303.10 Clearances. Appliances and their vent connectors

California Mechanical Code (Title 24, Part 4) · 2019 edition · updated 2026-09-10 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

shall be installed with clearances from combustible material so their operation does not create a hazard to persons or property. Minimum clearances between combustible walls and the back and sides of various conventional types of appliances and their vent connectors are specified in Chapter 8 and Chapter 9. [NFPA 54:9.2.2] Where not provided in this code, listed and unlisted equipment or appliances shall be installed to maintain the required clearances for servicing and to combustible construction in accordance with the listing and the manufacturer’s installation instructions.

303.10.1 Clearance Reduction. Reduce clearances to combustible construction for listed equipment and appliances shall comply with the listing and Table 303.10.1. Where permitted by the manufacturer, and not provided in this code, reduce clearances to combustible construction for unlisted equipment and appliances shall comply with Table 303.10.1.

303.10.1.1 Type I Hood Exhaust System. Reduce clearances for Type I exhaust systems shall be in accordance with Section 507.4.2 through Section 507.4.2.3. Clearances from the duct or the exhaust fan to the interior surface of enclosures of combustible construction shall be in accordance with Section 510.7.3 and clearances shall not be reduced. 303.10.1.2 Product Conveying Ducts. Reduce clearances to combustibles construction for product conveying ducts shall be in accordance with Section 506.10.3 through Section 506.11.6.3. 303.10.1.3 Solid-Fuel Burning Appliances. For solid-fuel burning appliances, the clearance,

2019 CALIFORNIA MECHANICAL CODE 49

GENERAL REGULATIONS any other purpose or distributed to any other persons or parti es.

304.4.1 Length of Passageway. Where the height of the passageway is less than 6 feet (1829 mm), the distance from the passageway access to the appliance shall not exceed 20 feet (6096 mm) measured along the centerline of the passageway. [NFPA 54:9.5.1.1] 304.4.2 Width of Passageway. The passageway shall be unobstructed and shall have solid flooring not less than 24 inches (610 mm) wide from the entrance opening to the appliance. [NFPA 54:9.5.1.2] 304.4.3 Work Platform. A level working platform not less than 30 inches by 30 inches (762 mm by 762 mm) shall be provided in front of the service side of the appliance. [NFPA 54:9.5.2]

304.3.1 Access. Buildings exceeding 15 feet (4572 mm) in height shall have an inside means of access to the roof unless other means acceptable to the Authority Having Jurisdiction are used. [NFPA 54:9.4.3.2]

»

after reduction, shall not be less than 12 inches (305 mm) to combustible walls and not less than 18 inches (457 mm) to combustible ceilings. The clearance, after reduction, shall be permitted to be less than 12 inches (305 mm) to combustible walls and less than 18 inches (457 mm) to combustible ceilings where the solid-fuel burning appliances is listed for lesser clearance.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Mechanical Code (Title 24, Part 4)
California Mechanical Code (Title 24, Part 4)
  1. Chapter 1 — GENERAL CODE PROVISIONS
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — GENERAL REGULATIONS
    Overview
    1. 301.2 Approval. Equipment or appliance shall be approved
    2. 301.3 Design of Equipment. Installers shall furnish satisfacto…
    3. 301.4 Electrical Connections. For equipment regulated
    4. 301.5 Oil-Burning Appliances. The tank, piping, and
    5. 301.6 Personnel Protection. A metal guard shall be provided ar…
    6. 302.0 Materials – Standards and Alternates.302.1 Minimum Stand…
    7. 302.2 Alternate Materials and Methods of Construc-tion Equival…
    8. 302.3 Alternative Engineered Design. An alternative
    9. 303.2 Closet or Alcove Installations. Central heating
    10. 303.3 Unlisted Appliances. Except as otherwise permitted in th…
    11. 303.4 Anchorage of Appliances. Appliances designed to
    12. 303.5 Movement. Movement of appliances with casters
    13. 303.6 Identification of Equipment. Where more than one
    14. 303.7 Liquefied Petroleum Gas Facilities. Containers,
    15. 303.8 Appliances on Roofs. Appliances on roofs shall be
    16. 303.9 Avoiding Strain on Gas Piping. Appliances shall
    17. 303.10 Clearances. Appliances and their vent connectors
    18. 303.11 Installation in Commercial Garages. Appliances installe…
    19. 303.12 Installation in Aircraft Hangars. Heaters in aircraft h…
    20. 303.13 Pit Location. Where excavation is necessary to install
    21. 304.1 General.304.0 Accessibility for Service. Appliances shal…
    22. 304.2 Sloped Roof. Where equipment or appliances that
    23. 304.3 Access to Appliances on Roofs. Appliances
    24. 304.4 Appliances in Attics and Under-Floor Spaces.
    25. 305.3 Elevator Shaft. Unless required for the functionality
    26. 305.4 Drainage Pan. Where a water heater is located in an
    27. 305.0 Location.305.1 Installation in Garages. Appliances in re…
    28. 305.2 Flood Hazard Areas. For buildings located in flood
    29. 306.0 Automatic Control Devices.306.1 General. Heating applian…
    30. 307.0 Labeling.307.1 Fuel-Burning Appliances. Fuel-burning hea…
    31. 307.2 Electric Heating Appliances. Electric heating
    32. 307.3 Heat Pump and Electric Cooling Appliances.
    33. 307.4 Absorption Units. Absorption units shall bear a permanen…
    34. 309.2 Concealing Imperfections. It shall be unlawful to
    35. 309.3 Installation Practices. Mechanical systems shall
    36. 310.0 Condensate Wastes and Control.310.1 Condensate Disposal.…
    37. 310.2 Condensate Control. Where an equipment or appliance is i…
    38. 310.4 Appliance Condensate Drains. Condensate drain
    39. 310.5 Point of Discharge. Air-conditioning condensate
    40. 310.6 Condensate Waste From Air-ConditioningCoils. Where the c…
    41. 310.7 Plastic Fittings. Female plastic screwed fittings shall
    42. 310.3 Condensate Waste Pipe Material and Sizing.
    43. 311.2 Air Filters. Air filters shall be installed in a heating,
    44. 311.3 Prohibited Source. Outside or return air for a heating
    45. 313.2 Material. Hangers and anchors shall be of sufficient
    46. 313.3 Suspended Piping. Suspended piping or tubing
    47. 313.4 Alignment. Piping or tubing shall be supported in such
    48. 313.5 Underground Installation. Piping or tubing in the
    49. 313.6 Hanger Rod Sizes. Hanger rod sizes shall be not
    50. 313.7 Gas Piping. Gas piping shall be supported by metal
    51. 314.0 Balancing.314.1 General. Heating, ventilating, and air-c…
    52. 311.4 Return-Air Limitations. Return air from one dwelling
    53. 315.0 Louvers in Hurricane Prone Regions.315.1 General. Louver…
    54. 316.2 Installation. Piping or tubing shall be installed so that
    55. 316.3 Corrosion, Erosion, and Mechanical Damage. Piping or tub…
    56. 316.4 Protectively Coated Pipe. Protectively coated pipe
    57. 316.5 Fire-Resistant Construction. Piping, tubing, and
    58. 316.6 Steel Nail Plates. Plastic piping or tubing, copper
    59. 316.7 Sleeves. Sleeves shall be provided to protect piping
    60. 316.8 Firewalls. A pipe sleeve through a firewall shall have
    61. 316.9 Structural Members. A structural member weakened or impa…
    62. 316.10 Rodentproofing. Mechanical system shall be constructed …
    63. 316.11 Metal Collars. In or on buildings where openings
    64. 317.1 Trenches. 317.0 Trenching, Excavation, and Backfill. Tre…
    65. 317.2 Tunneling and Driving. Tunneling and driving shall
    66. 317.3 Open Trenches. Excavations required to be made for
    67. 317.4 Excavations. Excavations shall be completely backfilled …
    68. 318.2 Services/Systems and Utilities. Refer to Section
    69. 319.1 Requirements for Hospitals and Optional Serv-
    70. 319.2 Requirements for Skilled Nursing, Intermedi-
    71. 320.1 Requirements for Hospitals and Optional Serv-
    72. 320.2 Requirements for Skilled Nursing, Intermedi-
    73. 320.3 Requirements for Outpatient Facilities and
    74. 320.5 Psychiatric Services. [OSHPD 1, 1R, 2, 4 & 5 ] For proje…
    75. 321.1 (Does not apply to OSHPD 3 surgical clinic.) All heat-
    76. 321.2 All heating equipment necessary to maintain the min-
    77. 321.3 Equipment necessary for humidification of the areas
    78. 321.4 All supply, return, and exhaust fans required to maintain
    79. 321.5 All control components and control systems necessary
    80. 321.6 Alarms for airborne infection isolation rooms and pro-
    81. 322.1 The following conditions shall be met for sensitive
  4. Chapter 4 — VENTILATION AIR
  5. Chapter 5 — EXHAUST SYSTEMS
  6. Chapter 6 — DUCT SYSTEMS
  7. Chapter 7 — COMBUSTION AIR
  8. Chapter 8 — CHIMNEYS AND VENTS
  9. Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
  10. Chapter 10 — BOILERS AND PRESSURE VESSELS
  11. Chapter 11 — REFRIGERATION
  12. Chapter 12 — HYDRONICS
  13. Chapter 13 — FUEL GAS PIPING
  14. Chapter 14 — PROCESS PIPING
  15. Chapter 15 — SOLAR ENERGY SYSTEMS
  16. Chapter 16 — STATIONARY POWER PLANTS
  17. Chapter 17 — REFERENCED STANDARDS
  18. Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
  19. Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
  20. Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
  21. Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
  22. Appendix E — SUSTAINABLE PRACTICES
  23. Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
  24. Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE