1310.11 Manual Gas Shutoff Valves. An accessible gas
California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
shutoff valve shall be provided upstream of each gas pressure regulator. Where two gas pressure regulators are installed in series in a single gas line, a manual valve shall not be required at the second regulator. [NFPA 54:7.8.1]
1310.11.1 Valves Controlling Multiple Systems. Main gas shutoff valves controlling several gas piping systems shall be readily accessible for operation and installed so as to be protected from physical damage. They shall be marked with a metal tag or other permanent means attached by the installing agency so that the gas piping systems supplied through them can be readily identified. [NFPA 54:7.8.2.1]
1310.11.1.1 Shutoff Valves for Multiple House Lines. In multiple-tenant buildings supplied through a master meter, through one service regulator where a meter is not provided, or where meters or service regulators are not readily accessible from the appliance or equipment location, an individual shutoff valve for each apartment or tenant line shall be provided at a convenient point of general accessibility. In a common system serving a number of individual buildings, shutoff valves shall be installed at each building. [NFPA 54:7.8.2.2]
2022 CALIFORNIA MECHANICAL CODE 269
FUEL GAS PIPING
shall be equipped with a gas control valve at its air entrance arranged so that gas is admitted to the airstream, entering the blower in proper proportions for correct combustion by the type of burners employed, the said gas control valve being of either the zero governor or mechanical ratio valve type that controls the gas and air adjustment simultaneously. No valves or other obstructions shall be installed between the blower discharge and the burner or burners. [NFPA 54:7.11.4]
is admitted to the airstream, entering the blower in proper proportions for correct combustion by the type of burners employed, the said gas control valve being of either the zero governor or mechanical ratio valve type that controls the gas and air adjustment simultaneously. No valves or other obstructions shall be installed between the blower discharge and the burner or burners. [NFPA 54:7.11.4]
1310.14.5 Installation of Gas-Mixing Machines. Installation of gas-mixing machines shall comply with the following: (1) The gas-mixing machine shall be located in a well ventilated area or in a detached building or cutoff room provided with room construction and explosion vents in accordance with sound engineering principles. Such rooms or below-grade installations shall have adequate positive ventilation. (2) Where gas-mixing machines are installed in well ventilated areas, the type of electrical equipment shall be in accordance with NFPA 70 for general service conditions unless other hazards in the area prevail. Where gas-mixing machines are installed in small detached buildings or cutoff rooms, the electrical equipment and wiring shall be installed in accordance with NFPA 70 for hazardous locations (Articles 500 and 501, Class I, Division 2). (3) Air intakes for gas-mixing machines using compres sors or blowers shall be taken from outdoors whenever practical. (4) Controls for gas-mixing machines shall include inter locks and a safety shutoff valve of the manual reset type in the gas supply connection to each machine arranged to automatically shut off the gas supply in the event of high or low gas pressure. Except for open burner installations only, the controls shall be interlocked so that the blower or compressor stops operating following a gas supply failure. Where a system employs pressurized air, means shall be provided to shut off the gas supply in the event of air failure. (5) Centrifugal gas-mixing machines in parallel shall be
reviewed by the user and equipment manufacturer before installation, and means or plans for minimizing the effects of downstream pulsation and equipment overload shall be prepared and utilized as needed. [NFPA 54:7.11.5.1 – 7.11.5.5]
1310.14.6 Use of Automatic Firechecks, Safety Blowouts, or Backfire Preventers. Automatic firechecks and safety blowouts or backfire preventers shall be provided in piping systems distributing flammable airgas mixtures from gas-mixing machines to protect the piping and the machines in the event of flashback, in accordance with the following: (1) Approved automatic firechecks shall be installed
upstream as close as practical to the burner inlets following the firecheck manufacturer’s instructions.
(2) A separate manually operated gas valve shall be pro vided at each automatic firecheck for shutting off the flow of the gas-air mixture through the firecheck after a flashback has occurred. The valve shall be located upstream as close as practical to the inlet of the automatic firecheck. Caution: These valves shall not be reopened after a flashback has occurred until the firecheck has cooled sufficiently to prevent re-ignition of the flammable mixture and has been reset properly. (3) A safety blowout or backfiring preventer shall be
provided in the mixture line near the outlet of each gas-mixing machine where the size of the piping is larger than 2 1 ⁄ 2 inches (65 mm) NPS, or equivalent, to protect the mixing equipment in the event of an explosion passing through an automatic firecheck. The manufacturers’ instructions shall be followed when installing these devices, particularly after a disc has burst. The discharge from the safety blowout or backfire preventer shall be located or shielded so that particles from the ruptured disc cannot be directed toward personnel. Wherever there are interconnected installations of gas-mixing machines with safety blowouts or backfire preventers, provision shall be made to keep the mixture from other machines from reaching any ruptured disc opening. Check valves shall not be used for this purpose. (4) Large-capacity premix systems provided with explo sion heads (rupture discs) to relieve excessive pressure in pipelines shall be located at and vented to a safe outdoor location. Provisions shall be provided for automatically shutting off the supply of the gas-air mixture in the event of rupture. [NFPA 54:7.11.6]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
▸Chapter 13 — FUEL GAS PIPING
Overview- 1301.1 Applicability. The regulations of this chapter shall
- 1302.1 General. Coverage of piping systems shall extend
- 1302.2 Piping System Requirements. Requirements for
- 1302.3 Applications. This code shall not apply to the followin…
- 1303.1 Inspection Notification. Upon completion of the
- 1303.2 Excavation. Excavations required for the installation o…
- 1303.3 Type of Inspections. The Authority Having Jurisdiction …
- 1303.4 Inspection Waived. In cases where the work authorized b…
- 1304.1 Issuance. Whereupon final piping inspection, the
- 1304.2 Gas Supplier. A copy of the certificate of such final
- 1304.3 Unlawful. It shall be unlawful for a serving gas suppli…
- 1305.1 Authorized Personnel. It shall be unlawful for a
- 1305.2 Outlets. It shall be unlawful to turn on or connect gas
- 1306.1 Disconnection. The Authority Having Jurisdiction
- 1306.2 Notice. Where such disconnection has been made, a
- 1306.3 Capped Outlets. It shall be unlawful to remove or
- 1307.1 General. Where temporary use of gas is desired, and
- 1308.1 Installation of Piping System. Where required
- 1308.2 Provision for Location of Point of Delivery.
- 1308.3 Interconnections Between Gas Piping Sys-
- 1308.4 Sizing of Gas Piping Systems. Gas piping systems shall …
- 1308.5 Acceptable Piping Materials and Joining
- 1308.6 Gas Meters. Gas meters shall be selected for the
- 1308.7 Gas Pressure Regulators. A line pressure regulator shal…
- 1308.8 Overpressure Protection. Where the serving gas
- 1308.9 Pressure Limitation Requirements. Where piping systems …
- 1308.10 Overpressure Protection Devices. Overpressure protecti…
- 1308.11 Backpressure Protection. Protective devices
- 1308.12 Low-Pressure Protection. A protective device
- 1308.13 Shutoff Valves. Shutoff valves shall be approved
- 1308.14 Expansion and Flexibility. Piping systems shall
- 1309.1 General. Where automatic excess flow valves are
- 1310.1 Piping Underground. Underground gas piping shall
- 1310.2 CSST Piping Systems. CSST piping systems shall
- 1310.3 Installation of Aboveground Piping. Piping
- 1310.4 Concealed Piping in Buildings. Gas piping in
- 1310.5 Piping in Vertical Chases. Where gas piping
- 1310.6 Maximum Operating Pressure in Buildings.
- 1310.7 Appliance Overpressure Protection. The maximum operatin…
- 1310.8 Gas Pipe Turns. Changes in direction of gas pipe
- 1310.9 Drips and Sediment Traps. For other than dry gas
- 1310.10 Outlets. Outlets shall be located and installed in
- 1310.7 Appliance Overpressure Protection. The maxi- [NFPA 54:7…
- 1310.12 Prohibited Devices. Devices shall not be placed
- 1310.13 Systems Containing Gas-Air Mixtures Out-
- 1310.14 Systems Containing Flammable Gas-Air
- 1310.11 Manual Gas Shutoff Valves. An accessible gas
- 1311.1 Pipe and Tubing Other than CSST. Each aboveground porti…
- 1311.2 Bonding of CSST Gas Piping. CSST gas piping
- 1312.2 Suspended Low-Intensity Infrared Tube
- 1312.3 Use of Nonmetalic Gas Hose Connectors.
- 1311.3 Arc-Resistant Jacketed CSST. CSST listed with
- 1311.4 Prohibited Use. Gas piping shall not be used as a
- 1311.5 Lightning Protection System. Where a lightning
- 1311.6 Electrical Circuits. Electrical circuits shall not util…
- 1311.7 Electrical Connections. All electrical connections
- 1312.1 Connecting Appliances and Equipment.
- 1312.4 Injection (Bunsen) Burners. Injection (Bunsen)
- 1312.5 Connection of Portable and Mobile Industrial
- 1312.6 Appliance Shutoff Valves and Connections.
- 1312.7 Quick-Disconnect Devices. Quick-disconnect
- 1312.8 Gas Convenience Outlets. Appliances shall be
- 1312.9 Sediment Trap. Where a sediment trap is not incorporate…
- 1312.10 Installation of Piping. Piping shall be installed in
- 1312.11 Liquefied Petroleum Gas Facilities and Pip-
- 1313.1 Piping Installations. Prior to acceptance and initial o…
- 1313.2 Test Preparation. Test preparation shall comply
- 1313.3 Test Pressure. This inspection shall include an air,
- 1313.4 Detection of Leaks and Defects. The piping system shall…
- 1313.5 Piping System Leak Test. Leak checks using fuel
- 1313.6 Purging Requirements. The purging of piping
- 1314.1 General. The following regulations, shall comply
- 1314.2 Volume. The hourly volume of gas required at each
- 1314.3 Gas Appliances. Where the gas appliances to be
- 1314.4 Size of Piping Outlets. The size of the supply piping o…
- 1315.1 Pipe Sizing Methods. Where the pipe size is to be
- 1315.2 Sizing of Gas Piping Systems. Sizing of piping
- 1315.3 Sizing Equations. The inside diameter of smooth
- 1315.4 Sizing of Piping Sections. To determine the size
- 1315.5 Engineering Methods. For conditions other than
- 1315.6 Variable Gas Pressures. Where the supply gas
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — GEOTHERMAL ENERGY SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE