OUTDOOR LIGHTING CONTROLS AND EQUIPMENT

Nonresidential, high-rise residential and hotel/motel build - ings shall comply with the applicable requirements of Sections 130.2(a) through 130.2(c).

(a) Reserved.

(b) Luminaire cutoff requirements. All outdoor luminaires of 6,200 initial luminaire lumens or greater, shall comply with backlight, uplight, and glare (collectively referred to as “BUG” in accordance with IES TM-15-11, Addendum A) requirements as follows:

  1. Maximum zonal lumens for backlight, uplight, and glare shall be in accordance with Title 24, Part 11, Section 5.106.8.

Exception 1 to Section 130.2(b): Signs.

Exception 2 to Section 130.2(b): Lighting for building facades, public monuments, statues and vertical surfaces of bridges.

TABLE 130.1-A MULTILEVEL LIGHTING CONTROLS AND UNIFORMITY REQUIREMENTS

LUMINAIRE TYPE MINIMUM REQUIRED CONTROL STEPS
(percent of full rated power1)
UNIFORM LEVEL OF ILLUMINANCE
SHALL BE ACHIEVED BY:
Line-voltage sockets except GU-24 Continuous dimming 10-100 percent Continuous dimming 10-100 percent Continuous dimming 10-100 percent Continuous dimming 10-100 percent Continuous dimming 10-100 percent
Low-voltage incandescent systems Low-voltage incandescent systems Low-voltage incandescent systems Low-voltage incandescent systems Low-voltage incandescent systems Low-voltage incandescent systems
LED luminaires and LED source systems LED luminaires and LED source systems LED luminaires and LED source systems LED luminaires and LED source systems LED luminaires and LED source systems LED luminaires and LED source systems
GU-24 rated for LED GU-24 rated for LED GU-24 rated for LED GU-24 rated for LED GU-24 rated for LED GU-24 rated for LED
GU-24 sockets rated for fluorescent > 20 watts Continuous dimming 20-100 percent Continuous dimming 20-100 percent Continuous dimming 20-100 percent Continuous dimming 20-100 percent Continuous dimming 20-100 percent
Pin-based compact fluorescent > 20 watts2
GU-24 sockets rated for fluorescent≤ 20 watts Minimum one step between
30-70 percent
Minimum one step between
30-70 percent
Minimum one step between
30-70 percent
Minimum one step between
30-70 percent
Stepped dimming; or
Continuous dimming; or
Switching alternate lamps in a luminaire
Pin-based compact fluorescent≤ 20 watts2
Linear fluorescent and U-bent fluorescent≤ 13 watts
Linear fluorescent and U-bent fluorescent > 13 watts Minimum one step in each range: Minimum one step in each range: Minimum one step in each range: Minimum one step in each range: Stepped dimming; or
Continuous dimming; or
Switching alternate lamps in each luminaire,
having a minimum of four lamps per luminaire,
illuminating the same area and in the same manner
Linear fluorescent and U-bent fluorescent > 13 watts 20-40% 50-70% 75-85% 100% 100%
Track Lighting Minimum one step between
30 – 70 percent
Minimum one step between
30 – 70 percent
Minimum one step between
30 – 70 percent
Minimum one step between
30 – 70 percent
Step dimming; or
Continuous dimming; or
Separately switching circuits in multicircuit track
with a minimum of two circuits.
HID > 20 watts Minimum one step between
50 - 70 percent
Minimum one step between
50 - 70 percent
Minimum one step between
50 - 70 percent
Minimum one step between
50 - 70 percent
Stepped dimming; or
Continuous dimming; or
Switching alternate lamps in each luminaire,
having a minimum of two lamps per luminaire,
illuminating the same area and in the same manner.
Induction > 25 watts Induction > 25 watts Induction > 25 watts Induction > 25 watts Induction > 25 watts Induction > 25 watts
Other light sources Other light sources Other light sources Other light sources Other light sources Other light sources
  1. Full rated input power of ballast and lamp, corresponding to maximum ballast factor.
  2. Includes only pin based lamps: twin tube, multiple twin tube, and spiral lamps.

Exception 1 to Table 130.1-A, Minimum Required Control Steps: Classrooms with a connected general lighting load of 0.7 watts per square feet or less shall have a minimum of one control step between 30–70 percent of full rated power, regardless of luminaire type.

