Chapter 3 — GENERAL REGULATIONS

322.1 The following conditions shall be met for sensitive

California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

areas or rooms:

(1) Thermostats and humidistats shall be either locally reset-

table and of the non-locking type or remotely resettable

(1) Thermostats and humidistats shall be either locally reset-

table and of the non-locking type or remotely resettable and of the locking type. (2) Systems shall be capable of maintaining the rooms within

the temperature range in Table 4-A during normal oper-

(2) Systems shall be capable of maintaining the rooms within

the temperature range in Table 4-A during normal oper- ation. Lower or higher temperature shall be permitted when patients’ comfort and/or medical conditions require those conditions. (3) The humidity ranges listed in Table 4-A are the minimum

and maximum limits where control is specifically needed.

(3) The humidity ranges listed in Table 4-A are the minimum

and maximum limits where control is specifically needed. (4) Types of intensive care service spaces are listed in the

California Building Code.

California Building Code.

2019 CALIFORNIA MECHANICAL CODE 57

GENERAL REGULATIONS any other purpose or distributed to any other persons or parti es.

TABLE 303.10.1 REDUCTION OF CLEARANCES WITH SPECIFIED FORMS OF PROTECTION 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11

[NFPA 54: TABLE 10.2.3]
TYPE OF PROTECTION
APPLIED TO AND COVERING
ALL SURFACES OF COM-
BUSTIBLE MATERIAL
WITHIN THE DISTANCE
SPECIFIED AS THE
REQUIRED CLEARANCE
WITH NO PROTECTION

WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR,
OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR,
OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR,
OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR,
OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR,
OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR,
OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR,
OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR,
OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR,
OR SINGLE-WALL METAL PIPE IS:
WHERE THE REQUIRED CLEARANCE WITH NO PROTECTION FROM APPLIANCE, VENT CONNECTOR,
OR SINGLE-WALL METAL PIPE IS:
TYPE OF PROTECTION
APPLIED TO AND COVERING
ALL SURFACES OF COM-
BUSTIBLE MATERIAL
WITHIN THE DISTANCE
SPECIFIED AS THE
REQUIRED CLEARANCE
WITH NO PROTECTION

36 (INCHES) 36 (INCHES) 18 (INCHES) 18 (INCHES) 12 (INCHES) 12 (INCHES) 9 (INCHES) 9 (INCHES) 6 (INCHES) 6 (INCHES)
TYPE OF PROTECTION
APPLIED TO AND COVERING
ALL SURFACES OF COM-
BUSTIBLE MATERIAL
WITHIN THE DISTANCE
SPECIFIED AS THE
REQUIRED CLEARANCE
WITH NO PROTECTION

ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES) ALLOWABLE CLEARANCES WITH SPECIFIED PROTECTION (INCHES)
TYPE OF PROTECTION
APPLIED TO AND COVERING
ALL SURFACES OF COM-
BUSTIBLE MATERIAL
WITHIN THE DISTANCE
SPECIFIED AS THE
REQUIRED CLEARANCE
WITH NO PROTECTION

USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
USE COLUMN 1 FOR CLEARANCES ABOVE APPLIANCE OR HORIZONTAL CONNECTOR. USE COLUMN 2 FOR
CLEARANCES FROM APPLIANCES, VERTICAL CONNECTOR, AND SINGLE-WALL METAL PIPE.
TYPE OF PROTECTION
APPLIED TO AND COVERING
ALL SURFACES OF COM-
BUSTIBLE MATERIAL
WITHIN THE DISTANCE
SPECIFIED AS THE
REQUIRED CLEARANCE
WITH NO PROTECTION

ABOVE
(COLUMN 1)
SIDES AND
REAR
(COLUMN 2)
ABOVE
(COLUMN 1)
SIDES AND
REAR
(COLUMN 2)
ABOVE
(COLUMN 1)
SIDES AND
REAR
(COLUMN 2)
ABOVE
(COLUMN 1)
SIDES AND
REAR
(COLUMN 2)
ABOVE
(COLUMN 1)
SIDES AND
REAR
(COLUMN 2)
(1) 31⁄2 inch thick masonry
wall without ventilated
air space

–– 24 –– 12 –– 9 –– 6 –– 5

(2) 1⁄2 of an inch insulation
board over 1 inch glass
fiber or mineral wool
batts

24 18 12 9 9 6 6 5 4 3
(3) 0.024 inch (nominal 24
gauge) sheet metal over 1
inch glass fiber or min-
eral wool batts reinforced
with wire on rear face
with ventilated air space

18
12
9
6
6
4
5
3
3
3

(4) 31⁄2 inch thick masonry
wall with ventilated air
space

––
12
––
6
––
6
––
6
––
6
[NFPA 54: TABLE 10.2.3]
(5) 0.024 inch (nominal 24
gauge) sheet metal with
ventilated air space

18
12
9
6
6
4
5
3
3
2

(6) 1⁄2 of an inch thick insula-
tion board with ventilated
air space

18 12 9 6 6 4 5 3 3 3

(7) 0.024 inch (nominal 24
gauge) sheet metal with
ventilated air space over
0.024 inch (nominal 24
gauge) sheet metal with
ventilated air space



18 12 9 6 6 4 5 3 3 3

(8) 1 inch glass fiber or
mineral
wool
batts
sandwiched
between
two sheets 0.024 inch
(nominal 24 gauge)
sheet metal with venti-
lated air space
18
12
9 6 6 4 5 3 3 3

Notes:

1

Notes:

1 Reduction of clearances from combustible materials shall not interfere with combustion air, draft hood clearance and relief, and accessibility of servicing. 2 Clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the appliance, disregarding an intervening protection applied to the combustible material. 3 Spacers and ties shall be of noncombustible material. No spacer or tie shall be used directly opposite the appliance or connector. 4 Where clearance reduction systems use a ventilated air space, a provision for air circulation shall be provided as described. [See Figure 303.10.1(2) and Figure 303.10.1(3)] 5 There shall be not less than 1 inch (25.4 mm) between clearance reduction systems and combustible walls and ceilings for reduction systems using a ventilated air space. 6 Where a wall protector is mounted on a single flat wall away from corners, it shall have not less than a 1 inch (25.4 mm) air gap. To provide air circulation, the bottom and top edges, or the side and top edges, or edges shall be left open. 7 Mineral wool batts (blanket or board) shall have a density of not less than 8 pounds per cubic foot (lb/ft3) (128 kg/m3) and a minimum melting point of 1500°F (816°C). 8 Insulation material used as part of a clearance reduction system shall have a thermal conductivity of 1 British thermal unit inch per hour square foot degree Fahrenheit [Btu•in/(h•ft 2 •°F)] [0.1W/(m•K)] or less. 9 There shall be not less than 1 inch (25.4 mm) between the appliance and the protector. In no case shall the clearance between the appliance and the combustible surface be reduced below that allowed in this table. 10 Clearances and thicknesses are minimum; larger clearances and thicknesses are acceptable. 11 Listed single-wall connectors shall be installed in accordance with the terms of their listing and the manufacturer’s installation instructions.

58 2019 CALIFORNIA MECHANICAL CODE

GENERAL REGULATIONS

Notes: 2 B – Equals the reduced clearance permitted in accordance with Table 303.10.1. 3 The protection applied to the construction using combustible material shall extend far enough in each direction to make C equal to A.

For SI units: 1 inch = 25.4 mm

FIGURE 303.10.1(3) MASONRY CLEARANCE REDUCTION SYSTEM

[NFPA 54: FIGURE 10.3.2.3(c)]

Note: Masonry walls shall be permitted to be attached to combustible walls using wall ties. Spacers shall not be used directly behind appliance or connector.

FIGURE 303.10.1(2) WALL PROTECTOR CLEARANCE REDUCTION SYSTEM

[NFPA 54: FIGURE 10.3.2.3(b)]

2019 CALIFORNIA MECHANICAL CODE 59

FIGURE 303.10.1(1)1, 2, 3

EXTENT OF PROTECTION NECESSARY TO REDUCE CLEARANCES FROM GAS APPLIANCES OR VENT CONNECTORS

[NFPA 54: FIGURE 10.3.2.3(a)]

GENERAL REGULATIONS any other purpose or distributed to any other persons or parti es.

TABLE 313.3 HANGERS AND SUPPORTS
MATERIALS
TYPES OF JOINTS
HORIZONTAL
VERTICAL
Cast
Lead and Oakum
5 feet, except 10 feet where 10 foot
lengths are installed1, 2, 3
Base and each floor, not to exceed 15 feet
Cast
Compression Gasket

Every other joint, unless over 4 feet
then support each joint1, 2, 3
Base and each floor, not to exceed 15 feet
Cast-Iron Hubless
Shielded Coupling

Every other joint, unless over 4 feet
then support each joint1, 2, 3, 4
Base and each floor, not to exceed 15 feet
Copper & Copper Alloys
Soldered, Brazed,
Threaded, or Mechanical

11⁄2 inches and smaller, 6 feet; 2
inches and larger, 10 feet
Each floor, not to exceed 10 feet5
Steel Pipe for Water DWV

Threaded or Welded

3⁄4 inch and smaller, 10 feet; 1 inch
and larger, 12 feet
Every other floor, not to exceed 25 feet5
Steel Pipe for Gas
Threaded or Welded

1⁄2 inch, 6 feet;3⁄4 inch and 1 inch, 8
feet; 11⁄4 inches and larger, 10 feet
1⁄2 inch, 6 feet;3⁄4 inch and 1 inch, 8 feet;
11⁄4 inches every floor level
Schedule 40 PVC and
ABS
Solvent Cemented
All sizes, 4 feet; allow for expansion
every 30 feet3
Base and each floor; provide mid-story
guides; provide for expansion every 30 feet

CPVC
Solvent Cemented

1 inch and smaller, 3 feet; 11⁄4 inches
and larger, 4 feet

Base and each floor; provide mid-story guides
Lead
Wiped or Burned

Continuous Support

Not to exceed 4 feet
Steel
Mechanical
In accordance with standards acceptable to the Authority Having Jurisdiction


In accordance with standards acceptable to the Authority Having Jurisdiction


PEX
Cold Expansion, Insert
and Compression
1 inch and smaller, 32 inches;
11⁄4 inches and larger, 4 feet


Base and each floor;
provide mid-story guides
PEX-AL-PEX
Metal insert and metal
compression
~~1⁄~~2 inch
3⁄4 inch
1 inch
All sizes 98 inches

Base and each floor;
provide mid-story guides
PE-AL-PE
Metal insert and metal
compression

~~1⁄~~2 inch
3⁄4 inch
1 inch
All sizes 98 inches
Base and each floor;
provide mid-story guides
PE-RT
Insert and Compression

1 inch and smaller, 32 inches;
11⁄4 inches and larger, 4 feet
Base and each floor;
provide mid-story guides
Polypropylene (PP)
Fusion weld (socket, butt,
saddle, electrofusion),
threaded (metal threads
only), or mechanical

1 inch and smaller, 32 inches;
11⁄4 inches and larger, 4 feet

Base and each floor;
provide mid-story guides

Notes:

first approved by the Authority Having Jurisdiction. 1 Support adjacent to joint, not to exceed 18 inches (457 mm). 2 Brace not to exceed 40 feet (12 192 mm) intervals to prevent horizontal movement. 3 Support at each horizontal branch connection. 4 Hangers shall not be placed on the coupling. 5 Vertical water lines shall be permitted to be supported in accordance with recognized engineering principles with regard to expansion and contraction, where

