Skip to content

Chapter 13 — FUEL GAS PIPING

1310.14 Systems Containing Flammable Gas-Air

California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

Mixtures. Systems containing flammable gas-air mixtures shall be in accordance with Section 1310.14.1 through Section 1310.14.6.

1310.14.1 Required Components. A central premix system with a flammable mixture in the blower or compressor shall consist of the following components: (1) Gas-mixing machine in the form of an automatic

gas-air proportioning device combined with a downstream blower or compressor. (2) Flammable mixture piping, minimum Schedule 40. (3) Automatic firecheck(s). (4) Safety blowout(s) or backfire preventers for systems

utilizing flammable mixture lines above 2 1 ⁄ 2 inches (64 mm) nominal pipe size or the equivalent. [NFPA 54:7.11.1] 1310.14.2 Optional Components. The following components shall also be permitted to be utilized in any type of central premix system: (1) Flowmeter(s) (2) Flame arrester(s) [NFPA 54:7.11.2] 1310.14.3 Additional Requirements. Gas-mixing machines shall have nonsparking blowers and shall be constructed so that a flashback does not rupture machine casings. [NFPA 54:7.11.3]

1310.14.4 Special Requirements for Mixing Blowers. A mixing blower system shall be limited to applications with minimum practical lengths of mixture piping, limited to a maximum mixture pressure of 10 inches water column (2.5 kPa) and limited to gases containing no more than 10 percent hydrogen. The blower

» »

(3) Outlets shall be located far enough from floors, walls,

patios, slabs, and ceilings to permit the use of wrenches without straining, bending, or damaging the piping. (4) The unthreaded portion of gas piping outlets shall extend

not less than 1 inch (25.4 mm) through finished ceilings or indoor or outdoor walls. (5) The unthreaded portion of gas piping outlets shall extend

not less than 2 inches (51 mm) above the surface of floors or outdoor patios or slabs. (6) The provisions of Section 1310.10(4) and Section

1310.10(5) shall not apply to listed quick-disconnect devices of the flush-mounted type or listed gas convenience outlets. Such devices shall be installed in accordance with the manufacturer’s installation instructions.

[NFPA 54:7.7.1.1 – 7.7.1.6] 1310.10.1 Cap Outlets. Each outlet, including a valve, shall be closed gastight with a threaded plug or cap immediately after installation and shall be left closed until the appliance or equipment is connected thereto. When an appliance or equipment is disconnected from an outlet and the outlet is not to be used again immediately, it shall be capped or plugged gastight. Exceptions: (1) Laboratory appliances installed in accordance with

Section 1312.3.1 shall be permitted. (2) The use of a listed quick-disconnect device with

integral shutoff or listed gas convenience outlet shall be permitted. [NFPA 54:7.7.2.1] 1310.10.1.1 Appliance Shutoff Valves. Appliance shutoff valves installed in fireplaces shall be removed and the piping capped gastight where the fireplace is used for solid fuel burning. [NFPA 54:7.7.2.2]

