510.3 Openings. Openings shall be provided at the sides or
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
at the top of the duct, whichever is more accessible, and at changes of direction. Openings shall be protected by approved access constructed and installed in accordance with the requirements of Section 510.3.7. [NFPA 96:7.3.1, 7.3.2]
Exception: Openings shall not be required in portions of the duct that are accessible from the duct entry or discharge.
[NFPA 96:7.3.3]
510.3.1 Access Panel. For hoods with dampers in the exhaust or supply collar, an access panel for cleaning and inspection shall be provided in the duct or the hood within 18 inches (457 mm) of the damper. [NFPA 96:7.3.4]
Exception: Dampers that are accessible from under the hood.
510.3.2 Access for Cleaning and Inspection. Exhaust fans with ductwork connected to both sides shall have access for cleaning and inspection within 3 feet (914 mm) of each side of the fan. Wall-mounted exhaust fans shall have access for cleaning and inspection within 3 feet (914 mm) of the exhaust fan. [NFPA 96:7.3.8, 7.3.9]
510.3.3 Horizontal Ducts. On horizontal ducts, at least one 20 inch by 20 inch (508 mm by 508 mm) opening shall be provided for personnel entry. [NFPA 96:7.4.1.1] 510.3.3.1 Cleaning. Where an opening of the size specified in Section 510.3.3 is not possible, openings large enough to permit thorough cleaning shall be provided at 12 feet (3658 mm) intervals. [NFPA 96:7.4.1.2]
510.3.3.2 Safe Access and Work Platform. If not easily accessible from a 10 foot (3048 mm) stepladder, openings on horizontal grease duct systems shall be provided with safe access and a work platform. [NFPA 96:7.4.1.3]
510.3.3.3 Support. Support systems for horizontal grease duct systems 24 inches (610 mm) and larger in any cross-sectional dimension shall be designed for the weight of the ductwork plus 800 pounds (362.9 kg) at any point in the duct systems.
[NFPA 96:7.4.1.4]
510.3.4 Vertical Ducts. On vertical ductwork where personnel entry is possible, access shall be provided at the top of the vertical riser to accommodate descent.
[NFPA 96:7.4.2.1]
510.3.4.1 Access. Where personnel entry is not possible, adequate access for cleaning shall be provided on each floor. [NFPA 96:7.4.2.2]
510.3.4.2 Safe Access and Work Platform. If not easily accessible from the floor or a 10 foot
EXHAUST SYSTEMS
(3048 mm) stepladder, openings on vertical grease ducts shall be provided with safe access and a work platform. [NFPA 96:7.4.2.3]
510.3.5 Nonlisted Ductwork. On nonlisted ductwork, the edge of the opening shall be not less than 1 [1] ⁄ 2 inches (38 mm) from all outside edges of the duct or welded seams. [NFPA 96:7.4.1.5]
510.3.6 Access Panels. Access panels shall be of the same material and thickness as the duct. Access panels shall have a gasket or sealant that is rated for 1500°F (816°C) and shall be greasetight. Fasteners, such as bolts, weld studs, latches, or wing nuts, used to secure the access panels shall be carbon steel or stainless steel and shall not penetrate duct walls. [NFPA 96:7.4.3.1 – 7.4.3.3]
510.3.6.1 Listed Grease Ducts. Listed grease duct access door assemblies (access panels) shall be installed in accordance with the terms of the listing and the manufacturer’s instructions. [NFPA 96:7.4.3.4]
510.3.6.2 Within an Enclosure. Where openings are located in ducts within an enclosure, the access panel including its components shall be of the same fire rating as the enclosure.
510.3.7 Fire Protection System Devices. Openings for installation, servicing, and inspection of listed fire protection system devices and for duct cleaning shall be provided in ducts and enclosures and shall be in accordance with the requirements of Section 510.3 through Section 510.3.2 and Section 510.7.7.