60 2019 CALIFORNIA MECHANICAL CODE

CALIFORNIA MECHANICAL CODE – MATRIX ADOPTION TABLE

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
    Overview
    1. 301.2 Approval. Equipment or appliance shall be approved
    2. 301.3 Design of Equipment. Installers shall furnish satisfacto…
    3. 301.4 Electrical Connections. For equipment regulated
    4. 301.5 Oil-Burning Appliances. The tank, piping, and
    5. 301.6 Personnel Protection. A metal guard shall be provided ar…
    6. 302.0 Materials – Standards and Alternates.302.1 Minimum Stand…
    7. 302.2 Alternate Materials and Methods of Construc-tion Equival…
    8. 302.3 Alternative Engineered Design. An alternative
    9. 303.2 Closet or Alcove Installations. Central heating
    10. 303.3 Unlisted Appliances. Except as otherwise permitted in th…
    11. 303.4 Anchorage of Appliances. Appliances designed to
    12. 303.5 Movement. Movement of appliances with casters
    13. 303.6 Identification of Equipment. Where more than one
    14. 303.7 Liquefied Petroleum Gas Facilities. Containers,
    15. 303.8 Appliances on Roofs. Appliances on roofs shall be
    16. 303.9 Avoiding Strain on Gas Piping. Appliances shall
    17. 303.10 Clearances. Appliances and their vent connectors
    18. 303.11 Installation in Commercial Garages. Appliances installe…
    19. 303.12 Installation in Aircraft Hangars. Heaters in aircraft h…
    20. 303.13 Pit Location. Where excavation is necessary to install
    21. 304.1 General.304.0 Accessibility for Service. Appliances shal…
    22. 304.2 Sloped Roof. Where equipment or appliances that
    23. 304.3 Access to Appliances on Roofs. Appliances
    24. 304.4 Appliances in Attics and Under-Floor Spaces.
    25. 305.3 Elevator Shaft. Unless required for the functionality
    26. 305.4 Drainage Pan. Where a water heater is located in an
    27. 305.0 Location.305.1 Installation in Garages. Appliances in re…
    28. 305.2 Flood Hazard Areas. For buildings located in flood
    29. 306.0 Automatic Control Devices.306.1 General. Heating applian…
    30. 307.0 Labeling.307.1 Fuel-Burning Appliances. Fuel-burning hea…
    31. 307.2 Electric Heating Appliances. Electric heating
    32. 307.3 Heat Pump and Electric Cooling Appliances.
    33. 307.4 Absorption Units. Absorption units shall bear a permanen…
    34. 309.2 Concealing Imperfections. It shall be unlawful to
    35. 309.3 Installation Practices. Mechanical systems shall
    36. 310.0 Condensate Wastes and Control.310.1 Condensate Disposal.…
    37. 310.2 Condensate Control. Where an equipment or appliance is i…
    38. 310.4 Appliance Condensate Drains. Condensate drain
    39. 310.5 Point of Discharge. Air-conditioning condensate
    40. 310.6 Condensate Waste From Air-ConditioningCoils. Where the c…
    41. 310.7 Plastic Fittings. Female plastic screwed fittings shall
    42. 310.3 Condensate Waste Pipe Material and Sizing.
    43. 311.2 Air Filters. Air filters shall be installed in a heating,
    44. 311.3 Prohibited Source. Outside or return air for a heating
    45. 313.2 Material. Hangers and anchors shall be of sufficient
    46. 313.3 Suspended Piping. Suspended piping or tubing
    47. 313.4 Alignment. Piping or tubing shall be supported in such
    48. 313.5 Underground Installation. Piping or tubing in the
    49. 313.6 Hanger Rod Sizes. Hanger rod sizes shall be not
    50. 313.7 Gas Piping. Gas piping shall be supported by metal
    51. 314.0 Balancing.314.1 General. Heating, ventilating, and air-c…
    52. 311.4 Return-Air Limitations. Return air from one dwelling
    53. 315.0 Louvers in Hurricane Prone Regions.315.1 General. Louver…
    54. 316.2 Installation. Piping or tubing shall be installed so that
    55. 316.3 Corrosion, Erosion, and Mechanical Damage. Piping or tub…
    56. 316.4 Protectively Coated Pipe. Protectively coated pipe
    57. 316.5 Fire-Resistant Construction. Piping, tubing, and
    58. 316.6 Steel Nail Plates. Plastic piping or tubing, copper
    59. 316.7 Sleeves. Sleeves shall be provided to protect piping
    60. 316.8 Firewalls. A pipe sleeve through a firewall shall have
    61. 316.9 Structural Members. A structural member weakened or impa…
    62. 316.10 Rodentproofing. Mechanical system shall be constructed …
    63. 316.11 Metal Collars. In or on buildings where openings
    64. 317.1 Trenches. 317.0 Trenching, Excavation, and Backfill. Tre…
    65. 317.2 Tunneling and Driving. Tunneling and driving shall
    66. 317.3 Open Trenches. Excavations required to be made for
    67. 317.4 Excavations. Excavations shall be completely backfilled …
    68. 318.2 Services/Systems and Utilities. Refer to Section
    69. 319.1 Requirements for Hospitals and Optional Serv-
    70. 319.2 Requirements for Skilled Nursing, Intermedi-
    71. 320.1 Requirements for Hospitals and Optional Serv-
    72. 320.2 Requirements for Skilled Nursing, Intermedi-
    73. 320.3 Requirements for Outpatient Facilities and
    74. 320.5 Psychiatric Services. [OSHPD 1, 1R, 2, 4 & 5 ] For proje…
    75. 321.1 (Does not apply to OSHPD 3 surgical clinic.) All heat-
    76. 321.2 All heating equipment necessary to maintain the min-
    77. 321.3 Equipment necessary for humidification of the areas
    78. 321.4 All supply, return, and exhaust fans required to maintain
    79. 321.5 All control components and control systems necessary
    80. 321.6 Alarms for airborne infection isolation rooms and pro-
    81. 322.1 The following conditions shall be met for sensitive
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  24. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.