Title 17 — BUILDING AND CONSTRUCTION
Petaluma Municipal Code Ch. 17.34 Earthquake Hazard Reduction in Existing Unreinforced
Petaluma Municipal Code · 2026-09 edition · updated 2026-10-04 · Petaluma
Cite as: Petaluma Municipal Code Chapter 17.34 · Text as of 2026-10-04
17.34.010 Purpose.¶
The purpose of this chapter is to promote public safety and welfare by reducing the risk of death or injury that
may result from the e]ects of earthquakes on unreinforced masonry bearing wall buildings.
The provisions of this chapter are intended as minimum standards for structural seismic resistance established
primarily to reduce the risk of life loss or injury. Compliance with these standards will not necessarily prevent loss
of life or injury or prevent earthquake damage to rehabilitated buildings. Building owners who retroZt their
buildings in Petaluma in accordance with the provisions of this chapter shall be deemed to have used an
acceptable standard of care to protect the safety of the public and occupants of the building. This chapter does
not require alteration of existing electrical; accessibility; plumbing; mechanical or Zre safety systems. (Ord. 1882
NCS §1, 1992.)
17.34.020 Applicability.¶
The provisions of this chapter shall apply to all existing buildings having at least one unreinforced wall as deZned
herein. Structural characteristics to be addressed are parapet stability; wall anchors (roof and [oor systems); shear
anchors (corners) and external hazards.
Exceptions: This chapter shall not apply to the following:
A. Single-Family Detached dwellings.
B. Detached apartment houses containing less than Zve dwelling units which are used solely for residential
purposes.
(Ord. 1882 NCS §1, 1992.)
17.34.030 Alternate materials and methods of construction.¶
Alternate materials; designs and methods of construction may be approved by the building o\cial in accordance
with the current "Uniform Code for Building Conservation." (Ord. 1882 NCS §1, 1992.)
17.34.040 DeKnitions.¶
For the purpose of this chapter; certain terms are deZned as follows:
"Cross walls" mean interior walls of masonry or wood frame construction with surface Znish of wood lath and
plaster; minimum one-half inch-thick gypsum wallboard or solid horizontal wood sheathing. In order to be
considered as a cross wall within the intent of this chapter; cross walls shall be spaced not more than forty feet
apart in each story; and shall be full story height with a minimum length of one and one-half times the story
height.
"Unreinforced masonry wall" means a masonry wall having all of the following characteristics:
1. Provides the vertical support for a [oor or roof.
2. The total superimposed load is over one hundred pounds per linear foot.
3. The area of reinforcing steel; if any; is less than Zfty percent of that required by Section 2407(h)4B of the
UBC.
"External hazard" means an object attached to or forming the exterior facade of a building which may fall onto
pedestrians or adjacent buildings. Examples of this type of hazard include; but are not limited to; the following:
1. Parapets;
2. Masonry chimneys;
3. Tile rooZng;
4. Masonry or stone wall veneer and wall ornamentation; including cornices or other decorative
appendages;
5. Nonstructural exterior wall panels; such as masonry in-Zll or decorative precast concrete.
(Ord. 1882 NCS §1, 1992.)
17.34.050 Administration.¶
A. Service of Order. The building o\cial shall issue an order; as provided in subsection B; to the owner of each
building within the scope of this chapter within sixty days from the e]ective date of this chapter.
B. Contents of Order. The order shall be in writing and shall be served either personally or by certiZed or
registered mail upon the owner. The order shall specify that the building has been determined by the building
o\cial to be within the scope of this chapter and; therefore; is required to meet the minimum standards of this
chapter. The order shall be accompanied by a copy of this chapter and shall specify the time limits for compliance.
C. Appeal From Order. The owner or the owner’s authorized agent may appeal to the city council the building
o\cial’s initial determination that the building is within the scope of this chapter. Such appeal shall be Zled with
the city clerk within sixty days from the service date of the order described in subsection B. Any such appeal shall
be decided by the city council no later than sixty days after the date that the appeal is Zled. Such appeal shall be
made in writing and the ground thereof shall be stated clearly and concisely.
