R303.1 Habitable rooms.¶
Habitable rooms shall have an aggregate glazing area of not less than 8 percent of the floor area of such rooms. Natural ventilation shall be through win
dows, skylights, doors, louvers or other approved openings to the outdoor air. Such openings shall be provided with ready access or shall otherwise be readily controllable by the building occupants. The openable area to the outdoors shall be not less than 4 percent of the floor area being ventilated.
Exceptions:
The glazed areas need not be openable where the opening is not required by Section R310 and a whole-house mechanical ventilation system is installed in accordance with the California Mechan- ical Code.
The glazed areas need not be installed in rooms where Exception 1 is satisfied and artificial light is provided that is capable of producing an average illumination of 6 footcandles (65 lux) over the area of the room at a height of 30 inches (762 mm) above the floor level.
Use of sunroom and patio covers, as defined in Section R202, shall be permitted for natural ventilation if in excess of 40 percent of the exterior sunroom walls are open, or are enclosed only by insect screening.
4. The windows, doors, louvers and other approved closeable openings not required by Section R310 may open into a passive solar energy collector for ventilation required by this section. The area of ventilation openings to the outside of the passive solar energy collector shall be increased to com- pensate for the openings required by the interior space.
5. Glazed openings may open into a passive solar energy collector provided the area of exterior glazed opening(s) into the passive solar energy collector is increased to compensate for the area required by the interior space.
R303.2 Adjoining rooms.¶
For the purpose of determining light and ventilation requirements, rooms shall be considered to be a portion of an adjoining room where not less than onehalf of the area of the common wall is open and unobstructed and provides an opening of not less than one-tenth of the floor area of the interior room and not less than 25 square feet (2.3 m 2 ).
Exception: Openings required for light or ventilation shall be permitted to open into a sunroom with thermal isolation or a patio cover, provided that there is an openable area between the adjoining room and the sunroom or patio cover of not less than one-tenth of the floor area of the interior room and not less than 20 square feet (2 m 2 ). The minimum openable area to the outdoors shall be based on the total floor area being ventilated.
R303.3 Bathrooms.¶
Bathrooms, water closet compartments and other similar rooms shall be provided with aggregate glazing area in windows of not less than 3 square feet (0.3 m 2 ), onehalf of which shall be openable.
Exception: The glazed areas shall not be required where artificial light and a local exhaust system are provided.
82 2019 CALIFORNIA RESIDENTIAL CODE
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
The minimum local exhaust rates shall be 50 cubic feet per minute (25 L/s) for intermittent ventilation or 20 cubic feet per minute (10 L/s) for continuous ventilation in accordance with the California Mechanical Code, Chapter 4 . Exhaust air from the space shall be exhausted directly to the outdoors.
R303.3.1 Bathroom exhaust fans. Each bathroom con- taining a bathtub, shower or tub/shower combination shall be mechanically ventilated for purposes of humidity con- trol in accordance with the California Mechanical Code, Chapter 4; and the California Green Building Standards Code, Chapter 4, Division 4.5.
Note: Window operation is not a permissible method of providing bathroom exhaust for humidity control.
R303.4 Ventilation¶
. Ventilation air rates shall be in compli- ance with the California Mechanical Code.
R303.5 Opening location.¶
Outdoor intake and exhaust openings shall be located in accordance with Sections R303.5.1 and R303.5.2.
R303.5.1 Intake openings. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) from any hazardous or noxious contaminant, such as vents, chimneys, plumbing vents, streets, alleys, parking lots and loading docks.
For the purpose of this section, the exhaust from dwelling unit toilet rooms, bathrooms and kitchens shall not be considered as hazardous or noxious.
Exceptions:
The 10-foot (3048 mm) separation is not required where the intake opening is located 3 feet (914 mm) or greater below the contaminant source.
Vents and chimneys serving fuel-burning appliances shall be terminated in accordance with the applicable provisions of Chapters 18 and 24.
Clothes dryer exhaust ducts shall be terminated in accordance with Section M1502.3.
R303.5.2 Exhaust openings. Exhaust air shall not be directed onto walkways.
R303.6 Outside opening protection.¶
Air exhaust and intake openings that terminate outdoors shall be protected with corrosion-resistant screens, louvers or grilles having an opening size of not less than 1 /4 inch (6 mm) and a maximum opening size of 1 /2 inch (13 mm), in any dimension. Openings shall be protected against local weather conditions. Outdoor air exhaust and intake openings shall meet the provisions for exterior wall opening protectives in accordance with this code.
