1112.11 Discharge from Pressure-Relief Devices.
California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Pressure-relief systems designed for vapor shall comply with Section 1112.11.1 through Section 1112.11.4.1.
1112.11.1 Discharging Location Interior to Build- ing. Pressure-relief devices, including fusible plugs, serving refrigeration systems shall be permitted to dis
REFRIGERATION
charge to the interior of a building where in accordance with the following: (1) The system contains less than 110 pounds (49.9 kg)
of a Group A1 refrigerant. (2) The system contains less than 6.6 pounds (2.99 kg)
of a Group A2, B1 or B2 refrigerant. (3) The system does not contain any quantity of a Group
A3 or B3 refrigerant. (4) The system is not required to be installed in a
machinery room in accordance with Section 1106.0. (5) The refrigerant concentration limits in Section
1104.2 are not exceeded. Refrigeration systems that do not comply with the above requirements shall comply with the requirements of Section 1112.11.2 through Section 1112.11.4. [ASHRAE 15:9.7.8.1] 1112.11.2 Discharging Location Exterior to Build- ing. Pressure-relief devices designed to discharge external to the refrigeration system shall be arranged to discharge outside of a building and shall be in accordance with the following: (1) The point of vent discharge shall be located not less
than 15 feet (4572 mm) above the adjoining ground level. Exception: Outdoor systems containing Group A1 refrigerant shall be permitted to discharge at any elevation where the point of discharge is located in an access-controlled area accessible to authorized personnel only. (2) The point of vent discharge shall be located not less
than 20 feet (6096 mm) from windows, building ventilation openings, pedestrian walkways, or building exits. (3) For heavier-than-air refrigerants, the point of vent
discharge shall be located not less than 20 feet (6096 mm) horizontally from below-grade walkways, entrances, pits or ramps where a release of the entire system charge into such a space would yield a concentration of refrigerant in excess of the RCL. The direct discharge of a relief vent into enclosed outdoor spaces, such as a courtyard with walls on all sides, shall not be permitted where a release of the entire system charge into such a space would yield a concentration of refrigerant in excess of the RCL. The volume for the refrigerant concentration calculation shall be determined using the gross area of the space and a height of 8.2 feet (2499 mm), regardless of the actual height of the enclosed space. (4) The termination point of a vent discharge line shall
be made in a manner that prevents discharged refrigerant from spraying directly onto personnel that are capable of being in the vicinity. (5) The termination point of vent discharge line shall be
made in a manner that prevents foreign material or debris from entering the discharge piping. (6) Relief vent lines that terminate vertically upward
and are subject to moisture entry shall be provided with a drip pocket having a length of not less than 24
2022 CALIFORNIA MECHANICAL CODE 225
REFRIGERATION
inches (610 mm) and having the size of the vent discharge pipe. The drip pocket shall be installed to extend below the first change in vent pipe direction and shall be fitted with a valve or drain plug to permit removal of accumulated moisture. [ASHRAE 15:9.7.8.2] 1112.11.3 Internal Relief. Pressure-relief valves designed to discharge from a higher-pressure vessel into a lower pressure vessel internal to the system shall comply with the following: (1) The pressure-relief valve that protects the higher pressure vessel shall be selected to deliver capacity in accordance with Section 1113.5 without exceeding the maximum allowable working pressure of the higher-pressure vessel accounting for the change in mass flow capacity due to the elevated backpressure. (2) The capacity of the pressure-relief valve protecting
the part of the system receiving a discharge from a pressure-relief valve protecting a higher-pressure vessel shall be not less than the sum of the capacity required in Section 1113.5 plus the mass flow capacity of the pressure-relief valve discharging into that part of the system. (3) The design pressure of the body of the relief valve
used on the higher-pressure vessel shall be rated for operation at the design pressure of the higher-pressure vessel in both pressure-containing areas of the valve. [ASHRAE 15:9.7.8.3] 1112.11.4 Discharge Location, Special Require- ments. Additional requirements for relief device discharge location and allowances shall apply for specific refrigerants in accordance with Section 1112.11.4.1.