Appeals or requests for modiZcations from any other determinations; orders; or action by the building o\cial
pursuant to this chapter; shall be made in accordance with the appeal procedures established in this chapter.
D. Recordation. At the conclusion of the appeal period; the building o\cial shall Zle with the o\ce of the county
recorder a certiZcate stating that the subject building is within the scope of Chapter 17.34; Earthquake Hazard
Reduction in Existing Unreinforced Masonry Wall Buildings. The certiZcate shall also state that the owner thereof
has been ordered to bring the building into conformance with Chapter 17.34.
E. Termination of Status. As a result of structural alterations or an analysis is found to be structurally capable of
resisting minimum seismic forces required by this chapter; or is demolished; the building o\cial shall Zle with the
o\ce of the county recorder a certiZcate terminating the status of the subject building as being classiZed within
the scope of Chapter 17.34.
Further; the building o\cial shall also notify the California Seismic Safety Commission and/or other agencies
hereafter charged with the maintenance of the California Unreinforced Masonry Building Inventory; that the
subject building has been removed from the city of Petaluma Inventory Of Unreinforced Masonry Buildings; and
instructing the commission and/or agencies to do the same.
F. Enforcement. If the owner fails to comply with any order issued by the building o\cial pursuant to this chapter
within any of the time limits set forth in Section 17.34.110; the building o\cial shall order the entire building
vacated and remain vacated until such order has been complied with. If compliance with such order has not been
accomplished within ninety days after the date the building has been ordered vacated; or by such additional time
as may have been granted by the city council; the building o\cial may initiate proceedings in accordance with the
Uniform Code for the Abatement of Dangerous Buildings.
In addition; the following remedies are available to:
1. The city may seek injunctive relief on behalf of the public to enjoin a building owner’s violation of this
chapter.
2. A building owner violating this ordinance shall be guilty of a misdemeanor and; upon conviction thereof;
shall be punishable by a Zne of not more than Zve hundred dollars or by imprisonment in the Sonoma
County Jail for a term not exceeding six months; or by both such Zne and imprisonment. Such building owner
is guilty of a separate o]ense for each and every day during any portion of which such violation of this
ordinance is committed; continued or permitted by such building owner.
3. These remedies are not exclusive.
(Ord. 1882 NCS §1, 1992.)
17.34.060 General requirements.¶
A. General. Unreinforced masonry wall buildings subject to this chapter shall undergo structural alterations
necessary to comply with the minimum requirements set forth in this chapter.
As an alternate; said buildings may be demolished subject to the restrictions set forth in the policies and
ordinances of Petaluma.
Buildings which have undergone earthquake hazard reduction work which is deemed by the building o\cial to be
equivalent to the requirements set forth in this chapter need have no additional work performed.
B. Mandatory Requirements.
1. Compliance with standards. Unreinforced masonry buildings shall comply with provisions of this chapter.
Should an owner elect to strengthen a building beyond the mandatory requirements set forth herein; such
additional strengthening work shall comply with other recognized standards (Appendix Chapter 1 of the 1991
UCBC) as approved by the building o\cial.
2. Change in Use. After the e]ective date of this chapter the time limits set forth in Table No. 17.34.110 shall
not apply to any building which will undergo a change of use or occupancy which will result in the building
being classiZed as a Group A Occupancy having an occupant load of one hundred or more. Before such building may be used or occupied as a Group A Occupancy it shall be made to comply with provisions of this
chapter.
C. Responsibility of Owner. As speciZed in Section 17.34.050; the owner shall comply with the requirements set
forth in this subsection by submitting to the building o\cial one of the following:
1. A structural analysis by a civil or structural engineer or architect licensed by the state of California which
shall demonstrate that the building meets the minimum requirements of this chapter, or
2. A structural analysis and plans by a civil or structural engineer or architect licensed by the state of
California for proposed structural alterations necessary to make the building comply with the minimum
requirements of this chapter; or
3. Plans for the demolition of the building.
After plans are submitted and approved by the building o\cial; the owner shall obtain a building permit;
commence and complete the required construction or demolition within the time limits set forth in Table No.
17.34.110.
(Ord. 1882 NCS §1, 1992.)
17.34.070 Material requirements.¶
A. Existing Materials. All existing materials utilized as part of the lateral force resisting system shall be in sound
condition or shall be removed and replaced with new materials.
B. Existing Unreinforced Masonry.
1. General. Unreinforced masonry parapets that exceed the maximum height in Section 17.34.100(C) shall
be tested as speciZed in this subsection. Masonry that does not meet or exceed the minimum standards
established by this chapter shall be removed and replaced by new materials or shall have its structural
functions replaced by new materials and anchored to supporting elements.
2. Lay-up of parapets. The facing and backing shall be bonded so that not less than four percent of the wall
surface of each face is composed of solid headers extending not less than four inches into the backing. The
distance between adjacent full-length headers shall not exceed twenty-four inches either vertically or
horizontally. In walls in which a single header does not extend through the wall; headers from opposite sides
shall overlap at least four inches; or headers from opposite sides shall be covered with another header
course overlapping the header below at least four inches. Wythes of walls not bonded as described above
shall be considered as veneer. The veneer wythe shall not be included in the e]ective thickness used in
calculating the height to thickness ratio of the wall unless it is bonded and anchored to the backing in a
manner acceptable to the building o\cial.
3. Mortar.
a. Tests. The quality of mortar in unreinforced masonry wall shall be determined by performing in-
place shear tests in accordance with UBC Standard 24-40. Alternate methods of testing may be approved
by the building o\cial.
b. Location of tests. Shear tests shall be taken at locations representative of the mortar conditions
throughout the entire building. The exact test location shall be determined at the building site by the
engineer or architect in responsible charge of the structural design work. An accurate record of such
tests and their location in the building shall be recorded and these results shall be submitted to the
building o\cial for approval as part of the structural analysis.
c. Number of tests. The minimum number of tests per wall or line of wall elements providing a common
line of resistance to lateral forces shall be as follows: Two tests per wall with a minimum total number of
eight tests or one test per one thousand Zve hundred square feet of wall area; whichever results in the
greater number of tests.
d. Minimum quality mortar.
(1) Mortar shear test values; vto; shall be obtained for each in-place shear test in accordance with
the following equation:
vto = vtest - PD+L/AW
WHERE:
Vto = Mortar shear test value; in psi.
vtest = Shear stress at incipient cracking
for each in-place test per UBC
Standard No. 24-7.
PD+L = Actual dead plus live load in place
at the time of testing, in pounds.
AW = Area of the wall supporting PD+L
at each in-place shear test.
(2) Individual unreinforced masonry walls with vto less than 30 psi shall be pointed prior to
retesting.
(3) The mortar shear strength; vto; is the value in psi that is exceeded by eighty percent of all of the
mortar shear test values, vto.
(4) Unreinforced masonry with mortar shear strength; vto; less than 30 psi shall be removed or
pointed and retested or treated as veneer.
e. Pointing. All deteriorated mortar joints in unreinforced masonry walls shall be pointed according to
UBC Standard No. 24-42. Nothing shall prevent pointing with mortar of all masonry wall joints before the
tests are made.
(Ord. 1882 NCS §1, 1992.)
17.34.080 Quality control.¶
A. Pointing. Special inspection shall be provided during preparation and mortar pointing.
B. Shear Tests. In-place shear tests shall comply with Section 17.34.070 B. and UBC Standard 24.41.
C. Existing Floor Level Wall Anchors. If existing rod anchors are to be utilized as all or part of the required wall
anchorage system at the [oor level; not less than Zve percent of such existing rod anchors shall be tested by an
approved testing laboratory. The minimum number of anchors tested shall be four per [oor; with two tests at
walls with joists parallel to the wall but not less than ten percent of the total number of existing tension anchors at
each level. The test apparatus shall be supported on the masonry wall at a minimum distance of the wall thickness
from the anchor tested. The rod anchor shall be given a preload of three hundred pounds prior to establishing a
datum for recording elongation. The tension test load reported shall be recorded at one-eighth inch relative
movement of the anchor and the adjacent masonry surface. Results of all tests shall be reported. The report shall
include the test results as related to the wall thickness and joint orientation. Ends of existing anchors shall be
secured into the wood framing by an approved method.