Enclosure openings required to reach access panels in the ductwork shall be large enough for removal of the access panel through the enclosure opening. [NFPA 96:7.4.4.1 – 7.4.4.2]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
▸Chapter 5 — EXHAUST SYSTEMS
Overview- 503.1 General. Motors and fans shall be sized to provide
- 503.2 Fans. Parts of fans in contact with explosive or flammab…
- 504.1 General. Where not specified in this chapter, exhaust
- 501.1 Applicability. This chapter includes requirements for
- 502.1 Exhaust Opening Protection. Exhaust openings
- 502.2 Termination of Exhaust Ducts. Exhaust ducts
- 504.2 Independent Exhaust Systems. Single or combined mechanic…
- 504.3 Domestic Cooking Exhaust Equipment.
- 504.4 Clothes Dryers. A clothes dryer exhaust duct shall
- 504.5 Heat Recovery Ventilation (HRV) and Energy
- 505.1 General. A mechanical ventilation or exhaust system
- 505.2 Incompatible Materials. Incompatible materials
- 505.3 Flammability Limit. Unless the circumstances stipulated …
- 505.4 Air-Moving Devices. Air-moving devices shall be
- 505.5 Generating Flames, Sparks, or Hot Materials.
- 505.6 Fire Dampers. Fire dampers shall be permitted to be
- 505.7 Fire Detection, Smoke Control, and Alarm Sys-
- 505.8 Product-Conveying Duct Classifications. Product-conveyin…
- 505.9 Minimum Velocities and Circulation. The velocity and cir…
- 505.10 Makeup Air. Makeup air shall be provided to replenish a…
- 505.11 Hoods and Enclosures. Hoods and enclosures shall
- 505.12 Pharmacies – Compounding Area of Par-
- 506.1 Materials. Materials used in product-conveying duct
- 506.2 Construction. Ducts used for conveying products
- 506.3 Penetrations. Exhaust ducts shall not pass through
- 506.4 Condensate. Joints in duct construction shall be liquidt…
- 506.5 Fittings. Fittings in Class 2, 3, and 4 systems shall be
- 506.6 Explosion Venting. Ducts conveying explosive dusts
- 506.7 Supports. Supports shall be of noncombustible materials,…
- 506.8 Fire Protection. Sprinklers or other fire-protection
- 506.9 Protection from Physical Damage. Ducts and
- 506.10 Duct Clearances. Unless the conditions stipulated
- 506.11 Clearance Reduction Methods. It shall be permitted to p…
- 507.1 Exhaust Systems. Exhaust systems serving Type I
- 507.2 Type I Hood Exhaust System Requirements.
- 507.3 Listed Devices. Penetrations shall be sealed with
- 507.4 Clearance. Where enclosures are not required, hoods,
- 507.5 Drawings. For cooking operations in buildings, a
- 507.6 Notification of Change. If required by the Authority Hav…
- 507.7 Pharmaceutical Compounding Exhaust Dis-
- 508.1 Where Required. Type I hoods shall be installed at
- 508.2 Listed Type I Hood Assemblies. Listed hood
- 508.3 Construction of Type I Hoods. The hood or that
- 508.4 Supports. Hoods shall be secured in place to resist
- 508.5 Hood Size. Hoods shall be sized in accordance with
- 508.6 Solid-Fuel Hood Assemblies. Where solid-fuel
- 508.7 Exhaust Outlets. An exhaust outlet within an
- 509.1 Grease Removal Devices. Listed grease filters or
- 509.2 Installation. The distance between the grease removal
- 509.3 Solid-Fuel Grease Removal Devices. Where
- 510.1 General. Ducts shall not pass through fire walls.
- 510.2 Clearance. Clearance between ducts and combustible
- 510.3 Openings. Openings shall be provided at the sides or
- 510.4 Listed Grease Ducts. Listed grease ducts shall be
- 510.5 Other Grease Ducts. Other grease ducts shall comply with…
- 510.6 Exterior Installations. For cooking operations in
- 510.7 Interior Installations. In all buildings more than one
- 510.8 Underground Installations. Grease ducts installed
- 510.9 Termination of Type I Hood Exhaust System.
- 510.10 Solid-Fuel Duct Systems. Where solid-fuel cooking equip…
- 511.1 Exhaust Fans for Commercial Cooking Opera-
- 511.2 Airflow. The air velocity through a duct shall be not
- 511.3 Makeup Air. The makeup air quantity shall prevent
- 511.4 Common Duct (Manifold) Systems. Master
- 511.5 Solid-Fuel Air Movement Requirements. Where
- 512.1 Dampers. Dampers shall not be installed in exhaust
- 512.2 Electrical Equipment. Wiring systems of any type
- 512.3 Other Equipment. Fume incinerators, thermal recovery uni…
- 512.4 Solid-Fuel Auxiliary Equipment. Where solid fuel
- 513.1 General. Fire-extinguishing equipment for the protection…
- 513.2 Types of Equipment. Fire-extinguishing equipment
- 513.3 Simultaneous Operation. Fixed pipe extinguishing
- 513.4 Fuel and Electric Power Shutoff. Upon actuation of
- 513.5 Manual Actuation. All systems shall have both automatic …
- 513.6 System Annunciation. Upon actuation of an automatic fire…
- 513.7 Special Design and Application. Hoods containing
- 513.8 Review and Certification. Where required, complete
- 513.9 Installation Requirements. Installation of systems
- 513.10 Portable Fire Extinguishers. Portable fire extinguisher…
- 513.11 Maintenance. Portable fire extinguishers shall be
- 513.12 Solid-Fuel Fire-Extinguishing Equipment.
- 514.1 Operating Procedures. Exhaust systems shall be
- 514.2 Inspection, Testing, and Maintenance. Maintenance of the…
- 514.3 Inspection for Grease Buildup. The entire exhaust
- 514.4 Cleaning of Exhaust Systems. If, upon inspection,
- 514.5 Cooking Equipment Maintenance. Inspection and
- 515.1 Cooking Equipment. Cooking equipment shall be
- 515.2 Operating Controls. Deep-fat fryers shall be equipped
- 516.1 General Requirements. Recirculating systems containing o…
- 516.2 Design Restrictions. All recirculating systems shall
- 516.3 Interlocks. The recirculating system shall be provided
- 516.4 Location and Application Restrictions. The
- 516.5 Additional Fire Safety Requirements. In addition to the …
- 516.6 Use and Maintenance. Automatic or manual covers on cooki…
- 517.1 Venting Application. Venting requirements of solidfuel c…
- 517.2 Location of Appliances. For cooking operations in
- 517.3 Hoods for Solid-Fuel Cooking. Hoods shall be sized
- 517.4 Exhaust Systems for Solid-Fuel Cooking. Where
- 517.5 Grease Removal Devices for Solid-Fuel Cook-
- 517.6 Air Movement for Solid-Fuel Cooking. Exhaust
- 517.7 Fire-Extinguishing Equipment for Solid-Fuel
- 517.8 Other Safety Requirements. Metal-fabricated solidfuel co…
- 518.1 General. Downdraft appliance ventilation system
- 518.2 Ventilation System. The downdraft appliance ventilation …
- 518.3 Fire-Extinguishing Equipment. For fire-extinguishing equ…
- 518.4 Airflow Switch or Transducer. An airflow switch or
- 518.5 Surface Materials. Any surface located directly
- 519.1 Where Required. Type II hoods shall be installed
- 519.2 Construction of Type II Hoods. Type II hoods
- 519.3 Type II Hood Exhaust System Net Airflow. The
- 519.4 Type II Exhaust Duct Systems. Ducts and
- 519.5 Termination of Type II Hood Exhaust System.
- 519.6 Makeup Air. Makeup air shall be provided in accordance w…
- 519.7 Independent Exhaust Duct System. Single or
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
- Chapter 18 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
- Appendix H — PROFESSIONAL QUALIFICATIONS
- Appendix I — INDOOR HORTICULTURAL FACILITIES
- Appendix J — CLEAN AIR DELIVERY