[ASHRAE 15:9.7.8.4]
1112.11.4.1 Water (R-718). Where water is the refrigerant, discharge to a floor drain shall be permitted where the following conditions are met: (1) The pressure-relief device set pressure shall not
exceed 15 psig (103 kPa). (2) The floor drain shall be sized to handle the flow
rate from a single broken tube in a refrigerantcontaining heat exchanger. (3) The Authority Having Jurisdiction finds it
acceptable that the working fluid, corrosion inhibitor, and other additives used in this type of refrigeration system are permitted to infrequently be discharged to the sewer system, or a catch tank that is sized to handle the expected discharge shall be installed and equipped with a normally closed drain valve and an overflow line to drain. [ASHRAE 15:9.7.8.4.1]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
▸Chapter 11 — REFRIGERATION
Overview- 1101.1 Applicability. Part I governs the design, installation,
- 1101.2 Equipment. Equipment for refrigerant recovery,
- 1102.1 General. Refrigeration systems using a refrigerant
- 1102.2 Ammonia Refrigeration Systems. Refrigeration
- 1102.3 Refrigerants. The refrigerant used shall be of a type
- 1103.1 Classification of Refrigerants. Refrigerants shall
- 1103.2 Classification of Refrigeration Systems.
- 1103.3 Higher Flammability Refrigerants. Group A3
- 1104.1 System Selection. Refrigeration systems shall be
- 1104.2 Refrigerant Concentration Limit. The concentration of r…
- 1104.3 Institutional Occupancies. The RCL value
- 1104.4 Industrial Occupancies and Refrigerated
- 1104.5 Flammable Refrigerants. The total of Group A2,
- 1104.6 Applications for Human Comfort and for Non-
- 1104.7 Refrigerant Type and Purity. Refrigerants shall
- 1104.8 Changing Refrigerants. A change in the type of
- 1105.1 Human Comfort. Cooling systems used for human
- 1105.2 Supports and Anchorage. Supports and anchorage for refr…
- 1105.3 Access. An unobstructed readily accessible opening and …
- 1105.4 Illumination and Service Receptacles. In addition to th…
- 1105.5 Ventilation of Rooms Containing Condensing
- 1105.6 Prohibited Locations. Refrigeration systems or
- 1105.7 Condensate. Condensate from air-cooling coils
- 1105.8 Defrost. Where defrost cycles are required for portions…
- 1105.9 Overflows. Where condensate or defrost liquids are
- 1105.10 Condensate, Defrost, and Overflow Dis-
- 1105.11 Refrigerant Port Protection. Air conditioning
- 1105.12 Storage. Refrigerants and refrigerant oils not
- 1106.1 Where Required. Refrigeration systems shall be
- 1106.2 Refrigeration Machinery Room, General
- 1106.4 Natural Ventilation. Where a refrigerating system
- 1106.5 Combustion Air. No open flames that use combustion air …
- 1106.6 Airflow. There shall be no airflow to or from an occupi…
- 1106.7 Ventilation Intake. Makeup air intakes to replace
- 1106.3 Normal Operation. A part of the refrigeration
- 1106.8 Maximum Temperature. Ventilation or mechanical cooling …
- 1106.9 Refrigerant Parts in Air Duct. Joints and refrigerant-c…
- 1106.10 Dimensions. Refrigeration machinery rooms shall
- 1106.11 Restricted Access. Access to the refrigeration
- 1106.12 Exits. Exits shall comply with the building code for
- 1107.1 General. In cases specified in the rules of Section
- 1108.1 General. Equipment, piping, ducts, vents, or similar
- 1108.2 Electrical. Electrical equipment and installations
- 1108.3 Emergency Shut-off. A clearly identified emergency shut…
- 1108.4 Installation, Maintenance, and Testing. Detection and a…
- 1108.5 Emergency Pressure Control System. Where
- 1109.1 Materials. Materials used in the construction and
- 1109.2 Joints. Iron or steel pipe joints shall be of approved
- 1109.3 Penetration of Piping. Refrigerant piping shall not
