Chapter 11 — REFRIGERATION

1106.2 Refrigeration Machinery Room, General

California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

Requirements. Where a refrigeration system is located indoors and a machinery room is required in accordance with Section 1106.1, the machinery room shall be in accordance with Section 1106.2.1 through Section 1106.2.5.2.

1106.2.1 Access. Machinery rooms shall not be prohibited from housing other mechanical equipment unless specifically prohibited elsewhere in this chapter. A machinery room shall be so dimensioned that parts are accessible with space for service, maintenance, and operations. There shall be clear head room of not less than 7.25 feet (2210 mm) below equipment situated over passageways. [ASHRAE 15:8.11.1] 1106.2.2 Openings. Each refrigeration machinery room shall have a tight-fitting door or doors opening outward, self-closing where they open into the building and adequate in number to ensure freedom for persons to escape in an emergency. With the exception of access doors and panels in air ducts and air-handling units in accordance with Section 1106.6, there shall be no openings that will permit passage of escaping refrigerant to other parts of the building. [ASHRAE 15:8.11.2]

1106.2.2.1 Detectors and Alarms. Each refrigeration machinery room shall contain one or more refrigerant detectors in accordance with Section 1106.2.2.2, located in areas where refrigerant from a leak will concentrate, that actuate an alarm and mechanical ventilation in accordance with Section 1106.2.4 at a set point not more than the corresponding Occupational Exposure Limit, OEL, in accordance with Table 1102.3, a set point determined in accordance with the OEL as defined in Chapter 2 shall be approved by the Authority Having Jurisdiction. The alarm shall annunciate visual and audible alarms inside the refrigeration machinery room and outside each entrance to the refrigeration machinery room. The alarms required in this section shall be of the manual reset type with the reset located inside the refrigeration machinery room. Alarms set at other levels, such as IDLH, and automatic reset alarms shall be permitted in addition to those required in accordance with this section. The meaning of each alarm shall be clearly marked by signage near the annunciator. Exception: Refrigerant detectors are not required where only systems using R-718 (water) are located in the refrigeration machinery room. 1106.2.2.2 Refrigerant Detectors. Refrigerant detectors required in accordance with Section 1106.2.2.1 or Section 1107.1.7 shall meet all of the following conditions: (1) The refrigerant detector shall perform automatic

self-testing of sensors. Where a failure is detected, a trouble signal shall be activated. (2) The refrigerant detector shall have one or more

set points to activate responses in accordance with Section 1106.2.2.1 or Section 1107.1.7.

REFRIGERATION

(3) The refrigerant detector as installed, including

any sampling tubes, shall activate responses within a time not to exceed 30 seconds after exposure to refrigerant concentration exceeding the set point value specified in Section 1106.2.2.1 or Section 1107.1.7. 1106.2.3 Mechanical Ventilation. Machinery rooms shall be vented to the outdoors, utilizing mechanical ventilation in accordance with Section 1106.2.4 and Section 1106.2.5. 1106.2.4 Ventilation. Mechanical ventilation referred to in Section 1106.2.3 shall be by one or more powerdriven fans capable of exhausting air from the machinery room at not less than the amount shown in accordance with Section 1106.2.5.

To obtain a reduced airflow for normal ventilation, multiple fans or multispeed fans shall be used. Provision shall be made to supply makeup air to replace that being exhausted. Ducts for supply and exhaust to the machinery room shall serve no other area. The makeup air supply locations shall be positioned relative to the exhaust air locations to avoid short-circuiting. Inlets to the exhaust ducts shall be located in an area where refrigerant from a leak will concentrate, in consideration of the location of the replacement supply air paths, refrigerating machines, and the density of the refrigerant relative to air.

Inlets to exhaust ducts shall be within 1 foot (305 mm) of the lowest point of the machinery room for refrigerants that are heavier than air, and shall be within 1 foot (305 mm) of the highest point for refrigerants that are lighter than air. The discharge of the exhaust air shall be to the outdoors in such a manner as not to cause a nuisance or danger. 1106.2.5 Emergency Ventilation-Required Air- flow. An emergency ventilation system shall be required to exhaust an accumulation of refrigerant due to leaks or a rupture of the system. The emergency ventilation required shall be capable of removing air from the machinery room in not less than the airflow quantity in Section 1106.2.5.1 or Section 1106.2.5.2. Where multiple refrigerants are present, then the highest airflow quantity shall apply.

1106.2.5.1 Ventilation - A1, A2, A3, B1, B2L, B2 and B3 refrigerants. The emergency ventilation for A1, A2, A3, B1, B2L, B2 and B3 refrigerants shall have the capacity to provide mechanical exhaust at a rate as determined in accordance with Equation 1106.2.5.1.

Q = 100 √ G (Equation 1106.2.5.1)

Where: Q = Air flow rate, cubic feet per minute. G = Refrigerant mass in largest system, pounds.

For SI units: 1 cubic foot per minute = 0.00047 m 3 /s, 1 pound = 0.453 kg

2022 CALIFORNIA MECHANICAL CODE 219

REFRIGERATION

1106.2.5.2 Ventilation - Group A2L Refriger- ants. The emergency ventilation for A2L refrigerants shall have the capacity to provide mechanical exhaust at a rate determined in accordance with Table 1106.2.5.2.

TABLE 1106.2.5.2

REQUIRED AIRFLOW FOR GROUP A2L REFRIGERANTS

REFRIGERANT MINIMUM AIR FLOW*


REFRIGERANT

(CFM)

R-32

32 500


R-143a


28 600


R-444A


13 700


R-444B


22 400

R-445A

16 400

R-446A

50 500

R-447A

50 200

R-447B

29 600

R-451A

14 900


R-451B


14 900


R-452B


31 500


R-454A


4290


R-454B


6650

R-454C

32 800

R-455A

4770

R-457A

31 400

R-1234yf

16 500

R-1234zeE

12 600

For SI units: 1 cubic foot per minute = 0.00047 m 3 /s

  • The values were tabulated from the following equation:

(Equation 1106.2.5.2) QA2L ≥ [( ρ · ν ·A )/( LFL - 0.50)]

Where:

ρ = Refrigerant density, pounds per cubic feet (kg/m 3 ).

ν = Refrigerant velocity equal to the refrigerant acoustic velocity (speed

of sound), feet per second (m/s).

A = Cross-section flow area of refrigerant leak, square feet (m 2 ),

A = 0.00136 ft 2 (0.000126 m 2 ).

LFL = Lower Flammability Limit, or ETFL60 where no LFL exist, pub lished value in accordance with ASHRAE 34.

QA2L = Minimum required air flow rate, conversion to other units of

measures is permitted, cubic feet per second (m 3 /s).

above inlet air temperature or a maximum temperature of 122°F (50°C).

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
    Overview
    1. 1101.1 Applicability. Part I governs the design, installation,
    2. 1101.2 Equipment. Equipment for refrigerant recovery,
    3. 1102.1 General. Refrigeration systems using a refrigerant
    4. 1102.2 Ammonia Refrigeration Systems. Refrigeration
    5. 1102.3 Refrigerants. The refrigerant used shall be of a type
    6. 1103.1 Classification of Refrigerants. Refrigerants shall
    7. 1103.2 Classification of Refrigeration Systems.
    8. 1103.3 Higher Flammability Refrigerants. Group A3
    9. 1104.1 System Selection. Refrigeration systems shall be
    10. 1104.2 Refrigerant Concentration Limit. The concentration of r…
    11. 1104.3 Institutional Occupancies. The RCL value
    12. 1104.4 Industrial Occupancies and Refrigerated
    13. 1104.5 Flammable Refrigerants. The total of Group A2,
    14. 1104.6 Applications for Human Comfort and for Non-
    15. 1104.7 Refrigerant Type and Purity. Refrigerants shall
    16. 1104.8 Changing Refrigerants. A change in the type of
    17. 1105.1 Human Comfort. Cooling systems used for human
    18. 1105.2 Supports and Anchorage. Supports and anchorage for refr…
    19. 1105.3 Access. An unobstructed readily accessible opening and …
    20. 1105.4 Illumination and Service Receptacles. In addition to th…
    21. 1105.5 Ventilation of Rooms Containing Condensing
    22. 1105.6 Prohibited Locations. Refrigeration systems or
    23. 1105.7 Condensate. Condensate from air-cooling coils
    24. 1105.8 Defrost. Where defrost cycles are required for portions…
    25. 1105.9 Overflows. Where condensate or defrost liquids are
    26. 1105.10 Condensate, Defrost, and Overflow Dis-
    27. 1105.11 Refrigerant Port Protection. Air conditioning
    28. 1105.12 Storage. Refrigerants and refrigerant oils not
    29. 1106.1 Where Required. Refrigeration systems shall be
    30. 1106.2 Refrigeration Machinery Room, General
    31. 1106.4 Natural Ventilation. Where a refrigerating system
    32. 1106.5 Combustion Air. No open flames that use combustion air …
    33. 1106.6 Airflow. There shall be no airflow to or from an occupi…
    34. 1106.7 Ventilation Intake. Makeup air intakes to replace
    35. 1106.3 Normal Operation. A part of the refrigeration
    36. 1106.8 Maximum Temperature. Ventilation or mechanical cooling …
    37. 1106.9 Refrigerant Parts in Air Duct. Joints and refrigerant-c…
    38. 1106.10 Dimensions. Refrigeration machinery rooms shall
    39. 1106.11 Restricted Access. Access to the refrigeration
    40. 1106.12 Exits. Exits shall comply with the building code for
    41. 1107.1 General. In cases specified in the rules of Section
    42. 1108.1 General. Equipment, piping, ducts, vents, or similar
    43. 1108.2 Electrical. Electrical equipment and installations
    44. 1108.3 Emergency Shut-off. A clearly identified emergency shut…
    45. 1108.4 Installation, Maintenance, and Testing. Detection and a…
    46. 1108.5 Emergency Pressure Control System. Where
    47. 1109.1 Materials. Materials used in the construction and
    48. 1109.2 Joints. Iron or steel pipe joints shall be of approved
    49. 1109.3 Penetration of Piping. Refrigerant piping shall not
    50. 1109.4 Location of Refrigeration Piping. Refrigerant
    51. 1109.5 Underground Piping. Refrigerant piping placed
    52. 1109.6 Support. In addition to the requirements of Section
    53. 1109.7 Pipe Enclosure. Refrigerant piping and tubing
    54. 1109.8 Visual Inspection. Refrigerant piping and joints
    55. 1109.9 Condensation. Piping and fittings that convey
    56. 1109.10 Identification. Piping shall be in accordance with
    57. 1110.1 More than 6.6 Pounds of Refrigerant. Systems
    58. 1110.2 More than 110 Pounds of Refrigerant. Systems
    59. 1110.3 Support. Stop valves installed in copper refrigerant
    60. 1110.4 Access. Stop valves required by Section 1110.0 shall
    61. 1110.5 Identification. Stop valves shall be identified by tagg…
    62. 1111.1 Where Required. Pressure-limiting devices complying wit…
    63. 1111.2 Setting. Pressure limiting devices shall be set in
    64. 1111.3 Location. Stop valves shall not be installed between
    65. 1111.4 Emergency Stop. Activation of a pressure-limiting
    66. 1112.1 General. Refrigeration systems shall be protected by
    67. 1112.2 Positive Displacement Compressor. A positive
    68. 1112.3 Liquid-Containing Portions of Systems. Liquid-containin…
    69. 1112.4 Evaporators. Heat exchanger coils located downstream, o…
    70. 1112.5 Hydrostatic Expansion. Pressure rise resulting
    71. 1112.6 Actuation. Pressure-relief devices shall be directpress…
    72. 1112.7 Stop Valves Prohibited. Stop valves shall not be
    73. 1112.8 Location. Pressure-relief devices shall be connected
    74. 1112.9 Materials. The seats and discs of pressure-relief
    75. 1112.10 Pressure-Relief Device Settings. Pressurerelief valves…
    76. 1112.11 Discharge from Pressure-Relief Devices.
    77. 1112.12 Discharge Piping. The piping used for pressurerelief d…
    78. 1112.13 Rating of Pressure-Relief Device. The rated
    79. 1112.14 Rating of Rupture Members and Fusible
    80. 1113.1 General. Pressure vessels shall be provided with
    81. 1113.2 Type of Protection. Pressure vessels with an internal g…
    82. 1113.3 Discharging into Lowside of System. For pressure-relief…
    83. 1113.4 Parallel Pressure-Relief Devices. Two or more
    84. 1113.5 Discharge Capacity. The minimum required discharge capa…
    85. 1113.6 Three-Way Valve. Pressure vessels of 10 cubic feet
    86. 1114.1 General. Systems containing other than Group A1 or
    87. 1114.2 Design Requirements. Flaring devices shall be
    88. 1114.3 Testing. Flaring systems shall be tested to demonstrate…
    89. 1115.1 General. In addition to labels required elsewhere in
    90. 1115.2 Volume and Type. A condenser, receiver, absorber,
    91. 1115.3 Permanent Sign. In a refrigeration machinery room
    92. 1115.4 Marking of Pressure-Relief Devices. Pressurerelief valv…
    93. 1116.1 Factory Tests. Refrigerant-containing parts of unit
    94. 1116.2 Field Tests. Refrigerant-containing parts of a system t…
    95. 1116.3 Test Gases. Tests shall be performed with dry nitrogen …
    96. 1116.4 Declaration. A dated declaration of test shall be provi…
    97. 1116.5 Brine Systems. Brine-containing portions of a system sh…
    98. 1117.1 Inside Dimensions 6 Inches or Less. Pressure
    99. 1117.2 Inside Dimensions More than 6 Inches. Pressure vessels …
    100. 1117.3 Pressure Vessels for 15 psig or Less. Pressure
    101. 1118.1 General. Refrigeration systems shall be operated and
    102. 1119.1 Applicability. Cooling towers, evaporative condensers, …
    103. 1120.1 General. Cooling towers, evaporative condensers,
    104. 1121.1 General. Drains, overflows, and blow-down provisions sh…
    105. 1122.1 General. Chemical treatment systems shall comply
    106. 1122.2 Automated Control of Cycles of Concentra-
    107. 1123.1 General. Cooling towers, evaporative condensers,
    108. 1124.1 General. Electrical systems shall be in accordance
    109. 1125.1 General. Equipment containing refrigerants as a part
    110. 1126.1 General. Cooling towers, evaporative condensers,
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — GEOTHERMAL ENERGY SYSTEMS
  24. Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  25. Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.