Skip to content

Chapter 3 — BUILDING PLANNING

Section R337.9

California Residential Code (Title 24, Part 2.5) · 2019 edition · updated 2026-09-12 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

DECKING

R337.9.1 General. The walking surface material of decks, porches, balconies and stairs shall comply with the requirements of this section.

R337.9.2 Where required. The walking surface material of decks, porches, balconies and stairs shall comply with the requirements of this section when any portion of such surface is within 10 feet (3048 mm) of the building.

R337.9.3 Decking surfaces. The walking surface material of decks, porches, balconies and stairs shall be con- structed with one of the following materials:

1. Material that complies with the performance requirements of Section R337.9.4 when tested in accordance with both ASTM E2632 and ASTM E2726.

2. Ignition-resistant material that complies with the performance requirements of Section R337.4.3 when tested in accordance with ASTM E84 or UL 723.

3. Material that complies with the performance requirements of both SFM Standard 12-7A-4 and SFM Standard 12-7A-5.

4. Exterior fire retardant treated wood.

5. Noncombustible material.

6. Any material that complies with the performance requirements of SFM Standard 12-7A-4A when attached exterior wall covering is also composed of noncombustible or ignition-resistant material.

Exception: Wall material may be of any material that otherwise complies with this chapter when the decking surface material complies with the performance requirements ASTM E84 with a Class B flame spread rating.

7. Any material that complies with the performance requirements of Section R337.9.5 when tested in accordance with ASTM E2632 and when attached exterior wall covering is also composed of only non- combustible or ignition-resistant materials.

Exception : Wall material shall be permitted to be of any material that otherwise complies with this chapter when the decking surface material com- plies with the performance requirements ASTM E84 with a Class B flame spread index.

R337.9.4 Requirements for type of ignition-resistant material in Section R337.9.3, Item 1. The material shall be tested in accordance with both ASTM E2632 and ASTM E2726 and shall comply with the conditions of acceptance in Sections R337.9.4.1 and R337.9.4.2. The material shall also be tested in accordance with ASTM E84 or UL 723 and comply with the performance requirements of Section R337.4.3.

R337.9.4.1 Conditions of acceptance for ASTM E2632. The ASTM E2632 test shall be conducted on a minimum of three test specimens and the conditions of acceptance in Items 1 through 3 below shall be met. If any one of the three tests does not meet the conditions of acceptance, three additional tests shall be run. All of the additional tests shall meet the conditions of acceptance.

1. Peak heat release rate of less than or equal to 25 kW/ft 2 (269 kW/m 2 ).

2. Absence of sustained flaming or glowing combus- tion of any kind at the conclusion of the 40-minute observation period.

3. Absence of falling particles that are still burning when reaching the burner or floor.

R337.9.4.2 Conditions of acceptance for ASTM E2726. The ASTM E2726 test shall be conducted, using a “Class A” size roof test brand, on a minimum of three test specimens and the conditions of acceptance in Items 1 and 2 below shall be met. If any one of the three test specimens does not meet the conditions of accep- tance, three additional tests shall be run. All of the additional tests shall meet the conditions of accep- tance.

1. Absence of sustained flaming or glowing combus- tion of any kind at the conclusion of the 40-min- ute observation period.

2. Absence of falling particles that are still burning when reaching the burner or floor.

R337.9.5 Requirements for type of material in Section R337.9.3, Item 7. The material shall be tested in accor- dance with ASTM E2632 and shall comply with the follow- ing condition of acceptance. The ASTM E2632 test shall be conducted on a minimum of three test specimens and the peak heat release rate shall be less than or equal to 25 kW/ft 2 (269 kW/m 2 ). If any one of the three tests does not meet the conditions of acceptance, three additional tests shall be run. All the additional tests shall meet the condi- tion of acceptance.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Residential Code (Title 24, Part 2.5)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.