- 1109.4 Location of Refrigeration Piping. Refrigerant
- 1109.5 Underground Piping. Refrigerant piping placed
- 1109.6 Support. In addition to the requirements of Section
- 1109.7 Pipe Enclosure. Refrigerant piping and tubing
- 1109.8 Visual Inspection. Refrigerant piping and joints
- 1109.9 Condensation. Piping and fittings that convey
- 1109.10 Identification. Piping shall be in accordance with
- 1110.1 More than 6.6 Pounds of Refrigerant. Systems
- 1110.2 More than 110 Pounds of Refrigerant. Systems
- 1110.3 Support. Stop valves installed in copper refrigerant
- 1110.4 Access. Stop valves required by Section 1110.0 shall
- 1110.5 Identification. Stop valves shall be identified by tagg…
- 1111.1 Where Required. Pressure-limiting devices complying wit…
- 1111.2 Setting. Pressure limiting devices shall be set in
- 1111.3 Location. Stop valves shall not be installed between
- 1111.4 Emergency Stop. Activation of a pressure-limiting
- 1112.1 General. Refrigeration systems shall be protected by
- 1112.2 Positive Displacement Compressor. A positive
- 1112.3 Liquid-Containing Portions of Systems. Liquid-containin…
- 1112.4 Evaporators. Heat exchanger coils located downstream, o…
- 1112.5 Hydrostatic Expansion. Pressure rise resulting
- 1112.6 Actuation. Pressure-relief devices shall be directpress…
- 1112.7 Stop Valves Prohibited. Stop valves shall not be
- 1112.8 Location. Pressure-relief devices shall be connected
- 1112.9 Materials. The seats and discs of pressure-relief
- 1112.10 Pressure-Relief Device Settings. Pressurerelief valves…
- 1112.11 Discharge from Pressure-Relief Devices.
- 1112.12 Discharge Piping. The piping used for pressurerelief d…
- 1112.13 Rating of Pressure-Relief Device. The rated
- 1112.14 Rating of Rupture Members and Fusible
- 1113.1 General. Pressure vessels shall be provided with
- 1113.2 Type of Protection. Pressure vessels with an internal g…
- 1113.3 Discharging into Lowside of System. For pressure-relief…
- 1113.4 Parallel Pressure-Relief Devices. Two or more
- 1113.5 Discharge Capacity. The minimum required discharge capa…
- 1113.6 Three-Way Valve. Pressure vessels of 10 cubic feet
- 1114.1 General. Systems containing other than Group A1 or
- 1114.2 Design Requirements. Flaring devices shall be
- 1114.3 Testing. Flaring systems shall be tested to demonstrate…
- 1115.1 General. In addition to labels required elsewhere in
- 1115.2 Volume and Type. A condenser, receiver, absorber,
- 1115.3 Permanent Sign. In a refrigeration machinery room
- 1115.4 Marking of Pressure-Relief Devices. Pressurerelief valv…
- 1116.1 Factory Tests. Refrigerant-containing parts of unit
- 1116.2 Field Tests. Refrigerant-containing parts of a system t…
- 1116.3 Test Gases. Tests shall be performed with dry nitrogen …
- 1116.4 Declaration. A dated declaration of test shall be provi…
- 1116.5 Brine Systems. Brine-containing portions of a system sh…
- 1117.1 Inside Dimensions 6 Inches or Less. Pressure
- 1117.2 Inside Dimensions More than 6 Inches. Pressure vessels …
- 1117.3 Pressure Vessels for 15 psig or Less. Pressure
- 1118.1 General. Refrigeration systems shall be operated and
- 1119.1 Applicability. Cooling towers, evaporative condensers, …
- 1120.1 General. Cooling towers, evaporative condensers,
- 1121.1 General. Drains, overflows, and blow-down provisions sh…
- 1122.1 General. Chemical treatment systems shall comply
- 1122.2 Automated Control of Cycles of Concentra-
- 1123.1 General. Cooling towers, evaporative condensers,
- 1124.1 General. Electrical systems shall be in accordance
- 1125.1 General. Equipment containing refrigerants as a part
- 1126.1 General. Cooling towers, evaporative condensers,
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — GEOTHERMAL ENERGY SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE