MANDATORY REQUIREMENTS
FOR DEMAND MANAGEMENT
Buildings, other than healthcare facilities, shall comply with the applicable demand responsive control requirements of Sections 110.12(a) through 110.12(d).
(a) Demand responsive controls.
- All demand responsive controls shall be either:
A. A certified OpenADR 2.0a or OpenADR 2.0b
Virtual End Node (VEN), as specified under Clause 11, Conformance, in the applicable OpenADR 2.0 Specification; or
B. Certified by the manufacturer as being capable
of responding to a demand response signal from a certified OpenADR 2.0b Virtual End Node by automatically implementing the control functions requested by the Virtual End Node for the equipment it controls.
All demand responsive controls shall be capable of communicating using one or more of the following: Wi-Fi, ZigBee, BACnet, Ethernet, or hard-wiring.
Demand responsive controls may incorporate and use additional protocols beyond those specified in Sections 110.12(a)1 and 2.
When communications are disabled or unavailable, all demand responsive controls shall continue to perform all other control functions provided by the control.
Demand responsive control thermostats shall comply with Reference Joint Appendix 5 (JA5), Technical Specifications for Occupant Controlled Smart Thermostats.
(b) Demand Responsive Zonal HVAC Controls. Non residential HVAC systems with DDC to the Zone level shall be programmed to allow centralized demand shed for noncritical zones as follows:
The controls shall have a capability to remotely increase the operating cooling temperature set points by 4 degrees or more in all noncritical zones on signal from a centralized contact or software point within an Energy Management Control System (EMCS).
The controls shall have a capability to remotely decrease the operating heating temperature set points by 4 degrees or more in all noncritical zones on signal from a centralized contact or software point within an EMCS.
The controls shall have capabilities to remotely reset the temperatures in all noncritical zones to original operating levels on signal from a centralized contact or software point within an EMCS.
The controls shall be programmed to provide an adjustable rate of change for the temperature increase, decrease, and reset.
The controls shall have the following features:
A. Disabled. Disabled by authorized facility
operators; and
B. Manual control. Manual control by authorized
facility operators to allow adjustment of heating and cooling set points globally from a single point in the EMCS; and
C. Automatic Demand Shed Control. Upon
receipt of a demand response signal, the space-conditioning systems shall conduct a centralized demand shed, as specified in Sections 110.12(b)1 and 110.12(b)2, for noncritical zones during the demand response period.
(c) Demand Responsive Lighting Controls. Lighting
controls in nonresidential buildings larger than 10,000 square feet shall be capable of automatically reducing lighting power in response to a Demand Response Signal. General lighting shall be reduced in a manner consistent with the uniform level of illumination requirements in Table 130.1-A.
- For compliance testing, the lighting controls shall demonstrate a lighting power reduction in controlled spaces of a minimum of 15 percent below the total installed lighting power. The controls may provide additional demand responsive functions or abilities.
Exception 1 to 110.12(c): Spaces with a lighting power density of 0.5 watts per square foot or less are not required to install demand responsive controls and do not count toward the 10,000 square foot threshold.
Exception 2 to 110.12(c): Spaces where a health or life safety statute, ordinance, or regulation does not permit the lighting to be reduced are not required to install demand responsive controls and do not count toward the 10,000 square foot threshold.
(d) Demand Responsive Electronic Message Center
Control. Controls for electronic message centers greater than 15 kW shall be capable of reducing the
54 2019 CALIFORNIA ENERGY CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
lighting power by a minimum of 30 percent when receiving a demand response signal.
Exception to Section 110.12(d): Electronic message centers that are not permitted by a health or life safety statute, ordinance, or regulation to be reduced.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
56 2019 CALIFORNIA ENERGY CODE Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
SUBCHAPTER 3
NONRESIDENTIAL, HIGH-RISE RESIDENTIAL HOTEL/MOTEL OCCUPANCIES, AND COVERED
PROCESSES—MANDATORY REQUIREMENTS
ii.Mechanical supply-only ventilation sys tems that provide outside air to an occupiable space.
iii.The supply side of mechanical balanced
ventilation systems, including heat recovery ventilation systems and energy recovery ventilation systems that provide outside air to an occupiable space.
B. System design and installation.
i. The system shall be designed to ensure that
all recirculated air or outdoor air supplied to the occupiable space is filtered before passing through any system thermal conditioning components.
Exception to Section 120.1(b)1Bi: For heat recovery ventilators and energy recovery ventilators the location of the filters required by Section 120.1(b) may be downstream of a system thermal conditioning component, provided the system is equipped with ancillary filtration upstream of the system’s thermal conditioning component.
ii.All systems shall be designed to accommo date the clean-filter pressure drop imposed by the system air filter(s). The design airflow rate, and maximum allowable cleanfilter pressure drop at the design airflow rate applicable to each air filter shall be determined and reported on labels according to subsection iv below.
Systems specified in Section 120.1(b)1Ai shall be equipped with air filters that meet either subsection a or b below:
a. Nominal 2-inch minimum depth
filter(s) shall be sized by the system designer; or
b. Nominal 1-inch minimum depth
filters(s) shall be allowed if the filter(s) are sized according to Equation 120.1-A, based on a maximum face velocity of 150 feet per minute and according to the maximum allowable clean filter pressure drop specified in Section 120.1(b)1Dii
Aface = Qfilter / Vface
(Equation 120.1-A)