D. Testing of Bolts. One-fourth of new embedded bolts in unreinforced masonry walls shall be tested by a special
inspector using a torque calibrated wrench to the following minimum torques:
1/2" diameter bolts or dowels= 40 foot-lbs
5/8" diameter bolts or dowels = 50 foot-lbs
3/4" diameter bolts or dowels = 60 foot-lbs
No bolts exceeding three-quarter inches diameter shall be used. Nuts shall be installed over malleable iron or cut
plate washers when bearing on wood and heavy cut washers when bearing on steel.
(Ord. 1882 NCS §1, 1992.)
17.34.090 Allowable design values.¶
A. Tension Anchors. Allowable values for tension anchors are given in Table No. 17-A. A one-third increase is not
allowed for values listed in this table.
B. Other Materials. Allowable values not speciZed in this chapter shall be as speciZed elsewhere in this code.
(Ord. 1882 NCS §1, 1992.)
17.34.100 Detailed system design requirements.¶
A. Lateral Force on Elements of Structures and Nonstructural Components. Parts or portions of structures;
nonstructural components and their anchorage to the main structural system shall be designed for lateral forces
in accordance with the following formula:
Fp = Cp Wp ...................... (100-1)
Wp shall be as deZned in Section 2312(c) of the UBC. The value of Cp need not exceed the values set forth in
Table No. 17-B.
B. Wall Anchorage.
1. Anchor locations. Unreinforced masonry walls shall be anchored at the roof and [oor levels in order to
resist the forces speciZed in this section.
2. Wall anchor requirements. Wall anchors shall be tension bolts through the wall having a maximum
spacing of six feet or six times the wall thickness; whichever is less. Alternate anchors shall be combination
tension and shear bolts complying with the requirements set forth in Table No. 17A. Tension bolts used to
resist required forces may be assumed to develop the allowable values listed in Table No. 17-A. If access to
the exterior face of a masonry wall is prevented by proximity of an existing building or when the appearance
of through the wall tension anchors will a]ect the architectural appearance of the building; embedded bolts
conforming to Table No. 17-A may be used. Wall anchors shall be secured to the rafters or joists to transfer
the required forces into roof or [oor sheathing.
3. Minimum wall anchorage force. Anchorage of masonry walls to each [oor or roof shall resist a minimum
force determined by Formula (100-1) or two hundred pounds per linear foot; whichever is greater; acting
normal to the wall at the level of the [oor or roof. Existing wall anchors installed under previous permits must
meet or must be upgraded to meet the requirements of this chapter.
4. Anchors at corners. At the roof and [oor levels, combination tension and shear anchors shall be provided
within two feet horizontally from the inside of the corners of the walls.
C. Parapets. Parapets and exterior wall appendages not capable of resisting the forces speciZed in this section
shall be removed; stabilized or braced to insure that the parapets and appendages remain in their original
position.
The maximum height of an unbraced unreinforced masonry parapet above the level of tension anchors shall not
exceed one and one-half times the thickness of the parapet wall. If the required parapet height exceeds this
maximum height; a bracing system designed for the force determined by formula (100-1) shall be installed to
support the parapet. Parapet corrective work shall be performed in conjunction with the installation of tension
roof anchors.
The minimum height of a parapet above the wall anchor shall be twelve inches.
Exception: If a reinforced concrete beam is provided at the top of the wall; the minimum height above the wall
anchor may be six inches.
D. Veneer.
1. Unreinforced concrete beam is provided at the top of the wall; the minimum height above the wall
anchor may be six inches.
2. Veneer shall be anchored with approved anchor ties; conforming to the required design capacity
speciZed in this code and placed at a maximum spacing of 24 inches with a maximum supported area of two
square feet.
Exception: Existing veneer anchor ties may be acceptable provided the ties are in good condition and conform
to the following minimum size; maximum spacing and material requirements.
Existing veneer anchor ties shall be corrugated galvanized iron strips not less than one inch in width; eight
inches in length and one-sixteenth of an inch in thickness or equal and shall be located in every alternate
course in the height of the wall at a spacing not to exceed eighteen inches on centers horizontally. As an
alternate; such ties may be laid in every fourth course vertically at a spacing not to exceed nine inches on
centers horizontally.
