Section 120.7
California Energy Code (Title 24, Part 6) · 2019 edition · updated 2026-09-12 · California
MANDATORY INSULATION REQUIREMENTS
Nonresidential, high-rise residential, and hotel/motel buildings shall comply with the applicable requirements in Sections 120.7(a) through 120.7(c).
(a) Roof/Ceiling insulation. The opaque portions of the roof/ceiling that separates conditioned spaces from unconditioned spaces or ambient air shall meet the applicable requirements of Items 1 through 3 below:
Metal building. The weighted average U -factor of the roof assembly shall not exceed 0.098.
Wood framed and others. The weighted average U factor of the roof assembly shall not exceed 0.075.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
NONRESIDENTIAL, HIGH-RISE RESIDENTIAL HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS
- Demising walls. The opaque portions of framed demising walls shall meet the requirements of Item A or B below:
A. Wood framed walls shall be insulated to meet a
U -factor not greater than 0.099.
B. Metal framed walls shall be insulated to meet a U -fac tor not greater than 0.151.
(c) Floor and soffit insulation. The opaque portions of floors and soffits that separate conditioned spaces from unconditioned spaces or ambient air shall meet the applicable requirements of Items 1 and 2 below:
Raised mass floors. Shall have a minimum of 3 inches of lightweight concrete over a metal deck, or the weighted average U -factor of the floor assembly shall not exceed 0.269.
Other floors. The weighted average U -factor of the floor assembly shall not exceed 0.071.
Heated slab on grade floor. A heated slab on grade floor shall be insulated to meet the requirements of Section 110.8(g).
Exception to Section 120.7: A dedicated building used solely as a data center that has a total covered process load exceeding 750 kW.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code .