Chapter 3 — GENERAL REGULATIONS
304.3 Access to Appliances on Roofs. Appliances
California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
located on roofs or other elevated locations shall be accessible. [NFPA 54:9.4.3.1]
304.3.1.1 Access Type. The inside means of access shall be a permanent, or foldaway inside stairway or ladder, terminating in an enclosure, scuttle, or trap door. Such scuttles or trap doors shall be not less than 22 inches by 24 inches (559 mm by 610 mm) in size, shall open easily and safely under all conditions, especially snow; and shall be constructed so as to permit access from the roof side unless deliberately locked on the inside.
Not less than 6 feet (1829 mm) of clearance shall be between the access opening and the edge of the roof or similar hazard or rigidly fixed rails or guards not less than 42 inches (1067 mm) in height shall be provided on the exposed side. Where parapets or other building structures are utilized in lieu of guards or rails, they shall be not less than 42 inches (1067 mm) in height. [NFPA 54:9.4.3.3] 304.3.1.2 Permanent Ladders. Permanent ladders required by Section 304.3.1.1 shall be constructed in accordance with the following: (1) Side railings shall extend not less than 30 inches
(762 mm) above the roof or parapet wall.
(1) Side railings shall extend not less than 30 inches
(762 mm) above the roof or parapet wall. (2) Landings shall not exceed 18 feet (5486 mm)
apart measured from the finished grade.
(2) Landings shall not exceed 18 feet (5486 mm)
apart measured from the finished grade. (3) Width shall be not less than 14 inches (356 mm)
on center.
(3) Width shall be not less than 14 inches (356 mm)
on center. (4) Rungs spacing shall not exceed 12 inches (305
mm) on center, and each rung shall be capable
(4) Rungs spacing shall not exceed 12 inches (305
mm) on center, and each rung shall be capable of supporting a 300 pound (136.1 kg) load. (5) Toe space shall be not less than 6 inches (152
mm).
(5) Toe space shall be not less than 6 inches (152
mm). 304.3.2 Permanent Lighting. Permanent lighting shall be provided at the roof access. The switch for such lighting shall be located inside the building near the access means leading to the roof. [NFPA 54:9.4.3.4]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
▸Chapter 3 — GENERAL REGULATIONS
Overview- 301.2 Approval. Equipment or appliance shall be approved
- 301.3 Design of Equipment. Installers shall furnish satisfacto…
- 301.4 Electrical Connections. For equipment regulated
- 301.5 Oil-Burning Appliances. The tank, piping, and
- 301.6 Personnel Protection. A metal guard shall be provided ar…
- 302.0 Materials – Standards and Alternates.302.1 Minimum Stand…
- 302.2 Alternate Materials and Methods of Construc-tion Equival…
- 302.3 Alternative Engineered Design. An alternative
- 303.2 Closet or Alcove Installations. Central heating
- 303.3 Unlisted Appliances. Except as otherwise permitted in th…
- 303.4 Anchorage of Appliances. Appliances designed to
- 303.5 Movement. Movement of appliances with casters
- 303.6 Identification of Equipment. Where more than one
- 303.7 Liquefied Petroleum Gas Facilities. Containers,
- 303.8 Appliances on Roofs. Appliances on roofs shall be
- 303.9 Avoiding Strain on Gas Piping. Appliances shall
- 303.10 Clearances. Appliances and their vent connectors
- 303.11 Installation in Commercial Garages. Appliances installe…
- 303.12 Installation in Aircraft Hangars. Heaters in aircraft h…
- 303.13 Pit Location. Where excavation is necessary to install
- 304.1 General.304.0 Accessibility for Service. Appliances shal…
- 304.2 Sloped Roof. Where equipment or appliances that
- 304.3 Access to Appliances on Roofs. Appliances
- 304.4 Appliances in Attics and Under-Floor Spaces.
- 305.3 Elevator Shaft. Unless required for the functionality
- 305.4 Drainage Pan. Where a water heater is located in an
- 305.0 Location.305.1 Installation in Garages. Appliances in re…
- 305.2 Flood Hazard Areas. For buildings located in flood
- 306.0 Automatic Control Devices.306.1 General. Heating applian…
- 307.0 Labeling.307.1 Fuel-Burning Appliances. Fuel-burning hea…
- 307.2 Electric Heating Appliances. Electric heating
- 307.3 Heat Pump and Electric Cooling Appliances.
- 307.4 Absorption Units. Absorption units shall bear a permanen…
- 309.2 Concealing Imperfections. It shall be unlawful to
- 309.3 Installation Practices. Mechanical systems shall
- 310.0 Condensate Wastes and Control.310.1 Condensate Disposal.…
- 310.2 Condensate Control. Where an equipment or appliance is i…
- 310.4 Appliance Condensate Drains. Condensate drain
- 310.5 Point of Discharge. Air-conditioning condensate
- 310.6 Condensate Waste From Air-ConditioningCoils. Where the c…
- 310.7 Plastic Fittings. Female plastic screwed fittings shall
- 310.3 Condensate Waste Pipe Material and Sizing.
- 311.2 Air Filters. Air filters shall be installed in a heating,
- 311.3 Prohibited Source. Outside or return air for a heating
- 313.2 Material. Hangers and anchors shall be of sufficient
- 313.3 Suspended Piping. Suspended piping or tubing
- 313.4 Alignment. Piping or tubing shall be supported in such
- 313.5 Underground Installation. Piping or tubing in the
- 313.6 Hanger Rod Sizes. Hanger rod sizes shall be not
- 313.7 Gas Piping. Gas piping shall be supported by metal
- 314.0 Balancing.314.1 General. Heating, ventilating, and air-c…
- 311.4 Return-Air Limitations. Return air from one dwelling
- 315.0 Louvers in Hurricane Prone Regions.315.1 General. Louver…
- 316.2 Installation. Piping or tubing shall be installed so that
- 316.3 Corrosion, Erosion, and Mechanical Damage. Piping or tub…
- 316.4 Protectively Coated Pipe. Protectively coated pipe
- 316.5 Fire-Resistant Construction. Piping, tubing, and
- 316.6 Steel Nail Plates. Plastic piping or tubing, copper
- 316.7 Sleeves. Sleeves shall be provided to protect piping
- 316.8 Firewalls. A pipe sleeve through a firewall shall have
- 316.9 Structural Members. A structural member weakened or impa…
- 316.10 Rodentproofing. Mechanical system shall be constructed …
- 316.11 Metal Collars. In or on buildings where openings
- 317.1 Trenches. 317.0 Trenching, Excavation, and Backfill. Tre…
- 317.2 Tunneling and Driving. Tunneling and driving shall
- 317.3 Open Trenches. Excavations required to be made for
- 317.4 Excavations. Excavations shall be completely backfilled …
- 318.2 Services/Systems and Utilities. Refer to Section
- 319.1 Requirements for Hospitals and Optional Serv-
- 319.2 Requirements for Skilled Nursing, Intermedi-
- 320.1 Requirements for Hospitals and Optional Serv-
- 320.2 Requirements for Skilled Nursing, Intermedi-
- 320.3 Requirements for Outpatient Facilities and
- 320.5 Psychiatric Services. [OSHPD 1, 1R, 2, 4 & 5 ] For proje…
- 321.1 (Does not apply to OSHPD 3 surgical clinic.) All heat-
- 321.2 All heating equipment necessary to maintain the min-
- 321.3 Equipment necessary for humidification of the areas
- 321.4 All supply, return, and exhaust fans required to maintain
- 321.5 All control components and control systems necessary
- 321.6 Alarms for airborne infection isolation rooms and pro-
- 322.1 The following conditions shall be met for sensitive
- Chapter 4 — VENTILATION AIR
- Chapter 5 — EXHAUST SYSTEMS
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE