509.2 Installation. The distance between the grease removal
California Mechanical Code (Title 24, Part 4) · 2025 edition · updated 2026-09-10 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
device and the cooking surface shall be as great as possible but not less than 18 inches (457 mm). [NFPA 96:6.2.1.1]
509.2.1 Vertical Distance. Where grease removal devices are used in conjunction with solid fuel or solid fueltype broilers, including gas or electrically heated charbroilers, a minimum vertical distance of 4 feet (1219 mm) shall be maintained between the lower edge of the grease removal device and the cooking surface. [NFPA 96:6.2.1.2]
Exceptions:
(1) For cooking equipment without exposed flame and where flue gases bypass grease removal devices, the minimum vertical distance shall be permitted to be reduced to not less than 6 inches (152 mm). [NFPA 96:6.2.1.3]
(2) Where a grease removal device is listed for separation distances less than those required in Section
509.2 and Section 509.2.1, the listing requirements shall be permitted. [NFPA 96:6.2.1.4]
(3) Grease removal devices supplied as part of listed hood assemblies shall be installed in accordance with the terms of the listing and the manufacturer’s instructions. [NFPA 96:6.2.1.5]
509.2.2 Grease Removal Device Protection. Where the distance between the grease removal device and the appliance flue outlet (heat source) is less than 18 inches (457 mm), grease removal devices shall be protected from combustion gas outlets and from direct flame impingement occurring during normal operation of cooking appliances producing high flue gas temperatures.
[NFPA 96:6.2.2.1]
509.2.2.1 Installation. This protection shall be permitted to be accomplished by the installation of a steel or stainless steel baffle plate between the heat source and the grease removal device. [NFPA 96:6.2.2.2]
509.2.2.2 Size and Location. The baffle plate shall be sized and located so that flames or combustion gases travel a distance not less than 18 inches (457 mm) from the heat source to the grease removal device. [NFPA 96:6.2.2.3]
509.2.2.3 Clearance. The baffle shall be located not less than 6 inches (152 mm) from the grease removal device. [NFPA 96:6.2.2.4]
509.2.3 Grease Filters. Grease filters shall be listed
and constructed of steel or other non-combustible material, and shall be of rigid construction that will not distort or crush under normal operation, handling, cleaning, or replacement. [SFM] For applications listed in Section 1.11.0 regulated by the Office of the State Fire Marshal, grease filters shall be Class I when tested in accordance with the test method in Title 24, Part 12, Chapter 12-71, SFM Standard 12-71-1.
509.2.3.1 Arrangement. Grease filters shall be arranged so that all exhaust air passes through the grease filters. [NFPA 96:6.2.3.4]
509.2.3.2 Accessibility. Grease filters shall be easily accessible for removal. [NFPA 96:6.2.3.5]
509.2.3.3 Angled Installation. Grease filters shall be installed at an angle not less than 45 degrees (0.79 rad) from the horizontal. [NFPA 96:6.2.3.6]
509.2.3.4 [DPH] Grease filters shall be Class I when tested in accordance with the test method in
SFM 12-71-1.
509.2.4 Grease Drip Trays. Grease filters shall be equipped with a grease drip tray beneath their lower edges. [NFPA 96:6.2.4.1]
509.2.4.1 Size and Pitch. Grease drip trays shall be kept to the minimum size needed to collect grease. Grease drip trays shall be pitched to drain into an enclosed metal container having a capacity not exceeding 1 gallon (4 L). [NFPA 96:6.2.4.2, 6.2.4.3]
114 2025 CALIFORNIA MECHANICAL CODE
EXHAUST SYSTEMS
509.2.5 Grease Filter Orientation. Grease filters that require a specific orientation to drain grease shall be clearly so designated on the face of the filter as to be visible with the filter installed, or the hood or filter shall be constructed so that filters cannot be installed in the wrong orientation. [NFPA 96:6.2.5]
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Mechanical Code (Title 24, Part 4)
- Chapter 1 — GENERAL CODE PROVISIONS
- Chapter 2 — DEFINITIONS
- Chapter 3 — GENERAL REGULATIONS
- Chapter 4 — VENTILATION AIR
▸Chapter 5 — EXHAUST SYSTEMS
Overview- 503.1 General. Motors and fans shall be sized to provide
- 503.2 Fans. Parts of fans in contact with explosive or flammab…
- 504.1 General. Where not specified in this chapter, exhaust
- 501.1 Applicability. This chapter includes requirements for
- 502.1 Exhaust Opening Protection. Exhaust openings
- 502.2 Termination of Exhaust Ducts. Exhaust ducts
- 504.2 Independent Exhaust Systems. Single or combined mechanic…
- 504.3 Domestic Cooking Exhaust Equipment.
- 504.4 Clothes Dryers. A clothes dryer exhaust duct shall
- 504.5 Heat Recovery Ventilation (HRV) and Energy
- 505.1 General. A mechanical ventilation or exhaust system
- 505.2 Incompatible Materials. Incompatible materials
- 505.3 Flammability Limit. Unless the circumstances stipulated …
- 505.4 Air-Moving Devices. Air-moving devices shall be
- 505.5 Generating Flames, Sparks, or Hot Materials.
- 505.6 Fire Dampers. Fire dampers shall be permitted to be
- 505.7 Fire Detection, Smoke Control, and Alarm Sys-
- 505.8 Product-Conveying Duct Classifications. Product-conveyin…
- 505.9 Minimum Velocities and Circulation. The velocity and cir…
- 505.10 Makeup Air. Makeup air shall be provided to replenish a…
- 505.11 Hoods and Enclosures. Hoods and enclosures shall
- 505.12 Pharmacies – Compounding Area of Par-
- 506.1 Materials. Materials used in product-conveying duct
- 506.2 Construction. Ducts used for conveying products
- 506.3 Penetrations. Exhaust ducts shall not pass through
- 506.4 Condensate. Joints in duct construction shall be liquidt…
- 506.5 Fittings. Fittings in Class 2, 3, and 4 systems shall be
- 506.6 Explosion Venting. Ducts conveying explosive dusts
- 506.7 Supports. Supports shall be of noncombustible materials,…
- 506.8 Fire Protection. Sprinklers or other fire-protection
- 506.9 Protection from Physical Damage. Ducts and
- 506.10 Duct Clearances. Unless the conditions stipulated
- 506.11 Clearance Reduction Methods. It shall be permitted to p…
- 507.1 Exhaust Systems. Exhaust systems serving Type I
- 507.2 Type I Hood Exhaust System Requirements.
- 507.3 Listed Devices. Penetrations shall be sealed with
- 507.4 Clearance. Where enclosures are not required, hoods,
- 507.5 Drawings. For cooking operations in buildings, a
- 507.6 Notification of Change. If required by the Authority Hav…
- 507.7 Pharmaceutical Compounding Exhaust Dis-
- 508.1 Where Required. Type I hoods shall be installed at
- 508.2 Listed Type I Hood Assemblies. Listed hood
- 508.3 Construction of Type I Hoods. The hood or that
- 508.4 Supports. Hoods shall be secured in place to resist
- 508.5 Hood Size. Hoods shall be sized in accordance with
- 508.6 Solid-Fuel Hood Assemblies. Where solid-fuel
- 508.7 Exhaust Outlets. An exhaust outlet within an
- 509.1 Grease Removal Devices. Listed grease filters or
- 509.2 Installation. The distance between the grease removal
- 509.3 Solid-Fuel Grease Removal Devices. Where
- 510.1 General. Ducts shall not pass through fire walls.
- 510.2 Clearance. Clearance between ducts and combustible
- 510.3 Openings. Openings shall be provided at the sides or
- 510.4 Listed Grease Ducts. Listed grease ducts shall be
- 510.5 Other Grease Ducts. Other grease ducts shall comply with…
- 510.6 Exterior Installations. For cooking operations in
- 510.7 Interior Installations. In all buildings more than one
- 510.8 Underground Installations. Grease ducts installed
- 510.9 Termination of Type I Hood Exhaust System.
- 510.10 Solid-Fuel Duct Systems. Where solid-fuel cooking equip…
- 511.1 Exhaust Fans for Commercial Cooking Opera-
- 511.2 Airflow. The air velocity through a duct shall be not
- 511.3 Makeup Air. The makeup air quantity shall prevent
- 511.4 Common Duct (Manifold) Systems. Master
- 511.5 Solid-Fuel Air Movement Requirements. Where
- 512.1 Dampers. Dampers shall not be installed in exhaust
- 512.2 Electrical Equipment. Wiring systems of any type
- 512.3 Other Equipment. Fume incinerators, thermal recovery uni…
- 512.4 Solid-Fuel Auxiliary Equipment. Where solid fuel
- 513.1 General. Fire-extinguishing equipment for the protection…
- 513.2 Types of Equipment. Fire-extinguishing equipment
- 513.3 Simultaneous Operation. Fixed pipe extinguishing
- 513.4 Fuel and Electric Power Shutoff. Upon actuation of
- 513.5 Manual Actuation. All systems shall have both automatic …
- 513.6 System Annunciation. Upon actuation of an automatic fire…
- 513.7 Special Design and Application. Hoods containing
- 513.8 Review and Certification. Where required, complete
- 513.9 Installation Requirements. Installation of systems
- 513.10 Portable Fire Extinguishers. Portable fire extinguisher…
- 513.11 Maintenance. Portable fire extinguishers shall be
- 513.12 Solid-Fuel Fire-Extinguishing Equipment.