3. The location and condition of existing veneer ties shall be veriZed as follows:
a. An approved testing laboratory shall verify the location and spacing of the ties and shall submit a
report to the building o\cial for approval as a part of the structural analysis.
b. The veneer in a selected area shall be removed to expose a representative sample of ties (not less
than four) for inspection by the building o\cial.
E. Mortar Joints. All deteriorated mortar joints in unreinforced masonry walls shall be pointed with Type S or N
mortar. Masonry cements shall not be used. Prior to any pointing; the wall surface must be raked and cleaned to
remove loose and deteriorated mortar. All preparation and pointing shall be done under continuous inspection by
a special inspection certiZed to inspect masonry or concrete. At the conclusion of the project; the special inspector
shall submit a written report to the building o\cial setting forth the portion of the work inspected.
(Ord. 1882 NCS §1, 1992.)
17.34.110 Time limits for compliance.¶
Building Groups
Building Owner Action I II III IV
Submit Plans for Review 7 yrs 12 yrs 17 yrs 22 yrs
Stabilize Parapet 10 yrs 12 yrs 12 yrs 12 yrs
Wall Anchors (roof and [oor 10 yrs 15 yrs 20 yrs 25 yrs
system)
Shear Anchors (corners) 10 yrs 15 yrs 20 yrs 25 yrs
Start construction within 180 days after building permit is issued.
Complete Construction within 10 yrs 15 yrs 20 yrs 25 yrs
Building Groupings are deZned in Petaluma Resolution No. 92-48 NCS "Establishing A List Of Unreinforced
Masonry Buildings". (Ord. 1882 NCS §1, 1992.)
17.34.111 Tables and standards.¶
TABLE NO. 17-A
ALLOWABLE VALUES FOR TENSION ANCHORS
Type of Installation 1 Allowable Values
Existing Tension Anchors for Floors: Allowable shall be 40% of the average of the tests
To be tested per Section 17.34.080(c) for anchors having same wall thickness and joist orientation.
Tension Bolts: 1800 lbs. per bolt
Bolts extending entirely through unreinforced 900 lbs. for 2 wythe walls
masonry walls secured with bearing plates on far
side of a 3 wythe minimum wall with a bearing plate
2 3
having an area of at least 30 square inches.
Combination Tension and Shear Bolts: Same as for tension bolts
Combination tension and shear bolts are tension
bolts centered in a 2-1/2 inch diameter by 8 inch
minimum depth hole with dry-pack or nonshrink
grout around the circumference of bolt.
Embedded Bolts: Same as for tension bolts
Bolts extending to the exterior wall with a 2-1/2
inch round plate under the head and drilled at an angle of 22-1/2 degrees to the horizontal. Bolts
shall be centered in 2-1/2 inch diameter holes with
dry-pack or non-shrink grout around circumference
of bolts. Bolts shall be tested per Section
17.34.080(d). (2) (3)
1 A 1/3 increase in allowable stresses is not allowed.
2 Bolts to be 1/2-inch minimum in diameter.
3 Drilling for bolts and dowels shall be done with an electric rotary drill. Impact tools shall not be used for
drilling holes or tightening anchors and shear bolt nuts.
TABLE NO. 17-B
HORIZONTAL FORCE FACTOR "Cp" FOR PARTS OR PORTIONS OF BUILDINGS OR OTHER STRUCTURES
Part or Portion of Buildings Direction of Force Value of Cp
Exterior bearing and nonbearing walls; Normal-to-[at surface 0.30
interior bearing walls and partitions;
interior non-bearing walls and partitions
over 10 feet in height.
Cantilever parapet and other cantilever Normal-to-[at surface 0.80
walls, except retaining walls.
Exterior and interior ornamentations and Any direction 1.00
appendages.
Prefabricated structural elements, other Any horizontal direction 0.30
than walls, with force applied at center of
gravity of assembly.
Connections for exterior panels or Any direction 2.00
elements.
