4 & 5]
- 616.1 For new acute care hospital buildings submitted after
- 616.2 The emergency supply of water shall be provided at ade-
- 616.3 Storage tank connections and circulation shall be
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
- Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS