Section 120.2
California Energy Code (Title 24, Part 6) · 2019 edition · updated 2026-09-12 · California
REQUIRED CONTROLS FOR SPACE-
CONDITIONING SYSTEMS
Nonresidential, high-rise residential, and hotel/motel build - ings shall comply with the applicable requirements of Sections 120.2(a) through 120.2(k).
(a) Thermostatic controls for each zone. The supply of heating and cooling energy to each space-conditioning zone or dwelling unit shall be controlled by an individual thermostatic control that responds to temperature within the zone and that meets the applicable requirements of Section 120.2(b). An energy management control system (EMCS) may be installed to comply with the requirements of one or more thermostatic controls if it complies with all applicable requirements for each thermostatic control.
Exception to Section 120.2(a): An independent perimeter heating or cooling system may serve more than one zone without individual thermostatic controls if:
All zones are also served by an interior cooling system; and
The perimeter system is designed solely to offset envelope heat losses or gains; and
The perimeter system has at least one thermostatic control for each building orientation of 50 feet or more; and
The perimeter system is controlled by at least one thermostat located in one of the zones served by the system.
(b) Criteria for zonal thermostatic controls. The individual thermostatic controls required by Section 120.2(a) shall meet the following requirements as applicable:
Where used to control comfort heating, the thermostatic controls shall be capable of being set, locally or remotely, down to 55°F or lower.
Where used to control comfort cooling, the thermostatic controls shall be capable of being set, locally or remotely, up to 85°F or higher.
Where used to control both comfort heating and comfort cooling, the thermostatic controls shall meet Items 1 and 2 and shall be capable of providing a temperature range or dead band of at least 5°F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.
Exception 1 to Section 120.2(b)3: Systems with thermostats that require manual changeover between heating and cooling modes.
Exception 2 to Section 120.2(b)3: Systems serving healthcare facilities.
- Thermostatic controls for all single zone, air conditioners and heat pumps shall comply with the requirements of Sections 110.2(c) and 110.12(a) and, if equipped with DDC to the Zone level, with the Automatic Demand Shed Controls of Section 110.12(b).
Exception 1 to Section 120.2(b)4: Systems serving exempt process loads that must have constant temperatures to prevent degradation of materials, a process, plants or animals.
Exception 2 to Section 120.2(b)4: Package terminal air conditioners, package terminal heat pumps, room air conditioners and room airconditioner heat pumps.
Exception 3 to Section 120.2(b)4: Systems serving healthcare facilities.
(c) Hotel/motel guest room and high-rise residential dwelling unit thermostats.
- Hotel/motel guest room thermostats shall:
A. Have numeric temperature setpoints in °F and °C; and
B. Have setpoint stops, which are accessible only to
authorized personnel, such that guest room occupants cannot adjust the setpoint more than ±5°F (±3°C); and
C. Meet the requirements of Section 110.2(c).
Exception to Section 120.2(c)1: Thermostats that are integrated into the room heating and cooling equipment.
- High-rise residential dwelling unit thermostats shall meet the requirements of Section 110.2(c).
(d) Heat pump controls. All heat pumps with supplementary electric resistance heaters shall be installed with controls that comply with Section 110.2(b).
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
NONRESIDENTIAL, HIGH-RISE RESIDENTIAL HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS
ture is between the active heating and cooling setpoints.
Exception 1 to Sections 120.2(e)1, 2, 3: Where it can be demonstrated to the satisfaction of the enforcing agency that the system serves an area that must operate continuously.
Exception 2 to Sections 120.2(e)1, 2, 3: Systems with full load demands of 2 kW or less, if they have a readily accessible manual shut-off switch.
Exception 3 to Sections 120.2(e) 1 and 2: Systems serving hotel/motel guest rooms, if they have a readily accessible manual shut-off switch.
- Hotel and motel guest rooms shall have captive card key controls, occupancy sensing controls or automatic controls such that, no longer than 30 minutes after the guest room has been vacated, setpoints are set up at least +5°F (+3°C) in cooling mode and set down at least -5°F (-3°C) in heating mode.
Exception to Section 120.2(e): Systems serving healthcare facilities.
(f) Dampers for air supply and exhaust equipment. Outdoor air supply and exhaust equipment shall be installed with dampers that automatically close upon fan shutdown.
Exception 1 to Section 120.2(f): Equipment that serves an area that must operate continuously.
Exception 2 to Section 120.2(f): Gravity and other nonelectrical equipment that has readily accessible manual damper controls.
Exception 3 to Section 120.2(f): At combustion air intakes and shaft vents.
Exception 4 to Section 120.2(f): Where prohibited by other provisions of law.
(g) Isolation area devices. Each space-conditioning system serving multiple zones with a combined conditioned floor area of more than 25,000 square feet shall be designed, installed and controlled to serve isolation areas.
Each zone, or any combination of zones not exceeding 25,000 square feet, shall be a separate isolation area.
Each isolation area shall be provided with isolation devices, such as valves or dampers, that allow the supply of heating or cooling to be reduced or shut off independently of other isolation areas.
Each isolation area shall be controlled by a device meeting the requirements of Section 120.2(e)1.
Exception to Section 120.2(g): Zones designed to be conditioned continuously.
(h) Automatic demand shed controls. See Section 110.12 for requirements for automatic demand shed controls.
(i) Economizer fault detection and diagnostics (FDD). All newly installed air handlers with a mechanical cooling capacity greater than 54,000 Btu/hr and an installed air economizer shall include a stand-alone or integrated Fault Detec
(e) Shut-off and reset controls for space-conditioning systems. Each space-conditioning system shall be installed with controls that comply with the following:
- The control shall be capable of automatically shutting off the system during periods of nonuse and shall have:
A. An automatic time switch control device complying
with Section 110.9(c), with an accessible manual override that allows operation of the system for up to 4 hours; or
B. An occupancy sensor; or
C. A 4-hour timer that can be manually operated.
Exception to Section 120.2(e)1: Mechanical systems serving retail stores and associated malls, restaurants, grocery stores, churches and theaters equipped with 7-day programmable timers.
- The control shall automatically restart and temporarily operate the system as required to maintain:
A. A setback heating thermostat setpoint if the system
provides mechanical heating; and
Exception to Section 120.2(e)2A: Thermostat setback controls are not required in nonresidential buildings in areas where the Winter Median of Extremes outdoor air temperature determined in accordance with Section 140.4(b)3 is greater than 32°F.
B. A setup cooling thermostat setpoint if the system
provides mechanical cooling.
Exception to Section 120.2(e)2B: Thermostat setup controls are not required in nonresidential buildings in areas where the Summer Design Dry Bulb 0.5 percent temperature determined in accordance with Section 140.4(b)3 is less than 100°F.
- Occupancy sensing zone controls. Space conditioning systems serving room(s) that are required to have occupant sensing controls in accordance with Section 130.1(c), and where the Table 120.1-A occupancy category permits ventilation air to be reduced to zero when the space is in occupied-standby mode, shall meet the following:
A. The zone shall be placed in occupied standby mode
when all room(s) served by the zone are unoccupied for more than 5 minutes; and
B. During occupied standby mode.
i. Automatically set up the operating cooling tem perature set point by 2°F or more and set back the operating heating temperature set point by 2°F or more; or
ii. For multiple zone systems with Direct Digital
Controls (DDC) to the zone level, setup the operating cooling temperature setpoint by 0.5°F or more and setback the operating heating temperature setpoint by 0.5°F or more.
C. During occupied-standby mode, all airflow to the
zone shall be shut off whenever the space tempera
68 2019 CALIFORNIA ENERGY CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
NONRESIDENTIAL, HIGH-RISE RESIDENTIAL HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS
tion and Diagnostics (FDD) system in accordance with Subsections 120.2(i)1 through 120.2(i)8.
The following temperature sensors shall be permanently installed to monitor system operation: outside air, supply air, and when required for differential economizer operation a return air sensor, and
Temperature sensors shall have an accuracy of ±2°F over the range of 40°F to 80°F; and
The controller shall have the capability of displaying the value of each sensor; and
The controller shall provide system status by indicating the following conditions:
A. Free cooling available;
B. Economizer enabled;
C. Compressor enabled;
D. Heating enabled, if the system is capable of heating;
and
E. Mixed-air low limit cycle active.
The unit controller shall allow manual initiation of each operating mode so that the operation of cooling systems, economizers, fans and heating system can be independently tested and verified; and
Faults shall be reported in one of the following ways:
A. Reported to an Energy Management Control System
regularly monitored by facility personnel.
B. Annunciated locally on one or more zone thermo stats, or a device within five (5) feet of zone thermostat(s), clearly visible, at eye level, and meeting the following requirements:
i. On the thermostat, device, or an adjacent written
sign, display instructions to contact appropriate building personnel or an HVAC technician; and
ii. In buildings with multiple tenants, the annun ciation shall either be within property management offices or in a common space accessible by the property or building manager.
C. Reported to a fault management application
which automatically provides notification of the fault to a remote HVAC service provider.
- The FDD system shall detect the following faults:
A. Air temperature sensor failure/fault;
B. Not economizing when it should;
C. Economizing when it should not;
D. Damper not modulating; and
E. Excess outdoor air.
- The FDD System shall be certified by the Energy Commission as meeting requirements of Subsections 120.2(i)1 through 120.2(i)7 in accordance with Section 110.0 and JA6.3.
Exception to 120.2(i)8: FDD algorithms based in direct digital control systems are not required to be certified to the Energy Commission.
(j) Direct Digital Controls (DDC) . Direct Digital Controls to the zone shall be provided as specified by Table 120.2-A.
The provided DDC system shall meet the control logic requirements of Sections 120.1(d) and 120.2(h), and be capable of the following:
Monitoring zone and system demand for fan pressure, pump pressure, heating and cooling;
Transferring zone and system demand information from zones to air distribution system controllers and from air distribution systems to heating and cooling plant controllers;
TABLE 120.2-A DDC APPLICATIONS AND QUALIFICATIONS
| BUILDING STATUS | APPLICATIONS | QUALIFICATIONS |
|---|---|---|
| Newly Constructed Buildings |
Air handling system and all zones served by the system |
Individual systems supplying more than three zones and with design heating or cooling capacity of 300 kBtu/ |
| Newly Constructed Buildings |
Chilled water plant and all coils and terminal units served by the system |
Individual plants supplying more than three zones and with design cooling capacity of 300 kBtu/ |
| Newly Constructed Buildings |
Hot water plant and all coils and terminal units served by the system |
Individual plants supplying more than three zones and with design heating capacity of 300 kBtu/ |
| Additions or Alterations |
Zone terminal unit such as VAV box | Where existing zones served by the same air handling, chilled water, or hot water systems that have DDC |
| Additions or Alterations |
Air handling system or fan coil | Where existing air handling system(s) and fan coil(s) served by the same chilled or hot water plant have DDC |
| Additions or Alterations |
New air handling system and all new zones served by the system |
Individual systems with design heating or cooling capacity of 300 kBtu/ more than 75 percent of zones are new |
| Additions or Alterations |
New or upgraded chilled water plant | Where all chillers are new and plant design cooling capacity is 300 kBtu/ |
| Additions or Alterations |
New or upgraded hot water plant | Where all boilers are new and plant design heating capacity is 300 kBtu/ |
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
NONRESIDENTIAL, HIGH-RISE RESIDENTIAL HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS
the fluid flow, such as expansion tanks, fill lines, chemical feeders, and drains.
(b) Insulation protection. Pipe insulation shall be protected from damage due to sunlight, moisture, equipment maintenance and wind. Protection shall, at minimum, include the following:
Pipe insulation exposed to weather shall be protected by a cover suitable for outdoor service. The cover shall be water retardant and provides shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be used to provide this protection.
Pipe insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall include, or be protected by, a Class I or Class II vapor retarder. All penetrations and joints shall be sealed.
Pipe insulation buried below grade must be installed in a water proof and noncrushable casing or sleeve.
(c) Insulation thickness
For insulation with a conductivity in the range shown in Table 120.3-A for the applicable fluid temperature range, the insulation shall have the applicable minimum thickness or R -value shown in Table 120.3-A.
For insulation with a conductivity outside the range shown in Table 120.3-A for the applicable fluid temperature range, the insulation shall have a minimum R -value shown in Table 120.3-A or thickness as calculated:
MINIMUM INSULATION THICKNESS EQUATION
T = PR 1 + ------- PRt
K
-- k -
= PR 1 + ------- - 1
Automatically detecting the zones and systems that may be excessively driving the reset logic and generate an alarm or other indication to the system operator;
Readily allow operator removal of zones(s) from the reset algorithm;
For new buildings, trending and graphically displaying input and output points; and
Resetting heating and cooling setpoints in all noncriti - cal zones upon receipt of a signal from a centralized contact or software point as described in Section 120.2(h).
(k) Optimum start/stop controls. Space conditioning systems with DDC to the zone level shall have optimum start/ stop controls. The control algorithm shall, as a minimum, be a function of the difference between space temperature and occupied setpoint, the outdoor air temperature, and the amount of time prior to scheduled occupancy. Mass radiant floor slab systems shall incorporate floor temperature onto the optimum start algorithm.
Exception to Section 120.2(k): Systems that must operate continuously.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.
Get a plain-English answer with a citation back to this text.
Ask AI about this code