- 514.1 Operating Procedures. Exhaust systems shall be
- 514.2 Inspection, Testing, and Maintenance. Maintenance of the…
- 514.3 Inspection for Grease Buildup. The entire exhaust
- 514.4 Cleaning of Exhaust Systems. If, upon inspection,
- 514.5 Cooking Equipment Maintenance. Inspection and
- 515.1 Cooking Equipment. Cooking equipment shall be
- 515.2 Operating Controls. Deep-fat fryers shall be equipped
- 516.1 General Requirements. Recirculating systems containing o…
- 516.2 Design Restrictions. All recirculating systems shall
- 516.3 Interlocks. The recirculating system shall be provided
- 516.4 Location and Application Restrictions. The
- 516.5 Additional Fire Safety Requirements. In addition to the …
- 516.6 Use and Maintenance. Automatic or manual covers on cooki…
- 517.1 Venting Application. Venting requirements of solidfuel c…
- 517.2 Location of Appliances. For cooking operations in
- 517.3 Hoods for Solid-Fuel Cooking. Hoods shall be sized
- 517.4 Exhaust Systems for Solid-Fuel Cooking. Where
- 517.5 Grease Removal Devices for Solid-Fuel Cook-
- 517.6 Air Movement for Solid-Fuel Cooking. Exhaust
- 517.7 Fire-Extinguishing Equipment for Solid-Fuel
- 517.8 Other Safety Requirements. Metal-fabricated solidfuel co…
- 518.1 General. Downdraft appliance ventilation system
- 518.2 Ventilation System. The downdraft appliance ventilation …
- 518.3 Fire-Extinguishing Equipment. For fire-extinguishing equ…
- 518.4 Airflow Switch or Transducer. An airflow switch or
- 518.5 Surface Materials. Any surface located directly
- 519.1 Where Required. Type II hoods shall be installed
- 519.2 Construction of Type II Hoods. Type II hoods
- 519.3 Type II Hood Exhaust System Net Airflow. The
- 519.4 Type II Exhaust Duct Systems. Ducts and
- 519.5 Termination of Type II Hood Exhaust System.
- 519.6 Makeup Air. Makeup air shall be provided in accordance w…
- 519.7 Independent Exhaust Duct System. Single or
- Chapter 6 — DUCT SYSTEMS
- Chapter 7 — COMBUSTION AIR
- Chapter 8 — CHIMNEYS AND VENTS
- Chapter 9 — INSTALLATION OF SPECIFIC APPLIANCES
- Chapter 10 — BOILERS AND PRESSURE VESSELS
- Chapter 11 — REFRIGERATION
- Chapter 12 — HYDRONICS
- Chapter 13 — FUEL GAS PIPING
- Chapter 14 — PROCESS PIPING
- Chapter 15 — SOLAR ENERGY SYSTEMS
- Chapter 16 — STATIONARY POWER PLANTS
- Chapter 17 — GEOTHERMAL ENERGY SYSTEMS AND AMBIENT TEMPERATURE…
- Chapter 18 — REFERENCED STANDARDS
- Appendix A — RESIDENTIAL PLAN EXAMINER REVIEW FORM FOR HVAC SY…
- Appendix B — PROCEDURES TO BE FOLLOWED TO PLACE GAS EQUIPMENT …
- Appendix C — INSTALLATION AND TESTING OF OIL (LIQUID) FUEL-FIR…
- Appendix D — FUEL SUPPLY: MANUFACTURED/MOBILE HOME PARKS AND R…
- Appendix E — SUSTAINABLE PRACTICES
- Appendix F — SIZING OF VENTING SYSTEMS AND OUTDOOR COMBUSTION …
- Appendix G — EXAMPLE CALCULATION OF OUTDOOR AIR RATE
- Appendix H — PROFESSIONAL QUALIFICATIONS
- Appendix I — INDOOR HORTICULTURAL FACILITIES
- Appendix J — CLEAN AIR DELIVERY