Section 141.1
California Energy Code (Title 24, Part 6) · 2019 edition · updated 2026-09-12 · California
REQUIREMENTS FOR COVERED PROCESSES IN ADDITIONS, ALTERATIONS TO EXISTING NONRESIDENTIAL, HIGH-RISE RESIDENTIAL, AND HOTEL/MOTEL BUILDINGS
Covered processes in additions or alterations to existing buildings that will be nonresidential, high-rise residential, and hotel/motel occupancies shall comply with the applicable subsections of Section 120.6 and 140.9.
Lab and Process Facility Exhaust Systems. All newly installed fan systems for a laboratory or process facility exhaust system greater than 10,000 CFM shall meet the requirements of Section 140.9(c).
NOTE: For alterations that change the occupancy classification of the building, the requirements of Section 141.1 apply to the occupancy that will exist after the alterations.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.
138 2019 CALIFORNIA ENERGY CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
SUBCHAPTER 7
LOW-RISE RESIDENTIAL BUILDINGS— MANDATORY FEATURES AND DEVICES
insulated between framing members with insulation having an installed thermal resistance of R-11 or greater.
2 × 6 inch or greater framing shall have an overall assembly U -factor not exceeding U-0.071.
Opaque nonframed assemblies shall have an overall assembly U -factor not exceeding U-0.102.
Bay or bow window roofs and floors shall be insulated to meet the wall insulation requirements of Table 150.1-A or B.
Masonry walls shall be insulated to meet the wall insulation requirements of Table 150.1-A or B.
In wood framed assemblies, compliance with U-factors may be demonstrated by installing wall insulation with an R-value of 13 in 2x4 assemblies, and 20 in 2x6 assemblies.
(d) Raised-floor insulation. Raised floors separating conditioned space from unconditioned space or ambient air shall have an overall assembly U -factor not exceeding U-0.037. In a wood framed assembly, compliance with the U-factor may be demonstrated by installing insulation with an R -value of 19 or greater.
Exception to Section 150.0(d): A building with a controlled ventilation or unvented crawlspace may omit raised floor insulation if all of the following are met:
i. The foundation walls are insulated to meet the
wall insulation minimums as shown in Table 150.1-A or B; and
ii. A Class I or Class II vapor retarder is placed over
the entire floor of the crawl space; and
iii. Vents between the crawlspace and outside air are
fitted with automatically operated louvers that are temperature actuated; and
iv. The requirements in Reference Residential
Appendix RA4.5.1.
(e) Installation of fireplaces, decorative gas appliances and gas logs. If a masonry or factory-built fireplace is installed, it shall comply with Section 110.5, Section 4.503 of Part 11, and shall have the following:
Closable metal or glass doors covering the entire opening of the firebox; and
A combustion air intake to draw air from the outside of the building, which is at least 6 square inches in area and is equipped with a readily accessible, operable and tight-fitting damper or combustion-air control device; and
Exception to Section 150.0(e)1B: An outside combustion-air intake is not required if the fireplace will