Exception 2 to Table 130.1-A, Minimum Required Control Steps: Library stack aisles, aisle ways and open areas in warehouses, parking garages, parking areas, loading and unloading areas, stairwells, and corridors shall have a minimum of one control step between 20–60 percent of full rated power, regardless of luminaire type.

88 2019 CALIFORNIA ENERGY CODE

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

NONRESIDENTIAL, HIGH-RISE RESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS

AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS

more than two hours when an override is initiated.

C. Acceptance tests of outdoor lighting controls

shall verify the scheduled occupied and unoccupied periods, as specified in Section 130.4(a)6.

D. Automatic scheduling controls shall be installed

for all outdoor lighting, and may be installed in combination with motion sensing controls or other outdoor lighting controls.

  1. Motion sensing controls.

A. Motion sensing controls shall be capable of

reducing the outdoor lighting power of each controlled luminaire by at least 50 percent and no more than 90 percent, and separately capable of turning the luminaire OFF, during unoccupied periods.

B. Motion sensing controls shall be capable of

reducing the lighting to its dim or OFF state no longer than 15 minutes after the area has been vacated, and of returning the lighting to its ON state when the area becomes occupied.

C. No more than 1,500 watts of lighting power shall

be controlled by a single sensor.

D. Motion sensing controls shall be installed for the

following luminaires, and may be installed for other outdoor lighting and in combination with other outdoor lighting controls:

i. Outdoor luminaires other than building

façade, ornamental hardscape, outdoor dining, or outdoor sales frontage lighting, where the bottom of luminaire is mounted 24 feet or less above grade; and,

ii. Outdoor wall mounted luminaires installed

for building façade, ornamental hardscape or outdoor dining lighting that have a bilaterally symmetric distribution as described in the IES Handbook (typically referred to as “wall packs”) mounted 24 feet above grade or lower.

Exception 1 to Section 130.2(c)3: Luminaires with a maximum rated wattage of 40 watts each are not required to have motion sensing controls.

Exception 2 to Section 130.2(c)3: Applications listed as Exceptions to Section 140.7(a) are not required to have motion sensing controls.

Exception 3 to Section 130.2(c)3: Lighting subject to a health or life safety statute, ordinance, or regulation may have a minimum time-out period longer than 15 minutes or a minimum dimming level above 50 percent when necessary to comply with the applicable law.

Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.

Exception 3 to Section 130.2(b): Lighting not permitted by a health or life safety statute, ordinance or regulation to be a cutoff luminaire.

Exception 4 to Section 130.2(b): Temporary outdoor lighting.

Exception 5 to Section 130.2(b): Replacement of existing pole mounted luminaires in hardscape areas meeting all of the following conditions:

A. Where the existing luminaire does not meet the

luminaire BUG requirements in Section 130.2(b); and

B. Spacing between existing poles is greater than six

times the mounting height of the existing luminaires; and

C. Where no additional poles are being added to the

site; and

D. Where new wiring to the luminaires is not being

installed; and

E. Provided that the connected lighting power wattage

is not increased.

Exception 6 to Section 130.2(b): Luminaires that illuminate the public right of way on publicly maintained roadways, sidewalks and bikeways.

Exception 7 to Section 130 . 2(b): Outdoor lighting attached to a high-rise residential or hotel/motel building and separately controlled from the inside of a dwelling unit or guest room.

(c) Controls for outdoor lighting. Outdoor lighting shall be independently controlled from other electrical loads, and the controls for outdoor lighting shall meet the following functional requirements:

Exception 1 to Section 130.2(c): Outdoor lighting not permitted by a health or life safety statute, ordinance or regulation to be turned OFF or reduced.

Exception 2 to Section 130.2(c): Lighting in tunnels required to be illuminated 24 hours per day and 365 days per year.

  1. Daylight availability. All installed outdoor lighting shall be controlled by a photo control, astronomical time-switch control, or other control capable of automatically shutting OFF the outdoor lighting when daylight is available.

  2. Automatic scheduling controls.

A. Automatic scheduling controls shall be capable

of reducing the outdoor lighting power by at least 50 percent and no more than 90 percent, and separately capable of turning the lighting OFF, during scheduled unoccupied periods.

B. Automatic scheduling controls shall allow sched uling of a minimum of two nighttime periods with independent lighting levels, and may include an override function that turns lighting ON during its scheduled dim or OFF state for no

Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.

100735044

NONRESIDENTIAL, HIGH-RISE RESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS

Get a plain-English answer with a citation back to this text.