R303.7 Interior stairway illumination.¶
Interior stairways shall be provided with an artificial light source to illuminate the landings and treads. The light source shall be capable of illuminating treads and landings to levels of not less than 1 foot-candle (11 lux) as measured at the center of treads and landings. There shall be a wall switch at each floor level to
BUILDING PLANNING
control the light source where the stairway has six or more risers.
Exception: A switch is not required where remote, central or automatic control of lighting is provided.
R303.8 Exterior stairway illumination.¶
Exterior stairways shall be provided with an artificial light source located at the top landing of the stairway. Exterior stairways providing access to a basement from the outdoor grade level shall be provided with an artificial light source located at the bottom landing of the stairway.
R303.9 Required glazed openings.¶
Required glazed openings shall open directly onto a street or public alley, or a yard or court located on the same lot as the building.
Exceptions:
Required glazed openings that face into a roofed porch where the porch abuts a street, yard or court and the longer side of the porch is not less than 65 percent unobstructed and the ceiling height is not less than 7 feet (2134 mm).
Eave projections shall not be considered as obstructing the clear open space of a yard or court.
Required glazed openings that face into the area under a deck, balcony, bay or floor cantilever where a clear vertical space not less than 36 inches (914 mm) in height is provided.
R303.9.1 Sunroom additions. Required glazed openings shall be permitted to open into sunroom additions or patio covers that abut a street, yard or court if in excess of 40 percent of the exterior sunroom walls are open, or are enclosed only by insect screening, and the ceiling height of the sunroom is not less than 7 feet (2134 mm).
R303.9.1.1 Passive solar energy collectors. When a passive solar energy collector is designed as a condi- tioned area it shall comply with the California Energy Code. Nonconditioned passive solar energy collectors are exempt from the California Energy Code.
R303.10 Required heating.¶
Where the winter design temperature in Table R301.2(1) is below 60°F (16°C), every dwelling unit shall be provided with heating facilities capable of maintaining a room temperature of not less than 68°F (20°C) at a point 3 feet (914 mm) above the floor and 2 feet (610 mm) from exterior walls in habitable rooms at the design temperature. The installation of one or more portable space heaters shall not be used to achieve compliance with this section.
Note: See Section R301.1.1.1 for limited-density owner- built rural dwellings.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Residential Code (Title 24, Part 2.5)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Chapter 1 — SCOPE AND APPLICATION
▸Chapter 3 — BUILDING PLANNING
Overview- Section R300
- Section R301
- Section R302
- Section R303
- Section R304
- Section R305
- Section R306
- Section R307
- Section R308
- Section R309
- Section R310
- Section R311
- Section R312
- Section R313
- Section R314
- Section R315
- Section R316
- Section R317
- Section R318
- Section R319
- Section R320
- Section R321
- Section R322
- Section R323
- Section 324
- Section R325
- Section R334
- Section R335
- Section R326
- Section R327
- Section R336
- Section R337
- Section R337.1
- Section R337.2
- Section R337.3
- Section R337.4
- Section R337.5
- Section R337.6
- Section R337.7
- Section R337.8
- Section R337.9
- Section R337.10
- Section R340
- Section R338
- Chapter 4 — FOUNDATIONS
- Chapter 5 — FLOORS
- Chapter 6 — WALL CONSTRUCTION
- Chapter 7 — WALL COVERING
- Chapter 8 — ROOF-CEILING CONSTRUCTION
- Chapter 9 — ROOF ASSEMBLIES
- Chapter 10 — CHIMNEYS AND FIREPLACES
- Chapter 44 — REFERENCED STANDARDS
- Appendix F — RADON CONTROL METHODS
- Appendix H — PATIO COVERS
- Appendix I — PRIVATE SEWAGE DISPOSAL
- Appendix J — EXISTING BUILDINGS AND STRUCTURES
- Appendix K — SOUND TRANSMISSION
- Appendix L — PERMIT FEES
- Appendix O — AUTOMATIC VEHICULAR GATES
- Appendix Q — TINY HOUSES
- Appendix R — LIGHT STRAW-CLAY CONSTRUCTION
- Appendix S — STRAWBALE CONSTRUCTION
- Appendix T — SOLAR-READY PROVISIONS—DETACHED ONE- AND
- Appendix V — SWIMMING POOL SAFETY ACT
- Appendix W — AREAS PROTECTED BY THE FACILITIES
- Appendix X — EMERGENCY HOUSING