1106.2 Refrigeration Machinery Room, General
California Mechanical Code (Title 24, Part 4) · 2022 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
Requirements. Where a refrigeration system is located indoors and a machinery room is required in accordance with Section 1106.1, the machinery room shall be in accordance with Section 1106.2.1 through Section 1106.2.5.2.
1106.2.1 Access. Machinery rooms shall not be prohibited from housing other mechanical equipment unless specifically prohibited elsewhere in this chapter. A machinery room shall be so dimensioned that parts are accessible with space for service, maintenance, and operations. There shall be clear head room of not less than 7.25 feet (2210 mm) below equipment situated over passageways. [ASHRAE 15:8.11.1] 1106.2.2 Openings. Each refrigeration machinery room shall have a tight-fitting door or doors opening outward, self-closing where they open into the building and adequate in number to ensure freedom for persons to escape in an emergency. With the exception of access doors and panels in air ducts and air-handling units in accordance with Section 1106.6, there shall be no openings that will permit passage of escaping refrigerant to other parts of the building. [ASHRAE 15:8.11.2]
1106.2.2.1 Detectors and Alarms. Each refrigeration machinery room shall contain one or more refrigerant detectors in accordance with Section 1106.2.2.2, located in areas where refrigerant from a leak will concentrate, that actuate an alarm and mechanical ventilation in accordance with Section 1106.2.4 at a set point not more than the corresponding Occupational Exposure Limit, OEL, in accordance with Table 1102.3, a set point determined in accordance with the OEL as defined in Chapter 2 shall be approved by the Authority Having Jurisdiction. The alarm shall annunciate visual and audible alarms inside the refrigeration machinery room and outside each entrance to the refrigeration machinery room. The alarms required in this section shall be of the manual reset type with the reset located inside the refrigeration machinery room. Alarms set at other levels, such as IDLH, and automatic reset alarms shall be permitted in addition to those required in accordance with this section. The meaning of each alarm shall be clearly marked by signage near the annunciator. Exception: Refrigerant detectors are not required where only systems using R-718 (water) are located in the refrigeration machinery room. 1106.2.2.2 Refrigerant Detectors. Refrigerant detectors required in accordance with Section 1106.2.2.1 or Section 1107.1.7 shall meet all of the following conditions: (1) The refrigerant detector shall perform automatic
self-testing of sensors. Where a failure is detected, a trouble signal shall be activated. (2) The refrigerant detector shall have one or more
set points to activate responses in accordance with Section 1106.2.2.1 or Section 1107.1.7.
REFRIGERATION
(3) The refrigerant detector as installed, including
any sampling tubes, shall activate responses within a time not to exceed 30 seconds after exposure to refrigerant concentration exceeding the set point value specified in Section 1106.2.2.1 or Section 1107.1.7. 1106.2.3 Mechanical Ventilation. Machinery rooms shall be vented to the outdoors, utilizing mechanical ventilation in accordance with Section 1106.2.4 and Section 1106.2.5. 1106.2.4 Ventilation. Mechanical ventilation referred to in Section 1106.2.3 shall be by one or more powerdriven fans capable of exhausting air from the machinery room at not less than the amount shown in accordance with Section 1106.2.5.
To obtain a reduced airflow for normal ventilation, multiple fans or multispeed fans shall be used. Provision shall be made to supply makeup air to replace that being exhausted. Ducts for supply and exhaust to the machinery room shall serve no other area. The makeup air supply locations shall be positioned relative to the exhaust air locations to avoid short-circuiting. Inlets to the exhaust ducts shall be located in an area where refrigerant from a leak will concentrate, in consideration of the location of the replacement supply air paths, refrigerating machines, and the density of the refrigerant relative to air.
Inlets to exhaust ducts shall be within 1 foot (305 mm) of the lowest point of the machinery room for refrigerants that are heavier than air, and shall be within 1 foot (305 mm) of the highest point for refrigerants that are lighter than air. The discharge of the exhaust air shall be to the outdoors in such a manner as not to cause a nuisance or danger. 1106.2.5 Emergency Ventilation-Required Air- flow. An emergency ventilation system shall be required to exhaust an accumulation of refrigerant due to leaks or a rupture of the system. The emergency ventilation required shall be capable of removing air from the machinery room in not less than the airflow quantity in Section 1106.2.5.1 or Section 1106.2.5.2. Where multiple refrigerants are present, then the highest airflow quantity shall apply.
1106.2.5.1 Ventilation - A1, A2, A3, B1, B2L, B2 and B3 refrigerants. The emergency ventilation for A1, A2, A3, B1, B2L, B2 and B3 refrigerants shall have the capacity to provide mechanical exhaust at a rate as determined in accordance with Equation 1106.2.5.1.
Q = 100 √ G (Equation 1106.2.5.1)
Where: Q = Air flow rate, cubic feet per minute. G = Refrigerant mass in largest system, pounds.
For SI units: 1 cubic foot per minute = 0.00047 m 3 /s, 1 pound = 0.453 kg
2022 CALIFORNIA MECHANICAL CODE 219
REFRIGERATION
1106.2.5.2 Ventilation - Group A2L Refriger- ants. The emergency ventilation for A2L refrigerants shall have the capacity to provide mechanical exhaust at a rate determined in accordance with Table 1106.2.5.2.
TABLE 1106.2.5.2
REQUIRED AIRFLOW FOR GROUP A2L REFRIGERANTS
| REFRIGERANT | MINIMUM AIR FLOW* |
|---|---|
REFRIGERANT |
(CFM) |
R-32 |
32 500 |
R-143a |
28 600 |
R-444A |
13 700 |
R-444B |
22 400 |
R-445A |
16 400 |
R-446A |
50 500 |
R-447A |
50 200 |
R-447B |
29 600 |
R-451A |
14 900 |
R-451B |
14 900 |
R-452B |
31 500 |
R-454A |
4290 |
R-454B |
6650 |
R-454C |
32 800 |
R-455A |
4770 |
R-457A |
31 400 |
R-1234yf |
16 500 |
R-1234zeE |
12 600 |
For SI units: 1 cubic foot per minute = 0.00047 m 3 /s
- The values were tabulated from the following equation:
(Equation 1106.2.5.2) QA2L ≥ [( ρ · ν ·A )/( LFL - 0.50)]
Where:
ρ = Refrigerant density, pounds per cubic feet (kg/m 3 ).
ν = Refrigerant velocity equal to the refrigerant acoustic velocity (speed
of sound), feet per second (m/s).
A = Cross-section flow area of refrigerant leak, square feet (m 2 ),
A = 0.00136 ft 2 (0.000126 m 2 ).
LFL = Lower Flammability Limit, or ETFL60 where no LFL exist, pub lished value in accordance with ASHRAE 34.
QA2L = Minimum required air flow rate, conversion to other units of
measures is permitted, cubic feet per second (m 3 /s).
above inlet air temperature or a maximum temperature of 122°F (50°C).
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
▸Chapter 11 — REFRIGERATION
Overview- 1101.1 Applicability. Part I governs the design, installation,
- 1101.2 Equipment. Equipment for refrigerant recovery,
- 1102.1 General. Refrigeration systems using a refrigerant
- 1102.2 Ammonia Refrigeration Systems. Refrigeration
- 1102.3 Refrigerants. The refrigerant used shall be of a type
- 1103.1 Classification of Refrigerants. Refrigerants shall
- 1103.2 Classification of Refrigeration Systems.
- 1103.3 Higher Flammability Refrigerants. Group A3
- 1104.1 System Selection. Refrigeration systems shall be
- 1104.2 Refrigerant Concentration Limit. The concentration of r…
- 1104.3 Institutional Occupancies. The RCL value
- 1104.4 Industrial Occupancies and Refrigerated
- 1104.5 Flammable Refrigerants. The total of Group A2,
- 1104.6 Applications for Human Comfort and for Non-
- 1104.7 Refrigerant Type and Purity. Refrigerants shall
- 1104.8 Changing Refrigerants. A change in the type of
- 1105.1 Human Comfort. Cooling systems used for human
- 1105.2 Supports and Anchorage. Supports and anchorage for refr…
- 1105.3 Access. An unobstructed readily accessible opening and …
- 1105.4 Illumination and Service Receptacles. In addition to th…
- 1105.5 Ventilation of Rooms Containing Condensing
- 1105.6 Prohibited Locations. Refrigeration systems or
- 1105.7 Condensate. Condensate from air-cooling coils
- 1105.8 Defrost. Where defrost cycles are required for portions…
- 1105.9 Overflows. Where condensate or defrost liquids are
- 1105.10 Condensate, Defrost, and Overflow Dis-
- 1105.11 Refrigerant Port Protection. Air conditioning
- 1105.12 Storage. Refrigerants and refrigerant oils not
- 1106.1 Where Required. Refrigeration systems shall be
- 1106.2 Refrigeration Machinery Room, General
- 1106.4 Natural Ventilation. Where a refrigerating system
- 1106.5 Combustion Air. No open flames that use combustion air …
- 1106.6 Airflow. There shall be no airflow to or from an occupi…
- 1106.7 Ventilation Intake. Makeup air intakes to replace
- 1106.3 Normal Operation. A part of the refrigeration
- 1106.8 Maximum Temperature. Ventilation or mechanical cooling …
- 1106.9 Refrigerant Parts in Air Duct. Joints and refrigerant-c…
- 1106.10 Dimensions. Refrigeration machinery rooms shall
- 1106.11 Restricted Access. Access to the refrigeration
- 1106.12 Exits. Exits shall comply with the building code for
- 1107.1 General. In cases specified in the rules of Section
- 1108.1 General. Equipment, piping, ducts, vents, or similar
- 1108.2 Electrical. Electrical equipment and installations
- 1108.3 Emergency Shut-off. A clearly identified emergency shut…
