Section 130.5
California Energy Code (Title 24, Part 6) · 2019 edition · updated 2026-09-12 · California
ELECTRICAL POWER DISTRIBUTION SYSTEMS
Nonresidential, high-rise residential and hotel/motel build - ings shall comply with the applicable requirements of Sections 130.5(a) through 130.5(e).
(a) Service electrical metering. Each electrical service or feeder shall have a permanently installed metering system which measures electrical energy use in accordance with Table 130.5-A.
Exception 1 to Section 130.5(a): Service or feeder for which the utility company provides a metering system that indicates instantaneous kW demand and kWh for a utilitydefined period.
Exception 2 to Section 130.5(a): Electrical power distribution systems subject to California Electrical Code Article 517.
(b) Separation of electrical circuits for electrical energy monitoring. Electrical power distribution systems shall be designed so that measurement devices can monitor the electrical energy usage of load types according to Table 130.5-B.
Exception 1 to Section 130.5(b): For each separate load type, up to 10 percent of the connected load may be of any type.
Exception 2 to Section 130.5(b): Electrical power distribution systems subject to California Electrical Code Article 517.
(c) Voltage drop. The maximum combined voltage drop on both installed feeder conductors and branch circuit conductors to the farthest connected load or outlet shall not exceed 5 percent.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
NONRESIDENTIAL, HIGH-RISE RESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS
v. Receptacles connected to an uninterruptible
power supply (UPS) that are intended to be in continuous use, 24 hours per day/365 days per year, and are marked to differentiate them from other uncontrolled receptacles or circuits.
Exception 2 to Section 130.5(d): Receptacles in healthcare facilities.
(e) Demand responsive controls and equipment. See Section 110.12 for requirements for demand responsive controls and equipment.
NOTE: Definitions of terms and phrases in Section 130.5 are determined as specified in Section 100.1(b). Terms and phrases not found in Section 100.1(b) shall be defined as specified in Title 24, Part 3, Article 100 of the California Electrical Code.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.
TABLE 130.5-A MINIMUM REQUIREMENTS FOR METERING OF ELECTRICAL LOAD
| METERING FUNCTIONALITY | ELECTRICAL SERVICES RATED 50 kVA OR LESS |
ELECTRICAL SERVICES RATED MORE THAN 50 kVA AND LESS THAN OR EQUAL TO 250 kVA |
ELECTRICAL SERVICES RATED MORE THAN 250 kVA AND LESS THAN OR EQUAL TO 1000kVA |
ELECTRICAL SERVICES RATED MORE THAN 1000kVA |
|---|---|---|---|---|
| Instantaneous (at the time) kW demand |
Required | Required | Required | Required |
| Historical peak demand (kW) | Not required | Not required | Required | Required |
| Tracking kWh for a user- definable period. |
Required | Required | Required | Required |
| kWh per rate period | Not required | Not required | Not required | Required |
TABLE 130.5-B MINIMUM REQUIREMENTS FOR SEPARATION OF ELECTRICAL LOAD
| ELECTRICAL LOAD TYPE | ELECTRICAL SERVICES RATED 50 kVA OR LESS |
ELECTRICAL SERVICES RATED MORE THAN 50 kVA AND LESS THAN OR EQUAL TO 250 kVA |
ELECTRICAL SERVICES RATED MORE THAN 250 kVA AND LESS THAN OR EQUAL TO 1000kVA |
ELECTRICAL SERVICES RATED MORE THAN 1000kVA |
|---|---|---|---|---|
| Lighting including exit and egress lighting and exterior lighting |
Not required | All lighting in aggregate | All lighting disaggregated by floor, type or area |
All lighting disaggregated by floor, type or area |
| HVAC systems and components including chillers, fans, heaters, furnaces, package units, cooling towers and circulation pumps associated with HVAC |
Not required | All HVAC in aggregate | All HVAC in aggregate and each HVAC load rated at least 50 kVA |
All HVAC in aggregate and each HVAC load rated at least 50kVA |
| Domestic and service water system pumps and related systems and components |
Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Plug load including appliances rated less than 25 kVA |
Not required | All plug load in aggregate Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf |
All plug load separated by floor, type or area Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf |
All plug load separated by floor, type or area All groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf |
| Elevators, escalators, moving walks and transit systems |
Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Other individual non HVAC loads or appliances rated 25kVA or greater |
Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Industrial and commercial load centers 25 kVA or greater including theatrical lighting installations and commercial kitchens |
Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Renewable power source (net or total) | Each group | Each group | Each group | Each group |
| Loads associated with renewable power source |
Not required | All loads in aggregate | All loads in aggregate | All loads in aggregate |
| Charging stations for electric vehicles | All loads in aggregate |
All loads in aggregate | All loads in aggregate | All loads in aggregate |
92 2019 CALIFORNIA ENERGY CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
SUBCHAPTER 5
NONRESIDENTIAL, HIGH-RISE RESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND
PRESCRIPTIVE COMPLIANCE APPROACHES FOR
ACHIEVING ENERGY EFFICIENCY
Get a plain-English answer with a citation back to this text.
Ask AI about this code