Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
1503.7 Drawings and Specifications.
California Plumbing Code (Title 24, Part 5) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
The Authority Having Jurisdiction may require the following information to be included with or in the plot plan before a permit is issued for a gray water system, or at a time during the construction thereof:
(1) Plot plan drawn to scale and completely dimensioned, showing lot lines and structures, direction and approximate slope of surface, location of present or proposed retaining walls, drainage channels, water supply lines, wells, paved areas and structures on the plot, number of bedrooms and plumbing fixtures in each structure, location of private sewage disposal system and expansion area or building sewer connecting to the public sewer, and location of the proposed gray water system.
(2) Details of construction necessary to ensure compliance with the requirements of this chapter, together with a full description of the complete installation, including installation methods, construction, and materials.
(3) Details for holding tanks shall include dimensions, structural calculations, bracings, and such other pertinent data as required.
(4) A log of soil formations and groundwater level as determined by test holes dug in proximity to proposed irrigation and/or disposal area, together with a statement of water absorption characteristics of the soil at the proposed site as determined by approved percolation tests.
Exception s :
(1) The Authority Having Jurisdiction shall permit the use of Table 1504.2 instead of percolation tests.
(2) The Enforcing Agency may waive the requirement for identification of groundwater level and/or soil absorption qualities based on knowledge of local conditions.
(3) The absence of groundwater in a test hole three (3) vertical feet (915 mm) below the deepest irrigation or disposal point shall be sufficient to satisfy this section unless seasonal high groundwater levels have been documented to rise to within this area.
(5) Distance between the plot and surface waters such as lakes, ponds, rivers or streams, and the slope of the plot and the surface water, wherein close proximity.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Plumbing Code (Title 24, Part 5)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — PLUMBING FIXTURES AND FIXTURE FITTINGS
- Chapter 5 — WATER HEATERS
- Chapter 6 — WATER SUPPLY AND DISTRIBUTION
- Chapter 7 — SANITARY DRAINAGE
- Chapter 8 — INDIRECT WASTES
- Chapter 9 — VENTS
- Chapter 10 — TRAPS AND INTERCEPTORS
- Chapter 11 — STORM DRAINAGE
- Chapter 12 — FUEL GAS PIPING
- Chapter 13 — HEALTH CARE FACILITIES AND MEDICAL GAS AND MEDICA…
- Chapter 14 — FIRESTOP PROTECTION
▸Chapter 15 — ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS
Overview- 1501.1 Applicability. [BSC-CG, DWR & HCD 1] The provisions of …
- 1501.2 System Design. [BSC-CG, HCD 1 & DWR]
- 1501.3 Permit. [BSC-CG, HCD 1 & DWR] It shall be
- 1501.4 Component Identification. System components
- 1501.5 Maintenance and Inspection. [BSC-CG, HCD
- 1505.16 .
- 1501.6 Operation and Maintenance Manual. [BSC-
- 1501.7 Minimum Water Quality Requirements. [BSC-
- 1501.8 Material Compatibility. Alternate water source systems …
- 1501.9 Signage. [BSC-CG, HCD 1, HCD 2 & HCD 1-
- 1501.10 System Controls. Controls for pumps, valves, and
- 1502.1 General. Alternate water source systems shall be
- 1502.2 Supply System Inspection and Test. Alternate
- 1502.3 Cross-Connection Inspection and Testing. An
- 1502.4 Separation Requirements. Underground alternate
- 1502.5 Abandonment. Alternate water source systems that
- 1502.6 Sizing. Unless otherwise provided for in this chapter, …
- 1503.1 General. The provisions of this section shall apply to
- 1503.2 System Requirements. Gray water shall be permitted to b…
- 1503.3 Connections to Potable and Reclaimed (Recy-
- 1503.4 Location. No gray water system or part thereof shall
- 1503.5 Plot Plan Submission. No permit for a gray water
- 1503.6 Prohibited Location. Where there is insufficient
- 1503.7 Drawings and Specifications. The Authority Having Juris…
- 1503.8 Procedure for Estimating Gray Water Dis-
- 1503.9 Gray Water System Components. Gray water
- 1504.1 General. Irrigation or disposal fields shall be permitt…
- 1504.2 Required Area of Subsurface Irrigation
- 1504.3 Determination of Maximum Absorption
- 1504.4 Groundwater Level. No excavation for an irrigation fiel…
- 1504.5 Irrigation, Disposal Field and Mulch Basin
- 1504.6 Reserved.
- 1504.7 Reserved .
- 1504.8 Gray Water System Color and Marking Infor-
- 1504.9 Other Collection and Distribution Systems.
- 1504.10 Testing. Building drains and vents for gray water
- 1504.11 Maintenance. Gray water systems and components shall b…
- 1505.1 General. The provisions of Section 1505.0 through
- 1505.2 Permit. It shall be unlawful for a person to construct,
- 1505.3 System Changes. No changes or connections shall
- 1505.4 Connections to Potable or Recycled Water
- 1505.5 Water Pressure. Reclaimed (recycled) water systems supp…
- 1505.6 Initial Cross-Connection Test. A cross-connection
- 1505.7 Recycled Water Supply System Materials.
- 1505.8 Recycled Water Supply System Color and
- 1505.9 Valves. Valves, except fixture supply control valves,
- 1505.13 Signage . Signs in rooms and water closet tanks in
- 1505.14 Inspection and Testing. Recycled water supply
- 1505.10 Hose Bibbs. Hose bibbs shall not be allowed on
- 1505.11 Required Appurtenances. The recycled water
- 1505.12 Pipe Separation in Trenches . Reclaimed (recycled) wat…
- 1505.15 Minimum Water Quality Requirements for
- 1505.16 Maintenance and Inspection. Recycled water
- 1506.1 General. The provisions of this section shall apply
- 1506.2 Plumbing Plan Submission. No permit for an
- 1506.3 System Changes. No changes or connections shall
- 1506.4 Connections to Potable or Recycled Water
- 1506.5 Water Pressure. On-site treated non-potable gray
- 1506.11 Valves. Valves, except fixture supply control
- 1506.12 Signs. Signs in buildings using on-site treated nonpot…
- 1506.13 Inspection and Testing. On-site treated nonpotable gra…
- 1506.6 Initial Cross-Connection Test. A cross-connection test …
- 1506.7 On-Site Treated Nonpotable Gray Water Sys-
- 1506.8 On-Site Treated Nonpotable Gray Water
- 1506.9 On-Site Treated Nonpotable Gray Water Sys-
- 1506.10 Design and Installation. The design and installation o…
- Chapter 16 — NONPOTABLE RAINWATER CATCHMENT SYSTEMS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYS…
- Appendix B — EXPLANATORY NOTES ON COMBINATION WASTE AND VENT S…
- Appendix C — ALTERNATE PLUMBING SYSTEMS
- Appendix D — SIZING STORM WATER DRAINAGE SYSTEMS
- Appendix E — MANUFACTURED/MOBILE HOME PARKS AND RECREATIONAL V…
- Appendix F — FIREFIGHTER BREATHING AIR REPLENISHMENT SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS
- Appendix H — PRIVATE SEWAGE DISPOSAL SYSTEMS
- Appendix I — INSTALLATION STANDARDS
- Appendix J — COMBINATION OF INDOOR AND OUTDOOR COMBUSTION AND …
- Appendix K — POTABLE RAINWATER CATCHMENT SYSTEMS
- Appendix L — SUSTAINABLE PRACTICES
- Appendix M — PEAK WATER DEMAND CALCULATOR
- Appendix N — IMPACT OF WATER TEMPERATURE ON THE POTENTIAL FOR …
- Appendix O — NON-SEWERED SANITATION SYSTEMS
- Appendix P — PROFESSIONAL QUALIFICATIONS
- Appendix Q — INDOOR HORTICULTURAL FACILITIES
- Appendix R — TINY HOUSES
- Appendix S — ONSITE STORMWATER TREATMENT SYSTEMS