Title 17 — BUILDING AND CONSTRUCTION
Petaluma Municipal Code Ch. 5 Fire Service Features
Petaluma Municipal Code · 2026-09 edition · updated 2026-10-04 · Petaluma
Cite as: Petaluma Municipal Code Chapter 5 · Text as of 2026-10-04
Section 501.1 is amended to read as follows:
501.1 Scope. Fire Service Features for buildings, structures and premises shall comply with this chapter.
This section applies to residential and commercial developments.
Floor Area. The [oor area used for calculating the required Zre [ow shall be the total [oor area of all
[oor levels within the exterior walls of a structure that are under the horizontal projection of the roof,
except as modiZed in Appendix Section B104 of the 2025 California Fire Code.
Section 503.2.6 is amended to read as follows:
503.2.6 Bridges and Elevated Surfaces. Where a bridge or an elevated surface is part of a Zre
apparatus access road, the bridge shall be constructed and maintained in accordance with the American
Association of State Highway and Transportation O\cials (AASHTO) Standard SpeciZcations, and
AASHTO’s Load and Resistance Factor Design. Bridges and elevated surfaces shall be designed for a live
load su\cient to carry the imposed loads of Zre apparatus. Vehicle load limits shall be posted at both
entrances to bridges when required by the Fire Code O\cial. Where elevated surfaces designed for
emergency vehicle use are adjacent to surfaces which are not designed for such use, approved barriers,
approved signs or both shall be installed and maintained when required by the Fire Code O\cial.
Section 503.2.6.1 is added to read:
503.2.6.1 Evaluation. All existing private bridges and elevated surfaces shall be evaluated by a California
licensed civil engineer experienced in structural engineering or a California licensed structural engineer
for the purposes of safety and weight rating. The vehicle load limits shall be posted at both entrances to
bridges. These evaluations shall be performed at the direction of the Fire Code O\cial.
Section 503.2.6.2 is added to read:
503.2.6.2 Bridge Maintenance. All new and existing bridges and elevated structures providing
emergency access shall be routinely evaluated and maintained in accordance with the American
Association of State Highway and Transportation O\cials (AASHTO) Manual: "The Manual for Bridge
Evaluation," 3rd Edition, 2018, published by the American Association of State Highway and
Transportation O\cials; or other approved standard.
Section 503.2.7.1 is added to read as follows:
503.2.7.1 Grade Angles. The maximum allowable grade for driveways and roadways used for Zre
apparatus access is twelve percent (12%). Special allowances up to a maximum of eighteen percent (18%)
may be granted with the approval of the Fire Code O\cial and City Engineer.
Section 503.3 is amended to read as follows:
503.3 Marking. Where required by the Fire Code O\cial, approved signs or other approved notices or
markings that include the words "NO PARKING – FIRE LANE" in accordance with the California Vehicle
Code, shall be provided for Zre apparatus access roads to identify such roads or prohibit the obstruction
thereof. The means by which Zre lanes are designated shall be maintained in a clean and legible
condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Section 505.1 is amended to read as follows:
505.1 Address IdentiKcation. New and existing buildings shall be provided with approved illuminated
or other approved means of illuminated address identiZcation. The address identiZcation shall be legible
and placed in a position that is visible from the street or road fronting the property. Address
identiZcation characters shall contrast with their background. Address numbers shall be Arabic numerals
or alphabetic letters. Numbers shall not be spelled out. Character size and stroke shall be in accordance
with Section 505.1.1 through 505.1.2. Where required by the Zre code o\cial, address identiZcation shall
be provided in additional approved locations to facilitate emergency response in accordance with this
code and Section 505.1.3. Where access is by means of a private road and the building cannot be viewed
from the public way or when determined by the Zre code o\cial, a monument, pole, or other approved
sign or means shall be used to identify the structure. Address identiZcation shall be maintained.
Section 505.1.1 is added to read as follows:
505.1.1 One- and Two-Family Dwellings. Numbers for one- and two-family dwellings shall be not less
than four inches (4") (101.6 mm) high with a minimum stroke width of 0.5 inches (12.7 mm).
Section 505.1.2 is added to read as follows:
505.1.2 Numbers for Other Than One- and Two-Family Dwellings. Each address identiZcation
character shall not be less than twelve inches (12") high with a minimum stroke width of one inch (1").
Suite and unit directional numbers shall be not less than six inches (6") in height with a minimum stroke
width of three-quarter inch (0.75"). Individual unit numbers shall not be less than four inches (4") in
height with a minimum stroke width of one-half inch (1/2").
Section 505.1.3 is added to read as follows:
505.1.3 Complex Directory. Where two (2) or more buildings cannot be viewed from the public way or
when determined by the Fire Code O\cial, an approved illuminated complex directory, monument pole,
or other approved sign or means shall be used to identify the structures at the main entrances to the
property.
Section 506.1 is amended to read as follows:
Section 506.1 Key Boxes. When access to or within a structure or area is determined by the Fire Code
O\cial to be unduly di\cult because of secured openings (doors or gates) or due to the presence of
hazardous materials or Zre protection systems, a key box shall be required to be installed at an
accessible location. The key box shall be an approved type and contain those keys necessary to gain
access.
Section 507.5 is amended to read as follows:
507.5 Fire Hydrant Systems. Fire hydrant systems shall comply with Sections 507.5.1 through 507.5.6
and Appendix C as amended.
Section 507.5.1 is amended to read as follows:
507.5.1 Where Required. Where a portion of the facility or building hereafter constructed or moved into
or within the jurisdiction is more than 150 feet (45.179 m) from a hydrant on a Zre apparatus access
road, as measured by an approved route around the exterior of the facility or building, on-site Zre
hydrants and mains shall be provided where required by the Fire Code O\cial.
Section 507.5.1: the exception is deleted.
Section 507.5.1.2 is added to read as follows:
507.5.1.2 Additional Requirements.
(a) Upon review of site conditions by the Fire Department, Zre hydrant spacing requirements may be
reduced or modiZed. Fire hydrants shall be placed along all adjoining public and private streets and Fire
Department access drives.
(b) Divided streets shall have hydrants located as required by the Fire Code O\cial on both sides of the
street and they shall be staggered to prevent a hydrant being placed directly across the divided street
from another hydrant.
(c) Types of Hydrants: Hydrants shall conform to the City of Petaluma Sewer and Water Design and
Construction Standards.
510.1 Responder Communications Enhancement Systems.
Section 510.1 exception 1 is deleted.
Get a plain-English answer with a citation back to this text.