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
    Overview
    1. 1301.1 Applicability. The regulations of this chapter shall
    2. 1302.1 General. Coverage of piping systems shall extend
    3. 1302.2 Piping System Requirements. Requirements for
    4. 1302.3 Applications. This code shall not apply to the followin…
    5. 1303.1 Inspection Notification. Upon completion of the
    6. 1303.2 Excavation. Excavations required for the installation o…
    7. 1303.3 Type of Inspections. The Authority Having Jurisdiction …
    8. 1303.4 Inspection Waived. In cases where the work authorized b…
    9. 1304.1 Issuance. Whereupon final piping inspection, the
    10. 1304.2 Gas Supplier. A copy of the certificate of such final
    11. 1304.3 Unlawful. It shall be unlawful for a serving gas suppli…
    12. 1305.1 Authorized Personnel. It shall be unlawful for a
    13. 1305.2 Outlets. It shall be unlawful to turn on or connect gas
    14. 1306.1 Disconnection. The Authority Having Jurisdiction
    15. 1306.2 Notice. Where such disconnection has been made, a
    16. 1306.3 Capped Outlets. It shall be unlawful to remove or
    17. 1307.1 General. Where temporary use of gas is desired, and
    18. 1308.1 Installation of Piping System. Where required
    19. 1308.2 Provision for Location of Point of Delivery.
    20. 1308.3 Interconnections Between Gas Piping Sys-
    21. 1308.4 Sizing of Gas Piping Systems. Gas piping systems shall …
    22. 1308.5 Acceptable Piping Materials and Joining
    23. 1308.6 Gas Meters. Gas meters shall be selected for the
    24. 1308.7 Gas Pressure Regulators. A line pressure regulator shal…
    25. 1308.8 Overpressure Protection. Where the serving gas
    26. 1308.9 Pressure Limitation Requirements. Where piping systems …
    27. 1308.10 Overpressure Protection Devices. Overpressure protecti…
    28. 1308.11 Backpressure Protection. Protective devices
    29. 1308.12 Low-Pressure Protection. A protective device
    30. 1308.13 Shutoff Valves. Shutoff valves shall be approved
    31. 1308.14 Expansion and Flexibility. Piping systems shall
    32. 1309.1 General. Where automatic excess flow valves are
    33. 1310.1 Piping Underground. Underground gas piping shall
    34. 1310.2 CSST Piping Systems. CSST piping systems shall
    35. 1310.3 Installation of Aboveground Piping. Piping
    36. 1310.4 Concealed Piping in Buildings. Gas piping in
    37. 1310.5 Piping in Vertical Chases. Where gas piping
    38. 1310.6 Maximum Operating Pressure in Buildings.
    39. 1310.7 Appliance Overpressure Protection. The maximum operatin…
    40. 1310.8 Gas Pipe Turns. Changes in direction of gas pipe
    41. 1310.9 Drips and Sediment Traps. For other than dry gas
    42. 1310.10 Outlets. Outlets shall be located and installed in
    43. 1310.7 Appliance Overpressure Protection. The maxi- [NFPA 54:7…
    44. 1310.12 Prohibited Devices. Devices shall not be placed
    45. 1310.13 Systems Containing Gas-Air Mixtures Out-
    46. 1310.14 Systems Containing Flammable Gas-Air
    47. 1310.11 Manual Gas Shutoff Valves. An accessible gas
    48. 1311.1 Pipe and Tubing Other than CSST. Each aboveground porti…
    49. 1311.2 Bonding of CSST Gas Piping. CSST gas piping
    50. 1312.2 Suspended Low-Intensity Infrared Tube
    51. 1312.3 Use of Nonmetalic Gas Hose Connectors.
    52. 1311.3 Arc-Resistant Jacketed CSST. CSST listed with
    53. 1311.4 Prohibited Use. Gas piping shall not be used as a
    54. 1311.5 Lightning Protection System. Where a lightning
    55. 1311.6 Electrical Circuits. Electrical circuits shall not util…
    56. 1311.7 Electrical Connections. All electrical connections
    57. 1312.1 Connecting Appliances and Equipment.
    58. 1312.4 Injection (Bunsen) Burners. Injection (Bunsen)
    59. 1312.5 Connection of Portable and Mobile Industrial
    60. 1312.6 Appliance Shutoff Valves and Connections.
    61. 1312.7 Quick-Disconnect Devices. Quick-disconnect
    62. 1312.8 Gas Convenience Outlets. Appliances shall be
    63. 1312.9 Sediment Trap. Where a sediment trap is not incorporate…
    64. 1312.10 Installation of Piping. Piping shall be installed in
    65. 1312.11 Liquefied Petroleum Gas Facilities and Pip-
    66. 1313.1 Piping Installations. Prior to acceptance and initial o…
    67. 1313.2 Test Preparation. Test preparation shall comply
    68. 1313.3 Test Pressure. This inspection shall include an air,
    69. 1313.4 Detection of Leaks and Defects. The piping system shall…
    70. 1313.5 Piping System Leak Test. Leak checks using fuel
    71. 1313.6 Purging Requirements. The purging of piping
    72. 1314.1 General. The following regulations, shall comply
    73. 1314.2 Volume. The hourly volume of gas required at each
    74. 1314.3 Gas Appliances. Where the gas appliances to be
    75. 1314.4 Size of Piping Outlets. The size of the supply piping o…
    76. 1315.1 Pipe Sizing Methods. Where the pipe size is to be
    77. 1315.2 Sizing of Gas Piping Systems. Sizing of piping
    78. 1315.3 Sizing Equations. The inside diameter of smooth
    79. 1315.4 Sizing of Piping Sections. To determine the size
    80. 1315.5 Engineering Methods. For conditions other than
    81. 1315.6 Variable Gas Pressures. Where the supply gas
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — GEOTHERMAL ENERGY SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  25. Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.