Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS

1506.5 Water Pressure. On-site treated non-potable gray

California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

water systems supplying water to water closets, urinals, and trap primers shall be capable of delivering not less than 15 pounds-force per square inch (psi) (103 kPa) residual pressure at the highest and most remote outlet served. Where the

TABLE 1505.16 MINIMUM RECLAIMED (RECYCLED) WATER SOURCE TESTING, INSPECTION, AND MAINTENANCE FREQUENCY

DESCRIPTION MINIMUM FREQUENCY*

Inspect and clean filters and screens, and replace (where necessary). [Every 3 months.]

Inspect pumps and verify operation. After initial installation and every 12 months thereafter.

Inspect valves and verify operation. After initial installation and every 12 months thereafter.

Inspect pressure tanks and verify operation. After initial installation and every 12 months thereafter.

Clear debris from and inspect storage tanks, locking devices, and verify operation.

After initial installation and every 12 months thereafter.

Inspect caution labels and marking. After initial installation and every 12 months thereafter.

* Note: Frequency is as described in this table, or more frequently as required by manufacturer’s instructions and/or the Authority Having Jurisdiction.

322 2025 CALIFORNIA PLUMBING CODE

ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS

1506.10.3 Deactivation and Drainage. The on-site treated nonpotable gray water system and the potable water system within the building shall be provided with the required appurtenances (e.g., valves, air/vacuum relief valves, etc.) to allow for deactivation or drainage as required for a cross-connection test in accordance with Section 1502.3.