Braced Parapets Normal-to-[at surface 0.30
TABLE NO. 17-C
ALLOWABLE VALUE OF HEIGHT-THICKNESS RATIO OF UNREINFORCED MASONRY WALLS WITH MINIMUM QUALITY MORTAR1
Buildings with Crosswalls As All Other Buildings
DeZned by Section 17.34.040
Walls of one-story buildings 16 13
First-story walls of two-story building 16 15
Walls in top story of two-story 14 9
buildings
1 Minimum quality mortar shall be determined by laboratory testing in accordance with Section 17.34.070.
UNIFORM BUILDING CODE STANDARD NO. 24-40 IN-PLACE MASONRY SHEAR TESTS
The bed joints of the outer wythe of the masonry shall be tested in shear by laterally displacing a single brick
relative to the adjacent bricks in the same wythe. The head joint opposite the loaded end of the test brick shall be
carefully excavated and cleared. The brick adjacent to the loaded end of the test brick shall be carefully removed
by sawing or drilling and excavating to provide space for a hydraulic ram and steel loading blocks. Steel blocks, the
size of the end of the brick, shall be used on each end of the ram to distribute the load to the brick. The blocks
shall not contact the mortar joints. The load shall be applied horizontally, in the plane of the wythe, until either a
crack can be seen or slip occurs. The strength of the mortar shall be calculated by dividing the load at the Zrst
crack or movement of the test brick by the nominal gross area of the sum of the two bed joints.
UNIFORM BUILDING CODE STANDARD NO. 24-42 POINTING OF UNREINFORCED MASONRY WALLS
POINTING
The old mortar should be cut out, by means of a toothing chisel or a special painter’s grinder, to a
uniform depth of 3/4", or until sound mortar is reached. Care must be taken not to damage the brick
edges. All dust and debris must be removed from the joint by brushing, blowing air or rinsing with water.
Mortar mix shall be Type "S" or "N" proportions as called for in the construction speciZcation, The tuck-
pointing mortar should be pre-hydrated to reduce excessive shrinkage. The proper pre-hydration
process is as follows:
All dry ingredients should be thoroughly mixed. Only enough clean water should be added to the dry mix to
produce a damp, workable consistency which will retain its shape when formed into a ball. The mortar should
stand in this dampened condition for one to one and one-half hours.
The joints to be tuck-pointed should be dampened, but to ensure a good bond, the brickwork must absorb all
surface water. Add water to the pre-hydrated mortar to bring it to a workable consistency which is somewhat drier
than conventional mortar. The mortar should be packed tightly into the joints in thin layers not to exceed 1/4 inch.
Each layer should become "thumbprint hard" before applying the next layer. The joints should be tooled to match
the original proZle after the last layer of mortar is "thumbprint hard".
RELAYING OF BRICK
Replacement bricks must match the originals with respect to size, color, and texture where exposed. A
tuck-pointing tooling chisel should be used to cut out of the mortar which surrounds the a]ected units.
Power driven impact tools are not allowed. Once the units are removed, all of the old mortar shall be
carefully chiseled out and all dust and debris shall be swept out with a brush.
If used brick is to be relayed, it shall be cleaned of all old mortar. The brick surfaces in the wall shall be
dampened before new units are placed, but the masonry should absorb all surface moisture to ensure a
good bond. The appropriate surfaces of the surrounding brickwork and the replacement brick should be
buttered with mortar. The replacement brick should be centered in the opening and pressed into
position. The excess mortar should be removed with a trowel. Pointing around the replacement brick will
help to ensure full head and bed joints. When the mortar becomes "thumbprint hard", the joints shall be
tooled to match the original proZle.
(Ord. 1882 NCS §1, 1992.)
17.34.112 Declaration of nuisance.¶
In addition to the penalties provided in this chapter, any condition caused or permitted to exist in violation of any
of the provisions of this code shall be deemed a public nuisance and may be abated by the city as such in any
manner authorized by law. (Ord. 1882 NCS §1, 1992.)
17.34.113 Interpretations.¶
The interpretation of the building o\cial shall prevail on matters relating to the implementation of this chapter.
(Ord. 1882 NCS §1, 1992.)
17.34.114 EMective date.¶
This chapter shall become e]ective on the thirty-Zrst day after its passage. (Ord. 1882 NCS §1, 1992.)
Get a plain-English answer with a citation back to this text.
Ask AI about this code