- 1108.4 Installation, Maintenance, and Testing. Detection and a…
- 1108.5 Emergency Pressure Control System. Where
- 1109.1 Materials. Materials used in the construction and
- 1109.2 Joints. Iron or steel pipe joints shall be of approved
- 1109.3 Penetration of Piping. Refrigerant piping shall not
- 1109.4 Location of Refrigeration Piping. Refrigerant
- 1109.5 Underground Piping. Refrigerant piping placed
- 1109.6 Support. In addition to the requirements of Section
- 1109.7 Pipe Enclosure. Refrigerant piping and tubing
- 1109.8 Visual Inspection. Refrigerant piping and joints
- 1109.9 Condensation. Piping and fittings that convey
- 1109.10 Identification. Piping shall be in accordance with
- 1110.1 More than 6.6 Pounds of Refrigerant. Systems
- 1110.2 More than 110 Pounds of Refrigerant. Systems
- 1110.3 Support. Stop valves installed in copper refrigerant
- 1110.4 Access. Stop valves required by Section 1110.0 shall
- 1110.5 Identification. Stop valves shall be identified by tagg…
- 1111.1 Where Required. Pressure-limiting devices complying wit…
- 1111.2 Setting. Pressure limiting devices shall be set in
- 1111.3 Location. Stop valves shall not be installed between
- 1111.4 Emergency Stop. Activation of a pressure-limiting
- 1112.1 General. Refrigeration systems shall be protected by
- 1112.2 Positive Displacement Compressor. A positive
- 1112.3 Liquid-Containing Portions of Systems. Liquid-containin…
- 1112.4 Evaporators. Heat exchanger coils located downstream, o…
- 1112.5 Hydrostatic Expansion. Pressure rise resulting
- 1112.6 Actuation. Pressure-relief devices shall be directpress…
- 1112.7 Stop Valves Prohibited. Stop valves shall not be
- 1112.8 Location. Pressure-relief devices shall be connected
- 1112.9 Materials. The seats and discs of pressure-relief
- 1112.10 Pressure-Relief Device Settings. Pressurerelief valves…
- 1112.11 Discharge from Pressure-Relief Devices.
- 1112.12 Discharge Piping. The piping used for pressurerelief d…
- 1112.13 Rating of Pressure-Relief Device. The rated
- 1112.14 Rating of Rupture Members and Fusible
- 1113.1 General. Pressure vessels shall be provided with
- 1113.2 Type of Protection. Pressure vessels with an internal g…
- 1113.3 Discharging into Lowside of System. For pressure-relief…
- 1113.4 Parallel Pressure-Relief Devices. Two or more
- 1113.5 Discharge Capacity. The minimum required discharge capa…
- 1113.6 Three-Way Valve. Pressure vessels of 10 cubic feet
- 1114.1 General. Systems containing other than Group A1 or
- 1114.2 Design Requirements. Flaring devices shall be
- 1114.3 Testing. Flaring systems shall be tested to demonstrate…
- 1115.1 General. In addition to labels required elsewhere in
- 1115.2 Volume and Type. A condenser, receiver, absorber,
- 1115.3 Permanent Sign. In a refrigeration machinery room
- 1115.4 Marking of Pressure-Relief Devices. Pressurerelief valv…
- 1116.1 Factory Tests. Refrigerant-containing parts of unit
- 1116.2 Field Tests. Refrigerant-containing parts of a system t…
- 1116.3 Test Gases. Tests shall be performed with dry nitrogen …
- 1116.4 Declaration. A dated declaration of test shall be provi…
- 1116.5 Brine Systems. Brine-containing portions of a system sh…
- 1117.1 Inside Dimensions 6 Inches or Less. Pressure
- 1117.2 Inside Dimensions More than 6 Inches. Pressure vessels …
- 1117.3 Pressure Vessels for 15 psig or Less. Pressure
- 1118.1 General. Refrigeration systems shall be operated and
- 1119.1 Applicability. Cooling towers, evaporative condensers, …
- 1120.1 General. Cooling towers, evaporative condensers,
- 1121.1 General. Drains, overflows, and blow-down provisions sh…
- 1122.1 General. Chemical treatment systems shall comply
- 1122.2 Automated Control of Cycles of Concentra-
- 1123.1 General. Cooling towers, evaporative condensers,
- 1124.1 General. Electrical systems shall be in accordance
- 1125.1 General. Equipment containing refrigerants as a part
- 1126.1 General. Cooling towers, evaporative condensers,
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — GEOTHERMAL ENERGY SYSTEMS
- Appendix G — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix H — EXAMPLE CALCULATION OF OUTDOOR AIR RATE