Section 110.9
California Energy Code (Title 24, Part 6) · 2019 edition · updated 2026-09-12 · California
MANDATORY REQUIREMENTS
FOR LIGHTING CONTROLS
(a) All lighting control devices and systems and all light sources subject to the requirements of Section 110.9 shall meet the following requirements:
Shall be installed only if the lighting control or light source complies with all of the applicable requirements of Section 110.9.
Lighting controls may be individual devices or systems consisting of two or more components.
(b) All lighting controls. Lighting controls listed in Section 110.9(b) shall comply with the requirements listed below; and all components of the system considered together as installed shall meet all applicable requirements for the application for which they are installed as required in Sections 130.0 through 130.5, Sections 140.6 through 140.8, Section 141.0, and Section 150.0(k).
- Time-switch lighting controls. All controls that provide time-switch functionality, including all automatic and astronomical time-switch controls, shall have program backup capabilities that prevent the loss of the device’s schedule for at least 7 days, and the device’s date and time for at least 72 hours if power is interrupted. In addition:
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
- Part-night outdoor lighting controls, as defined in Section 100.1, shall meet all of the following requirements:
A. Have sunrise and sunset prediction accuracy within
+/- 15 minutes, using both light sensing and time measurement; and
B. Have the ability to reduce or turn off outdoor lumi naire power at night as required in Section 130.2(c); and
C. Shall be programmable to reduce or turn off outdoor
luminaire power at any time as determined by the user. Time-based scheduling control is allowed to be relative to both sunset and sunrise, and to the midpoint between sunset and sunrise.
- Sensors used to detect occupants. Sensors that are used by occupant sensing controls to detect occupants shall meet all of the following requirements:
A. Sensors shall not incorporate switches or
mechanical devices that allow the sensor to be disabled without changing the settings of the control.
B. Sensors that utilize ultrasonic radiation for detec tion of occupants shall:
i. comply with 21 C.F.R. part 1002.12;
ii. not emit audible sound; and
iii. not emit ultrasound in excess of the deci bel levels shown in Table 110.9-A measured no more than 5 feet from the source, on axis.
C. Sensors that utilize microwave radiation for
detection of occupants shall:
i. comply with 47 C.F.R. parts 2 and 15;
and
ii. not emit radiation in excess of 1 milliwatt
per square centimeter measured at no more than 5 centimeters from the emission surface of the device.
- Indicator lights. Indicator lights integral to lighting controls shall consume no more than 1 watt of power per indicator light.
(c) Track lighting integral current limiter. An integral current limiter for line-voltage track lighting shall be recognized for compliance with Part 6 only if it meets all of the following requirements:
- Shall have the identical volt-ampere (VA) rating of the current limiter as installed and rated for compliance with Part 6 clearly marked as follows; and
A. So that it is visible for the enforcement agency’s
field inspection without opening coverplates, fixtures or panels; and
B. Permanently marked on the circuit breaker; and
B. Have a set point control that easily distinguishes
settings to within 10 percent of full-scale adjustment;
C. Provide a linear response within 5 percent accu racy over the range of illuminance measured by the light sensor; and
D. Be capable of being calibrated in a manner that
the person initiating the calibration is remote from the sensor during calibration to avoid influencing calibration accuracy, for example by having a light sensor that is physically separated from where the calibration adjustments are made.
- Dimmers. Controls that provide dimming functionality shall:
A. Be capable of reducing lighting power consump tion by a minimum of 65 percent when at its lowest setting;
B. Provide reduced flicker operation, meaning that
directly controlled light sources shall be provided electrical power such that the light output has an amplitude modulation of less than 30 percent for frequencies less than 200 Hz without causing premature lamp failure;
C. Provide an off setting that produces a zero lumen
output; and
D. For wall box dimmers and associated switches
designed for use in three way circuits, be capable of turning lights off, and on to the level set by the dimmer if the lights are off.
- Occupant sensing controls. Occupant sensing controls include occupant sensors, motion sensors, and vacancy sensors, including those with a partial-ON or partialOFF function. Occupant sensing controls shall:
A. Be capable of automatically turning the con trolled lights in the area either off or down no more than 20 minutes after the area has been vacated;
B. For manual-on controls, have a grace period of
no less than 15 seconds and no more than 30 seconds to turn on lighting automatically after the sensor has timed out; and
C. Provide a visible status signal that indicates that
the device is operating properly, or that it has failed or malfunctioned. The visible status signal may have an override that turns off the signal.
Exception to Section 110.9(b)4: Occupant sensing control systems may consist of a combination of single or multilevel occupant, motion or vacancy sensor controls, provided that components installed to comply with manual-on requirements shall not be capable of conversion by occupants from manual-on to automatic-on functionality.
50 2019 CALIFORNIA ENERGY CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
C. On a factory-printed label that is permanently
affixed to a nonremovable base-plate inside the wiring compartment.
Shall have a conspicuous factory installed label permanently affixed to the inside of the wiring compartment warning against removing, tampering with, rewiring or bypassing the device; and
Each electrical panel from which track lighting integral current limiters are energized shall have a factory printed label permanently affixed and prominently located, stating the following: “NOTICE: Current limiting devices installed in track lighting integral current limiters connected to this panel shall only be replaced with the same or lower amperage. Adding track or replacement of existing current limiters with higher continuous ampere rating will void the track lighting integral current limiter certification, and will require resubmittal of compliance documentation to the enforcement agency responsible for compliance with the California Title 24, Part 6 Building Energy Efficiency Standards.”
(d) Track lighting supplementary overcurrent protec- tion panel. A Track Lighting Supplementary Overcurrent Protection Panel shall be used only for line-voltage track lighting and shall be recognized for compliance with Part 6 only if it meets all of the following requirements:
Shall be listed as defined in Section 100.1; and
Shall have a permanently installed label that is prominently located stating the following: “NOTICE: This Panel for Track Lighting Energy Code Compliance Only.” The overcurrent protection devices in this panel shall only be replaced with the same or lower amperage. No other overcurrent protective device shall be added to this panel. Adding to, or replacement of, existing overcurrent protective device(s) with higher continuous ampere rating will void the panel listing and require resubmittal of compliance documentation to the enforcement agency responsible for compliance with the California Title 24, Part 6 Building Energy Efficiency Standards.
TABLE 110.9-A ULTRASOUND MAXIMUM DECIBEL VALUES
| MID-FREQUENCY OF SOUND PRESSURE THIRD-OCTAVE BAND (IN kHz) |
MAXIMUM DB LEVEL WITHIN THIRD-OCTAVE BAND (IN dB REFERENCE 20 MICROPASCALS) |
|---|---|
| Less than 20 | 80 |
| 20 or more to less than 25 | 105 |
| 25 or more to less than 31.5 | 110 |
| 31.5 or more | 115 |
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 52943, Public Resources Code .