Chapter 3 — BUILDING PLANNING

Section R337.4

California Residential Code (Title 24, Part 2.5) · 2019 edition · updated 2026-09-12 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

IGNITION-RESISTANT CONSTRUCTION

R337.4.1 General. The materials prescribed herein for ignition resistance shall conform to the requirements of this chapter.

R337.4.2 Ignition-resistant materials. Ignition-resistant materials shall comply with one of the following:

1. The requirements in Section R337.4.3 when tested in accordance with the test procedures set forth in ASTM E84 or UL 723,

2. The test procedures and requirements set forth in SFM Standard 12-7A-5 “Ignition-Resistant Mate- rial”, or

3. One of the alternative methods in Section R337.4.4.

R337.4.3 Conditions of acceptance for ignition-resistant material tested in accordance with ASTM E84 or UL 723 . A material shall comply with the conditions of accep- tance in 1 and 2 below when the test is continued for an additional 20-minute period, meaning for a total test period of an “extended” 30-minute test period.

1. The material shall exhibit a flame spread index not exceeding 25 and shall show no evidence of pro- gressive combustion following the extended 30-min- ute test period.

2. The material shall exhibit a flame front that does not progress more than 10 1 /2 feet (3200 mm) beyond the centerline of the burner at any time during the extended 30-minute test period.

R337.4.4 Alternative methods for determining ignition- resistant material. Any one of the following shall be accepted as meeting the definition of ignition-resistant material:

1. Noncombustible material. Material that complies with the definition for noncombustible materials in Section 202.

2. Fire-retardant-treated wood. Fire-retardant-treated wood identified for exterior use that complies with the requirements of Section 2303.2 of the California Building Code.

3. Fire-retardant-treated wood shingles and shakes. Fire-retardant-treated wood shingles and shakes, as defined in Section 1505.6 of the California Building Code and listed by State Fire Marshal for use as “Class B” roof covering, shall be accepted as an Ignition-resistant wall covering material when installed over solid sheathing.