1506.10.4 Near Underground Potable Water Pipe. On-site treated nonpotable gray water pipes shall be permitted to be run or laid in the same trench as potable water pipes with a 12 inch (305 mm) minimum vertical and horizontal separation where both pipe materials are approved for use within a building. Where piping materials do not meet this requirement the minimum separation shall be increased to 60 inches (1524 mm). The potable water piping shall be installed at an elevation above the on-site treated nonpotable gray water piping. 1506.10.5 Required Filters. A filter permitting the passage of particulates no larger than 100 microns (100 µm) shall be provided for on-site treated nonpotable gray water supplied to water closets, urinals, trap primers, and drip irrigation system s . 1506.10.6 Disinfection. Where the intended use of onsite treated nonpotable gray water requires disinfec- tion and/or other treatment, on-site treated nonpotable gray water shall be disinfected as needed to ensure the required water quality is obtained at the point of use. Where chlorine is used for disinfection or treatment, water shall be tested for residual chlorine in accordance with ASTM D1253.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Plumbing Code (Title 24, Part 5)
California Plumbing Code (Title 24, Part 5)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
  5. Chapter 5 — WATER HEATERS
  6. Chapter 6 — WATER SUPPLY AND DISTRIBUTION
  7. Chapter 7 — SANITARY DRAINAGE
  8. Chapter 8 — INDIRECT WASTES
  9. Chapter 9 — VENTS
  10. Chapter 10 — TRAPS AND INTERCEPTORS
  11. Chapter 11 — STORM DRAINAGE
  12. Chapter 12 — FUEL GAS PIPING
  13. Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
  14. Chapter 14 — FIRESTOP PROTECTION
  15. Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
    Overview
    1. 1501.1 Applicability. [BSC-CG, DWR & HCD 1] The provisions of …
    2. 1501.2 System Design. [BSC-CG, HCD 1 & DWR]
    3. 1501.3 Permit. [BSC-CG, HCD 1 & DWR] It shall be
    4. 1501.4 Component Identification. System components
    5. 1501.5 Maintenance and Inspection. [BSC-CG, HCD
    6. 1505.16 .
    7. 1501.6 Operation and Maintenance Manual. [BSC-
    8. 1501.7 Minimum Water Quality Requirements. [BSC-
    9. 1501.8 Material Compatibility. Alternate water source systems …
    10. 1501.9 Signage. [BSC-CG, HCD 1, HCD 2 & HCD 1-
    11. 1501.10 System Controls. Controls for pumps, valves, and
    12. 1502.1 General. Alternate water source systems shall be
    13. 1502.2 Supply System Inspection and Test. Alternate
    14. 1502.3 Cross-Connection Inspection and Testing. An
    15. 1502.4 Separation Requirements. Underground alternate
    16. 1502.5 Abandonment. Alternate water source systems that
    17. 1502.6 Sizing. Unless otherwise provided for in this chapter, …
    18. 1503.1 General. The provisions of this section shall apply to
    19. 1503.2 System Requirements. Gray water shall be permitted to b…
    20. 1503.3 Connections to Potable and Reclaimed (Recy-
    21. 1503.4 Location. No gray water system or part thereof shall
    22. 1503.5 Plot Plan Submission. No permit for a gray water
    23. 1503.6 Prohibited Location. Where there is insufficient
    24. 1503.7 Drawings and Specifications. The Authority Having Juris…
    25. 1503.8 Procedure for Estimating Gray Water Dis-
    26. 1503.9 Gray Water System Components. Gray water
    27. 1504.1 General. Irrigation or disposal fields shall be permitt…
    28. 1504.2 Required Area of Subsurface Irrigation
    29. 1504.3 Determination of Maximum Absorption
    30. 1504.4 Groundwater Level. No excavation for an irrigation fiel…
    31. 1504.5 Irrigation, Disposal Field and Mulch Basin
    32. 1504.6 Reserved.
    33. 1504.7 Reserved .
    34. 1504.8 Gray Water System Color and Marking Infor-
    35. 1504.9 Other Collection and Distribution Systems.
    36. 1504.10 Testing. Building drains and vents for gray water
    37. 1504.11 Maintenance. Gray water systems and components shall b…
    38. 1505.1 General. The provisions of Section 1505.0 through
    39. 1505.2 Permit. It shall be unlawful for a person to construct,
    40. 1505.3 System Changes. No changes or connections shall
    41. 1505.4 Connections to Potable or Recycled Water
    42. 1505.5 Water Pressure. Reclaimed (recycled) water systems supp…
    43. 1505.6 Initial Cross-Connection Test. A cross-connection
    44. 1505.7 Recycled Water Supply System Materials.
    45. 1505.8 Recycled Water Supply System Color and
    46. 1505.9 Valves. Valves, except fixture supply control valves,
    47. 1505.13 Signage . Signs in rooms and water closet tanks in
    48. 1505.14 Inspection and Testing. Recycled water supply
    49. 1505.10 Hose Bibbs. Hose bibbs shall not be allowed on
    50. 1505.11 Required Appurtenances. The recycled water
    51. 1505.12 Pipe Separation in Trenches . Reclaimed (recycled) wat…
    52. 1505.15 Minimum Water Quality Requirements for
    53. 1505.16 Maintenance and Inspection. Recycled water
    54. 1506.1 General. The provisions of this section shall apply
    55. 1506.2 Plumbing Plan Submission. No permit for an
    56. 1506.3 System Changes. No changes or connections shall
    57. 1506.4 Connections to Potable or Recycled Water
    58. 1506.5 Water Pressure. On-site treated non-potable gray
    59. 1506.11 Valves. Valves, except fixture supply control
    60. 1506.12 Signs. Signs in buildings using on-site treated nonpot…
    61. 1506.13 Inspection and Testing. On-site treated nonpotable gra…
    62. 1506.6 Initial Cross-Connection Test. A cross-connection test …
    63. 1506.7 On-Site Treated Nonpotable Gray Water Sys-
    64. 1506.8 On-Site Treated Nonpotable Gray Water
    65. 1506.9 On-Site Treated Nonpotable Gray Water Sys-
    66. 1506.10 Design and Installation. The design and installation o…
  16. Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
  19. Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
  20. Appendix C — ALTERNATE PLUMBING SYSTEMS
  21. Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
  22. Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
  23. Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS
  25. Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
  26. Appendix I — INSTALLATION STANDARDS
  27. Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
  28. Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
  29. Appendix L — SUSTAINABLE PRACTICES
  30. Appendix M — PEAK WATER DEMAND CALCULATOR
  31. Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
  32. Appendix O — NON-SEWERED SANITATION SYSTEMS
  33. Appendix P — PROFESSIONAL QUALIFICATIONS
  34. Appendix Q — INDOOR HORTICULTURAL FACILITIES
  35. Appendix R — TINY HOUSES
  36. Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.